FIRE RESISTANCE CABLES

N2XY 1 x (1.5 - 800) mm2 0.6/1 kV


Cu / MGT / XLPE / LSFH

FRC 1 CORE
(Copper Conductor, Mica Glass Tape, XLPE Insulated, Low Smoke Free Halogen Sheathed)
Standard Specification : SS 299, BS 6387 & IEC 60331

Construction Data
Copper conductor Special Features on Request:
UV Resistance Nom Overall Cable
Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Mica Glass Tape
Flame Retardant Non Category Area approx. approx.
XLPE Insulation
Heat Resistance
mm mm kg/km
Anti Termite
Orange LSFH Outer sheath Anti Rodent 1.5 6.9 59
Low Smoke Zero Halagen 2.5 7.5 75
4 7.9 93
Note: 6 8.1 110
Conductor Shape 10 9.0 155
1.5 - 10 sqmm supplied in solid (re) or non compact-
ed circular stranded (rm) conductor shape 16 10.0 215
16 sqmm supplied in non compacted circular 25 11.7 315
stranded (rm) conductor shape
35 12.8 405
25 - 800 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm) 50 14.5 535
conductor shape 70 16.5 745
Standard Packing 95 18.5 1,005
Application:
1.5 - 10 sqmm supplied in coil @ 100 meters
For wiring of fire resistance safety circuits, such as 120 20.5 1,245
16 - 400 sqmm supplied in wooden drum @ 1000
fire alarm system, emergency lighting and power, meters 150 22.5 1,530
public address and emergency voice 500 - 800 sqmm supplied in wooden drum on 185 25.0 1,895
communication systems in highrise building, available length
Length Tolerance per drum 2%
240 28.0 2,465
control and instrumentation services in industrial,
300 31.0 3,075
commercial and residential complexes.
400 35.0 3,935
500 39.5 5,025
630 43.0 6,375
800 49.0 8,185

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C *
Short
Nom DC AC Trefoil formation Flat formation Circuit current
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground in air in ground Max.
Area Max. Max. Max. Max. Max. Max. (kA)
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A)
1.5 12.1 15.429 0.478 0.524 25 33 26 33 0.22
2.5 7.41 9.449 0.441 0.487 34 43 35 43 0.37
4 4.61 5.787 0.409 0.455 45 56 46 55 0.59
6 3.08 3.927 0.387 0.433 57 69 58 68 0.89
10 1.83 2.334 0.356 0.402 78 92 80 91 1.49
16 1.15 1.466 0.333 0.379 104 118 107 117 2.38
25 0.727 0.927 0.317 0.363 141 152 145 151 3.71
35 0.524 0.668 0.303 0.349 173 182 178 180 5.20
50 0.387 0.494 0.290 0.336 213 216 220 214 7.43
70 0.268 0.342 0.280 0.326 271 265 279 261 10.40
95 0.193 0.347 0.272 0.318 335 316 346 312 14.11
120 0.153 0.196 0.268 0.314 392 359 404 355 17.83
150 0.124 0.160 0.267 0.313 451 403 466 397 22.29
185 0.0991 0.128 0.265 0.311 526 455 543 449 27.49
240 0.0754 0.099 0.260 0.306 630 527 650 519 35.66
300 0.0601 0.080 0.255 0.301 728 593 751 584 44.57
400 0.0470 0.064 0.254 0.300 848 671 875 660 59.43
500 0.0366 0.052 0.251 0.297 985 757 1018 744 74.29
630 0.0283 0.043 0.247 0.293 1141 849 1179 834 93.60
800 0.0221 0.036 0.244 0.291 1295 937 1339 921 118.86
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
FIRE RESISTANCE CABLES
N2XY 2 x (1.5 - 300) mm2 0.6/1 kV
Cu / MGT / XLPE / LSFH

FRC 2 CORE
(Copper Conductor, Mica Glass Tape, XLPE Insulated, Low Smoke Free Halogen Sheathed)
Standard Specification : SS 299, BS 6387 & IEC 60331

Construction Data
Special Features on Request:
UV Resistance Nom Overall Cable
Copper conductor
Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Mica Glass Tape
Flame Retardant Non Category Area approx. approx.
XLPE Insulation Heat Resistance
mm mm kg/km
LSFH Inner sheath Anti Termite
Anti Rodent 1.5 14.5 255
Orange LSFH Outer sheath Low Smoke Zero Halagen 2.5 15.5 305
4 16.5 365
Note:
6 18.0 445
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compact- 10 20.0 585
ed circular stranded (rm) conductor shape
16 22.0 755
16 sqmm supplied in non compacted circular
stranded (rm) conductor shape 25 25.0 1,050
25 - 300 sqmm supplied in non compacted circular
35 27.5 1,325
stranded (rm) or compacted circular stranded (cm)
conductor shape 50 30.0 1,625
Standard Packing 70 34.5 2,250
Application:
1.5 - 120 sqmm supplied in wooden drum @ 1000
For wiring of fire resistance safety circuits, such as meters 95 38.0 2,875
fire alarm system, emergency lighting and power, 150 - 300 sqmm supplied in wooden drum on 120 41.5 3,485
public address and emergency voice available length
Length Tolerance per drum 2%
150 46.5 4,335
communication systems in highrise building,
185 51.0 5,255
control and instrumentation services in industrial,
commercial and residential complexes. 240 56.5 6,645
300 62.5 8,205

Electrical Data
Conductor Inductance Current - Carrying
Capacity at Short
Nom DC AC Circuit current
at 30 C *
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground Max.
Area Max. Max. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (A) (A)
1.5 12.1 15.429 0.315 29 34 0.22
2.5 7.41 9.449 0.293 38 44 0.37
4 4.61 5.878 0.275 50 58 0.59
6 3.08 3.927 0.263 64 73 0.89
10 1.83 2.334 0.248 88 98 1.49
16 1.15 1.467 0.238 116 128 2.38
25 0.727 0.927 0.240 154 165 3.71
35 0.524 0.669 0.233 190 199 5.20
50 0.387 0.494 0.232 230 236 7.43
70 0.268 0.342 0.229 292 292 10.40
95 0.193 0.247 0.224 356 348 14.11
120 0.153 0.196 0.223 414 397 17.83
150 0.124 0.160 0.224 474 445 22.29
185 0.0991 0.128 0.225 544 502 27.49
240 0.0754 0.099 0.223 644 582 35.66
300 0.0601 0.080 0.221 737 654 44.57

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
FIRE RESISTANCE CABLES
N2XY 3 x (1.5 - 300) mm2 0.6/1 kV
Cu / MGT / XLPE / LSFH

FRC 3 CORE
(Copper Conductor, Mica Glass Tape, XLPE Insulated, Low Smoke Free Halogen Sheathed)
Standard Specification : SS 299, BS 6387 & IEC 60331

Construction Data
Special Features on Request:
UV Resistance Nom Overall Cable
Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
Copper conductor Heat Resistance
mm mm kg/km
Anti Termite
Mica Glass Tape Anti Rodent 1.5 15.5 285
XLPE Insulation
Low Smoke Zero Halagen 2.5 16.5 335
LSFH Inner sheath

4 17.5 415
Orange LSFH Outer sheath
Note:
6 19.0 515
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compact- 10 21.0 690
ed circular stranded (rm) conductor shape
16 23.5 915
16 sqmm supplied in non compacted circular
stranded (rm) conductor shape 25 26.5 1,290
25 - 300 sqmm supplied in non compacted circular
35 29.0 1,645
stranded (rm) or compacted circular stranded (cm)
conductor shape 50 32.0 2,040
Standard Packing 70 37.0 2,830
Application:
1.5 - 95 sqmm supplied in wooden drum @ 1000
For wiring of fire resistance safety circuits, such as meters 95 40.5 3,685
fire alarm system, emergency lighting and power, 120 - 300 sqmm supplied in wooden drum on 120 44.5 4,495
public address and emergency voice available length
Length Tolerance per drum 2%
150 50.0 5,575
communication systems in highrise building,
185 54.5 6,815
control and instrumentation services in industrial,
commercial and residential complexes. 240 61.0 8,795
300 66.5 10,755

Electrical Data
Conductor Inductance Current - Carrying
Capacity at Short
Nom DC AC Circuit current
at 30 C *
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground Max.
Area Max. Max. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (A) (A)
1.5 12.1 15.429 0.315 21 28 0.22
2.5 7.41 9.449 0.293 32 37 0.37
4 4.61 5.878 0.275 43 49 0.59
6 3.08 3.927 0.263 54 61 0.89
10 1.83 2.334 0.248 74 83 1.49
16 1.15 1.467 0.238 99 107 2.38
25 0.727 0.927 0.240 131 139 3.71
35 0.524 0.669 0.233 162 167 5.20
50 0.387 0.494 0.232 200 203 7.43
70 0.268 0.342 0.229 252 248 10.40
95 0.193 0.247 0.224 309 296 14.11
120 0.153 0.196 0.223 359 339 17.83
150 0.124 0.160 0.224 411 379 22.29
185 0.0991 0.128 0.225 475 430 27.49
240 0.0754 0.099 0.223 562 497 35.66
300 0.0601 0.080 0.221 645 560 44.57

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
FIRE RESISTANCE CABLES
N2XY 4 x (1.5 - 300) mm2 0.6/1 kV
Cu / MGT / XLPE / LSFH

FRC 4 CORE
(Copper Conductor, Mica Glass Tape, XLPE Insulated, Low Smoke Free Halogen Sheathed)
Standard Specification : SS 299, BS 6387 & IEC 60331

Construction Data
Special Features on Request:
UV Resistance Nom Overall Cable
Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
Copper conductor Heat Resistance
mm mm kg/km
Anti Termite
Mica Glass Tape Anti Rodent 1.5 16.5 325
XLPE Insulation Low Smoke Zero Halagen 2.5 17.5 390
LSFH Inner sheath
4 19.0 485
Orange LSFH Outer sheath Note:
6 20.5 605
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compact- 10 23.0 840
ed circular stranded (rm) conductor shape
16 25.5 1,125
16 sqmm supplied in non compacted circular
stranded (rm) conductor shape 25 29.0 1,605
25 - 300 sqmm supplied in non compacted circular
35 32.0 2,075
stranded (rm) or compacted circular stranded (cm)
conductor shape 50 36.0 2,630
Standard Packing 70 41.0 3,585
Application:
1.5 - 70 sqmm supplied in wooden drum @ 1000
For wiring of fire resistance safety circuits, such as meters 95 44.5 4,700
fire alarm system, emergency lighting and power, 95 - 300 sqmm supplied in wooden drum on 120 50.0 5,850
public address and emergency voice available length
Length Tolerance per drum 2%
150 55.5 7,145
communication systems in highrise building,
185 61.0 8,850
control and instrumentation services in industrial,
commercial and residential complexes. 240 67.5 11,315
300 74.0 13,870

Electrical Data
Conductor Inductance Current - Carrying
Capacity at Short
Nom DC AC Circuit curent
at 30 C *
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground Max.
Area Max. Max. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (A) (A)
1.5 12.1 15.429 0.315 27 31 0.22
2.5 7.41 9.449 0.293 35 41 0.37
4 4.61 5.878 0.275 47 53 0.59
6 3.08 3.927 0.263 59 67 0.89
10 1.83 2.334 0.248 81 89 1.49
16 1.15 1.467 0.238 108 116 2.38
25 0.727 0.927 0.240 146 151 3.71
35 0.524 0.669 0.233 180 181 5.20
50 0.387 0.494 0.232 212 208 7.43
70 0.268 0.342 0.229 265 254 10.40
95 0.193 0.247 0.224 327 305 14.11
120 0.153 0.196 0.223 379 347 17.83
150 0.124 0.160 0.224 442 392 22.29
185 0.0991 0.128 0.225 504 441 27.49
240 0.0754 0.099 0.223 597 511 35.66
300 0.0601 0.080 0.221 685 576 44.57

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XY 1 x (1.5 - 500) mm2 0.6/1 kV
Cu / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed)

N2XY 1 CORE
Standard Specification : SPLN 43 - 6 : 1994 & IEC 60502 - 1

Construction Data
Copper conductor
Special Features on Request:
Fire Resistance Nom Overall Cable
Cross Section Diameter Weight
XLPE Insulation Oil Resistance
UV Resistance Area approx. approx.
Black PVC Outer sheath Flame Retardant Cat. A, B, C
mm mm kg/km
Flame Retardant Non Category
Heat Resistance 1.5 5.8 47
Anti Termite 2.5 6.2 59
Anti Rodent 4 6.8 77
Low Smoke Zero Halagen
6 7.3 98

Note: 10 8.2 145

Conductor Shape 16 9.3 205


1.5 - 10 sqmm supplied in solid (re) or non compact- 25 11.0 305
ed circular stranded (rm) conductor shape
35 12.1 405
16 sqmm supplied in non compacted circular
stranded (rm) conductor shape 50 14.0 525
25 - 500 sqmm supplied in non compacted circular 70 16.0 730
stranded (rm) or compacted circular stranded (cm)
Application: conductor shape 95 18.0 1,005
Power cable : Indoors, cable trunking, outdoors Standard Packing
120 20.0 1,250
and buried in the ground, for power stations, 1.5 - 10 sqmm supplied in coil @ 100 meters 150 22.0 1,525
industry and switchgear as well as for urban 16 - 300 sqmm supplied in wooden drum @ 1000 185 24.0 1,885
supply networks, if mechanical damage is unlikely. meters
240 27.5 2,475
400 - 500 sqmm supplied in wooden drum on
available length 300 30.0 3,045
Length Tolerance per drum 2%
400 34.0 3,930
500 38.0 4,960

