Sunteți pe pagina 1din 31

www.kaeser.

com

Compressed Air Engineering


Basic principles, tips and suggestions
www.kaeser.com

Contents Foreword
Fundamentals
Chapter 1 Fundamentals of compressed air production......................................................................................... 4
Chapter 2 Ecient compressed air treatment........................................................................................................ 6
Chapter 3 Why do we need to dry compressed air?.............................................................................................. 8
Chapter 4 Condensate: Correct drainage.............................................................................................................. 10
Chapter 5 Condensate: Safe, economical treatment.............................................................................................. 12 Dipl.-Wirtsch.-Ing. Dipl.-Wirtsch.-Ing.
Thomas Kaeser Tina-Maria Vlantoussi-Kaeser
Chapter 6 Ecient compressor control.................................................................................................................. 14
Chapter 7 Optimised compressor performance to meet actual demand................................................................ 18 Dear reader,

Chapter 8 Energy savings with heat recovery........................................................................................................ 20 More than two thousand years ago, Socrates, the famous Moreover, they should have a detailed understanding of
Chapter 9 Designing and installing a new compressed air distribution network.................................................... 22 Greek philosopher, succinctly said: There is only one the numerous interactions and influences that occur within
good, knowledge, and one evil, ignorance. the system, as well as how it integrates into the operating
Chapter 10 Optimising an existing air distribution network....................................................................................... 24 environment.
These ancient words of wisdom from one of the founding
Chapter 11 Compressed air demand analysis (ADA) Determining the current situation...................................... 26 fathers of Western civilisation apply today more than ever, KAESER KOMPRESSOREN is therefore dedicated to
Chapter 12 Determining the most ecient concept.................................................................................................. 30 since nothing seems more permanent than change. The the further training of its customers and achieves this in a
ever-increasing scope and speed of change brought about number of ways. For example, qualified technical experts
Chapter 13 Ecient compressor station cooling...................................................................................................... 32 by technological evolution and economic globalisation with extensive practical experience travel around the world
demand new answers and new strategies. every year, making stops on every continent to speak
Chapter 14 Ensuring long-term reliability and cost-optimisation.............................................................................. 34 at conferences, information events and seminars about
Now, more than ever, challenges should be seen as efficient compressed air production and usage. Of course,
opportunities to achieve even greater success in the future this is in addition to the many technical publications across
and should therefore be adopted and utilised to their a broad range of media.
Practical tips full potential. Our increasingly networked and complex
world is transforming knowledge into becoming the most In this brochure youll find an executive summary of our
Tip 1 Savings with optimised pressure........................................................................................................... 40 valuable raw material of the future. Due to the exponential experts extensive knowledge. Following an in-depth yet
growth of this commodity, it is only those with a strong highly accessible introduction to the field of compressed
Tip 2 Correct pressure at the air connection.................................................................................................. 42 commitment to education and continued training who will air technology, youll find a series of practical tips for
Tip 3 Ecient compressed air distribution...................................................................................................... 44 reap the true rewards. system operators and compressed air users. You will also
recognise a common theme throughout: in so many cases
Tip 4 Pipework in the compressed air station................................................................................................. 46 In the world of compressed air engineering, for example, and in so many different ways, even small changes in the
merely having the knowledge of how to construct powerful compressed air system result in significant and tangible
Tip 5 Correct compressor installation............................................................................................................. 48 compressors, and install and operate them correctly, is not improvements in the efficiency and availability of this key
Tip 6 Compressed air station ventilation (intake)........................................................................................... 49 enough and hasnt been for some time. energy carrier.

Tip 7 Compressed air station ventilation (exhaust)........................................................................................ 50 Those who wish to take full advantage of what com-
pressed air, as an energy carrier, has to offer must
consider the entire compressed air system as a whole.

Appendices
Appendix 1 Nomograph Determining pipe diameter............................................................................................ 50
Appendix 2 Questionnaire examples regarding the Energy Saving System Service.............................................. 52

2 3
www.kaeser.com

Chapter 1

Fundamentals of compressed air production

Its the same with compressed air as shaft power). The power consumption resulted in significantly improved energy
with many other things in life: a small V2 x P2 x T1
exceeds the motor shaft power by the efficiency for premium class electrical Fan motor
V1 =
cause can have a large effect both value of the motor losses both elec- motors. High efficiency motors provide
[p1 (pD x Frel)] x T2
in a positive and negative sense. trical and mechanical from bearings, significant advantages:
Upon closer inspection things are
fan, etc. The ideal electric power con-
often different from how they at first Electrical
The result is the free air delivery (FAD) sumption P can be calculated using the a) Lower operating temperatures
appear. In unfavourable conditions power
compressed air can be expensive, of the compressor package. This figure formula: The internal efficiency loss caused by consumption
but in the right circumstances it is is not to be confused with the airend heat generation and friction can be as
very economical. In this first chapter delivery (block delivery). P = Un x ln x 3 x cos n high as 20 percent in small motors
we will explain the terms used in and 4-5 percent in motors upward of
compressed air engineering and the Note: 160 kW. IE3/IE4 motors operate with
things you should watch for in con- DIN 1945 and ISO 1217 alone only Un, ln, and cos n are quoted on the significantly less heating and, as a Air inlet
nection with them. define the airend delivery. motor nameplate. result, with much lower losses (Fig. 3): Internal motor losses
A conventional motor with F class insu- Compressed air included in motor
1. Free air delivery 2. Motor shaft power 4. Specific power lation operates at about 80 K, giving it outlet (delivery) efficiency rating
The air delivery of a compressor (known The motor shaft power is the power The specific power of a compressor a temperature reserve of 20 K, whereas
also as the free air delivery or FAD) is that the motor delivers mechanically to (Fig. 2) is the relationship between an IE motor, working under the same
the expanded volume of air it forces its output shaft. The optimal value for the electric power consumed and the operating conditions, will run at only
into the air main (network) over a given motor shaft power is the point at which compressed air delivered at a given about 65 K, increasing its reserve to
period of time. The correct method of optimum electrical energy efficiency is working pressure. The electrical power 40 K.
measuring this volume is given in the achieved and the cos power factor is consumption is the sum of the power
following standards: DIN 1945, Part 1, reached without the motor overloading. consumed by all consumers in a com- b) Longer life
Annex F and ISO 1217, Annex C. The This figure lies within the range of the pressor, for example, drive motor, fan, Lower working temperatures mean less Fig. 2: Basic layout of a rotary screw compressor; determining specific power
measurement process is performed as rated motor power. The rated power is oil pump, auxiliary heating, etc. thermal stress on the motor, the motor
follows as shown in Fig. 1: the tem- shown on the motors nameplate. bearings and terminals. Motor service
perature, atmospheric pressure and Note: If the motor shaft power devi- If the specific power is needed for an life is significantly extended as a result.
humidity must first be measured at the ates too far from the rated motor economic appraisal, it should refer to 100 Values for
air inlet of the compressor package. power, the compressor will run inef- the compressor package as a whole and c) Six percent more compressed air 95
4-pole motors,
50 Hz
Then, the maximum working pressure, ficiently and/or will be subject to the maximum working pressure. The for less power consumption 90
IE4
temperature and volume of compressed increased wear. overall electrical power consumption at Less heat loss leads to increased effi- 85

Efficiency (%)
IE3
air discharged from the compressor are maximum pressure is then divided by ciency. Thus, with precise matching 80
75 IE2
measured. Finally, the volume V2 meas- 3. Electrical power consumption the FAD at maximum pressure: of the compressors to the enhanced IE1
70
ured at the compressor outlet is referred The electric power consumption is the efficiency motors, KAESER is able to 65
back to the inlet conditions using the power that the drive motor draws from Electrical power achieve up to a six percent increase in
consumption 60 Range of application
shown equation (see formula). the mains power supply with a defined Pspec. = air delivery and a five percent improve- 55
according to EU Directive

mechanical load on its shaft (motor Delivery ment in specific power. This means 50
Up to 1,000
12 18 20 5 7 40 5 75 .1 .5 .2 3 4 5.5 7.5 11 15 8.5 22 30 37 45 55 75 90 110 132 160 200 315 355 400 450 500
improved performance, shorter com- 0. 0. 0. 0.2 0.3 0. 0.5 0. 1 1 2 1

pressor running time and less power Output (kW)


Intake 5. IE The new formula consumed per cubic metre of com-
temperature T1 for energy-saving drives pressed air delivered.
Discharge Efforts in the USA to reduce the energy Fig. 3: The IEC standard the new efficiency classification of electric motors. Beginning with 1 January
Discharge pressure p2 requirements of three-phase asynchro- 2015, IE3 motors are mandatory in the EU. Meanwhile, a further improved motor efficiency class IE 4
sure p1 has been defined.
volume V2 Inlet pres nous motors resulted in the Energy
Policy Act (EPACT) becoming law in
1997. A short while later, an efficiency
Inlet classification system was also intro-
humidity Frel duced in Europe. The international IEC
Discharge temperature T2 Vapour pressure pp standard for electric motors has been
in place since 2010. Classifications
Fig. 1: Free air delivery as per ISO 1217, Appendix C (DIN 1945, Appendix F) and legal requirements subsequently

4 5
www.kaeser.com

Chapter 2

Ecient compressed air treatment

So, which compressor system pro- above, it is impossible to produce oil-free lated in the ISO standard. The system
vides the most cost-effective way compressed air with a compressor that includes all the treatment components
of producing oil-free compressed is equipped only with a three-micron needed for achieving the required air Choose the required grade of treatment according to your field of application: Explanation
air? Leaving aside the claims of indi- dust filter. Other than these dust filters, quality. Depending on the application, Examples: Selection of treatment classes to ISO 8573-1 (2010) ACT Activated carbon adsorber
vidual manufacturers, there is no AQUAMAT AQUAMAT
so-called oil-free compressors have either refrigeration or desiccant dryers Air treatment with refrigeration dryer Installation for
doubt that premium quality, oil-free fluctuating air demand DD Desiccant dryer
no further treatment components. (also see Chapter 3, pg. 9) are used DHS Air-main charging system
compressed air can be achieved both Solids1 Water Oil2

with dry-running and fluid-cooled together with various filter combina- Pure air and clean room
DHS KE
AR Air receiver
ED ECO-DRAIN
b) Fluid- or oil-cooled compressors tions. Air qualities ranging from simple technology, breweries, 1 4 1
compressors. Ideally therefore, the dairies KA Activated carbon filter, adsorption

