Permissible Temperature Rise over ambient temperature
of 40 / 45C
a) Of top oil measured by thermometer. 40C
b) Of winding measured by resistance. 45 C
3 8.1 inspection
9 h) Off Load Tap changer
6 Clause 1.2
The core shall be constructed .......... shall be used). The maximum flux density in
any part of the cores and yoke at normal voltage and frequency shall be such
that it should under 10% overvoltage condition should not be more than 1.9
Tesla. The supplier .... under any circumstances.
21
Maximum Flux Density in any part of the core and yoke at rated MVA, 112.5 % of
rated voltage 1.9 Tesla
xiii) Sheet steel, weather, vermin and dust proof cable box ...........r to prevent the
ingress of moisture from the cable trench for those transformers which are used
in partly indoor substation,
11 Clause 7.6.6.8
The current density adopted in all winding shall not exceed 2.4 A/mm2. The total
net cross sectional area of the strip conductors for calculating current density for
each winding shall be obtained after deducting the copper area lost due to rounding
up of the sharp edges at the rectangular conductors.
12 New Clause added
iv) Following additional routine tests shall also be carried out on each transformer:
a) Magnetic Circuit Test Each core shall be tested for 1 minute at 2000 Volt DC
All the necessary tools and tackles required for normal operation & maintenance of
the transformers shall be supplied by the Contractor
The equipment shall be commissioned as per CBIP manual, IS: 10028 and
manufacturers recommendations. All the related drawings and manuals shall be
pre-requisite for release of final payment. (Manufacturer shall send person to
witness and one week prior notice shall be given to manufacturer)
18 2 SPECIFIC TECHNICAL REQUIREMENTS
18 a) Type of tap changer (For3.15, 5, 6.3, 8, 10&12.5 MVA only) On-load tap
changer.
24.1 The purchaser reserves the right to conduct all tests on transformer after arrival
at site and the manufacturer shall guarantee test certificate figures under actual
service conditions.
22 xix) Two numbers tank earthing terminals with associated nuts and bolts for
connections to Employers grounding strip. Bi-directional flagged rollers with
locking and bolting device.
Amended Clause
26
Permissible Temperature Rise over ambient temperature shall be as per
IS-2026.
8.1 Inspections
9. H) On/Off Load Tap changer as per BOQ
Clause 1.2
The core shall be constructed .......... shall be used).The supplier.... under
any circumstances.
21
Maximum Flux Density in any part of the core and yoke at rated MVA
with +12.5% combined voltage and frequency variation from rated
voltage and frequency 1.9 Tesla
xiii) Sheet steel, weather, vermin and dust proof cable box ...........r to
prevent the ingress of moisture from the cable trench for those
transformers which are used in partly indoor substation,
If required as per BOQ, a cable box for LV bushings shall be provided.
iv) Following additional routine tests shall also be carried out on each
transformer:
a) Magnetic Circuit Test Each core shall be tested for 1 minute at 2000
Volt AC
xix) Two numbers tank earthing terminals with associated nuts and
bolts for connections to Employers grounding strip.