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C *
Short
Nom DC AC Trefoil formation Flat formation Circuit current
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground in air in ground Max.
Area Max. Max. Max. Max. Max. Max. (kA)
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A)
1.5 12.1 15.429 0.452 0.505 25 33 26 33 0.22
2.5 7.41 9.449 0.417 0.470 34 43 35 43 0.37
4 4.61 5.787 0.387 0.498 45 56 46 55 0.59
6 3.08 3.927 0.364 0.463 57 69 58 68 0.89
10 1.83 2.334 0.336 0.433 78 92 80 91 1.49
16 1.15 1.466 0.315 0.410 104 118 107 117 2.38
25 0.727 0.927 0.302 0.382 141 152 145 151 3.71
35 0.524 0.668 0.289 0.361 173 182 178 180 5.20
50 0.387 0.494 0.279 0.348 213 216 220 214 7.43
70 0.268 0.342 0.270 0.335 271 265 279 261 10.40
95 0.193 0.347 0.263 0.325 335 316 346 312 14.11
120 0.153 0.196 0.259 0.316 392 359 404 355 17.83
150 0.124 0.160 0.259 0.310 451 403 466 397 22.29
185 0.0991 0.128 0.258 0.305 526 455 543 449 27.49
240 0.0754 0.099 0.253 0.305 630 527 650 519 35.66
300 0.0601 0.080 0.249 0.304 728 593 751 584 44.57
400 0.0470 0.064 0.249 0.300 848 671 875 660 59.43
500 0.0366 0.052 0.246 0.295 985 757 1018 744 74.29

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XY 2 x (1.5 - 300) mm2 0.6/1 kV
Cu / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed)

N2XY 2 CORE
Standard Specification : SPLN 43 - 6 : 1994 & IEC 60502 - 1

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
XLPE Insulation Area approx. approx.
Flame Retardant Non Category
PVC Inner sheath
Heat Resistance mm mm kg/km
Black PVC Outer sheath Anti Termite 1.5 11.5 170
Anti Rodent
Low Smoke Zero Halagen 2.5 12.5 205
4 14.0 260
Note: 6 15.0 320
Conductor Shape
10 17.0 445
1.5 - 10 sqmm supplied in solid (re) or non compact-
ed circular stranded (rm) conductor shape 16 19.0 605
16 sqmm supplied in non compacted circular
25 22.0 885
stranded (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular 35 24.5 1,145
stranded (rm) or compacted circular stranded (cm)
Application: conductor shape
50 27.5 1,480
Power cable : Indoors, cable trunking, outdoors Standard Packing 70 31.5 2,025
and buried in the ground, for power stations, 1.5 - 150 sqmm supplied in coil @ 100 meters 95 36.0 2,745
industry and switchgear as well as for urban 185 - 300 sqmm supplied in wooden drum @ 1000
meters
120 40.0 3,415
supply networks, if mechanical damage is unlikely.
Length Tolerance per drum 2% 150 44.0 4,180
185 49.0 5,210
240 55.0 6,730
300 61.0 8,335

Electrical Data
Conductor Inductance Current - Carrying
Capacity at Short
Nom DC AC Circuit current
at 30 C *
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground Max.
Area Max. Max. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (A) (A)
1.5 12.1 15.429 0.315 27 33 0.22
2.5 7.41 9.449 0.293 36 44 0.37
4 4.61 5.878 0.275 48 58 0.59
6 3.08 3.927 0.263 61 72 0.89
10 1.83 2.334 0.248 83 97 1.49
16 1.15 1.467 0.238 113 128 2.38
25 0.727 0.927 0.240 150 167 3.71
35 0.524 0.669 0.233 186 201 5.20
50 0.387 0.494 0.232 226 239 7.43
70 0.268 0.342 0.229 290 295 10.40
95 0.193 0.247 0.224 353 355 14.11
120 0.153 0.196 0.223 413 404 17.83
150 0.124 0.160 0.224 468 458 22.29
185 0.0991 0.128 0.225 540 516 27.49
240 0.0754 0.099 0.223 590 600 35.66
300 0.0601 0.080 0.221 745 695 44.57

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XY 3 x (1.5 - 300) mm2 0.6/1 kV
Cu / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed)

N2XY 3 CORE
Standard Specification : SPLN 43 - 6 : 1994 & IEC 60502 - 1

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Area approx. approx.
Flame Retardant Non Category
XLPE Insulation
Heat Resistance mm mm kg/km
PVC Inner sheath
Anti Termite 1.5 12.0 190
Black PVC Outer sheath Anti Rodent
Low Smoke Zero Halagen 2.5 13.0 235
4 14.5 305
Note: 6 15.5 380
Conductor Shape
10 17.5 545
1.5 - 10 sqmm supplied in solid (re) or non compact-
ed circular stranded (rm) conductor shape 16 20.0 755
16 sqmm supplied in non compacted circular
25 23.5 1,120
stranded (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular 35 26.0 1,465
stranded (rm) or compacted circular stranded (cm)
Application: conductor shape
50 29.0 1,905
Power cable : Indoors, cable trunking, outdoors Standard Packing 70 34.0 2,670
and buried in the ground, for power stations, 1.5 - 120 sqmm supplied in coil @ 100 meters 95 38.5 3,580
industry and switchgear as well as for urban 150 - 300 sqmm supplied in wooden drum @ 1000
meters
120 42.5 4,465
supply networks, if mechanical damage is unlikely.
Length Tolerance per drum 2% 150 47.5 5,535
185 53.0 6,840
240 59.0 8,865
300 66.0 10,995

Electrical Data
Conductor Inductance Current - Carrying
Capacity at Short
Nom DC AC Circuit current
at 30 C *
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground Max.
Area Max. Max. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (A) (A)
1.5 12.1 15.429 0.315 21 29 0.22
2.5 7.41 9.449 0.293 28 38 0.37
4 4.61 5.878 0.275 37 49 0.59
6 3.08 3.927 0.263 47 60 0.89
10 1.83 2.334 0.248 64 97 1.49
16 1.15 1.467 0.238 86 108 2.38
25 0.727 0.927 0.240 115 141 3.71
35 0.524 0.669 0.233 142 170 5.20
50 0.387 0.494 0.232 172 201 7.43
70 0.268 0.342 0.229 218 249 10.40
95 0.193 0.247 0.224 269 299 14.11
120 0.153 0.196 0.223 311 340 17.83
150 0.124 0.160 0.224 356 381 22.29
185 0.0991 0.128 0.225 413 434 27.49
240 0.0754 0.099 0.223 491 506 35.66
300 0.0601 0.080 0.221 569 585 44.57

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XY 4 x (1.5 - 300) mm2 0.6/1 kV
Cu / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed)

N2XY 4 CORE
Standard Specification : SPLN 43 - 6 : 1994 & IEC 60502 - 1

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Copper conductor Flame Retardant Cat. A, B, C
Area approx. approx.
Flame Retardant Non Category
XLPE Insulation Heat Resistance mm mm kg/km
PVC Inner sheath Anti Termite 1.5 13.0 220
Anti Rodent
Black PVC Outer sheath
Low Smoke Zero Halagen 2.5 14.0 275
4 15.5 360
Note: 6 17.0 460
Conductor Shape
10 19.0 665
1.5 - 10 sqmm supplied in solid (re) or non compact-
ed circular stranded (rm) conductor shape 16 21.5 935
16 sqmm supplied in non compacted circular
25 25.5 1,395
stranded (rm) conductor shape
25 - 35 sqmm supplied in non compacted circular 35 28.5 1,840
stranded (rm) or compacted circular stranded (cm)
Application: conductor shape
50 29.5 2,240
Power cable : Indoors, cable trunking, outdoors 50 - 400 sqmm supplied in non compacted circular 70 34.5 3,125
stranded (rm) or compacted circular stranded (cm)
and buried in the ground, for power stations, 95 39.0 4,205
or sector shaped stranded (sm) conductor
industry and switchgear as well as for urban
120 43.0 5,305
supply networks, if mechanical damage is unlikely. Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 150 48.0 6,445
meters
185 53.5 8,045
95 - 300 sqmm supplied in wooden drum on
available length 240 59.5 10,430
Length Tolerance per drum 2% 300 65.0 12,945

Electrical Data
Conductor Inductance Current - Carrying
Capacity at Short
Nom DC AC Circuit current
at 30 C *
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground Max.
Area Max. Max. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (A) (A)
1.5 12.1 15.429 0.315 23 29 0.22
2.5 7.41 9.449 0.293 32 38 0.37
4 4.61 5.878 0.275 41 49 0.59
6 3.08 3.927 0.263 52 60 0.89
10 1.83 2.334 0.248 71 97 1.49
16 1.15 1.467 0.238 96 108 2.38
25 0.727 0.927 0.240 130 141 3.71
35 0.524 0.669 0.233 159 170 5.20
50 0.387 0.494 0.232 193 201 7.43
70 0.268 0.342 0.229 245 249 10.40
95 0.193 0.247 0.224 302 299 14.11
120 0.153 0.196 0.223 349 340 17.83
150 0.124 0.160 0.224 400 381 22.29
185 0.0991 0.128 0.225 464 434 27.49
240 0.0754 0.099 0.223 552 506 35.66
300 0.0601 0.080 0.221 640 585 44.57

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XY 1 x (10 - 800) mm2 0.6/1 kV
AL / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)

NA2XY 1 CORE
Standard Specification : SPLN 43 - 6 : 1994 & IEC 60502 - 1

Aluminium conductor
Special Features on Request: Construction Data
Oil Resistance
XLPE Insulation UV Resistance Nom Overall Cable
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Black PVC Outer sheath Flame Retardant Non Category
Heat Resistance Area approx. approx.
Anti Termite mm mm kg/km
Anti Rodent
10 8.3 83
Low Smoke Zero Halagen
16 9.4 111
25 11.1 155
Note:
35 12.2 195
Conductor Shape
50 14.0 255
10 - 16 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 16.0 335
25 - 800 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm)
95 18.5 440
conductor shape 120 20.0 530
Application: Standard Packing 150 22.0 640
Power cable : Indoors, cable trunking, outdoors 10 - 800 sqmm supplied in wooden drum @ 1000 185 24.5 785
meters
and buried in the ground, for power stations,
Length Tolerance per drum 2%
240 28.0 1,015
industry and switchgear as well as for urban
300 30.0 1,230
supply networks, if mechanical damage is unlikely.
400 34.5 1,600
500 38.0 1,940
630 43.0 2,480
800 47.0 3,050

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C *
Short
Nom DC AC Trefoil formation Flat formation Circuit current
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground in air in ground Max.
Area Max. Max. Max. Max. Max. Max. (kA)
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A)
10 3.08 3.949 0.336 0.382 60 71 62 70 0.98
16 1.91 2.449 0.311 0.357 81 92 84 91 1.57
25 1.20 1.539 0.302 0.348 109 118 112 117 2.45
35 0.868 1.113 0.289 0.335 134 142 138 140 3.43
50 0.641 0.822 0.279 0.325 165 168 170 166 4.91
70 0.443 0.568 0.269 0.316 211 206 218 203 6.87
95 0.320 0.411 0.263 0.309 260 245 269 242 9.32
120 0.253 0.325 0.260 0.306 303 279 312 275 11.77
150 0.206 0.265 0.258 0.304 353 313 364 309 14.72
185 0.164 0.212 0.258 0.304 411 355 424 350 18.15
240 0.125 0.162 0.253 0.299 494 412 510 406 23.55
300 0.100 0.130 0.249 0.295 571 465 590 458 29.44
400 0.0778 0.103 0.245 0.292 688 536 711 528 39.25
500 0.0605 0.081 0.245 0.291 796 609 823 599 49.06
630 0.0469 0.065 0.243 0.289 932 692 963 680 61.82
800 0.0367 0.053 0.241 0.287 1074 778 1111 764 78.5

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XY 2 x (10 - 300) mm2 0.6/1 kV
AL / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)

NA2XY 2 CORE
Standard Specification : SPLN 43 - 6 : 1994 & IEC 60502 - 1

Special Features on Request: Construction Data


Oil Resistance
UV Resistance Nom Overall Cable
Aluminium conductor
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Flame Retardant Non Category
XLPE Insulation Heat Resistance Area approx. approx.
PVC Inner sheath Anti Termite mm mm kg/km
Anti Rodent
Black PVC Outer sheath 10 17.0 325
Low Smoke Zero Halagen
16 19.0 425
25 22.5 595
Note:
35 25.0 735
Conductor Shape
50 28.5 965
10 - 16 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 32.0 1,255
25 - 300 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm)
95 36.5 1,635
conductor shape 120 40.0 1,985

Application: Standard Packing 150 44.5 2,415


Power cable : Indoors, cable trunking, outdoors 10 - 185 sqmm supplied in wooden drum @ 1000 185 50.0 3,015
meters
and buried in the ground, for power stations, 240 56.0 3,815
240 - 300 sqmm supplied in wooden drum on
industry and switchgear as well as for urban available length
300 62.0 4,715
supply networks, if mechanical damage is unlikely. Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying
Capacity at Short
Nom DC AC Circuit current
at 30 C *
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground Max.
Area Max. Max. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (A) (A)
10 3.08 3.949 0.248 61 72 0.98
16 1.91 2.449 0.236 88 99 1.57
25 1.20 1.539 0.242 119 130 2.45
35 0.868 1.113 0.234 145 157 3.43
50 0.641 0.822 0.232 175 185 4.91
70 0.443 0.568 0.229 220 229 6.87
95 0.320 0.411 0.224 272 276 9.32
120 0.253 0.325 0.223 317 320 11.77
150 0.206 0.265 0.225 362 351 14.72
185 0.164 0.212 0.225 420 400 18.15
240 0.125 0.162 0.223 297 467 23.55
300 0.100 0.130 0.222 577 532 29.44

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XY 3 x (10 - 300) mm2 0.6/1 kV
AL / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)