deciding factor to consider when In contrast, aggressive matter is neu- dry air through to particle- and oil-free Foodstuff and luxury food
DHS KD ACT KE Optional KB Coalescence filter, Basic
AR filtration RD ZK KBE Extra Combination
selecting an air system should be tralised and solid particles are partly air to sterile air are reliably and cost-ef- production, especially clean 2 4 1
conveying air, chemical KD Particulate filter, dust
efficiency. washed out of the air by the cooling fluid fectively achieved in accordance with plants KE Coalescence filter, Extra
KEA Carbon Combination
(oil) in fluid-cooled rotary compressors. the quality classes set out in the ISO
RD Refrigeration dryer
1. What does oil-free compressed standard (Fig. 1). THNF Bag filter
air mean? 3. Non-defined compressed Pharmaceuticals industry, DHS KEA AR ZK Centrifugal separator
weaving machines, photo 1 4 1
According to ISO 8573-1, compressed air quality without treatment labs Compressed air quality classes to ISO 8573-1(2010):
RD ED Compressor THNF
air can be described as oil-free if its oil Despite the higher degree of achieved Solid particles / dust
content (including oil vapour) is less compressed air purity, the same applies Max. particle count per m * of a
Paint spraying, powder particle size d in [m]
than 0.01 mg/m. That is approximately here too: Its a no-go without com- coating packing, control DHS KE Class
and instrument air 1 4 2 0.1 d 0.5 0.5 d 1.0 1.0 d 5.0
four-hundredths of that contained in pressed air treatment. With dry or
0 Please consult KAESER
normal atmospheric air. This amount is oil-cooled compression alone, under regarding specific requirements
AQUAMAT 1 20,000 400 10
so minute as to be barely measurable. normal intake conditions and with the General works air, high-grade
DHS
2 400,000 6,000 100
sand blasting 4 4 3
But what about the quality of the com- associated air contaminant levels, it is 3 Not defined 90,000 1,000
4 Not defined Not defined 10,000
pressors intake air? not possible to achieve defined oil-free Shot-blasting
DHS KB
5 Not defined Not defined 100,000
4 7 3
compressed air quality in accordance Class Particle concentration Cp in mg/m *
Of course, this depends greatly on local with ISO 8573-1. 6 0 < Cp 5
ambient conditions. Even in normally As to how efficient compressed air Conveying air for With KAESER rotary screw compressors 7 5 < Cp 10
wastewater systems, X Cp > 10
contaminated zones, the hydrocar- production is, depends on the pres- no quality specifications 6 7-X 4
bons in the air caused by industry and sure and delivery range, as well as on Water
traffic emissions can lie between 4 and the required compressor type. Suffi- Class Pressure dew point, in C

14 mg/m. In industrial areas, where cient drying forms the foundation for Compressed air treatment with desiccant dryer Installation for 0 Please consult KAESER
regarding specific requirements
oil is used as a lubricating, cooling all application-tailored compressed air fluctuating air demand
1 70 C
and processing medium, the mineral treatment. Energy-saving refrigera- Solids1 Water Oil2 2 40 C
DHS KE 3 20 C
Pure air and clean room
oil content can be far in excess of tion drying is usually the most efficient technology, pharmaceut- 1 1-3 1 4 + 3 C
10 mg/m. method (also see Chapter 3, pg. 9). icals, dairies, breweries 5 + 7 C
Optional 6 + 10 C
DHS KE KD ACT AR filtration DD3 KE ZK
Other impurities such as hydrocarbons, Microchip production,
1 1-3 1 Concentration of liquid water
optics and foodstuffs Class
CW in g/m *
sulphur dioxide, soot, metals and dust 4. Treatment with the AR 7 CW 0.5
are also present. KAESER Pure Air System Paint spraying installations
DHS
8 0.5 < CW 5
2 1-3 1 KBE4
Modern fluid-/oil-cooled rotary screw 9 5 < CW 10
X CW > 10
2. Why treat air? compressors are approximately 10 % Process air,
DHS KEA
1 1-3 1 AT3 Compressor THNF
Every compressor, regardless of type, more efficient than dry-running, or oil- pharmaceuticals Oil

draws in contaminated air, concentrates free, compressor models. The Pure DHS KE KD Class
Total oil concentration
(fluid, aerosol + gaseous) mg/m *
Especially dry conveying
the contamination by compression and, Air System, developed by KAESER for air, paint spraying, fine 1 1-3 2
AQUAMAT
pressure controllers 0 Please consult KAESER
if no measures are taken to remove fluid-/oil-cooled rotary screw compres- regarding specific requirements
1 0.01
it, passes it on to the compressed air sors, and for dry-running compressors, 2 0.1
network. provides further cost-savings of up to 1)
Achievable particle class with expert-implemented pipework and commissioning.
3 1.0
4 5.0
30 %. The residual compressed air Achievable total oil content with use of recommended compressor oils and unloaded intake air.
2)

3)
High temperature filters and possibly an aftercooler are required downstream from heat-regenerated desiccant dryers. X > 5.0
a) Oil-free compressors oil content achieved by this system is The use of an Extra Combination (a filter combination comprising a KB and downstream KE filter) is recommended for critical
4)

applications requiring exceptionally high compressed air purity (e.g. in the electronics and optics sectors). *) With reference conditions 20C, 1 bar(a), 0%

This especially applies to so-called less than 0.003 mg/m and is therefore
dry-running, or oil-free compressors. far below the limit for Quality Class 1 Fig. 1: An air treatment chart, such as the one shown above, is included in every KAESER rotary screw compressor brochure. The correct combination of
Because of the pollution mentioned (regarding residual oil content) stipu- treatment equipment for any application can be easily determined at a glance.

6 7
www.kaeser.com

Chapter 3

Why do we need to dry compressed air?

The problem is in the air quite lit- 80 to approx. 30 C in the compressors absorb water is reduced. This is pre- sure then its volume multiplies by 10
erally: When atmospheric air cools aftercooler. cisely what happens in the airend and Air consumption over a 24-hour period
times. The water vapour component
down, as is the case after com- At this temperature, a cubic metre in the aftercooler of a compressor. of 6 g remains unchanged, but is now 100 % 43 C

in ambient temperature
pression in a compressor, water Additional energy-saving potential
of air can absorb only about 30 g distributed over 10 times the volume. (for use at summer temperatures, e.g. 40 C

Designed for use


vapour precipitates as condensate. 90 %
ambient temperature 40 C)
of water. As a result, an excess of 4. Important terms This means that every cubic metre 35 C
Under reference conditions (+20 C

Compressed air demand / energy consumption


approx. 70 g/min occurs, which con- A brief explanation of free air now contains only 0.6 g of 80 % 30 C
ambient temperature, 70 % relative
humidity and 1 barabs), a compressor denses and is then separated. This a) Absolute air humidity water vapour, which corresponds to an 25 C
70 %
with a free air delivery of 5 m/min will means that approximately 35 litres Absolute air humidity is the water con- atmospheric dew point of -24 C.
produce approximately 30 litres of of condensate accumulate during tent of the air, given in g/m. Energy-saving potential SECOTEC energy-saving
60 % potential:
condensate per eight hour shift. This an eight hour working shift. A fur- 5. Efficient and environment- Early shift Below the blue line:
condensate has to be removed from ther 6 litres are separated each shift b) Relative air humidity (Hrel) ally-friendly compressed air drying 50 %
Air consumption
the air system in order to prevent if using a downstream refrigeration Relative air humidity is the ratio of the with a refrigeration or desiccant 40 % Above the blue line:
potential damage and avoid costly dryer. The air is initially cooled current absolute humidity to the highest dryer? Energy-saving potential
production downtime. Cost-effective Day shift
down to +3 C in these dryers possible absolute humidity, or satura- New environmental legislation con- 30 %
and environmentally-friendly com-
and is then later rewarmed tion point (100 % Hrel). This is variable cerning refrigerants cannot change the
pressed air drying is therefore a key 20 %
component of application-tailored to ambient temperature. This leads according to temperature; warm air can fact that desiccant dryers do not provide
Midday break
compressed air treatment. to a water vapour saturation deficit of hold more water vapour than cold air. an alternative to refrigeration dryers, 10 %

approximately 20 % and therefore to neither from an economical nor from Compressed air demand Night shift
0%
1. A practical example drier, better quality compressed air c) Atmospheric dew point an environmental point of view. Refrig- Time 6 - 14 14 - 22 22 - 6
If a fluid- / oil-cooled rotary screw com- (Fig. 1). The atmospheric dew point is the tem- eration dryers consume only 3 % of the
pressor draws in 10 m of air per minute perature at which the air reaches 100 % power that the compressor needs to
at 20 C at atmospheric pressure and 2. Causes of humidity humidity saturation (Hrel) at atmospheric produce the compressed air; desiccant Fig. 3: Energy-saving potential of refrigeration dryers with cycling control
with a relative humidity of 60 %, this Our ambient air always, to a lesser or pressure (ambient conditions). dryers, on the other hand, require 10
air will contain approximately 100 g of greater extent, contains a certain amount to 25 percent, or more. For this reason, course of a year as a result of large However, using a cost-effective and
water vapour. If this air is compressed of water. The actual amount of moisture d) Pressure dew point refrigeration dryers should always be fluctuations in temperature. There- energy-efficient combination process,
to an absolute pressure of 10 bar at a depends on the temperature of the air. The pressure dew point (PDP) is the used wherever possible. fore, compressed air dryers should be such as with the HYBRITEC system,
compression ratio of 1:10, then this is For example, air saturated to 100 % temperature at which compressed air designed to handle the least favourable it has been possible to significantly
referred to as 1 working cubic metre. with water vapour at a temperature reaches its humidity saturation point Pressure
Typical specific operating conditions that may occur, for reduce energy consumption. The
Drying power-
However, at a temperature of 80 C of +25 C holds almost 23 g of water (100 % Hrel ) under its absolute pres- process
point
requirement example: lowest pressure, maximum system comprises both a refrigeration
C
after compression, the air is capable per cubic metre. sure. This means, in the above case, kW / m/min **) compressed air consumption, as well dryer and a desiccant dryer. The refrig-
of absorbing up to 290 g of water per that air subjected to a pressure of as maximum ambient and compressed eration dryer first brings the inflowing
Refrigeration dryer +3 0.1
cubic metre. As only approx. 100 g is 3. Accumulation of condensate 10 bar (a) with a pressure dew point of air inlet temperatures. compressed air to a pressure dew point
available, the air is very dry with a rela- Condensate forms if the volume of the +3 C has an absolute humidity of 6 g This requirement used to be solved of +3 C efficiently and cost-effectively.
+ 3 / 40 *) 0.2
tive humidity of approximately 35 %, so air is reduced and the temperature of per working cubic metre. To clarify if HYBRITEC simply by continuous dryer opera- Having been pre-dried, the air then
40 0.3
that no condensate can form. The tem- the air is reduced at the same time. the cubic metre mentioned is expanded tion, which especially in partial load passes into the desiccant dryer, which
Heat-regenerated
perature of the air is then reduced from Therefore, the capacity of the air to from 10 bar (a) to atmospheric pres- desiccant dryer
40 0.5 0.6 operation led to considerable energy subsequently requires considerably
wastage. Modern refrigeration dryers less energy to dry the air further to a
Heatless-regenerated 20 with efficient cycling control, on the other pressure dew point of -40 C.
1.4 1.6
desiccant dryer 70
Refrigeration dryer hand, ensure consistent air quality and
Fig. 2: Different drying processes are available are able to adapt their energy usage
depending on the required pressure dew point according to changing operating con-
ditions (Fig. 3). Consequently, they are
The use of a desiccant dryer only makes able to achieve average annual energy
sense if an extremely dry air quality with savings of more than 50 %.
a pressure dew point down to -20, -40 It is particularly important to use
or -70 C is required (Fig. 2). Over the energy-efficient technology to reach
48 l 35 l 6l course of a working day, compressed
air systems often experience consid-
pressure dew points in the minus
range, as the desiccant dryers required
erable fluctuations in compressed air to achieve this level of performance
Fig. 1: Condensate occurs as a result of compressed air production, storage and treatment (figures based on 10 m/min, 10 barabs, 8 h, 60 % Hrel and 20 C) demand. Similar also occurs over the have a very high energy demand.

8 9
www.kaeser.com

Chapter 4

Condensate: Correct drainage

Condensate is an unavoidable
Compressed air feed line, Connection
by-product of compressed air pro- air return pipe
gently sloping (2 %) Inlet
duction. We explained how, under To com-
average conditions, a 30 kW com- pressed air Swan neck
pressor with a FAD of 5 m/min network
produces approximately 20 litres Connection from compressor
of condensate per shift. This liquid ECO-DRAIN
must be removed from the air Condensate trap in the comp-
system to prevent system failures, ressed air feed line (water pocket)
costly production downtime and
corrosion. In this chapter we explain To compressed air network
how to drain condensate correctly Aquamat
and achieve significant cost-savings Condensate drain
at the same time.
Condensate feed line Outlet Manual valve

1. Condensate drainage Fig. 1: Condensate accumulates at certain points in every compressed air system Fig. 3: Water trap with condensate drain in the wet area of a compressed air system Fig. 4: Float drain for compressed air condensate
Condensate, contaminated by diverse
pollutants, collects at certain points in (Fig. 1). If sufficiently sized (com- drainage points to be found within the c) Local separators c) Condensate drains with
every air system (Fig. 1). Reliable con- pressor FAD in m/min divided by 3 = compressed air drying process. If no central drying system exists, large level-sensing control
densate drainage is therefore essential, air receiver size in m), the air receiver quantities of condensate collect at the Nowadays, drains equipped with
otherwise air quality, operational reli- is just as effective as a centrifugal Refrigeration dryers: local separators fitted just upstream intelligent level-sensing control are pre-
ability and compressed air system separator. Further condensate is separated in the from air-consuming equipment. How- dominantly used (Fig. 5). They have
efficiency can be seriously affected. In contrast to the centrifugal separator, refrigeration dryers due to the drying ever, these systems are exceptionally the advantage that the float, which is
however, the air receiver can be used effect of cooling the compressed air. maintenance-intensive. highly susceptible to faults, is replaced
a) Condensate collection in the main air line of the compressed by an electronic sensor. This eliminates
and drainage points air system, providing the air inlet is at Desiccant dryers: 2. Drainage systems the faults caused by dirt, or mechanical
Initially, mechanical elements of the the bottom and the outlet is at the top. Due to the considerable cooling effect At present, three systems are mainly wear associated with float drains. Fur-
air system serve to collect and drain Moreover, due to its large heat dissi- of the air line, condensate can collect at used: thermore, air losses (which also occur
condensate. 70 to 80 % of all the con- pation surface area, the air receiver the pre-filter in the inlet to the desiccant with float valves) are prevented by the
densate is collected at these points additionally cools the air thereby dryer. In the desiccant dryer itself, water a) Float drains automatically controlled valve opening
provided the compressors are fitted enhancing condensate separation yet only exists as vapour because of the The float drain is one of the oldest periods. Additional benefits include
with effective after-cooling. further. partial pressure conditions prevailing in drainage systems and replaced manual automatic self-monitoring and the Fig. 5: Condensate drain with electronic
the dryer. drainage, which was both inefficient ability to send signals to a central con- level-sensing control (ECO-DRAIN)
Centrifugal separator: Water-traps in the air line: and highly unreliable. However, even trol system.
This is a mechanical separator that To avoid undefined condensate flow, condensate drainage using the float
separates the condensate from the the air line should be designed so that principle (Fig. 4) proved to be extremely d) Correct installation
air by means of centrifugal force all inlet and outlet points are are con- susceptible to malfunction due to dirt A short length of pipe containing a
(Fig. 2). In order to ensure optimum nected from above or from the side. and contaminants in the compressed shut-off valve should be fitted between
performance, each compressor should air. the condensate separating system and
be equipped with its own dedicated Defined condensate outlets leading the condensate drain (Figs. 2 and 3).
centrifugal separator. downwards, so-called water traps, b) Solenoid valves This allows the drain to be isolated
allow condensate to be removed from Time-controlled solenoid valves are during maintenance and the com-
Intercoolers: the main air line. With correct design more reliable than float drains, but they pressed air system can remain in
On two-stage compressors equipped and an airflow of 2 to 3 m/s a water trap have to be checked regularly for clog- operation.
with intercoolers, the condensate also (Fig. 3) in the wet area of the air system ging and contamination. Incorrectly
collects at the intercoolers separator. separates condensate just as effec- adjusted valve opening periods can
tively as an air receiver (Fig. 1). cause air losses and increased energy
Air receivers: consumption.
As well as its main function as a storage b) Compressed air dryers
or buffer tank, the air receiver sepa- As well as those already mentioned,
rates condensate from the air by gravity there are additional collecting and Fig. 2: Centrifugal separator with condensate
drain

10 11
www.kaeser.com

Chapter 5

Condensate: Safe, economical treatment

The term condensate is misleading from the atmosphere are captured in a disposed of in accordance with envi-
because it could be misunderstood floating layer of oil that is easily sepa- ronmental regulations. Pressure relief chamber
to mean only condensed water rated from the water.
vapour. Be careful! Every com- Pre-separation tank
4. Treatment processes
pressor works just like an oversized Removable catchment container
b) Emulsion a) For dispersions
vacuum cleaner: it draws in contam-
A visible sign of emulsion is a milky A triple chamber separator comprising
inated air from the surroundings and Oil catchment container
passes it on in a concentrated form fluid that does not separate even after two initial separating chambers and an
in the untreated compressed air to several days. This composition often activated carbon filter chamber is used Prefilter
the condensate. occurs in reciprocating, rotary screw to treat this kind of condensate (Fig. 2).
Main filter cartridge
and sliding vane compressors that are The actual separation process takes
1. Why treat condensate? used with conventional oils. The pollut- place under the force of gravity. The oil Water outlet
Users who dispose of condensate ants are also captured by the oil. layer floating on the surface of the fluid
Drain for reference condensate
by simply pouring it down the drain Because of the thick, stable mixture, in the separating chamber is skimmed cloudiness test
risk heavy fines. Why? Because con- oil, water and pollutants such as dust off into a container and disposed of as
densate accumulating during the and heavy metals cannot be sepa- waste oil.
production of compressed air is a rated by gravity. If the oils contain ester The remaining water is then filtered in
highly noxious mixture. In addition to compounds, the condensate could be two stages and can be disposed of as
solid particles, condensate contains aggressive and must be neutralised. waste water. This process saves up to Fig. 2: Condensate separation system for compressed air technology using the gravity principle
hydrocarbons, sulphur dioxide, copper, Treatment of such condensate is only 95 % of the costs involved if a special- (functional diagram)
lead, iron and other substances caused possible with emulsion splitting units. ised company were to dispose of the
by increased environmental pollution. condensate. so-called cross-flow process. During
In Germany, regulations concerning 3. Specialist disposal These separators can be supplied to this process, pre-filtered condensate
condensate disposal are set out in the Of course, it is possible to collect the handle compressor air deliveries of up flows across the membrane.
Water Management Act. This act stipu- condensate and have it disposed of to 105 m/min. If needed, several sep-
lates that polluted water must be treated by a specialist company. However arators can be connected in parallel. A portion of the condensate permeates
according to the generally recognised these costs are typically between the membrane and leaves the separator
engineering regulations. This affects 40 and 150 per m. In view of the b) For emulsions as clean water that can be disposed of
all types of condensate including con- amount of condensate accumulated, In general, two types of separator as waste water. The second type uses
densate from oil-free compressors. treatment would be the more econom- are used for the treatment of stable a powdered splitting agent. This encap-
There are legal limits for all pollut- ical approach. This method has the emulsions: sulates oil particles, forming easily
ants and for pH-values. These vary advantage that only approx. 0.25 % of Membrane separating systems work on filtered macro flocs. Filters of a defined
according to federal state and the the original volume is left over to be the principle of ultra-filtration using the pore size reliably retain these flocs. The
branch of engineering involved. The drained water can be disposed of as
maximum permissible limit for hydro- waste water.
carbons, for example, is 20 mg/l and
the pH limit for disposable condensate
ranges from 6 to 9.

2. Composition of condensate
(Fig. 1)
a) Dispersion
The composition of condensate can
vary widely. Generally, dispersion
occurs in fluid-cooled rotary screw
compressors using synthetic coolants,
such as Kaesers Sigma Fluid S460
for example. This condensate normally
has a pH value between 6 and 9 and
Fig. 1: Every compressor draws in water vapours and pollutants together with the atmospheric air.
can be regarded as pH neutral. With The accumulating compressed air condensate (Fig. 1.1) must therefore be free from oil and other
this condensate, pollutants drawn in contaminants (Fig. 1. 2) before it can be drained away as pure water (Fig. 1. 3)

12 13
www.kaeser.com

Chapter 6

Ecient compressor control

By correctly matching com- Perfectly matched control systems can demand. These switching cycles can end up consuming a lot of energy
pressed air delivery to fluctuating help by increasing the load factor to would only unload the pressurised without the user ever being aware of

Pressure
Motor temperature
compressed air demand, ener- over 90 % and by achieving power sav- areas of the compressor system. The the fact. This means that variable fre-
gy-intensive, and therefore costly, ings of up to 20 % or more. drive motor, on the other hand, must quency drive is not a universal remedy
partial load phases can be virtually
carry on running for a certain period to in the search for maximum efficiency Pmax
eliminated. The right compressor Pmin
1. Internal control avoid exceeding its starting frequency. and energy-saving operation.
controller consequently plays a key
role in ensuring optimum energy a) Full-load/idle control (Fig. 1). The power needed to turn the
100
efficiency. Most compressors are fitted with three motor during this off-load period must 2. Classification of air demand
Full load
phase asynchronous drive motors. be regarded as a loss. The power con- Generally, compressors can be clas-

Motor power in %
Compressors operating at less than However, the permissible starting fre- sumption of a compressor switched to sified according to function into base
50 % load should set off loud alarm bells quency of these motors becomes lower off-load running is still 20 % of full load load, medium load, peak load or Idle
20
with regards to serious energy wastage. in relation to increased motor size. This drive power. standby-units. Stop
Many users are not even aware of this does not correspond to the starting Idling, only with high motor temperature Time
Variable maximum switching frequency
fact because their compressors have frequency necessary to cut in and cut Modern, computer-optimised control a) Base load air demand
an indicator showing only the hours in out compressors with lower switching systems such as Quadro control with Base load air demand is the volume of Fig. 3: Dynamic control, based on Dual control, with drive motor temperature dependent idling
operation but not the hours under load. differentials to meet the actual air automatic optimal operating mode air that is constantly needed by a pro-
selection (Fig. 2), Dynamic control with duction facility.
drive motor temperature dependent
idling (Fig. 3) and Vario control with b) Peak load air demand
Pressure