NA2XY 3 CORE
Standard Specification : SPLN 43 - 6 : 1994 & IEC 60502 - 1

Special Features on Request: Construction Data


Oil Resistance
UV Resistance Nom Overall Cable
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Aluminium conductor
Flame Retardant Non Category
Heat Resistance Area approx. approx.
XLPE Insulation
Anti Termite mm mm kg/km
PVC Inner sheath Anti Rodent
10 17.5 365
Low Smoke Zero Halagen
Black PVC Outer sheath
16 20.0 480
25 24.0 680
Note:
35 26.0 845
Conductor Shape
50 30.0 1,110
10 - 16 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 35.0 1,500
25 - 300 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm)
95 39.0 1,895
conductor shape 120 43.0 2,305

Application: Standard Packing 150 48.0 2,870


Power cable : Indoors, cable trunking, outdoors 10 - 185 sqmm supplied in wooden drum @ 1000 185 53.0 3,530
meters
and buried in the ground, for power stations, 240 60.0 4,525
240 - 300 sqmm supplied in wooden drum on
industry and switchgear as well as for urban available length
300 66.0 5,525
supply networks, if mechanical damage is unlikely. Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying
Capacity at Short
Nom DC AC Circuit current
at 30 C *
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground Max.
Area Max. Max. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (A) (A)
10 3.08 3.949 0.248 52 60 0.98
16 1.91 2.449 0.236 75 84 1.57
25 1.20 1.539 0.242 100 110 2.45
35 0.868 1.113 0.234 123 132 3.43
50 0.641 0.822 0.232 149 156 4.91
70 0.443 0.568 0.229 189 193 6.87
95 0.320 0.411 0.224 233 232 9.32
120 0.253 0.325 0.223 271 268 11.77
150 0.206 0.265 0.225 310 296 14.72
185 0.164 0.212 0.225 359 336 18.15
240 0.125 0.162 0.223 429 429 23.55
300 0.100 0.130 0.222 496 447 29.44

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XY 4 x (10 - 300) mm2 0.6/1 kV
AL / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)

NA2XY 4 CORE
Standard Specification : SPLN 43 - 6 : 1994 & IEC 60502 - 1

Special Features on Request: Construction Data


Oil Resistance
UV Resistance Nom Overall Cable
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Aluminium conductor
Flame Retardant Non Category
Heat Resistance Area approx. approx.
XLPE Insulation
Anti Termite mm mm kg/km
PVC Inner sheath
Anti Rodent
10 19.0 425
Black PVC Outer sheath
Low Smoke Zero Halagen
16 22.0 565
25 26.0 810
Note:
35 28.5 1,015
Conductor Shape
50 29.5 1,055
10 - 16 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 34.5 1,435
25 - 35 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm)
95 39.0 1,820
conductor shape 120 43.0 2,240
50 - 400 sqmm supplied in non compacted circular
Application: stranded (rm) or compacted circular stranded (cm) or 150 48.0 2,725
sector shaped stranded (sm) conductor
Power cable : Indoors, cable trunking, outdoors 185 53.5 3,365
and buried in the ground, for power stations, 240 59.5 4,280
Standard Packing
industry and switchgear as well as for urban 10 - 120 sqmm supplied in wooden drum @ 1000
300 65.0 5,205
supply networks, if mechanical damage is unlikely. meters
150 - 300 sqmm supplied in wooden drum on
available length
Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying
Capacity at Short
Nom DC AC Circuit current
at 30 C *
Cross Resistance Resistance at 1 second
Section at 20 C at 90 C in air in ground Max.
Area Max. Max. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (A) (A)
10 3.08 3.949 0.248 52 60 0.98
16 1.91 2.449 0.236 75 84 1.57
25 1.20 1.539 0.242 110 110 2.45
35 0.868 1.113 0.234 123 132 3.43
50 0.641 0.822 0.232 149 156 4.91
70 0.443 0.568 0.229 189 193 6.87
95 0.320 0.411 0.224 233 232 9.32
120 0.253 0.325 0.223 271 268 11.77
150 0.206 0.265 0.225 310 296 14.72
185 0.164 0.212 0.225 359 336 18.15
240 0.125 0.162 0.223 429 393 23.55
300 0.100 0.130 0.222 496 447 29.44

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NAYA 10 - 400 mm2 450 /750 V
AL / PVC
(Aluminium Conductor, PVC Insulated)

NAYA
Standard Specification : IEC 60227 - 1 & IEC 60228

Special Features on Request: Construction Data


Oil Resistance
Aluminium conductor
Flame Retardant Cat. A, B, C Nom Overall Cable
Flame Retardant Non Category Cross Section Diameter Weight

Area approx. approx.


PVC Insulation
mm mm kg/km
Note:
10 6.1 55
Conductor Shape
10 - 400 sqmm supplied in non compacted circular 16 7.2 79
stranded (rm) conductor shape
25 8.9 120
Standard Packing 35 10.0 155
10 - 400 sqmm supplied in wooden drum @ 1000 50 12.0 215
meters
Length Tolerance per drum 2% 70 14.0 290
95 16.0 385
120 17.5 465

Application: 150 20.0 575


For building wire installed in donduit in dry 185 22.0 725
location, sometimes can be used as grounding 240 25.0 935
conductor, inherently flame retardant in compli-
300 28.0 1,160
ance with IEC 60332 - 1
400 32.0 1,505

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in pipe in air Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
10 3.08 3.701 0.0065 0.274 35 57 1.08
16 1.91 2.295 0.0050 0.258 48 77 1.72
25 1.20 1.442 0.0050 0.257 65 101 2.69
35 0.868 1.043 0.0040 0.249 80 123 3.77
50 0.641 0.771 0.0045 0.248 103 154 5.39
70 0.443 0.533 0.0035 0.239 129 191 7.54
95 0.320 0.385 0.0035 0.239 162 226 10.24
120 0.253 0.305 0.0032 0.235 184 269 12.93
150 0.206 0.249 0.0032 0.235 - 305 16.16
185 0.1640 0.199 0.0032 0.235 - 348 19.93
240 0.1250 0.152 0.0032 0.233 - 410 25.86
300 0.100 0.123 0.0030 0.232 - 473 32.33
400 0.0778 0.097 0.0028 0.229 - 566 43.10

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NAYY 1 x (10 - 800) mm2 0.6/1 kV
AL / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed)

NAYY 1 CORE
Standard Specification : SPLN 43 - 1 : 1994, IEC 60502 - 1 & IEC 60228

Special Features on Request: Construction Data


Aluminium conductor Oil Resistance
UV Resistance Nom Overall Cable
PVC Insulation Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Flame Retardant Non Category
Black PVC Outer sheath Heat Resistance Area approx. approx.
Anti Termite mm mm kg/km
Anti Rodent
10 9.0 105
Low Smoke Zero Halagen
16 10.0 135
25 12.0 190
Note:
35 13.0 230
Conductor Shape
50 15.0 305
10 - 16 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 17.0 395
25 - 800 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm)
95 19.5 515
conductor shape 120 21.0 610
Application: Standard Packing 150 23.0 740
Power cable : Indoors, cable trunking, outdoors 10 - 800 sqmm supplied in wooden drum @ 1000 185 25.5 915
meters
and buried in the ground, for power stations,
Length Tolerance per drum 2%
240 29.0 1,160
industry and switchgear as well as for urban
300 32.0 1,425
supply networks, if mechanical damage is unlikely.
400 36.0 1,825
500 39.5 2,200
630 44.0 2,760
800 48.0 3,335

Electrical Data
Conductor Insulation Inductance Current - Carrying Capacity at 30 C *
Short
Nom DC AC Insulation Trefoil formation Flat formation Circuit current
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground in air in ground Max.
Area Max. Max. Min. Max. Max. Max. Max. (kA)
mm (/km) (/km) (M..km) (mH/km) (mH/km) (A) (A) (A) (A)
10 3.08 3.701 50 0.350 0.396 49 59 50 58 1.08
16 1.91 2.295 40 0.323 0.370 66 77 68 76 1.72
25 1.20 1.442 40 0.313 0.359 88 98 91 97 2.69
35 0.868 1.043 40 0.298 0.344 109 118 112 117 3.77
50 0.641 0.770 30 0.290 0.336 134 140 138 138 5.39
70 0.443 0.533 30 0.279 0.325 170 171 175 169 7.54
95 0.320 0.385 30 0.274 0.320 210 205 216 202 10.24
120 0.253 0.305 30 0.270 0.316 244 233 251 229 12.93
150 0.206 0.249 20 0.265 0.312 283 261 291 258 16.16
185 0.164 0.198 20 0.264 0.310 328 296 339 292 19.93
240 0.125 0.152 20 0.260 0.306 395 344 407 339 25.86
300 0.100 0.122 20 0.258 0.304 456 388 471 382 32.33
400 0.0778 0.096 20 0.252 0.298 548 447 565 440 43.10
500 0.0605 0.076 20 0.251 0.298 633 507 653 499 53.88
630 0.0469 0.061 20 0.246 0.293 738 576 762 566 67.88
800 0.0367 0.050 20 0.242 0.289 848 646 877 635 86.20

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NAYY 2 x (10 - 800) mm2 0.6/1 kV
AL / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed)

NAYY 2 CORE
Standard Specification : SPLN 43 - 1 : 1994, IEC 60502 - 1 & IEC 60228

Special Features on Request: Construction Data


Oil Resistance
Aluminium conductor UV Resistance Nom Overall Cable
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Flame Retardant Non Category
PVC Insulation
Heat Resistance Area approx. approx.
PVC Inner sheath
Anti Termite mm mm kg/km
Anti Rodent
Black PVC Outer sheath 10 18.0 390
Low Smoke Zero Halagen
16 20.0 495
25 23.5 690
Note:
35 26.0 845
Conductor Shape
50 30.0 1,115
10 - 16 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 33.5 1,420
25 - 300 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm)
95 38.0 1,840
conductor shape 120 41.5 2,180
Application: Standard Packing 150 45.5 2,640
Power cable : Indoors, cable trunking, outdoors 10 - 150 sqmm supplied in wooden drum @ 1000 185 51.5 3,355
meters
and buried in the ground, for power stations,
185 - 300 sqmm supplied in wooden drum on 240 58.0 4,255
industry and switchgear as well as for urban
available length
300 64.0 5,245
supply networks, if mechanical damage is unlikely. Length Tolerance per drum 2%

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A))
10 3.08 3.701 50 0.269 48 59 1.08
16 1.91 2.295 40 0.253 70 79 1.72
25 1.20 1.442 40 0.257 94 102 2.69
35 0.868 1.043 40 0.247 115 125 3.77
50 0.641 0.770 30 0.247 140 147 5.39
70 0.443 0.533 30 0.238 155 156 7.54
95 0.320 0.385 30 0.238 190 191 10.24
120 0.253 0.305 30 0.233 220 220 12.93
150 0.206 0.248 20 0.235 245 245 16.16
185 0.164 0.198 20 0.233 275 275 19.93
240 0.125 0.152 20 0.232 320 320 25.86
300 0.100 0.122 20 0.231 365 365 32.33

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NAYY 3 x (10 - 400) mm2 0.6/1 kV
AL / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed)

NAYY 3 CORE
Standard Specification : SPLN 43 - 1 : 1994, IEC 60502 - 1 & IEC 60228

Special Features on Request: Construction Data


Oil Resistance
UV Resistance Nom Overall Cable
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Aluminium conductor
Flame Retardant Non Category
Heat Resistance Area approx. approx.
PVC Insulation
Anti Termite mm mm kg/km
PVC Inner sheath
Anti Rodent
10 19.0 445
Black PVC Outer sheath Low Smoke Zero Halagen
16 21.5 570
25 25.0 795
Note:
35 27.5 980
Conductor Shape
50 32.0 1,300
10 - 16 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 36.5 1,710
25 - 400 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm)
95 41.0 2,215
conductor shape 120 45.0 2,615
Application: Standard Packing 150 50.0 3,215
Power cable : Indoors, cable trunking, outdoors 10 - 150 sqmm supplied in wooden drum @ 1000 185 55.0 3,960
meters
and buried in the ground, for power stations,
185 - 400 sqmm supplied in wooden drum on 240 62.5 5,080
industry and switchgear as well as for urban
available length
300 69.0 6,230
supply networks, if mechanical damage is unlikely. Length Tolerance per drum 2%
400 78.0 7,980

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
10 3.08 3.701 50 0.269 44 52 1.08
16 1.91 2.295 40 0.253 62 69 1.72
25 1.20 1.442 40 0.257 82 89 2.69
35 0.868 1.043 40 0.247 100 107 3.77
50 0.641 0.770 30 0.247 125 129 5.39
70 0.443 0.533 30 0.238 155 156 7.54
95 0.320 0.385 30 0.238 190 191 10.24
120 0.253 0.305 30 0.233 220 220 12.93
150 0.206 0.248 20 0.235 250 245 16.16
185 0.164 0.198 20 0.233 285 275 19.93
240 0.125 0.152 20 0.232 340 320 25.86
300 0.100 0.122 20 0.231 390 365 32.33
400 0.0778 0.096 20 0.229 460 420 43.10

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NAYY 4 x (10 - 400) mm2 0.6/1 kV
AL / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed)

NAYY 4 CORE
Standard Specification : SPLN 43 - 1 : 1994, IEC 60502 - 1 & IEC 60228

Special Features on Request: Construction Data


Oil Resistance
UV Resistance Nom Overall Cable
Aluminium conductor Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Flame Retardant Non Category
Heat Resistance Area approx. approx.
PVC Insulation

PVC Inner sheath


Anti Termite mm mm kg/km
Anti Rodent
10 21.0 520
Black PVC Outer sheath Low Smoke Zero Halagen
16 23.0 680
25 27.5 960
Note:
35 30.0 1,185
Conductor Shape
50 32.0 1,325
10 - 16 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 36.0 1,710
25 - 35 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm)
95 42.0 2,225
conductor shape 120 45.0 2,640
50 - 400 sqmm supplied in non compacted circular
Application: stranded (rm) or compacted circular stranded (cm) or 150 50.5 3,225
Power cable : Indoors, cable trunking, outdoors sector shaped stranded (sm) conductor
185 56.0 3,965
and buried in the ground, for power stations,
Standard Packing 240 62.5 5,055
industry and switchgear as well as for urban
10 - 120 sqmm supplied in wooden drum @ 1000
300 68.5 6,175
supply networks, if mechanical damage is unlikely. meters
150 - 400 sqmm supplied in wooden drum on 400 78.0 7,945
available length
Length Tolerance per drum 2%