Pressure
variable calculated idling periods In contrast, the peak load is the volume
(Fig. 4) help to keep costly idling of air demanded at certain peak load
Pmax periods to a minimum and ensure max- times. It varies in volume because Pmax
Pmin imum motor protection. of the differing demand from various Pmin
consumers.
100 Proportional controllers using intake- In order to fulfil this wide range of load 100
Full load side throttling are not recommended, demands as best as possible, the com- Full load
Motor power in %

Motor power in %
since the compressor still requires 90 % pressors need to be equipped with
t2
of the energy it would otherwise need individual control systems.
Idle Idle
20 to provide 100 % free air delivery, in These slave controllers must be 20
Stop Stop
order to deliver just 50 % of maximum capable of maintaining compressor 1 hour
Time Time
capacity. operation, and therefore the supply of Maximum number of motor starts: 6 per hour

compressed air should a defect occur


Fig. 1: Full load Start / stop control with fixed idling periods, so-called Dual control
b) Variable frequency drive on the master controller. Fig. 4: Vario control with variable calculated idling periods
The efficiency of compressors which
are speed controlled by a frequency 3. Master control
converter (Fig. 5) is inconsistent over Modern master controllers equipped
Pressure

the control range. In the control range with web-based software are not only

Pressure
between 30 and 100 % for example, able to co-ordinate compressor oper-
Pmax efficiency is reduced from 94 to 86 % ation within a compressed air station
Pmin for a 90 kW motor. Added to this are in order to ensure optimum energy Pmax Control pressure
the losses in the frequency converter efficiency, but are also able to gather Pmin
100
and the non-linear power character- performance data and document com-
Full load 100
istic of the compressors. FC-controlled pressed air supply efficiency.
Motor power in %

t3 t3 t2 t3 Full load t2 t2
compressors should be operated in the

Motor power in %
t2 t2
Idle 40-70 % control range: this is where a) System splitting
20
Stop they provide optimal performance. Splitting is the division of compressors Idle
20
Time These components should of equal or differing capacities and type Stop
be designed for 100 % load. If of control according to base load and Time
Fig. 2: Full load Idle Start / stop control with automatic optimal mode selection, variable speed compressors are inap- peak load air demand of a production
so-called Quadro control propriately used for an application, they facility (Fig. 6). Fig. 5: Continuous delivery control via motor speed (frequency conversion)

14 15
www.kaeser.com

Chapter 6

Ecient compressor control

b) Master controller tasks efficiency of the compressed air supply munications technology, connection to
Coordination of compressor operation cannot be guaranteed. standardised computer and monitoring
is a demanding and complicated task. systems is also possible. This means
Modern master controllers must not d) Secure data transfer that master controllers do not have to
only be able to simultaneously activate Another important requirement for per- be located in the compressed air instal-
and deactivate compressors of dif- fect function and efficiency of a master lation itself (Fig. 7). Phone WWW
fering make and size. They must also controller is the safe and secure transfer
be capable of monitoring the system for of data. Tablet
maintenance purposes, balancing the It must be ensured that messages
operating hours of the machines and are transferable between each com-
recording alarms to minimise servicing pressor and between the compressors
costs and maximise reliability. and the master controller. In addition, Laptop
the signal paths must be monitored so
c) Correct grading that faults such as loss of continuity
For a master controller to operate with in a connecting cable are immediately
maximum efficiency, the compressors recognised.
within the compressed air station must The normal transfer methods are:
Desktop
be perfectly graded. 1. Floating relay contacts KAESER Service Center
The sum of the air capacities of the 2. Analogue signals 4 20 mA
peak load machines must therefore 3. Electronic interfaces, e.g. RS 232,
be larger than that of the next base RS 485, Profibus DP or Ethernet.
load machine to be cut in. If a peak Profibus offers the most advanced data
load machine with variable frequency transfer technology. This system can Fig. 7: The wide range of connection possibilities for a master controller helps to significantly enhance energy-efficient operation of a compressed air station
drive is used, the control range must quickly transfer large volumes of data
be larger than the capacity of the next over long distances. When combined
compressor to be cut in. Otherwise the with Ethernet and modern telecom-

Demand-dependent 16 m/min + ~ 40 %
system splitting 16 m/min Standby

1st shift 15 m/min


2nd shift 9 m/min
2 x 8 m/min +
3rd shift 4 m/min 8 m/min Standby ~ 60 %

2 x 4.5 m/min + 8 m/min + 5.7 m/min + ~ 95 %


5.7 m/min Standby

1.6 - 6.3 m/min + 3.9 m/min + 5.7 m/min


~ 95 %
5.7 m/min Standby

Fig. 6: Demand-dependent load distribution across compressors of differing sizes

16 17
www.kaeser.com

Chapter 7

Optimised compressor performance to meet


actual demand
Compressed air systems typically this compressors preset minimum in combination with more than two of this regulation variant is that it allows p/bar
comprise multiple compressors of (pmin) and maximum pressure (pmax) compressors. the average operating pressure of the
similar or various sizes. As effec- points, pressure falls when air demand compressed air system to be signifi- Pressure curve Average vector
tive control is essential to ensure is higher and several compressors 2. Pressure band control cantly reduced and therefore helps to
efficient system operation, a master pmax
cut in to meet this demand (Fig. 1, In contrast to cascade regulating sys- achieve considerable energy and cost 7.7
controller is needed to coordi-
Column 1). tems, pressure band control (Fig. 1, savings.
nate the operation of individual 7.5
machines: Compressed air produc- Column 2) enables co-ordination of
tion is precisely matched to suit This results in a relatively large, and multiple compressors within a single 3. Demand pressure control
actual compressed air demand and unfavourable, overall pressure swing defined pressure range. This allows the Demand pressure control (Fig. 1,
maximum efficiency is ensured at all with maximum values well above nom- pressure range within which the com- Column 4) is currently the most favour-
times. inal working pressure, increasing the pressed air station is regulated to be able regulation method. With this 7.0
pmin
significance of leaks and their sub- kept relatively narrow. variant, no minimum and maximum tt t t
Within the scope of regulation and con- sequent energy losses; on the other pressure is specified, just the lowest t/s
trol technology, the systems generally hand, if consumption is high, pressure 2. a) Simple pressure band control possible working pressure at which the
referred to as compressor controllers falls well below nominal working pres- Simple versions of pressure band con- pressure sensor measurement point is Fig. 2: Optimum pressure is set taking all control-relevant losses into account
should be considered as regulating sure and there is a reduced reserve of trol are, however, not able to co-ordinate not undershot (Fig. 3). Taking into con-
systems. These are chiefly divided into pressure in the system. operation of compressors of different sideration all possible losses caused
four groups: Depending on whether conventional sizes; they therefore do not meet by pressure increase, start-up time,
p
membrane pressure switches, contact the requirements to cover peak load reaction and idling periods, as well as
1. Cascade control pressure gauges or electronic pressure demand in compressed air networks speed control of individual units, this
pO2
The classic method of controlling a sensors are used as measurement that have to accommodate continuously regulation method determines optimum
pO1
group of compressors is cascade sensors, the control system pressure fluctuating demand conditions. performance with regards to switching
control. Each individual compressor spread will be very large due to the This method was therefore replaced and compressor selection. Thanks to WP
is assigned lower and upper pressure individual allocation of the compressors by a system that, based on periods recognition of individual reaction times, pu1 x
set points that either add or subtract to a certain pressure range. The more of pressure fall and rise, aims to con- the system is able to ensure that the pu2 x
compressor capacity to meet system compressors that are in use, the larger trol the appropriate compressors and minimum allowable demand pressure
pmin
demand. If several compressors are to the pressure ranges overall. This leads to therefore cover the compressed air is not undershot (Fig. 4).
be coordinated, this strategy results in to ineffective regulation with the already peak load demand. This regulation With this new variant of adaptive p
Alarm
a cascaded, or stepped control system. mentioned higher pressures, leakages approach does however have a rel- 3Dadvance Control, which is included in
When air demand is low only one com- and energy losses. Cascade regulating atively large pressure band spread the SIGMA AIR MANAGER 2 (SAM 2) t
pressor is cut in and pressure rises and systems should therefore be replaced (Fig. 2). Moreover, similar to cascade master controller, it is possible to reduce
fluctuates in the upper range between by other regulation methods when used control, the reactions of the compres- energy consumption even further than Fig. 3: Input of minimum and maximum pressure limits is not required with demand pressure control
sors and the compressed air network with set pressure oriented pressure
p/bar 1 2 3 4 are not taken into consideration, which band control. Moreover, the potential for
results in a shortfall of the minimum pos- undershooting of the preset pressure
sible pressure dew point. It is therefore level is eliminated and it is surprisingly
p
7,5
K4 necessary to maintain a safety distance simple for the operator to adjust the
K3 between the minimum required pres- demand pressure control him-/herself.
pO2
K2 sure and the lowest switching pressure
pO1
K1 of the regulation system.
WP
7
WP 2. b) Set pressure oriented pressure pu1

Pressure flexibility
band control pu2
x
Set pressure oriented pressure band
pmin
p
Demand control introduced a significant key
6,5
Band control without set
p
Alarm improvement (Fig. 1, Column 3). This p
Cascade SAM with set pressure SAM with demand pressure Alarm
pressure method strives to maintain a certain set
t pressure and, according to compressed es Con t
loss trol
hing loss
air demand, can control compressors Swit
c es

Fig. 1: Different variants of master pressure control of different sizes. The key advantage Fig. 4: The system prevents undershooting of the preset minimum demand pressure