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
10 3.08 3.701 50 0.269 44 52 1.08
16 1.91 2.295 40 0.253 62 69 1.72
25 1.20 1.442 40 0.257 82 89 2.69
35 0.868 1.043 40 0.247 100 107 3.77
50 0.641 0.770 30 0.247 125 129 5.39
70 0.443 0.533 30 0.238 155 156 7.54
95 0.320 0.385 30 0.238 190 191 10.24
120 0.253 0.305 30 0.233 220 220 12.93
150 0.206 0.248 20 0.235 250 245 16.16
185 0.164 0.198 20 0.233 285 275 19.93
240 0.125 0.152 20 0.232 340 320 25.86
300 0.100 0.122 20 0.231 390 365 32.33
400 0.0778 0.096 20 0.229 460 420 43.10

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYA 1.5 - 400 mm2 450 / 750 V
Cu / PVC
(Copper Conductor, PVC Insulated)

NAYA
Standard Specification : SPLN 42 - 1 & SNI 04 - 6629.3

Special Features on Request: Construction Data


Fire Resistance
Copper conductor
Oil Resistance Nom Overall Cable
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Flame Retardant Non Category
Area approx. approx.
PVC Insulation
mm mm kg/km
Note:
1.5 2.9 20
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted 2.5 3.5 31
circular stranded (rm) conductor shape
4 3.9 46
16 - 400 sqmm supplied in non compacted circular
stranded (rm) conductor shape 6 4.4 65
10 5.6 110
Standard Packing
1.5 - 16 sqmm supplied in coil @ 100 meters 16 7.2 175
25 - 400 sqmm supplied in wooden drum @ 1000 25 9.0 270
meters
Length Tolerance per drum 2% 35 10.0 365

Application: 50 12.0 495


For building wire installed in donduit in dry 70 13.5 690
location and interwiring in swich board and 95 16.0 955
control panel.
120 17.5 1,185
150 19.5 1,465
185 22.0 1,825
240 25.0 2,415
300 27.5 2,980
400 31.5 3,885

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 70 C in pipe in air Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 0.0100 0.320 15 24 0.17
2.5 7.41 8.866 0.0900 0.309 19 32 0.28
4 4.61 5.516 0.0077 0.290 25 42 0.45
6 3.08 3.685 0.0065 0.276 33 54 0.68
10 1.83 2.190 0.0065 0.274 45 73 1.13
16 1.15 1.376 0.0050 0.260 61 98 1.81
25 0.727 0.870 0.0050 0.257 83 129 2.82
35 0.524 0.627 0.0040 0.249 103 158 3.45
50 0.387 0.464 0.0045 0.248 132 197 5.65
70 0.268 0.321 0.0035 0.240 165 245 7.91
95 0.193 0.232 0.0032 0.239 207 290 10.73
120 0.153 0.184 0.0032 0.235 235 345 13.56
150 0.124 0.150 0.0032 0.235 - 390 16.94
185 0.0991 0.121 0.0032 0.235 - 445 20.90
240 0.0754 0.093 0.0032 0.233 - 525 27.11
300 0.0601 0.075 0.0030 0.232 - 605 33.89
400 0.0470 0.060 0.0028 0.231 - 725 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYB(AL)Y 1 x (16 - 500) mm2 0.6/1 kV
Cu / PVC / DATA / PVC
(Copper Conductor, PVC Insulated, Double Aluminium Tape Armor, PVC Sheathed)

NYBY 1 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 3 ; 1994

Special Features on Request: Construction Data


Fire Resistance
Copper conductor Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
PVC Insulation Flame Retardant Cat. A, B, C
PVC Armor bedding Flame Retardant Non Category Area approx. approx.
Double Aluminium Tape Armor Heat Resistance mm mm kg/km
Black PVC Outer sheath Anti Termite
16 15.0 265
Anti Rodent
Low Smoke Zero Halagen 25 16.5 495
35 18.0 610
Note: 50 19.5 765
Conductor Shape 70 21.0 995
16 sqmm supplied in non compacted circular strand-
ed (rm) conductor shape 95 23.5 1,300
25 - 500 sqmm supplied in non compacted circular 120 25.0 1,565
stranded (rm) or compacted circular stranded (cm)
conductor shape 150 27.0 1,880
Application: 185 29.5 2,290
Standard Packing
For installation indoors, cable channels and in 240 33.0 2,935
16 - 300 sqmm supplied in wooden drum @ 1000
ground, for industry installations, switchgear, and meters
300 36.0 3,620
power station, if there is a risk that low mechani- 400 - 500 sqmm supplied in wooden drum on
available length 400 40.0 4,565
cal damage may occur.
Length Tolerance per drum 2% 500 44.0 5,690

Electrical Data
Conductor Insulation Inductance Current - Carrying Capacity at 30 C *
Short
Nom DC AC Insulation Trefoil formation Flat formation Circuit current
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground in air in ground Max.
Area Max. Max. Min. Max. Max. Max. Max. (kA)
mm (/km) (/km) (M..km) (mH/km) (mH/km) (A) (A) (A) (A)
16 1.15 1.376 40 0.412 0.458 94 98 97 101 1.81
25 0.727 0.870 40 0.374 0.420 124 127 127 131 2.82
35 0.524 0.627 40 0.356 0.402 151 152 155 156 3.95
50 0.387 0.463 30 0.341 0.387 184 180 189 185 5.65
70 0.268 0.321 30 0.324 0.370 230 221 236 226 7.91
95 0.193 0.232 30 0.313 0.359 282 264 289 269 10.7
120 0.153 0.184 30 0.303 0.349 326 299 334 305 13.56
150 0.124 0.150 20 0.298 0.344 372 335 380 341 16.94
185 0.0991 0.120 20 0.291 0.338 428 377 437 383 20.90
240 0.0754 0.093 20 0.285 0.331 506 434 515 438 27.11
300 0.0601 0.075 20 0.279 0.325 578 485 586 488 33.89
400 0.0470 0.060 20 0.278 0.324 663 542 668 542 40.06
500 0.0366 0.049 20 0.272 0.318 757 603 757 598 50.08

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYB(AL)Y 2 x (1.5-300) mm2 0.6/1 kV
Cu / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Double Steel Tape Armor, PVC Sheathed)

NYBY 2 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 3 ; 1994

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
PVC Insulation Flame Retardant Non Category Area approx. approx.
PVC Inner sheath
Heat Resistance mm mm kg/km
Double Steel Tape Armor
Anti Termite
Black PVC Outer sheath 1.5 13.0 260
Anti Rodent
Low Smoke Zero Halagen 2.5 14.0 305
4 15.5 405
Note: 6 16.5 480
Conductor Shape 10 18.5 630
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 21.0 825
16 sqmm supplied in non compacted circular strand- 25 24.0 1,160
ed (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular
35 26.5 1,455
stranded (rm) or compacted circular stranded (cm) 50 30.0 1,880
Application:
conductor shape
For installation indoors, cable channels and in 70 34.0 2,480
ground, for industry installations, switchgear, and Standard Packing
95 40.5 3,710
power station, if there is a risk that low mechani- 1.5 - 120 sqmm supplied in wooden drum @ 1000
meters 120 44.0 4,445
cal damage may occur.
150 - 300 sqmm supplied in wooden drum on 150 48.0 5,370
available length
Length Tolerance per drum 2% 185 53.0 6,580
240 59.5 8,375
300 66.0 10,280

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 50 0.340 23 27 0.17
2.5 7.41 8.866 50 0.304 31 36 0.28
4 4.61 5.516 50 0.303 41 48 0.45
6 3.08 3.685 50 0.288 52 60 0.68
10 1.83 2.190 50 0.269 71 81 1.13
16 1.15 1.376 40 0.255 94 105 1.81
25 0.727 0.870 40 0.255 124 135 2.82
35 0.524 0.627 40 0.246 152 163 3.95
50 0.387 0.464 30 0.247 184 193 5.65
70 0.268 0.321 30 0.238 232 238 7.91
95 0.193 0.232 30 0.238 282 283 10.7
120 0.153 0.184 30 0.233 330 324 13.56
150 0.124 0.150 20 0.233 376 363 16.94
185 0.0991 0.121 20 0.233 430 408 20.9
240 0.0754 0.093 20 0.232 506 472 27.11
300 0.0601 0.075 20 0.231 576 528 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYB(AL)Y 3 x (1.5-300) mm2 0.6/1 kV
Cu / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Double Steel Tape Armor, PVC Sheathed)

NYBY 3 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 3 ; 1994

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
PVC Insulation Flame Retardant Non Category Area approx. approx.
PVC Inner sheath Heat Resistance mm mm kg/km
Double Steel Tape Armor
Anti Termite
1.5 13.5 285
Black PVC Outer sheath Anti Rodent
Low Smoke Zero Halagen 2.5 14.5 345
4 16.5 465
Note: 6 18.0 555
Conductor Shape 10 20.0 745
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 22.0 990
16 sqmm supplied in non compacted circular strand- 25 25.5 1,420
ed (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular
35 28.0 1,805
stranded (rm) or compacted circular stranded (cm) 50 32.0 2,350
Application:
conductor shape
For installation indoors, cable channels and in 70 38.0 3,485
ground, for industry installations, switchgear, and Standard Packing
95 43.0 4,635
power station, if there is a risk that low mechani- 1.5 - 95 sqmm supplied in wooden drum @ 1000
meters 120 47.0 5,890
cal damage may occur.
120 - 300 sqmm supplied in wooden drum on 150 52.0 6,830
available length
Length Tolerance per drum 2% 185 57.0 8,320
240 64.0 10,710
300 71.0 13,085

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 50 0.340 20 23 0.17
2.5 7.41 8.866 50 0.304 26 31 0.28
4 4.61 5.516 50 0.303 35 41 0.45
6 3.08 3.685 50 0.288 44 51 0.68
10 1.83 2.190 50 0.269 61 69 1.13
16 1.15 1.376 40 0.255 80 89 1.81
25 0.727 0.870 40 0.255 106 115 2.82
35 0.524 0.627 40 0.246 131 138 3.95
50 0.387 0.464 30 0.247 164 170 5.65
70 0.268 0.321 30 0.238 205 207 7.91
95 0.193 0.232 30 0.238 255 249 10.7
120 0.153 0.184 30 0.233 294 284 13.56
150 0.124 0.150 20 0.233 336 317 16.94
185 0.0991 0.121 20 0.233 386 358 20.9
240 0.0754 0.093 20 0.232 455 413 27.11
300 0.0601 0.075 20 0.231 522 565 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYB(AL)Y 4 x (1.5-300) mm2 0.6/1 kV
Cu / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Double Steel Tape Armor, PVC Sheathed)

NYBY 4 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 3 ; 1994

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Copper conductor
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Insulation Heat Resistance mm mm kg/km
PVC Inner sheath Anti Termite
Double Steel Tape Armor 1.5 14.5 325
Anti Rodent
Black PVC Outer sheath Low Smoke Zero Halagen 2.5 15.5 395
4 18.0 540
Note: 6 19.0 660
Conductor Shape 10 21.5 895
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 24.0 1,205
16 sqmm supplied in non compacted circular strand- 25 28.0 1,750
ed (rm) conductor shape
25 - 35 sqmm supplied in non compacted circular
35 30.5 2,235
stranded (rm) or compacted circular stranded (cm) 50 33.0 2,670
conductor shape
Application: 70 38.5 3,890
50 - 400 sqmm supplied in non compacted circular
For installation indoors, cable channels and in stranded (rm) or compacted circular stranded (cm) or
95 44.0 6,195
ground, for industry installations, switchgear, and sector shaped stranded (sm) conductor
power station, if there is a risk that low mechani- 120 47.5 6,330
Standard Packing
cal damage may occur. 150 52.5 7,610
1.5 - 70 sqmm supplied in wooden drum @ 1000
meters 185 58.0 9,425
95 - 300 sqmm supplied in wooden drum on
240 64.5 11,985
available length
Length Tolerance per drum 2% 300 70.5 14,745

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 50 0.328 22 27 0.17
2.5 7.41 8.866 50 0.304 30 36 0.28
4 4.61 5.516 50 0.303 40 47 0.45
6 3.08 3.685 50 0.288 51 58 0.68
10 1.83 2.190 50 0.269 69 78 1.13
16 1.15 1.376 40 0.255 92 100 1.81
25 0.727 0.870 40 0.255 123 130 2.82
35 0.524 0.627 40 0.246 151 156 3.95
50 0.387 0.464 30 0.247 174 175 5.65
70 0.268 0.321 30 0.238 220 215 7.91
95 0.193 0.232 30 0.238 271 257 10.7
120 0.153 0.184 30 0.233 313 292 13.56
150 0.124 0.150 20 0.233 362 329 16.94
185 0.0991 0.121 20 0.233 411 369 20.9
240 0.0754 0.093 20 0.232 487 427 27.11
300 0.0601 0.075 20 0.231 557 480 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYCY 1 x (1.5 - 500) mm2 0.6/1 kV
Cu / PVC / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)

NYCY 1 CORE
Standard Specification : SPLN 43 - 4 : 1994 & IEC 60502 - 1

Special Features on Request: Construction Data


Fire Resistance
Copper conductor Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
PVC Insulation Area approx. approx.
Flame Retardant Non Category
PVC Inner Sheath
Copper Wire Screen Heat Resistance mm mm kg/km
Anti Termite
Black PVC Outer sheath 1.5 / 1.5 10.0 130
Anti Rodent
Low Smoke Zero Halagen 2.5 / 2.5 11.0 155
4/4 12.0 200
Note: 6/6 13.0 245
Conductor Shape 10 / 10 13.5 335
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 / 16 15.0 465
16 sqmm supplied in non compacted circular strand- 25 / 16 16.5 585
ed (rm) conductor shape
25 - 500 sqmm supplied in non compacted circular
35 / 16 17.5 695
stranded (rm) or compacted circular stranded (cm) 50 / 25 20.0 935
Application:
conductor shape
For installation in the ground, indoors, cable 70 / 35 22.0 1,245
trunking and outdoors if subsequent mechanical Standard Packing
95 / 50 24.0 1,675
damage is likely, for urban networks, household 1.5 - 240 sqmm supplied in wooden drum @ 1000
meters 120 / 70 26.0 2,110
feeder and street lighting.
300 - 500 sqmm supplied in wooden drum on 150 / 70 28.0 2,415
available length
Length Tolerance per drum 2% 185 / 95 31.0 3,030
240 / 120 34.0 3,885
300 / 150 38.0 4,815
400 / 185 42.0 6,095
500 / 240 47.0 7,725
Electrical Data
Conductor Insulation Inductance Current - Carrying Capacity at 30 C *
Short
Nom DC AC Insulation Trefoil formation Flat formation Circuit current
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground in air in ground Max.
Area Max. Max. Min. Max. Max. Max. Max. (kA)
mm (/km) (/km) (M..km) (mH/km) (mH/km) (A) (A) (A) (A)
1.5 / 1.5 12.1 14.478 50 0.455 0.601 24 27 24 28 0.17
2.5 / 2.5 7.41 8.866 50 0.514 0.561 31 35 32 36 0.28
4/4 4.61 5.516 50 0.485 0.531 41 46 42 47 0.45
6/6 3.08 3.685 50 0.457 0.503 52 57 53 59 0.68
10 / 10 1.83 2.190 50 0.420 0.466 70 76 72 78 1.13
16 / 16 1.15 1.376 40 0.399 0.445 94 99 96 101 1.81
25 / 16 0.727 0.870 40 0.373 0.419 124 127 127 130 2.82
35 / 16 0.524 0.627 40 0.355 0.401 151 152 155 156 3.95
50 / 25 0.387 0.463 30 0.345 0.391 185 181 190 185 5.65
70 / 35 0.268 0.321 30 0.329 0.375 232 221 237 226 7.91
95 / 50 0.193 0.232 30 0.322 0.368 284 263 290 267 10.7
120 / 70 0.153 0.184 30 0.316 0.363 329 297 334 300 13.56
150 / 70 0.124 0.150 20 0.310 0.357 373 331 378 333 16.94
185 / 95 0.0991 0.121 20 0.305 0.351 426 368 429 368 20.9
240 / 120 0.0754 0.093 20 0.298 0.344 495 416 495 412 27.11
300 / 150 0.0601 0.075 20 0.294 0.340 555 455 550 447 33.89
400 / 185 0.0470 0.061 20 0.293 0.339 624 497 615 485 40.06
500 / 240 0.0366 0.049 20 0.289 0.335 694 537 684 523 50.08
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYCY 2 x (1.5 - 300) mm2 0.6/1 kV
Cu / PVC / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)

NYCY 2 CORE
Standard Specification : SPLN 43 - 4 : 1994 & IEC 60502 - 1

Copper conductor
Special Features on Request: Construction Data
Fire Resistance
Oil Resistance Nom Overall Cable
PVC Insulation UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
PVC Inner sheath
Flame Retardant Non Category Area approx. approx.
Copper Wire Screen
Heat Resistance mm mm kg/km
Anti Termite
1.5 / 1.5 13.5 220
Anti Rodent
Black PVC Outer sheath 2.5 / 2.5 14.5 265
Low Smoke Zero Halagen
4/4 16.5 365
Note: 6/6 17.5 445
Conductor Shape 10 / 10 19.5 615
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 / 16 22.0 845
16 sqmm supplied in non compacted circular strand- 25 / 16 25.0 1,150
ed (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular
35 / 16 27.5 1,425
stranded (rm) or compacted circular stranded (cm) 50 / 25 31.5 1,895
conductor shape
70 / 35 35.5 2,565
Application: Standard Packing
95 / 50 41.0 3,505
For installation in the ground, indoors, cable 1.5 - 120 sqmm supplied in wooden drum @ 1000
meters 120 / 70 44.5 4,350
trunking and outdoors if subsequent mechanical
150 - 300 sqmm supplied in wooden drum on 150 / 70 48.5 5,155
damage is likely, for urban networks, household available length
feeder and street lighting. Length Tolerance per drum 2% 185 / 95 54.5 6,490
240 / 120 61.0 8,355
300 / 150 67.5 10,345

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 / 1.5 12.1 14.478 50 0.328 21 27 0.17
2.5 / 2.5 7.41 8.866 50 0.304 29 36 0.28
4/4 4.61 5.516 50 0.303 38 47 0.45
6/6 3.08 3.685 50 0.288 48 59 0.68
10 / 10 1.83 2.190 50 0.269 66 78 1.13
16 / 16 1.15 1.376 40 0.255 90 102 1.81
25 / 16 0.727 0.870 40 0.255 120 134 2.82
35 / 16 0.524 0.627 40 0.246 150 180 3.95
50 / 25 0.387 0.464 30 0.247 180 210 5.65
70 / 35 0.268 0.321 30 0.238 230 260 7.91
95 / 50 0.193 0.232 30 0.238 280 315 10.7
120 / 70 0.153 0.184 30 0.233 320 320 13.56
150 / 70 0.124 0.150 20 0.233 375 355 16.94
185 / 95 0.0991 0.121 20 0.233 430 409 20.9
240 / 120 0.0754 0.093 20 0.232 510 472 27.11
300 / 150 0.0601 0.075 20 0.231 590 525 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYCY 3 x (1.5 - 300) mm2 0.6/1 kV
Cu / PVC / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)

NYCY 3 CORE
Standard Specification : SPLN 43 - 4 : 1994 & IEC 60502 - 1

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
PVC Insulation Flame Retardant Non Category Area approx. approx.
PVC Inner sheath Heat Resistance mm mm kg/km
Copper Wire Screen
Anti Termite
1.5 / 1.5 14.0 245
Anti Rodent
Black PVC Outer sheath Low Smoke Zero Halagen 2.5 / 2.5 15.0 305
4/4 17.0 420
Note: 6/6 18.5 520
Conductor Shape 10 / 10 20.5 735
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 / 16 23.0 1,015
16 sqmm supplied in non compacted circular strand- 25 / 16 27.0 1,405
ed (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular
35 / 16 29.0 1,775
stranded (rm) or compacted circular stranded (cm) 50 / 25 33.5 2,370
Application:
conductor shape
For installation in the ground, indoors, cable 70 / 35 38.0 3,240
trunking and outdoors if subsequent mechanical Standard Packing
95 / 50 44.0 4,425
damage is likely, for urban networks, household 1.5 - 95 sqmm supplied in wooden drum @ 1000
meters 120 / 70 47.5 5,480
feeder and street lighting.
120 - 300 sqmm supplied in wooden drum on 150 / 70 52.5 6,590
available length
Length Tolerance per drum 2% 185 / 95 58.0 8,225
240 / 120 65.5 10,675
300 / 150 73.0 13,255

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 / 1.5 12.1 14.478 50 0.328 18 24 0.17
2.5 / 2.5 7.41 8.866 50 0.304 25 32 0.28
4/4 4.61 5.516 50 0.303 34 41 0.45
6/6 3.08 3.685 50 0.288 44 52 0.68
10 / 10 1.83 2.190 50 0.269 60 69 1.13
16 / 16 1.15 1.376 40 0.255 80 89 1.81
25 / 16 0.727 0.870 40 0.255 105 116 2.82
35 / 16 0.524 0.627 40 0.246 130 138 3.95
50 / 25 0.387 0.464 30 0.247 160 165 5.65
70 / 35 0.268 0.321 30 0.238 200 205 7.91
95 / 50 0.193 0.232 30 0.238 245 245 10.7
120 / 70 0.153 0.184 30 0.233 285 285 13.56
150 / 70 0.124 0.150 20 0.233 325 315 16.94
185 / 95 0.0991 0.121 20 0.233 370 355 20.9
240 / 120 0.0754 0.093 20 0.232 435 415 27.11
300 / 150 0.0601 0.075 20 0.231 600 535 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYCY 4 x (1.5 - 300) mm2 0.6/1 kV
Cu / PVC / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)

NYCY 4 CORE
Standard Specification : SPLN 43 - 4 : 1994 & IEC 60502 - 1

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
Copper conductor
Heat Resistance mm mm kg/km
Anti Termite
PVC Insulation 1.5 / 1.5 15.0 290
PVC Inner sheath
Anti Rodent
Copper Wire Screen Low Smoke Zero Halagen 2.5 / 2.5 16.0 365
4/4 18.5 510
Black PVC Outer sheath
Note: 6/6 19.5 635
Conductor Shape 10 / 10 22.0 900
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 / 16 25.0 1,255
16 sqmm supplied in non compacted circular strand- 25 / 16 29.0 1,770
ed (rm) conductor shape
25 - 35 sqmm supplied in non compacted circular
35 / 16 31.5 2,245
stranded (rm) or compacted circular stranded (cm) 50 / 25 34.5 2,760
conductor shape
Application: 70 / 35 38.5 3,725
50 - 300 sqmm supplied in non compacted circular
For installation in the ground, indoors, cable stranded (rm) or compacted circular stranded (cm) or
95 / 50 44.5 5,085
trunking and outdoors if subsequent mechanical sector shaped stranded (sm) conductor
120 / 70 48.0 6,330
damage is likely, for urban networks, household
Standard Packing
feeder and street lighting. 150 / 70 53.5 7,585
1.5 - 70 sqmm supplied in wooden drum @ 1000
meters 185 / 95 59.0 9,500
95 - 300 sqmm supplied in wooden drum on
240 / 120 66.0 12,260
available length
Length Tolerance per drum 2% 300 / 150 73.0 15,230

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 / 1.5 12.1 14.478 50 0.328 18 24 0.17
2.5 / 2.5 7.41 8.866 50 0.304 25 32 0.28
4/4 4.61 5.516 50 0.303 34 41 0.45
6/6 3.08 3.685 50 0.288 44 52 0.68
10 / 10 1.83 2.190 50 0.269 60 69 1.13
16 / 16 1.15 1.376 40 0.255 80 89 1.81
25 / 16 0.727 0.870 40 0.255 105 116 2.82
35 / 16 0.524 0.627 40 0.246 130 138 3.95
50 / 25 0.387 0.464 30 0.247 160 165 5.65
70 / 35 0.268 0.321 30 0.238 200 205 7.91
95 / 50 0.193 0.232 30 0.238 245 245 10.7
120 / 70 0.153 0.184 30 0.233 285 285 13.56
150 / 70 0.124 0.150 20 0.233 325 315 16.94
185 / 95 0.0991 0.121 20 0.233 370 355 20.9
240 / 120 0.0754 0.093 20 0.232 435 415 27.11
300 / 150 0.0601 0.075 20 0.231 500 465 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYFGbY 2 x (25 - 300) mm2 0.6/1 kV
Cu / PVC / SFA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Armor, PVC Sheathed)

NYFGbY 2 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 : 1994

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Insulation
Heat Resistance mm mm kg/km
PVC Inner sheath Anti Termite
Galvanized Steel Flat 25 25.5 1,500
Anti Rodent
Galvanized Steel tape
Low Smoke Zero Halagen 35 28.0 1,830
Black PVC Outer sheath
50 32.0 2,345
Note: 70 36.0 3,060
Conductor Shape 95 40.5 3,975
25 - 300 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm) 120 44.0 4,730
conductor shape 150 48.5 5,720

Standard Packing 185 53.5 6,930


25 - 95 sqmm supplied in wooden drum @ 1000 240 60.0 8,790
Application:
meters
For installation in ground, indoors, cable trunking 300 66.0 10,705
120 - 300 sqmm supplied in wooden drum on
and outdoors if increased mechanical protection available length
is required or where high-pulling stress may occur Length Tolerance per drum 2%
during installation or operation.

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
25 0.727 0.870 40 0.255 120 134 2.82
35 0.524 0.627 40 0.246 150 160 3.95
50 0.387 0.464 30 0.247 180 187 5.65
70 0.268 0.321 30 0.238 230 230 7.91
95 0.193 0.232 30 0.238 275 280 10.7
120 0.153 0.184 30 0.233 320 320 13.56
150 0.124 0.150 20 0.233 375 355 16.94
185 0.0991 0.121 20 0.233 430 409 20.9
240 0.0754 0.093 20 0.232 510 472 27.11
300 0.0601 0.075 20 0.231 590 525 33.89

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYFGbY 3 x (25 - 400) mm2 0.6/1 kV
Cu / PVC / SFA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Armor, PVC Sheathed)

NYFGbY 3 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 : 1994

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Copper conductor
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Insulation
PVC Inner sheath
Heat Resistance mm mm kg/km
Galvanized Steel Flat Anti Termite
Galvanized Steel Tape 25 27.0 1,800
Anti Rodent
Low Smoke Zero Halagen 35 29.5 2,235
Black PVC Outer sheath
50 34.0 2,830
Note: 70 38.0 3,725
Conductor Shape 95 43.0 4,925
25 - 300 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm) 120 47.0 5,895
conductor shape 150 52.0 7,145

Standard Packing 185 57.0 8,705


25 - 70 sqmm supplied in wooden drum @ 1000 240 64.0 11,155
Application:
meters
For installation in ground, indoors, cable trunking 300 71.0 13,575
95 - 400 sqmm supplied in wooden drum on
and outdoors if increased mechanical protection available length
400 79.0 17,315
is required or where high-pulling stress may occur Length Tolerance per drum 2%
during installation or operation.