18 19
www.kaeser.com

Chapter 8

Energy savings with heat recovery

In view of ever-increasing energy 100 % of up to 70 C can be achieved with


prices, efficient use of energy is not total electrical power these heat exchangers. Experience
only important for the environment, consumption 25 % shows that for compressor packages
ambient heat Heat exchanger
but is also increasingly becoming upward of 7.5 kW capacity the addi- (internal)
an economic necessity. Compressor
tional costs for these heat recovery
manufacturers are able to provide
systems amortise within two years. This
various solutions in this regard,
such as heat recovery with rotary of course depends on correct planning.
screw compressor systems for
example.
25 % 3. Considerations of reliability
compressed Air-cooled
air energy Normally, the compressors primary rotary screw compressor Cold w
potential ater
1. Compressors primarily cooling system should never be used
Hot wa
generate heat both for cooling and as a heat recovery ter
Amazing as it may seem, 100 % of system. The reason for this is that if
the electrical energy input to a com- Approx. 5 % the heat recovery system fails then
pressor is turned into heat. The action heat dissipation compressor cooling and, as a result, Hot water storage
of compression charges the air in the from the drive Approx. 2 % compressed air production would be
motor heat dissipated
compressor with potential energy by the compressor into endangered. The safest method is to Hot water heating
(Fig. 1). This energy is given up at the surrounding air install an additional specialised heat
Shower
the point of use by the compressed air exchanger within the compressor sta-
expanding and drawing heat from the tion that is solely responsible for heat Fig. 3: Heat recovery process
surroundings. Approx. 76 % Approx. 2 % recovery. Compressor operation and
heat energy recov-
erable through Approx. 15 % heat remaining in the
reliability are therefore safeguarded in
heat energy recoverable compressed air
2. Choices of heat recovery fluid cooling the event of a fault: if heat is not dis- Potential energy cost savings
through compressed air
Compressed air users interested in fur- cooling sipated by the heat recovery systems Energy cost savings with heat recovery
ther increasing the efficiency of their fluid / water heat exchanger, the com- through system
optimisation
compressed air supply system can pressor can revert to its primary air or
choose between various heat recovery water cooling system and so continue
options: operation (Figs. 2 and 3).

a) Air heating Approx. 96 % 4. Up to 96 percent usable energy


recoverable heat energy
The simplest and most direct method The major proportion of the energy
of recovering the heat generated in Fig. 1: Heat flow diagram recoverable as heat, about 76 %, is
a fluid-/oil-cooled rotary screw com- found in the compressor cooling oil,
pressor is by using the heat from the as a 7.5 kW compressor, can easily approx. 15 % in the compressed air
compressor systems warmed cooling generate enough recyclable heat itself and up to 5 % is lost through drive
air. This heated air is ducted away to be energy to warm a typical family home. motor heat losses. In a fully encap- Compressed air system investment Energy costs
used for space heating of warehouses sulated fluid-/oil-cooled rotary screw Maintenance costs Energy cost savings potential
and workshops. The hot air can also b) Hot water compressor package even the losses
be used for other applications such as Hot water for various purposes can be from the electric motor can be recov- Fig. 4: Heat recovery offers significant additional energy cost savings potential
drying, heat curtains and pre-heating recovered from either an air-cooled or ered as heat energy if appropriate
combustion air. When the heated air water-cooled rotary screw compressor cooling is used. This brings the total
is not needed, a manual or automatic package by means of a heat exchanger proportion of input energy available as 5. Conclusion purpose for which the heat is used and
flap, or louvre, discharges it into the installed in the airend cooling oil circuit. heat up to a startling 96 %. Recovering the heat of compression for the method of recovery chosen (Fig. 4).
open. The louvre can be thermostati- Plate or fail-safe heat exchangers are Of the remaining energy, 2 % radiates a useful purpose is an intelligent way
cally regulated to maintain a constant, employed, depending on whether the away from the compressor package of improving the economics of com-
set temperature. The space heating water is used for heating, laundry or and 2 % remains in the compressed air pressed air production and benefiting
method allows 96 % of the electrical showering, production or commercial (Fig. 1). the environment at the same time;
energy consumption of a rotary screw cleaning purposes. Water temperatures the effort involved is relatively small.
compressor to be recovered. It is well Fig. 3: Correct connection of compressors to a heat The investment is quickly recovered
worth is too: even small systems, such recovery system depending on local circumstances, the

20 21
www.kaeser.com

Chapter 9

Designing and installing a new compressed air


distribution network
Compressed air is an efficient source eliminate the pressure losses associ- lation cost, freezing of inadequately Most manufacturers offer tables in
of energy provided that its produc- ated with in-line filters in the air network insulated external piping in winter, or which the optimal conditions for every
tion, treatment and distribution and consume only approx. 3 % of the increased pressure drops caused by pipe material are given. It is advisable
components are perfectly matched energy that the compressor would long sections of piping. to study tables such as these before
with one another. Moreover, cor-
otherwise use to make up for these making a decision, to take into account
rect system design and appropriate
pressure losses. In addition, the saving a) Correctly sizing the network the loads placed on the air main during
sizing and installation of the air dis-
tribution network are also essential. in costs for maintenance and repair of A calculation must always be used to normal operation in the future and then
air-consuming equipment and pipe- correctly size air distribution piping. to create specifications for the pipework
work can easily amount to ten times the This calculation is based on the rule that accordingly. This is the only way to
1. Economical compressed air average cost of refrigeration drying. the maximum pressure drop between ensure a truly effective air main system.
production the compressor and the air-consuming
When the cost of energy, cooling b) Space-saving combination equipment (including standard air treat- d) Important correct jointing
medium, maintenance and equipment systems ment, i.e. refrigeration drying) should The pipes should be jointed either
depreciation is taken into account, the For smaller or local applications, space- be no greater than 1 bar. through welding, with adhesive or
cost of each cubic metre of air pro- saving compressed air packages The following individual pressure losses screwed with adhesive. It is especially
duced, depending on the compressor comprising a rotary screw compressor, should be taken into account (Fig. 2): important that the jointing is correctly
size, utilisation, condition and model, a refrigeration dryer and air receiver carried out to ensure a mechanically
is between 0.5 and 2.5 cents (Euro). (Fig. 1) are also available.
Air-main 0.03 bar sound and leak-proof joint, even if it is
Many production facilities place great
Distribution piping 0.03 bar difficult to take them apart again.
importance on highly efficient com- 3. Designing and installing an air
Connection piping 0.04 bar Fig. 2: Main components of a compressed air distribution system: Air-main (1), Distribution piping (2),
pressed air production. This is one of distribution network
Dryer 0.20 bar Connection piping (3), Dryer (4), FRL unit/hose (5)
the key reasons why fluid-/oil-cooled When designing a new compressed
Filter/regulator/lubricator Approximation formula: In wet pipework areas, e.g. only the
rotary screw compressors have air installation, one of the key factors unit and hoses 0.50 bar compressor room in the case of modern
become so popular: They can reduce to consider is whether it should be Total max. 0.80 bar air systems, pipe connections to and


compressed air production costs by designed as a centralised or a decen- 5 from the main line should be made
as much as 20 % compared with other tralised system. A centralised system The importance of calculating the pres- di = 1.6 x 103 x V1.85 x L from above or at least from the side.
types of compressor. is usually suitable for smaller and mid- sure drops in the individual piping areas p x ps The main line should have a drop of 2
sized businesses, since many of the becomes apparent when they are item- in 1000. The possibility of connecting a
2. The influence of air treatment on problems that occur in larger systems ised in this way. Shaped components condensate drain should be provided
the air main do not generally arise, e.g. high instal- and shut-off units should also be taken d i = Internal pipe diameter (m) at the lowest point in this line. In dry
However, less consideration is given into consideration. Therefore it is not p s = System pressure (absolute in Pa) areas the pipeline can be horizontal
to ensuring application-specific com- enough to just simply input the number L = Nominal length (m) with branch lines connected directly
pressed air treatment. This is a shame, of metres of straight piping into a cal- V = Flow volume (m/s) downwards.
since only correctly treated air can culation formula or table, as the actual p = Pressure loss (Pa)
reduce the maintenance costs of air technical flow length of the piping has Fig. 3: Approximation formula to determine pipe c) Which piping material?
consumers and associated pipework. to be determined. During the initial diameters No specific recommendation can be
Wherever pipework conveys mois- system-planning phase however, the made with regard to material proper-
ture-laden, non-dried compressed air, calculation figure for all shaped com- b) Installing energy-saving pipework ties. However, due to the high thermal
it is essential that corrosion-resistant ponents and shut-off units is usually In order to save energy the pipe layout loads associated with compressors,
pipework is used. Care should also be unclear. Hence, the flow length of the should be as straight and direct as metallic piping should always be used.
taken to ensure that inadequate pipe- piping is calculated by multiplying the possible. For instance, one can avoid The investment price alone provides
work does not negatively impact the number of metres of straight piping by bends in laying pipe work around an little help in making a decision, as gal-
compressed air quality achieved by the a factor of 1.6. The piping diameter can obstacle by repositioning the run in a vanised steel, copper and plastic pipes
treatment system. then be easily determined by referring straight line alongside it. Sharp, 90 all cost about the same when material
to tried and tested formulas (Fig. 3) or corners cause high pressure drops and and installation costs are added. Stain-
a) Refrigeration dryers reduce design diagrams (Appendix 1, pg. 54). should be replaced with large-radius less steel piping is about 20 % more
maintenance requirement A design diagram can also be elbows. Instead of the commonly-used expensive. However, more efficient pro-
Refrigeration drying provides an air created via the KAESER Toolbox water shut-off valves, ball or butterfly cessing methods have allowed prices to
Fig. 1: The all-in-one AIRCENTER compressed air
quality sufficient to meet 80 % of all package for space-saving compressed air produc- (www.kaeser.com/Online_Services/ valves with full through-flow bores drop in recent years.
applications. Refrigeration dryers often tion, treatment and storage Toolbox). should be used.

22 23
www.kaeser.com

Chapter 10

Optimising an existing air distribution network

A huge amount of cash is needlessly Working pressure


wasted year in, year out due to ageing
or poorly maintained air distribu-
tion systems which allow valuable
energy to escape unused. Resolving
these deficiencies requires consid-
erable thought and involves a lot
of hard work. Here are some useful
tips for correct refurbishment and
modernisation of compressed distri-
bution systems.

1. The basic requirement:


Dry compressed air
When planning a new air main, mis- Fig. 1: Modernising a compressed air distribution line through installation of a supplementary ring main Fig. 4: Leakage measurement of compressed air
takes leading to problems in the future consumers + air distribution network
can be avoided. Modernisation of an
existing compressed air main is not
always straightforward and is pointless
if the air being fed into the distribution
network contains moisture. Before
beginning such work, make sure the air t1 t2 t3 t4 t5
is dried at source.