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
25 0.727 0.870 40 0.255 120 134 2.82
35 0.524 0.627 40 0.246 150 160 3.95
50 0.387 0.464 30 0.247 180 187 5.65
70 0.268 0.321 30 0.238 230 230 7.91
95 0.193 0.232 30 0.238 275 280 10.7
120 0.153 0.184 30 0.233 320 320 13.56
150 0.124 0.150 20 0.233 375 355 16.94
185 0.0991 0.121 20 0.233 430 409 20.9
240 0.0754 0.093 20 0.232 510 472 27.11
300 0.0601 0.075 20 0.231 590 525 33.89
400 0.0470 0.060 20 0.229 600 535 40.06

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYFGbY 4 x (16 - 400) mm2 0.6/1 kV
Cu / PVC / SFA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Armor, PVC Sheathed)

NYFGbY 4 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 : 1994

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Insulation
Heat Resistance mm mm kg/km
PVC Inner sheath
Galvanized Steel Flat Anti Termite
16 25.0 1,585
Galvanized Steel Tape Anti Rodent
Low Smoke Zero Halagen 25 29.0 2,150
Black PVC Outer sheath
35 32.0 2,704
Note: 50 34.5 3,175
Conductor Shape 70 38.5 4,135
16 sqmm supplied in non compacted circular strand-
ed (rm) conductor shape 95 44.0 5,455
25 - 35 sqmm supplied in non compacted circular 120 48.0 6,610
stranded (rm) or compacted circular stranded (cm)
conductor shape 150 53.0 7,965
50 - 400 sqmm supplied in non compacted circular 185 58.5 9,830
Application:
stranded (rm) or compacted circular stranded (cm) or
For installation in ground, indoors, cable trunking sector shaped stranded (sm) conductor 240 65.0 12,435
and outdoors if increased mechanical protection
300 71.0 15,240
is required or where high-pulling stress may occur Standard Packing
16 - 50 sqmm supplied in wooden drum @ 1000 400 80.0 19,310
during installation or operation.
meters

70 - 400 sqmm supplied in wooden drum on
available length
Length Tolerance per drum 2%

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
16 1.15 1.376 40 0.255 80 89 1.81
25 0.727 0.870 40 0.255 105 116 2.82
35 0.524 0.627 40 0.246 130 138 3.95
50 0.387 0.464 30 0.247 160 165 5.65
70 0.268 0.321 30 0.238 200 205 7.91
95 0.193 0.232 30 0.238 245 245 10.7
120 0.153 0.184 30 0.233 285 280 13.56
150 0.124 0.150 20 0.233 325 315 16.94
185 0.0991 0.121 20 0.233 370 355 20.9
240 0.0754 0.093 20 0.232 435 415 27.11
300 0.0601 0.075 20 0.231 500 465 33.89
400 0.0470 0.060 20 0.229 600 535 40.06

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYFGbY 5 x (16 - 50) mm2 0.6/1 kV
Cu / PVC / SFA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Armor, PVC Sheathed)

NYFGbY 5 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 : 1994

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Copper conductor
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Insulation Heat Resistance mm mm kg/km
Anti Termite
PVC Inner Sheath 16 27.0 1,835
Galvanized Steel Flat Anti Rodent
Galvanized Steel Tape Low Smoke Zero Halagen 25 32.0 2,585
Black PVC Outer sheath 35 35.5 3,285
Note: 50 40.5 4,250
Conductor Shape
16 sqmm supplied in non compacted circular strand-
ed (rm) conductor shape
25 - 50 sqmm supplied in non compacted circular
stranded (rm) or compacted circular stranded (cm)
conductor shape

Application:
Standard Packing
For installation in ground, indoors, cable trunking
16 - 50 sqmm supplied in wooden drum @ 1000
and outdoors if increased mechanical protection meters
is required or where high-pulling stress may occur Length Tolerance per drum 2%
during installation or operation.

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
16 1.15 1.376 40 0.255 80 89 1.81
25 0.727 0.870 40 0.255 105 116 2.82
35 0.524 0.627 40 0.246 130 138 3.95
50 0.387 0.464 30 0.247 160 165 5.65

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYM 2 x (1.5 - 35) mm2 300 /500 V
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)

NYM 2 CORE
Standard Specification : SPLN 42 - 2 : 1992 & SNI 04 - 6629.4 : 2006

Special Features on Request: Construction Data


Fire Resistance
Copper conductor Oil Resistance Nom Overall Cable
PVC Insulation Flame Retardant Cat. A, B, C Cross Section Diameter Weight
PVC filler extruded Flame Retardant Non Category
White PVC Outer sheath Area approx. approx.

Note: mm mm kg/km

Conductor Shape 1.5 9.0 116


1.5 - 10 sqmm supplied in solid (re) or non compacted 2.5 10.5 157
circular stranded (rm) conductor shape
16 - 35 sqmm supplied in non compacted circular 4 11.5 205
stranded (rm) conductor shape
6 12.5 265
Standard Packing 10 16.0 425
1.5 - 4 sqmm supplied in coil @ 100 meters or in 16 19.0 640
wooden drum @ 1000/2000 meters
Application: 6 - 35 sqmm supplied in wooden drum @ 1000 25 23.0 965
meters
For building wire installed in donduit in dry 35 25.5 1,290
Length Tolerance per drum 2%
location and interwiring in swich board and control
panel, inherently flame retardant in compliance
with IEC 60332 - 1.

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 70 C in air Max.
Area Max. Max. Min. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A)
1.5 12.1 14.478 0.0100 0.329 19 0.17
2.5 7.41 8.866 0.0900 0.318 25 0.28
4 4.61 5.516 0.0077 0.297 34 0.45
6 3.08 3.685 0.0065 0.281 44 0.68
10 1.83 2.190 0.0065 0.278 61 1.13
16 1.15 1.376 0.0052 0.255 82 1.81
25 0.727 0.870 0.0050 0.252 108 2.82
35 0.524 0.627 0.0044 0.244 134 3.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYM 3 x (1.5 - 35) mm2 300 /500 V
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)

NYM 3 CORE
Standard Specification : SPLN 42 - 2 : 1992 & SNI 04 - 6629.4 : 2006

Special Features on Request: Construction Data


Copper conductor Fire Resistance
Oil Resistance Nom Overall Cable
PVC Insulation
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
PVC filler extruded
Flame Retardant Non Category
White PVC Outer sheath Area approx. approx.

Note: mm mm kg/km

Conductor Shape 1.5 9.5 135


1.5 - 10 sqmm supplied in solid (re) or non compacted 2.5 11.0 185
circular stranded (rm) conductor shape
16 - 35 sqmm supplied in non compacted circular 4 12.0 250
stranded (rm) conductor shape
6 13.5 335
Standard Packing 10 16.5 530
1.5 - 4 sqmm supplied in coil @ 100 meters or in 16 20.0 820
wooden drum @ 1000/2000 meters
6 - 35 sqmm supplied in wooden drum @ 1000 25 24.0 1,235
meters
35 27.0 1,630
Length Tolerance per drum 2%
Application:
For building wire installed in donduit in dry
location and interwiring in swich board and control
panel, inherently flame retardant in compliance
with IEC 60332 - 1.

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 70 C in air Max.
Area Max. Max. Min. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A)
1.5 12.1 14.478 0.0100 0.329 19 0.17
2.5 7.41 8.866 0.0900 0.318 25 0.28
4 4.61 5.516 0.0085 0.297 34 0.45
6 3.08 3.685 0.0065 0.281 44 0.68
10 1.83 2.190 0.0065 0.278 61 1.13
16 1.15 1.376 0.0052 0.255 82 1.81
25 0.727 0.870 0.0050 0.252 108 2.82
35 0.524 0.627 0.0044 0.244 134 3.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYM 4 x (1.5 - 35) mm2 300 /500 V
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)

NYM 4 CORE
Standard Specification : SPLN 42 - 2 : 1992 & SNI 04 - 6629.4 : 2006

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
PVC Insulation
Flame Retardant Non Category
PVC filler extruded
Area approx. approx.
White PVC Outer sheath
Note: mm mm kg/km

Conductor Shape 1.5 10.5 165


1.5 - 10 sqmm supplied in solid (re) or non compacted 2.5 11.5 225
circular stranded (rm) conductor shape
16 - 35 sqmm supplied in non compacted circular 4 13.0 315
stranded (rm) conductor shape
6 14.5 410
Standard Packing 10 18.0 655
1.5 - 2.5 sqmm supplied in coil @ 100 meters or in 16 22.0 1,020
wooden drum @ 1000/2000 meters
4 - 35 sqmm supplied in wooden drum @ 1000 25 27.0 1,570
meters
35 29.5 2,045
Length Tolerance per drum 2%
Application:
For building wire installed in donduit in dry
location and interwiring in swich board and control
panel, inherently flame retardant in compliance
with IEC 60332 - 1.

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 70 C in air Max.
Area Max. Max. Min. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A)
1.5 12.1 14.478 0.0100 0.329 19 0.17
2.5 7.41 8.866 0.0900 0.318 25 0.28
4 4.61 5.516 0.0077 0.297 34 0.45
6 3.08 3.685 0.0065 0.281 44 0.68
10 1.83 2.190 0.0065 0.278 61 1.13
16 1.15 1.376 0.0052 0.255 82 1.81
25 0.727 0.870 0.0050 0.252 108 2.82
35 0.524 0.627 0.0044 0.244 134 3.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYM 5 x (1.5 - 35) mm2 300 /500 V
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)

NYM 5 CORE
Standard Specification : SPLN 42 - 2 : 1992 & SNI 04 - 6629.4 : 2006

Special Features on Request: Construction Data


Copper conductor Fire Resistance
PVC Insulation Oil Resistance Nom Overall Cable
Flame Retardant Cat. A, B, C Cross Section Diameter Weight
PVC filler extruded
Flame Retardant Non Category
Area approx. approx.
White PVC Outer sheath
Note: mm mm kg/km

Conductor Shape 1.5 11.0 195


1.5 - 10 sqmm supplied in solid (re) or non compacted 2.5 12.5 275
circular stranded (rm) conductor shape
16 - 35 sqmm supplied in non compacted circular 4 15.0 395
stranded (rm) conductor shape
6 16.0 515
Standard Packing 10 19.5 800
1.5 - 2.5 sqmm supplied in coil @ 100 meters or in 16 24.5 1,270
wooden drum @ 1000/2000 meters
4 - 35 sqmm supplied in wooden drum @ 1000 25 29.5 1,930
meters
35 33.0 2,550
Length Tolerance per drum 2%
Application:
For building wire installed in donduit in dry
location and interwiring in swich board and control
panel, inherently flame retardant in compliance
with IEC 60332 - 1.

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 70 C in air Max.
Area Max. Max. Min. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A)
1.5 12.1 14.478 0.0100 0.329 19 0.17
2.5 7.41 8.866 0.0900 0.318 25 0.28
4 4.61 5.516 0.0077 0.297 34 0.45
6 3.08 3.685 0.0065 0.281 44 0.68
10 1.83 2.190 0.0065 0.278 61 1.13
16 1.15 1.376 0.0052 0.255 82 1.81
25 0.727 0.870 0.0050 0.252 108 2.82
35 0.524 0.627 0.0044 0.244 134 3.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYR(AL)Y 1 x (10 - 500) mm2 0.6/1 kV
Cu / PVC / AWA / PVC
(Copper Conductor, PVC Insulated, Aluminium Wire Armor, PVC Sheathed)

NYR(AL)Y 1 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 ; 1994

Special Features on Request: Construction Data


Fire Resistance
Copper conductor Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
PVC Insulation Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Inner Sheath
Aluminium Wire Armor Heat Resistance mm mm kg/km
Polyester Binder Tape
Anti Termite
Black PVC Outer sheath 10 13.5 285
Anti Rodent
Low Smoke Zero Halagen 16 14.5 365
25 16.5 495
Note: 35 17.5 610
Conductor Shape 50 19.0 765
10 - 16 sqmm supplied in non compacted circular
stranded (rm) conductor shape 70 21.0 995
25 - 500 sqmm supplied in non compacted circular 95 23.5 1,300
stranded (rm) or compacted circular stranded (cm)
conductor shape 120 26.5 1,680
Application: 150 28.5 2,000
Standard Packing
For installation in ground, indoors, cable trunking 185 31.0 2,415
10 - 300 sqmm supplied in wooden drum @ 1000
and outdoors if increased mechanical protection meters
240 34.0 3,070
is required or where high-pulling stress may occur 400 - 500 sqmm supplied in wooden drum on
available length 300 37.0 3,745
during installation or operation.
Length Tolerance per drum 2% 400 42.0 4,835
500 46.0 5,970

Electrical Data
Conductor Insulation Inductance Current - Carrying Capacity at 30 C *
Short
Nom DC AC Insulation Trefoil formation Flat formation Circuit current
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground in air in ground Max.
Area Max. Max. Min. Max. Max. Max. Max. (kA)
mm (/km) (/km) (M..km) (mH/km) (mH/km) (A) (A) (A) (A)
10 1.83 2.190 50 0.460 0.506 75 77 77 80 1.13
16 1.15 1.376 40 0.429 0.475 98 100 101 103 1.81
25 0.727 0.870 40 0.401 0.447 129 128 133 132 2.82
35 0.524 0.627 40 0.382 0.428 157 153 161 158 3.95
50 0.387 0.463 30 0.364 0.410 190 181 195 186 5.65
70 0.268 0.321 30 0.345 0.391 237 221 243 227 7.91
95 0.193 0.232 30 0.333 0.379 290 264 296 270 10.7
120 0.153 0.184 30 0.325 0.371 335 299 342 304 13.56
150 0.124 0.150 20 0.318 0.365 380 333 386 338 16.94
185 0.0991 0.120 20 0.310 0.356 435 374 441 378 20.90
240 0.0754 0.093 20 0.302 0.348 510 428 514 429 27.11
300 0.0601 0.075 20 0.296 0.342 579 476 581 474 33.89
400 0.0470 0.060 20 0.296 0.342 652 521 646 512 40.06
500 0.0366 0.049 20 0.289 0.335 734 572 721 557 50.08

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYRGbY 2 x (10 - 300) mm2 0.6/1 kV
Cu / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed)

NYRGbY 2 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 : 1994

Copper conductor Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
PVC Insulation
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Inner Sheath
Heat Resistance mm mm kg/km
Galvanized Steel Wire Armor Anti Termite
10 20.0 850
Anti Rodent
Galvanized Steel Tape Low Smoke Zero Halagen 16 22.0 1,070
25 27.0 1,775

Black PVC Outer sheath


Note: 35 29.5 2,135
Conductor Shape 50 33.0 2,650
10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 37.5 3,580
16 sqmm supplied in non compacted circular strand- 95 43.0 4,695
ed (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular
120 46.5 5,500
stranded (rm) or compacted circular stranded (cm) 150 52.0 6,920
conductor shape
185 57.0 8,345
Standard Packing
240 63.5 10,355
10 - 70 sqmm supplied in wooden drum @ 1000
meters 300 69.5 12,455
Application:
95 - 300 sqmm supplied in wooden drum on
For installation in ground, indoors, cable trunking available length
and outdoors if increased mechanical protection Length Tolerance per drum 2%
is required or where high-pulling stress may occur
during installation or operation.