2. What if there is an excessive


pressure drop in the air distribution
network?
If the pressure drop in the main is T Time (t)
excessive, even after a satisfactory
treatment system has been installed, Fig. 2: Expansion of distribution pipework capacity using cross-connection lines Fig. 3: Determining total leakage by measuring compressor cut-in times with all consumers switched off Fig. 5: Leakage rate of air distribution network
then the cause is probably deposits
in the pipes. Contaminants carried in mentary ring main can also be laid if the a) Determining total leakage losses tx = t1 + t2 + t3 + t4 + t5 The difference between the total and been located, removed and the effec-
the compressed air are deposited on inside diameter of the original ring is too The scope of the overall air leakage loss Time that the compressor network leakage is the leakage caused tive diameter of the pipeline is sufficient
the pipe walls, reducing their effective narrow (Fig.1). should be determined before searching ran on-load (min) by the air-consuming equipment and for the flow rate required, then the old
diameter and narrowing the passage If correctly sized, a supplementary spur for individual leaks in the network. This T= Total time (min) their fittings. air main has (once more) become an
through which air flows. line or double ring not only relieves is done relatively simply with the help efficient air distribution system.
the pressure drop problem but also of a compressor all air consumers b) Measuring leakages 4. Where do most leakages occur?
a) Replacement or blow out increases the reliability of the distribu- are left connected but switched off and at the air-consuming equipment Experience shows that 70 % of leaks
If the deposits are firmly encrusted tion network in general. the cut-in times of the compressor are In order to determine leakage losses from an air main occur in the last few
there may be no alternative but to A further possibility for improving the measured over a specific period (Fig. in decentralised compressed air con- metres of the network, i.e. at or near
replace sections of pipe. airflow in a ring main is to expand the 3). The results are then used to deter- sumers, all pneumatic tools, machines the air take-off point. These leaks can
However, it is possible to blow out the system by using cross-connection lines mine leakage with the following formula: and equipment should first be con- usually be pinpointed with the help of
pipes if the inside diameter is only (Fig. 2). nected and the sum of all leakages soap suds or special sprays. The main
slightly narrowed by deposits, followed VC x tx should be measured (Fig. 4). Then, the pipe work is only a source of significant
by thorough drying before bringing 3. Identifying and rectifying leaks VL = shut off valves upstream of all air-con- leakage if old hemp seals in an origi-
T
them back into service. A primary objective of any modern- suming equipment are closed and the nally damp network that have been kept
isation project must be to stop, as far Key: measurement is made again to deter- damp by the moist air then dry out when
b) Installing supplementary lines as possible, leakage of air in the main VL = Leakage volume (m/min) mine the leakage in the air distribution the network is fed by dry air. Leaks in
A good way of increasing the effective network. VC = Compressor flow rate network (Fig. 5). main air pipe distribution networks are
diameter of a spur line is to connect a (m/min) best detected with the aid of ultrasonic
second pipe in parallel with it. A supple- equipment. When the last leak has

24 25
www.kaeser.com

Chapter 11

Compressed air demand analysis (ADA)


Determining the current situation
Modern compressed air installations other words: the compressors, air treat- This computer-aided process, devel-
are usually highly complex systems. ment equipment and pipe work must be oped by KAESER and called ADA (Air
They are only able to operate at the correctly chosen, sized and controlled. Demand Analysis), has to take the spe-
peak of their performance if this Furthermore, there must be adequate cific circumstances of the application
aspect is properly taken into account
ventilation and a means of dealing into account:
during all stages of system plan-
with accumulating condensate and, if Situation on-site
ning, expansion and modernisation.
KAESER has developed a compre- possible, there should be a means of a) Designing a new air supply system
hensive service tool to aid these recovering the exhaust heat generated When planning a new compressed air
processes. It combines familiar by the compressors. The KAESER supply system, the future operator is first
elements such as compressed air Energy Saving System (KESS) covers given a special design questionnaire
components, customer consultation all of these aspects and more as it com- (Fig. 2). A KAESER consultant can
and advice with modern advances in prises air demand analysis, planning then interpret the provided information
compressed air engineering infor- (Fig. 1), implementation, further training to determine what system equipment
mation technology. ADA
and exceptional customer service. would be required in order to best meet
the needs of the specific compressed
Compressed air is used in more appli- The deciding factors are the quality of air application. The questions cover
cations than one can possibly imagine. the consultation and selection of the every aspect of what comprises an
But, the common prerequisite for effi- correct technology, since the greatest efficient and environmentally-friendly
cient use of compressed air is the potential for cost savings with any compressed air supply system.
reliable production and treatment of the compressed air system lies in efficient
air itself. The air system must be able power consumption and minimal main- KESS b) Expansion and modernisation
to deliver the air cost-effectively in the tenance requirement rather than in the In contrast to new projects, expan-
specified quantity and at the required initial purchase price. sion or modernisation programmes
quality. involving existing systems usually pro- Fig. 3: Layout of a compressed air distribution network
2. Air Demand Analysis vide sufficient reference points for new
1. Consultation influences efficiency Detailed investigation into the users application-tailored design solutions. duty cycles (partial load range) and will b) Compressed air applications
An air system is cost effective only if current and possible future compressed KAESER provides measuring instru- also assist in the selection of a suitable As compressed air is a highly versatile
it suits the application for which it is air requirements form the basis of every Safety ments and data loggers with which the master control system. medium, it is essential for the user to
intended and fits the location and the KESS analysis. air demand is precisely determined in provide exact details regarding the spe-
concept
conditions under which it operates. In various locations and at different times. d) Changes in operating conditions cific air application: Given information
It is particularly important to determine It is well worth consulting a specialist should include, for example, whether
maximum and minimum as well as when the conditions under which an air the air is to be used as control air, for
average values (Fig. 8, pg. 29). system operates change. Often simple surface treatment, for rotating tools, for
changes to air treatment methods or cleaning or as process air, etc.
ice
pro Ser
d to tem
?
vide vice
Saving
System
Service
emk-up )? ice
Serv
c) Testing the efficiency pressure matching can be made to suit
Serv nee Sys Energy Energy Sav
Syst
ingcap
aving acity, bac

c) Installed compressors
sors
of an existing air system the new circumstances, achieving sig-
tem use? to provide?
resy S
e
(reserv ressors need
neprg y edin
Sys until now

CAD
ad do the comp
ing e cE
om rs altuare lculat
l ca ption been in
use up
What maxim
um pressure Energy Saving System Service
Sav th so presso
rsued
pres ity Acair com Contin
um 7.
do
ns in
dby com future bar(g
rgy
ivery
very com Simultane /m
Have stan air del
use d for the pWmin

Ene ed Are Free


d? Planne er
deli tor 3. planne at the consum
re 8. Operating conditions
s us2.

As well as model and type, the com-


n

It is recommended that the efficiency nificant cost savings.


duty No fac% re m/mi d working pressu
air ee
hine ad /ac Lo
Pressu many? Yes No 7.1 Min. require
dm bar (g)Yes, how
at fr s an of cycle Model Energy Saving
Wh No.
System
=
tool %
Yes acture
r 8.1 Maximum intake temperature
future: tImax C
1.
ptio
n of
umpti
on tools, s
ine Ma+nuf
No
in use
? Planne
d for the cer + Service
um cons tool, mach x
troller 7.2 Pressure
losses sequen
cons Air
per ine ster con Base load _/_
er SAM8.2 Minimum air pressure (at max.
bar
Air =

pressors technical data such as


pP intake temperature) PImin

of an existing air system is checked


tors bar
ch Opera ation
x Is a ma controll 8.6 Heat
recovery
1.1 ma in + 4. Master k er VES
IS
, m/m design x controll
networ
pipeter
Tools ines x across theMas
= 8.3 Maximum relative airmhumidity (at max. intake temperature) HrelImax %
mach ch?
x
+ Yes, whi Pipework material + Use of hot air
pipe network of Purpose:
Alternative: Length
x
x bar

from time to time with the help of 3. Operator information working pressure, free air delivery,
= bar pACmax
8.4 Minimum intake temperature tImin C
No
x
er pACmin Water heating
+ ed carbon adsorb +
x
x from the activat bar
Purpose:
= pFSTmax
ry used? 8.5 re:
futu Cooling bar
d for the
x
recove pFSTmin Water inlet temper
+ Is heat Planne
filter + ature
5. from the sterile
x tInHR

a computer-aided analysis method a) Layout plan power consumption, type of cooling and
x bar
= Air-cooled C
ose: bar pFXAmax Water return
Yes, purp
x temperature
pFXAmin tRetHR
x d? lter +
in microfi
the uire Water-cooled C
x
m/m No from
lity is req bar Water volume
d air qua tment) bar pFXmax VWaterHR
sate trea
x
presse condenlter combination
Closed
pFXmincooling system Cooling water inlet temperatures tInMax C
of com tment,
m/h
at grade ed s +

that determines whether the com- A layout plan of the production facility use of heat recovery should also be
x in be us from the microfi
air trea lity clas 8.7 Comp
m/m 6. Wh e to essed sed air
quaOpen cooling system bar ressor tInMin
room C
V Tools ntinu Compr Compres 8573-1 aining bar pFVmax installation conditions
= ll co worksheet
t wier ISO/DIS pRem
tha(ref to as per ng FVmin
+ in so rs al
Loc from other filters Rem aini water + tRetMax C
m/m mpres n ng dust
Cooling water quality: Cooling water return temperatures
Dustin
bar ess
ols m/mi Remaini
l to
V Other
ist ing co Cen tralised Air n tent pDry
nts:
ptio con
of al of ex sum oil As per KAESER standard tRetMin C Cleanliness

should be available for general ori- mentioned.


con

pressors are (still) correctly loaded,


ptio
n +
ge de
livery m/m
in Air neptio
posum n in
ed m/mfrom the dryers
+ Low
um air mcon
ent co m/minRe
eaka marks ectly siz bar
cons fre
V Le
= V Exis
ting

Air Total Incorr pControl bar(g)


eatm for
Cooling water pressure pCoolW Low
e.g.
ers + air tr bar(g) control deviati
on High
nsum
leak
ages ve
sed m/minDesigned 7.3 Compressor
er co
mpresManufacturer
V Reser n
Oth ork m/mi bar(g High
g co

entation (Fig. 3). It should show the


netw

whether the control systems are (still)


1.2 = pMaxReq
air tin
Exis
essors Ventilation openin
sed re from the compr g
pres l .) um pressu
Com V Total in etc
ode Required maxim
1.3 Type/m= filter, dra bar(g)
presen
, t,
(dryer pmin
- pControl) m
rve the ssoren (pMaxReq
2010
. Mai

Rese from re from the compre

correctly programmed and whether compressed air stations compressed d) Compressed air treatment
-1\04 y 2010
ning

Minimum pressu
04.Ma
y
plan ing-1\
1.4
on
Not present
liver
stati n plann
d air air statio

r de
esse ssed
mpr mpre 2010
ai 8-Co 8--Co -1\04. May

free
3011 03011 planning
MV-0 UMV- air station

q'd rs
I/QU -VKI/Q ressed
e-VK Jeske 8-Comp

. re
Jesk V-03011

Exhaust openin
KI/QUM

Min presso
Jeske-V

g
com

leakage rates are still within an accept- air main, connection lines and feeder As far as air treatment is concerned,
May 2010
planning-1\04.
ressed air station
Jeske-VKI/QUM
V-030118-Comp
present,
m

Not present

able tolerance range. ADA should line connections. Details of pipe diame- it is important to know whether the air
Jeske-VKI/QUMV-030118-Compressed air station planning-1\04. May 2010

Jeske-VKI/QUM
V-030118-Comp
ressed air station
planning-1\04.
May 2010

also be used if compressors are to ters and materials, the main air take-off is treated centrally or locally and what
be replaced by new machines. This points and any take-off points for air at classes of quality are required. Obvi-
will avoid possible errors in capacity special pressures and qualities must ously, the technical specifications of the
Fig. 2: Compressed air station questionnaire to gather information regarding new and existing systems Fig. 1: KAESER Kompressorens compressed air selection that may lead to inefficient also be shown. components should be listed and a flow
(also see Appendix, Page 56 f.) analysis system

26 27
www.kaeser.com

Chapter 11

Compressed air demand analysis (ADA)


Determining the current situation
diagram provides the necessary over-
view (Fig. 4, pg. 28).
10

e) Compressor control

bar
and monitoring
As the efficiency of a compressed air
9
system is significantly affected by the 29.0
28.0
characteristics both of the individual 27.0
26.0
compressors and they way they interact 25.0
24.0
with one another, it is also important 23.0
22.0
to include details regarding the control 21.0
20.0
and monitoring systems that are used. 19.0
18.0
Fig. 6: Maintenance unit with pressure regulator 17.0
16.0

m/min
4. Discussions between the user 15.0
14.0
and specialist 13.0
12.0
Once the above information is made 11.0
10.0

available, the compressed air spe- Fig. 4: Hand-drawn P & I diagram of a compressed air station 9.0
8.0
cialist should be familiarised with the 7.0
6.0

relevant documents and then a discus- that these are often the final com- checked for fluid accumulation and con- 5.0
4.0

sion should follow detailing any issues pressed air take-off points. taminant build-up. The same applies to 3.0
2.0

with the air supply. Such issues might drainage pipes that lead straight down 1.0
0.0

include: low or fluctuating pressure, a) Connection hoses, pressure (Fig. 7).

00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
poor air quality, inadequate utilisation of regulators, water separators
compressors or problems with cooling. The hose connections to the air b) Shut-off valves Logger1 K2_B95_10 Logger1 K1_B111_10 Logger1 Pressure_Production
Logger1 Pressure_vessel Logger1 Pressure_before treatment
consuming equipment are highly sus- Distribution lines and their fittings leading Condensate
5. Inspection ceptible to leaks. These should be away from the main line significantly
The most revealing phase is an inspec- thoroughly checked. If pressure regu- affect system efficiency. Shut-off valves Fig. 7: Check compressed air branch lines for Fig. 8: A businesss pressure and compressed air consuming structure measured with ADA.
tion of the compressed air system. This lators are installed then their pressure and similar equipment also play an moisture
should always start in the most critical settings (inlet and outlet pressure) important role: they should be adequately
zone, i.e. where the greatest pres- should be checked under load (Fig. 6). sized, full-flow ball or butterfly types, not c) Main ring receiver and the location of the pres- over a period of at least 10 days with
sure drops or poor air quality are to be Water separators installed upstream inefficient water taps or angle valves. The most important point is to detect sure measurement points from which the help of advanced data logger tech-
expected (Fig. 5). Experience shows from pressure regulators should be causes of pressure drops such as nar- the compressors are controlled must nology. The data logger collects all
rowed sections. be checked. relevant information and transfers it to
a PC which uses this data to create an
d) Compressed air treatment system f) Determining ADA measurement air demand profile. The graph shows
The most important inspection cri- points pressure drops, fluctuations in pressure
teria here are the pressure dew point When the inspection is completed, the and consumption, off-load profiles,
achieved (degree of dryness) and the specialist and the user decide on the on-load and standstill periods of the
pressure drop across each component. points at which the measurements are compressors and the relationship of
Further quality checks may be required to be taken. The minimum requirement individual compressor performance to
depending on the application. is to measure points upstream and respective air consumption. In order
downstream of the air treatment system to complete the picture, the leaks also
e) Compressed air station and at the outlet of the compressed air have to be determined during this
Of course the compressed air station distribution network. measurement process. This is carried
itself may have its own shortcomings. out as described in Chapter 10, (pg.
In particular, the location of the com- 6. Measurement of pressure and 24 f.) and requires selective closure of
Compressed air Paint spraying pressors, ventilation, cooling and air consumption (ADA) defined sections of the air main over the
station facility with pipework should be checked. Further- During measurement of pressure and course of a weekend.
robots
more, the cumulative pressure swing air consumption, the operation of the
Fig. 5: Insightful: compressed air system inspection of the compressors, the size of the air compressed air system is monitored

28 29
www.kaeser.com

Chapter 12

Determining the most ecient concept

With meticulous compressed air solution. The mix generally consists of sors and additional components such in the compressor room. Air-cooling
system optimisation, it is possible large capacity base load and standby as condensate drains, dryers, etc. and saves between 30 and 40 % of the
to save more than 30 % of average compressors combined with smaller allow data exchange via a powerful bus costs normally associated with water-
European compressed air costs peak load machines. system. cooled systems (Figs. 2a to c).
for industrial businesses. Approxi-
The master controllers task is to ensure
mately 70 to 90 % of these costs are
the best possible balanced specific 3. Structural optimisation 4. Operational optimisation
accounted for by energy demand.
In view of ever-increasing energy power requirement. To do this it must A newly designed or modernised air and controlling
prices, it is therefore more important be able to automatically select the most supply system should make optimum In order to ensure compressed air
than ever for users to determine and appropriate combination of base-load use of the space in which it is to be system efficiency over the long-term, it
implement the most efficient com- and peak-load machines from up to installed. Modern design systems is essential to have an optimised cost/
pressed concept for their business. 16 compressors working within a pres- such as those used by KAESER pro- use ratio and complete transparency
sure band of only 0.2 bar. Intelligent vide worthwhile support in this regard. via an effective control system. This is
Using the optimisation calculation from master control systems such as KAES- During the design process they not where KAESERs integrated PC-based
the KAESER Energy Saving System ERs SIGMA AIR MANAGER meet only make use of floor plans and P & SIGMA CONTROL comes into to its
(KESS), it is possible to compare var- I diagrams, but also use advanced own, as it features five pre-programmed
ious system solutions for the specific these needs and enable highly sophis- 3-D computer-generated plans and control modes and is able to gather Fig. 2a: CAD-optimised 3-D planning of a compressed air station
application in question and identify the ticated system control. In addition, they animations. This means that it is often data and transfer it back to a data
most efficient. For new systems, the can be connected to centralised control possible to take advantage of efficient network. At the master control level a
completed design questionnaire pro- systems, as well as other compres- air-cooling despite cramped conditions further industrial computer is used: the
vides the basis for this calculation. For SIGMA AIR MANAGER (mentioned
existing air systems the calculation is earlier on page 18). Its task, as well
based on the characteristic daily profile as appropriate control and monitoring
determined by an Air Demand Analysis of the air supply system, is to collect all
(ADA) (see pg. 29, Fig. 8). relevant data and pass it on to a com-
puter network (Ethernet). This can take
1. Computer-aided analysis place via Internet or via the SIGMA
Before an existing air supply system CONTROL CENTRE centralised con-
can be optimised, all the technical trol software. Together with the SIGMA
data relating to it and any possible new AIR CONTROL visualisation system,
alternatives are entered into the KESS this PC-installed software can display
software. KESS then identifies the a list of all the air compressors and
optimum system design and calculates their key operational data. This shows
the potential cost savings. Moreover, at a glance whether the system is func-
the momentary power consumption tioning correctly, whether maintenance Fig. 2b: Layout diagram of a compressed air station
at a defined air demand, including all or alarm messages are activated and
losses, is also calculated. how high system pressure is.
It is also possible to establish a precise
picture of the specific power profile of
the air system throughout the entire
running period (Fig. 1). This means that
any weak points in partial load opera-
tion can be detected in advance and
remedied. The overall result is a clear
statement of the potential cost savings
and amortisation period.

2. Its the mix that counts


In most cases a precisely co-ordinated
configuration of compressors of different Fig. 1: Comparison of the power consumption of an existing air supply system with new alternative
capacities has proven to be the best systems over a one-day period related to air demand Fig. 2c: P+I diagram of a compressed air station

30 31
www.kaeser.com

Chapter 13

Ecient compressor station cooling

Compressors convert 100 percent through an aperture placed near the exhaust ducting. The compressor fan
of the electrical power consumed ceiling (Fig. 1). This kind of ventilation draws in cooling air through an appro-
into heat. Even a relatively small can only be recommended, however, for priately sized aperture and discharges
18.5 kW compressor easily gener- use in exceptional cases and for com- it into a duct that takes it straight out of
ates enough surplus thermal energy
pressor powers below 5.5 kW, since the compressor room (Fig. 3). The prin-
to heat a typical family home. This is
even sunshine or wind pressure on the cipal advantage of this method is that
why efficient cooling is essential for
reliable operation of a compressed exhaust aperture can cause problems. the temperature of the cooling air may
air system. be allowed to rise significantly higher,
3.2 Forced ventilation to approximately 20 K above ambient.
The exhaust heat generated by com- This method uses a forced flow of This reduces the volume of cooling
pressors is a perfect source of reusable cooling air. Ventilation is thermo- air needed. Normally, the cooling fans Fig. 1: Natural ventilation for compressors up to
energy. With the help of appropriate statically controlled to prevent the fitted in the packaged compressors 5.5 kW
heat recovery systems, up to 96 % of the temperature in the compressor room have sufficient residual thrust to drive
power consumed can be recovered as from falling below +3 C during colder the cooling air through the ducting and
heat, and if this is put to good use it can times of the year. Low temperatures out of the room. This means that in
significantly reduce the costs of com- negatively impact the performance contrast to ventilation with an external
pressed air production (see Chapter 8, of the compressors, the condensate extractor fan no additional energy is
pg. 20 f.). However, even where heat drains and the air treatment equipment. required. This applies only, however,
is recovered, the compressor still needs Thermostatic control is necessary if the residual thrust of the fans is suf-
an effective cooling system. The costs Example of a compressed air station with exhaust air system and thermostatically controlled additional because with forced ventilation the ficient for the ducting used. Ideally,
for air cooling can be up to 30 percent ventilation for the refrigeration dryers compressor room is subjected to slight the exhaust duct should be provided
lower than those for water-cooled sys- negative pressure that prevents back- with a thermostatically controlled flap
tems. This is why air-cooled systems 1.2 The compressor room increase the room temperature con- flow of hot air into the room. There are (Fig. 4) to direct hot air into the com-
should be given preference wherever is not a storage area siderably. Even in temperate climate two methods of forced ventilation: pressor room in winter to maintain Fig. 2: Forced ventilation with extractor fan for
possible. A compressor room is not a storage zones room temperatures can reach proper operating temperatures. If air- compressors from 5.5 to 11 kW
area and should be kept free of dust over +40 C. This is why apertures for 3.2.1 Ventilation with cooled dryers are also installed in the
1. The compressor environment and other contaminants, as well as cooling and inlet air should be located an external extractor fan compressor room then the compres-
1.1 Clean and cool is best extraneous equipment that has nothing in shaded walls and not in direct sun- A fan installed in the exhaust aper- sor(s) and dryer(s) should not influence
One of the main requirements of health to do with the production of compressed light. The size of the apertures is ture of the compressor room and fitted each others ventilation air flows. At
and safety regulations is that compres- air; the floor should also be non-friable. related to the capacity of the compres- with a thermostatic control (Fig. 2) temperatures above + 25 C it is rec-
sors must be installed in such a way Under no circumstances may air be sors installed and to the method of exhausts the heated air. An important ommended to increase the cooling air
as to allow adequate accessibility and drawn in to the compressor room from ventilation used. requirement for this type of ventilation flow rate by running a supplementary
sufficient cooling. Regulations for the a dusty or otherwise contaminated is that the cooling air inlet aperture is thermostatically controlled fan in the
installation of compressors require that environment unless intensive filtration 2. Ventilating the compressor room of sufficient size (see lower right in the ducting for the refrigeration dryers.
ambient temperatures for the operation is used. But, even under normal oper- No matter whether using air- or illustration); if it is too small, it could
of air and oil-cooled compressors may ating conditions, intake and cooling water-cooled compressors, adequate cause too high a vacuum resulting in
not exceed +40 C. air should be cleaned with appropriate compressor room ventilation is essen- increased noise from excessive air- Fig. 3: Forced ventilation with exhaust
Regulations also state that dangerous filters. tial. Whatever the case, heat radiated flow speeds. In addition, cooling of ducting for machines above 11 kW
substances must never be released within the compressor package from the compressed air station would be
near compressor intake areas. These 1.3 A suitable and constant the airend and electric motor has to be endangered. The ventilation should be
regulations stipulate just the minimum temperature extracted from the room. This corre- designed to restrict the temperature rise
requirements. Their purpose is to keep Temperature has a considerable influ- sponds to approximately 10 percent of in the room caused by waste heat from
the risk of accidents as low as pos- ence on the reliability and maintenance compressor drive power. the compressor to 7 K above inlet tem-
sible. Efficient compressor operation requirements of compressors; inlet perature. Otherwise heat will build up
with minimal maintenance requirement, and cooling air should be neither too 3. Various methods of ventilation and cause a compressor breakdown.
however, demands a lot more. cold (<+3 C) nor too hot (>+40 C). 3.1 Natural ventilation
This must be taken into account in the Cooling air is drawn into the room by 3.2.2 Ducted ventilation
planning and installation phases. For the compressor fan, the air is heated as Modern, fully encapsulated rotary
example, summer sun shining on south it passes over the compressor and rises screw compressors provide an almost
or west-facing walls of a building can upwards, leaving the compressor room ideal way of ventilation by means of Fig. 4: A thermostatically-controlled flap directs
warm air into the compressor room in winter