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
10 1.83 2.190 50 0.269 66 78 1.13
16 1.15 1.376 40 0.255 90 102 1.81
25 0.727 0.870 40 0.255 120 134 2.82
35 0.524 0.627 40 0.246 150 160 3.95
50 0.387 0.464 30 0.247 180 187 5.65
70 0.268 0.321 30 0.238 230 230 7.91
95 0.193 0.232 30 0.238 275 280 10.7
120 0.153 0.184 30 0.233 320 320 13.56
150 0.124 0.150 20 0.233 375 355 16.94
185 0.0991 0.121 20 0.233 430 409 20.9
240 0.0754 0.093 20 0.232 510 472 27.11
300 0.0601 0.075 20 0.231 590 525 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYRGbY 3 x (10 - 400) mm2 0.6/1 kV
Cu / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed)

NYRGbY 3 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 : 1994

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
PVC Insulation
Flame Retardant Non Category Area approx. approx.
PVC Inner Sheath Heat Resistance mm mm kg/km
Galvanized Steel Wire Armor
Anti Termite
10 21.0 975
Galvanized Steel Tape Anti Rodent
Low Smoke Zero Halagen 16 23.5 1,255
Black PVC Outer sheath 25 28.5 2,065
Note: 35 31.0 2,525
Conductor Shape 50 35.0 3,195
10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 40.0 4,370
16 sqmm supplied in non compacted circular strand- 95 46.0 5,675
ed (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular
120 49.5 6,720
stranded (rm) or compacted circular stranded (cm) 150 55.0 8,505
conductor shape
Application: 185 61.0 10,205
For installation in ground, indoors, cable trunking Standard Packing
240 69.0 13,555
and outdoors if increased mechanical protection 10 - 70 sqmm supplied in wooden drum @ 1000
is required or where high-pulling stress may occur meters 300 76.0 16,235
during installation or operation. 95 - 400 sqmm supplied in wooden drum on 400 84.0 20,075
available length
Length Tolerance per drum 2%

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
10 1.83 2.190 50 0.269 60 69 1.13
16 1.15 1.376 40 0.255 80 89 1.81
25 0.727 0.870 40 0.255 105 116 2.82
35 0.524 0.627 40 0.246 130 138 3.95
50 0.387 0.464 30 0.247 160 165 5.65
70 0.268 0.321 30 0.238 200 205 7.91
95 0.193 0.232 30 0.238 245 245 10.7
120 0.153 0.184 30 0.233 285 285 13.56
150 0.124 0.150 20 0.233 325 315 16.94
185 0.0991 0.121 20 0.233 370 355 20.9
240 0.0754 0.093 20 0.232 435 415 27.11
300 0.0601 0.075 20 0.231 500 465 33.89
400 0.0470 0.060 20 0.229 600 535 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYRGbY 4 x (10 - 400) mm2 0.6/1 kV
Cu / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed)

NYRGbY 4 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 : 1994

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Copper conductor
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Insulation Heat Resistance mm mm kg/km
PVC Inner Sheath Anti Termite
10 23.0 1,150
Galvanized Steel Wire Armor
Anti Rodent
Low Smoke Zero Halagen 16 27.0 1,805
Galvanized Steel Tape
25 31.0 2,455
Black PVC Outer sheath Note: 35 34.0 3,055
Conductor Shape 50 37.0 3,765
10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 70 41.0 4,790
16 sqmm supplied in non compacted circular strand- 95 48.0 6,605
ed (rm) conductor shape
25 - 35 sqmm supplied in non compacted circular
120 51.0 7,855
stranded (rm) or compacted circular stranded (cm) 150 57.0 9,345
conductor shape
50 - 400 sqmm supplied in non compacted circular 185 62.0 11,255
stranded (rm) or compacted circular stranded (cm) or
Application: 240 70.0 14,840
sector shaped stranded (sm) conductor
For installation in ground, indoors, cable trunking 300 76.0 17,885
and outdoors if increased mechanical protection Standard Packing
400 85.0 22,325
is required or where high-pulling stress may occur 10 - 50 sqmm supplied in wooden drum @ 1000
meters
during installation or operation.
70 - 400 sqmm supplied in wooden drum on
available length
Length Tolerance per drum 2%

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
10 1.83 2.190 50 0.269 60 69 1.13
16 1.15 1.376 40 0.255 80 89 1.81
25 0.727 0.870 40 0.255 105 116 2.82
35 0.524 0.627 40 0.246 130 138 3.95
50 0.387 0.464 30 0.247 160 165 5.65
70 0.268 0.321 30 0.238 200 205 7.91
95 0.193 0.232 30 0.238 245 245 10.7
120 0.153 0.184 30 0.233 285 285 13.56
150 0.124 0.150 20 0.233 325 315 16.94
185 0.0991 0.121 20 0.233 370 355 20.9
240 0.0754 0.093 20 0.232 435 415 27.11
300 0.0601 0.075 20 0.231 500 465 33.89
400 0.0470 0.060 20 0.229 600 535 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYSY 1 x (1.5 - 500) mm2 0.6/1 kV
Cu / PVC / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)

NYSY 1 CORE
Standard Specification : IEC 60502 - 1

Special Features on Request: Construction Data


Copper conductor Fire Resistance
Oil Resistance Nom Overall Cable
PVC Insulation
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
PVC Inner Sheath
Flame Retardant Non Category Area approx. approx.
Copper Tape Screen
Non-hygroscopic tape Heat Resistance mm mm kg/km
Anti Termite
Black PVC Outer sheath 1.5 9.0 120
Anti Rodent
Low Smoke Zero Halagen 2.5 9.5 140
4 10.5 175
Note: 6 11.0 205
Conductor Shape 10 12.0 260
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 13.0 335
16 sqmm supplied in non compacted circular strand- 25 15.0 460
ed (rm) conductor shape
25 - 500 sqmm supplied in non compacted circular
35 16.0 575
stranded (rm) or compacted circular stranded (cm) 50 17.5 725
Application:
conductor shape
For power plants and switchgear as well as for 70 19.5 950
installation of sub-station; for installation indoors Standard Packing
95 22.0 1,260
in confinned spaces and cable channels because 1.5 - 300 sqmm supplied in wooden drum @ 1000
meters 120 23.5 1,520
of small bending radius. As buried cable, because
400 - 500 sqmm supplied in wooden drum on 150 25.5 1,830
of its light weight prefered in where installation
available length
is difficult. Length Tolerance per drum 2% 185 28.0 2,235
240 31.0 2,865
300 34.5 3,550
400 38.0 4,490
500 42.0 5,605
Electrical Data
Conductor Insulation Inductance Current - Carrying Capacity at 30 C *
Short
Nom DC AC Insulation Trefoil formation Flat formation Circuit current
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground in air in ground Max.
Area Max. Max. Min. Max. Max. Max. Max. (kA)
mm (/km) (/km) (M..km) (mH/km) (mH/km) (A) (A) (A) (A)
1.5 12.1 14.478 50 0.531 0.577 23 26 23 27 0.17
2.5 7.41 8.866 50 0.491 0.537 30 35 31 36 0.28
4 4.61 5.516 50 0.464 0.510 40 45 40 47 0.45
6 3.08 3.685 50 0.436 0.483 50 56 51 58 0.68
10 1.83 2.190 50 0.401 0.447 68 75 70 77 1.13
16 1.15 1.376 40 0.374 0.420 89 97 92 100 1.81
25 0.727 0.870 40 0.352 0.399 119 125 122 129 2.82
35 0.524 0.627 40 0.336 0.382 146 150 150 155 3.95
50 0.387 0.463 30 0.323 0.369 178 179 183 184 5.65
70 0.268 0.321 30 0.307 0.353 224 219 230 225 7.91
95 0.193 0.232 30 0.298 0.345 276 262 284 269 10.7
120 0.153 0.184 30 0.289 0.335 320 299 329 306 13.56
150 0.124 0.150 20 0.285 0.331 366 335 376 343 16.94
185 0.0991 0.12 20 0.280 0.326 424 379 436 388 20.9
240 0.0754 0.093 20 0.273 0.319 505 439 518 448 27.11
300 0.0601 0.075 20 0.270 0.316 581 493 596 503 33.89
400 0.0470 0.060 20 0.268 0.314 672 557 689 567 40.06
500 0.0366 0.049 20 0.263 0.310 776 626 793 636 50.08
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYSY 2 x (1.5 - 300) mm2 0.6/1 kV
Cu / PVC / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)

NYSY 2 CORE
Standard Specification : IEC 60502 - 1

Copper conductor
Special Features on Request: Construction Data
Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
PVC Insulation
Flame Retardant Cat. A, B, C
PVC Inner Sheath Area approx. approx.
Flame Retardant Non Category
Copper Tape Screen Heat Resistance mm mm kg/km
Non-hygroscopic tape Anti Termite
1.5 12.5 235
Anti Rodent
Black PVC Outer sheath Low Smoke Zero Halagen 2.5 13.0 280
4 15.0 375
Note: 6 16.0 445
Conductor Shape 10 18.0 590
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 20.0 780
16 sqmm supplied in non compacted circular strand- 25 23.5 1,115
ed (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular
35 26.0 1,405
stranded (rm) or compacted circular stranded (cm) 50 30.0 1,830
conductor shape
Application: 70 34.0 2,465
Standard Packing
For power plants and switchgear as well as for 95 38.5 3,310
1.5 - 120 sqmm supplied in wooden drum @ 1000
installation of sub-station; for installation indoors 120 42.5 4,015
meters
in confinned spaces and cable channels because 150 - 300 sqmm supplied in wooden drum on 150 47.0 4,935
of small bending radius. As buried cable, because available length
of its light weight prefered in where installation Length Tolerance per drum 2% 185 52.0 6,055
is difficult. 240 58.5 7,855
300 64.5 9,625

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 50 0.328 23 28 0.17
2.5 7.41 8.866 50 0.304 31 37 0.28
4 4.61 5.516 50 0.303 41 48 0.45
6 3.08 3.685 50 0.288 52 60 0.68
10 1.83 2.190 50 0.269 71 81 1.13
16 1.15 1.376 40 0.255 94 105 1.81
25 0.727 0.870 40 0.255 123 135 2.82
35 0.524 0.627 40 0.246 152 163 3.95
50 0.387 0.464 30 0.247 183 193 5.65
70 0.268 0.321 30 0.238 231 238 7.91
95 0.193 0.232 30 0.238 282 283 10.7
120 0.153 0.184 30 0.233 327 323 13.56
150 0.124 0.150 20 0.233 373 362 16.94
185 0.0991 0.121 20 0.233 426 407 20.9
240 0.0754 0.093 20 0.232 502 470 27.11
300 0.0601 0.075 20 0.231 572 527 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYSY 3 x (1.5 - 300) mm2 0.6/1 kV
Cu / PVC / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)

NYSY 3 CORE
Standard Specification : IEC 60502 - 1

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Copper conductor
Flame Retardant Non Category Area approx. approx.
Heat Resistance mm mm kg/km
PVC Insulation
Anti Termite
PVC Inner Sheath
1.5 13.0 260
Anti Rodent
Copper Tape Screen Low Smoke Zero Halagen 2.5 14.0 315
Non-hygroscopic tape
4 16.0 430
Black PVC Outer sheath
Note: 6 17.0 520
Conductor Shape 10 19.0 705
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 21.5 945
16 sqmm supplied in non compacted circular strand- 25 25.0 1,365
ed (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular
35 27.5 1,750
stranded (rm) or compacted circular stranded (cm) 50 32.0 2,330
Application: conductor shape
70 36.0 3,115
For power plants and switchgear as well as for
Standard Packing
installation of sub-station; for installation indoors 95 41.5 4,205
1.5 - 95 sqmm supplied in wooden drum @ 1000
in confinned spaces and cable channels because meters 120 45.5 5,180
of small bending radius. As buried cable, because 120 - 300 sqmm supplied in wooden drum on 150 50.0 6,305
available length
of its light weight prefered in where installation
Length Tolerance per drum 2% 185 56.0 7,825
is difficult.
240 63.0 10,090
300 69.0 12,400

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 50 0.328 20 24 0.17
2.5 7.41 8.866 50 0.304 26 31 0.28
4 4.61 5.516 50 0.303 35 41 0.45
6 3.08 3.685 50 0.288 44 51 0.68
10 1.83 2.190 50 0.269 60 68 1.13
16 1.15 1.376 40 0.255 80 89 1.81
25 0.727 0.870 40 0.255 106 114 2.82
35 0.524 0.627 40 0.246 130 138 3.95
50 0.387 0.464 30 0.247 163 169 5.65
70 0.268 0.321 30 0.238 204 207 7.91
95 0.193 0.232 30 0.238 251 248 10.7
120 0.153 0.184 30 0.233 291 283 13.56
150 0.124 0.150 20 0.233 332 316 16.94
185 0.0991 0.121 20 0.233 383 357 20.9
240 0.0754 0.093 20 0.232 452 413 27.11
300 0.0601 0.075 20 0.231 518 464 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYSY 4 x (1.5 - 300) mm2 0.6/1 kV
Cu / PVC / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)

NYSY 4 CORE
Standard Specification : IEC 60502 - 1

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Insulation
Heat Resistance mm mm kg/km
PVC Inner Sheath
Anti Termite
Copper Tape Screen 1.5 13.5 300
Anti Rodent
Non-hygroscopic tape
Low Smoke Zero Halagen 2.5 15.0 365
Black PVC Outer sheath 4 17.0 505
Note: 6 18.5 620
Conductor Shape 10 21.0 855
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 23.5 1,160
16 sqmm supplied in non compacted circular strand- 25 27.5 1,690
ed (rm) conductor shape
25 - 35 sqmm supplied in non compacted circular
35 30.5 2,190
stranded (rm) or compacted circular stranded (cm) 50 32.0 2,780
conductor shape
50 - 400 sqmm supplied in non compacted circular 70 36.5 3,725
Application: stranded (rm) or compacted circular stranded (cm) or
95 42.0 5,060
For power plants and switchgear as well as for sector shaped stranded (sm) conductor
installation of sub-station; for installation indoors 120 45.5 6,215
Standard Packing
in confinned spaces and cable channels because 150 51.0 7,570
1.5 - 70 sqmm supplied in wooden drum @ 1000
of small bending radius. As buried cable, because meters 185 56.0 9,445
of its light weight prefered in where installation 95 - 300 sqmm supplied in wooden drum on
240 62.5 12,105
is difficult. available length
Length Tolerance per drum 2% 300 68.5 14,990

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 50 0.328 22 27 0.17
2.5 7.41 8.866 50 0.304 29 36 0.28
4 4.61 5.516 50 0.303 40 47 0.45
6 3.08 3.685 50 0.288 50 58 0.68
10 1.83 2.190 50 0.269 69 78 1.13
16 1.15 1.376 40 0.255 91 100 1.81
25 0.727 0.870 40 0.255 122 130 2.82
35 0.524 0.627 40 0.246 150 155 3.95
50 0.387 0.464 30 0.247 174 174 5.65
70 0.268 0.321 30 0.238 217 213 7.91
95 0.193 0.232 30 0.238 268 256 10.7
120 0.153 0.184 30 0.233 310 290 13.56
150 0.124 0.150 20 0.233 359 328 16.94
185 0.0991 0.121 20 0.233 407 367 20.9
240 0.0754 0.093 20 0.232 483 426 27.11
300 0.0601 0.075 20 0.231 554 479 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYY 1 x (1.5 - 500) mm2 0.6/1 kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)

NYY 1 CORE
Standard Specification : SPLN 43 - 1 : 1994 & SNI IEC 60502 - 1 : 2009

Special Features on Request: Construction Data


Copper conductor Fire Resistance
Oil Resistance Nom Overall Cable
PVC Insulation UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
Black PVC Outer sheath
Heat Resistance mm mm kg/km
Anti Termite
1.5 6.0 53
Anti Rodent
Low Smoke Zero Halagen 2.5 6.5 65
4 7.5 91
Note: 6 8.0 114
Conductor Shape 10 9.0 162
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 10.0 225
16 sqmm supplied in non compacted circular strand- 25 12.0 334
ed (rm) conductor shape
25 - 500 sqmm supplied in non compacted circular
35 13.0 437
stranded (rm) or compacted circular stranded (cm) 50 14.5 571
conductor shape
Application: 70 16.5 779
Power cable : Indoors, cable trunking, outdoors Standard Packing
95 19.0 1,069
and buried in the ground, for power stations, in- 1.5 - 10 sqmm supplied in coil @ 100 meters
16 - 300 sqmm supplied in wooden drum @ 1000
120 20.5 1,315
dustry and switchgear as well as for urban supply
meters 150 23.0 1,615
networks, if mechanical damage is unlikely.
400 - 500 sqmm supplied in wooden drum on
available length 185 25.0 2,005
Length Tolerance per drum 2% 240 28.5 2,610
300 31.5 3,230
400 35.0 4,130
500 39.0 5,200
Electrical Data
Conductor Insulation Inductance Current - Carrying Capacity at 30 C *
Short
Nom DC AC Insulation Trefoil formation Flat formation Circuit current
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground in air in ground Max.
Area Max. Max. Min. Max. Max. Max. Max. (kA)
mm (/km) (/km) (M..km) (mH/km) (mH/km) (A) (A) (A) (A)
1.5 12.1 14.478 50 0.459 0.505 21 27 21 28 0.17
2.5 7.41 8.866 50 0.423 0.470 27 35 28 36 0.28
4 4.61 5.516 50 0.404 0.450 37 46 38 47 0.45
6 3.08 3.685 50 0.380 0.426 46 57 48 59 0.68
10 1.83 2.190 50 0.350 0.396 64 76 65 78 1.13
16 1.15 1.376 40 0.327 0.374 84 98 87 101 1.81
25 0.727 0.870 40 0.312 0.358 114 127 117 130 2.82
35 0.524 0.627 40 0.299 0.345 140 152 144 156 3.95
50 0.387 0.464 30 0.290 0.336 172 180 177 185 5.65
70 0.268 0.321 30 0.278 0.324 218 221 224 227 7.91
95 0.193 0.232 30 0.274 0.321 270 264 278 271 10.7
120 0.153 0.184 30 0.267 0.313 315 300 324 309 13.56
150 0.124 0.150 20 0.266 0.313 362 336 373 346 16.94
185 0.0991 0.121 20 0.264 0.310 420 379 433 391 20.9
240 0.0754 0.093 20 0.261 0.307 503 439 518 453 27.11
300 0.0601 0.075 20 0.258 0.305 580 494 598 510 33.89
400 0.0470 0.061 20 0.256 0.302 674 558 695 577 40.06
500 0.0366 0.049 20 0.252 0.299 781 629 806 650 50.08
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYY 2 x (1.5 - 500) mm2 0.6/1 kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)

NYY 2 CORE
Standard Specification : SPLN 43 - 1 : 1994 & SNI IEC 60502 - 1 : 2009

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
Copper conductor
UV Resistance Cross Section Diameter Weight
Flame Retardant Cat. A, B, C
PVC Insulation Flame Retardant Non Category Area approx. approx.
PVC Inner sheath Heat Resistance mm mm kg/km
Anti Termite
Black PVC Outer sheath 1.5 12.5 200
Anti Rodent
Low Smoke Zero Halagen 2.5 13.0 240
4 15.0 330
Note: 6 16.0 397
Conductor Shape 10 18.0 535
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 20.0 715
16 sqmm supplied in non compacted circular strand- 25 23.5 1,032
ed (rm) conductor shape
25 - 500 sqmm supplied in non compacted circular
35 26.0 1,315
stranded (rm) or compacted circular stranded (cm) 50 29.0 1,715
Application:
conductor shape
Power cable : Indoors, cable trunking, outdoors 70 33.0 2,295
and buried in the ground, for power stations, in- Standard Packing
95 38.0 3,140
dustry and switchgear as well as for urban supply 1.5 - 120 sqmm supplied in wooden drum @ 1000
meters 120 41.5 3,825
networks, if mechanical damage is unlikely.
150 - 300 sqmm supplied in wooden drum on 150 45.5 4,665
available length
Length Tolerance per drum 2% 185 51.0 5,820
240 57.5 7,520
300 63.5 9,295

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 50 0.328 21 27 0.17
2.5 7.41 8.866 50 0.304 29 36 0.28
4 4.61 5.516 50 0.303 38 47 0.45
6 3.08 3.685 50 0.288 48 59 0.68
10 1.83 2.190 50 0.269 66 78 1.13
16 1.15 1.376 40 0.255 90 102 1.81
25 0.727 0.870 40 0.255 120 134 2.82
35 0.524 0.627 40 0.246 150 160 3.95
50 0.387 0.464 30 0.247 180 187 5.65
70 0.268 0.321 30 0.238 230 230 7.91
95 0.193 0.232 30 0.238 275 280 10.7
120 0.153 0.184 30 0.233 320 320 13.56
150 0.124 0.150 20 0.233 375 355 16.94
185 0.0991 0.121 20 0.233 430 409 20.9
240 0.0754 0.093 20 0.232 510 472 27.11
300 0.0601 0.075 20 0.231 590 525 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYY 3 x (1.5 - 500) mm2 0.6/1 kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)

NYY 3 CORE
Standard Specification : SPLN 43 - 1 : 1994 & SNI IEC 60502 - 1 : 2009

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Copper conductor
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Insulation Heat Resistance mm mm kg/km
PVC Inner sheath Anti Termite
1.5 13.0 224
Anti Rodent
Black PVC Outer sheath
Low Smoke Zero Halagen 2.5 14.0 274
4 16.0 380
Note: 6 17.0 465
Conductor Shape 10 19.0 645
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 21.0 875
16 sqmm supplied in non compacted circular strand- 25 25.0 1,280
ed (rm) conductor shape
25 - 400 sqmm supplied in non compacted circular
35 27.0 1,650
stranded (rm) or compacted circular stranded (cm) 50 31.0 2,160
Application:
conductor shape
Power cable : Indoors, cable trunking, outdoors 70 35.5 2,970
and buried in the ground, for power stations, in- Standard Packing
95 41.0 4,025
dustry and switchgear as well as for urban supply 1.5 - 95 sqmm supplied in wooden drum @ 1000
meters 120 44.5 4,925
networks, if mechanical damage is unlikely.
120 - 400 sqmm supplied in wooden drum on 150 49.5 6,065
available length
Length Tolerance per drum 2% 185 54.5 7,500
240 62.0 9,785
300 69.0 12,200
400 76.5 15,415

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 50 0.328 18 24 0.17
2.5 7.41 8.866 50 0.304 25 32 0.28
4 4.61 5.516 50 0.303 34 41 0.45
6 3.08 3.685 50 0.288 44 52 0.68
10 1.83 2.190 50 0.269 60 69 1.13
16 1.15 1.376 40 0.255 80 89 1.81
25 0.727 0.870 40 0.255 105 116 2.82
35 0.524 0.627 40 0.246 130 138 3.95
50 0.387 0.464 30 0.247 160 165 5.65
70 0.268 0.321 30 0.238 200 205 7.91
95 0.193 0.232 30 0.238 245 245 10.7
120 0.153 0.184 30 0.233 285 285 13.56
150 0.124 0.150 20 0.233 325 315 16.94
185 0.0991 0.121 20 0.233 370 355 20.9
240 0.0754 0.093 20 0.232 435 415 27.11
300 0.0601 0.075 20 0.231 500 465 33.89
400 0.0470 0.060 20 0.229 600 535 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYY 4 x (1.5 - 500) mm2 0.6/1 kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)

NYY 4 CORE
Standard Specification : SPLN 43 - 1 : 1994 & SNI IEC 60502 - 1 : 2009

Special Features on Request: Construction Data


Fire Resistance
Oil Resistance Nom Overall Cable
UV Resistance Cross Section Diameter Weight
Copper conductor
Flame Retardant Cat. A, B, C
Flame Retardant Non Category Area approx. approx.
PVC Insulation Heat Resistance mm mm kg/km
PVC Inner sheath Anti Termite
1.5 13.5 260
Anti Rodent
Black PVC Outer sheath Low Smoke Zero Halagen 2.5 14.5 325
4 17.0 455
Note: 6 18.0 565
Conductor Shape 10 20.5 785
1.5 - 10 sqmm supplied in solid (re) or non compacted
circular stranded (rm) conductor shape 16 23.0 1,085
16 sqmm supplied in non compacted circular strand- 25 27.0 1,595
ed (rm) conductor shape
25 - 35 sqmm supplied in non compacted circular
35 30.0 2,070
stranded (rm) or compacted circular stranded (cm) 50 32.0 2,470
conductor shape
Application: 70 36.5 3,345
50 - 400 sqmm supplied in non compacted circular
Power cable : Indoors, cable trunking, outdoors stranded (rm) or compacted circular stranded (cm) or
95 42.0 4,545
and buried in the ground, for power stations, in- sector shaped stranded (sm) conductor
dustry and switchgear as well as for urban supply 120 45.0 5,630
Standard Packing
networks, if mechanical damage is unlikely. 150 51.0 6,850
1.5 - 70 sqmm supplied in wooden drum @ 1000
meters 185 56.0 8,575
95 - 400 sqmm supplied in wooden drum on
240 62.5 11,048
available length
Length Tolerance per drum 2% 300 68.5 13,705
400 78.0 17,570

Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
at 30 C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 C at 70 C at 20 C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm (/km) (/km) (M..km) (A) (A)
1.5 12.1 14.478 50 0.328 18 24 0.17
2.5 7.41 8.866 50 0.304 25 32 0.28
4 4.61 5.516 50 0.303 34 41 0.45
6 3.08 3.685 50 0.288 44 52 0.68
10 1.83 2.190 50 0.269 60 69 1.13
16 1.15 1.376 40 0.255 80 89 1.81
25 0.727 0.870 40 0.255 105 116 2.82
35 0.524 0.627 40 0.246 130 138 3.95
50 0.387 0.464 30 0.247 160 165 5.65
70 0.268 0.321 30 0.238 200 205 7.91
95 0.193 0.232 30 0.238 245 245 10.7
120 0.153 0.184 30 0.233 285 280 13.56
150 0.124 0.150 20 0.233 325 315 16.94
185 0.0991 0.121 20 0.233 370 355 20.9
240 0.0754 0.093 20 0.232 435 415 27.11
300 0.0601 0.075 20 0.231 500 465 33.89
400 0.0470 0.060 20 0.229 600 535 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information