32 33
www.kaeser.com

Chapter 14

Ensuring long-term reliability and cost-optimisation

On pages 22 to 33 we covered the extra cost for a more efficient


aspects that had to be taken into
7% 2% machine working with a lower pres- Ineciencies
account during installation and 36% Other motors sure. Therefore, when considering the in compressed air stations and production areas
refurbishment of existing com- 16%
specification of new air-consuming pro-
pressed air networks and how an Pumps
duction machines, the pressure of the
efficient compressed air system
should be planned and designed.
Compressed air compressors air needed is just as important as the Compressed air station
Energy, cost-conscious planning Fans electrical power supply, which is why
guidelines should be written for the
and implementation, however, go
only halfway. Efficient compressed Refrigerant compressors purchase of such production machines
Unnecessary treatment
30%
air system operation also ensures Conveying systems that cover both electrical power and
cost-effective compressed air pro- 18% 22% compressed air supplies.
Solenoid valves / float drains
50%
duction over the long-term.
No air-main charging system 90%
Maximum compressed air efficiency Fig. 1: Amount of energy consumption attributed to compressed air compressors in relation to the 2.3 New production-related
brings triple savings: air system reli- energy consumed by industrial electrical drives in the EU (Source: SAVE II (2000) requirements Incorrect compressor configuration 60%
ability increases, whilst compressed 2.3.1 Compressed air consumption
air costs and power consumption sig- factors are compressor operating life, in 2003 (Fig. 3, pg. 35) highlighted the Refrigeration dryer with hot gas bypass
90%
nificantly decrease. The efficiency working pressure and other commercial inefficiencies of compressed air sta- a) Changes to production
potential is impressive to say the least:
The EU SAVE II study showed the
parameters.
The example illustrated is an optimised
tions in use in Germany. In most manufacturing facilities the
compressed air demand varies from
No heat recovery
70%
extent of the potential savings that can system with air-cooled compressors, 2. Maintaining efficiency shift to shift. However, if not taken into
be achieved: Compressors in the EU operational life 5 years, power costs Anyone interested in long-term com- consideration, changes to a production
No control technology or incorrectly set control systems
60%
consumed 80 billion kWh in 2000. At 8 cent/kWh, interest rate 6 %, 7 bar pressed air system efficiency should process may result in compressors Dirty / contami-
least 30 percent of this energy could be working pressure, air quality to ISO consider the following points carefully: operating far below capacity in one nated station 20%
saved (Fig. 1). 8573-1: Class 1 residual oil content, shift, yet in others not being able to
Class 1 remaining dust content, Class 4 2.1 Demand-oriented maintenance cover demand even with reserve Problems with system ventilation / exhaust
50%
1. What is optimum efficiency? remaining water content. The example Advanced internal compressor control- capacity. The air supply should there-
Inadequate / no air
The efficiency of a compressed air shows that even under optimum lers such as the SIGMA CONTROL, fore be designed to accommodate any treatment 20%
system is reflected by its cost structure. conditions power consumption still and compressed air management sys- such changes.
The achievable optimum is never the takes up the lions share of overall tems, such as the PC-based SIGMA
same because it is related to a specific compressed air costs (around 70 %) AIR MANAGER 2, provide detailed b) Expansion in production Production
company and its production. Critical (Fig. 2). A University of Coburg study service interval information for the com- In this case not only the compressor
ponents that comprise the compressed capacity but also the pipe work and the Long compressed
air station. This has made it possible to air treatment equipment may have to be
air hoses 20%
Compressor energy costs
63 % carry out preventive maintenance and adapted to meet the increased demand.
demand-oriented service work. This It is advisable to precisely measure and
Seat valves
40%
Air treatment energy costs 6%
results in lower maintenance costs, document the air consumption of the
Compressor maintenance costs 3% as well as increased efficiency and existing compressor system in order to
Inadequate pipe diameters
50%
reliability. gather enough detailed information to
Water in CA
Air treatment system maintenance costs 1%
economically modify or expand the air network 20%
Compressor investment 13 %
2.2 Matching air-consuming supply system to produce the higher
equipment capacity needed.
Air treatment system investment 5% It is only too easy to make savings
for compressed air production and 2.3.2 Air supply reliability 0 20 40 60 80 100
Installation costs / control centre technology 7%
consumption in the wrong places, e.g. It is usual to include a standby com-
Businesses surveyed (in %)
Condensate treatment (all) 1% to use a budget-priced production pressor in an air station to provide
machine that requires a higher working coverage when another is being ser-
Commissioning / training 1% pressure. The cost of generating pres- viced or replaced and to cater for Fig. 3: For original findings, please refer to the results analysis of the compressed air audits performed
sure higher than the standard 6 bar, occasional demand peaks. Such a by KAESER KOMPRESOREN within the scope of the Drucklufteffizient campaign. Thesis: Anja Seitz,
Coburg University, Specialism: Mechanical Engineering (2003)
Fig. 2: The cost structure of an optimised compressed air system for example, would quickly rise above reserve capacity, however, should be

34 35
www.kaeser.com

Chapter 14

Ensuring long-term reliability and cost-optimisation

matched by reserve capacity in the SIGMA AIR CONTROL plus Contact / Service SIGMA AIR CONTROL plus Contact / Service out potential savings and give priority
air treatment equipment. When air to energy efficiency rather than price
Settings Settings
System status Total costs System status
Load/idle
Current system SIGMA AIR MANAGER 8/4
Load/idling costs Maintenance/Warning

consumption rises, the standby com- when purchasing air supply equipment,
pressure Current system
System data Display period (max. 1 year) Fault
pressure Operating mode................. STATION AUTO
Event history 1:Load 15347.80 Starting date End date
pressor cuts in, but because of the lack the nearer we will get to achieving the
System data Local mode
Process data history Network pressure.............. 6.25 bar
Costs Costs: 2:Idling 296.45 Indicators
Event history Demand pressure.............. 6.15 bar 1: SK 19

of additional air treatment capacity the Energy costs: Image


General costs: Start of record: 00:00:10
Process data history
Costs
Pressure max.................... 7.41 bar
Pressure min..................... 5.79 bar
2: ASD 32 calculated 30 percent energy-saving
compressed air quality deteriorates as potential. Thats not only good for the
Energy costs: Table 3: BSD 62
3:Maintenance 1152.02 Resetting the time: Data recall Free air delivery................. 3,150 m/min
4: SK 19
Total costs 4:Maintenance 1617.35 Currency fluctuation:

a result. Therefore, a treatment unit Data recall 5:Downtime


6: Other
0.00
348.98


F1 F2 F3 F4 F5 F6 balance sheet, but also benefits the
(dryer/filter) should be provided for 6: Other 0.00 environment.
6: Other 0.00
each standby compressor. 6: Other 0.00
6: Other 0.00

Sum 2934.49
2.3.3 Changing of air quality 1:Load 2:Idling 3:Maintenance 1 2 3 4 5 6 7 8

If higher air quality is needed the pro-


1:Load 15347.80 15347.80 296.45 1152.02
2:Idling 296.45 81.80 % 1.58 % 6.14 % Date Time State Message No.

cedure differs depending on whether Total 18762.60 4:Miscellaneous 5:Downtime 4:Material 15.04.11 Time KQ: OIL SEPARATOR Garage 176

all areas of production are affected or


348.98 0.00 1671.35
Accept
1.86 % 0.00 % 8.62 %

only one specific area. In the former


Ready

Fig. 5a: Management system: Compressed air cost analysis (web-based) Fig. 5c: Overview: Control and management system

main cause is wear on tool, hose con- 3. Cost management ensures SIGMA AIR CONTROL plus Contact / Service

nections and machine components efficiency


Settings
System status
Free air delivery

(Fig. 4). This is why it is vital to keep Information gathered through analysis
Current system pressure Time 14:26:20 Free air delivery 3,150 m/min

System data

track of such problems and to take during the planning stage is also rele-
Event history FAD / m/min

Process data history

prompt action whenever they occur. It is vant for future system operation. Once
System pressure

Free air delivery 7.00

advisable to regularly measure overall the system is installed and running, Specific power
Compressor status 6.00

leakage with the aid of modern control however, no special analysis is needed Load/idle/
Total power
5.00

and monitoring systems such as the to acquire data at a later stage. These
Analogue inputs - 4.00
Progress over time

SIGMA AIR MANAGER. If an increase tasks are taken over by advanced


Analogue inputs - 3.00
Cumulative display
2.00

is recorded, the leaks must be traced master controllers such as the SIGMA
Costs
Data recall 1.00

and eliminated. AIR MANAGER. This forms the basis 0.00


13:00:00 13:15:00 13:30:00 13:45:00 14:00:00 14:26:20 Time

for comprehensive compressed air 20.04.11

audits and effective compressed air X 1 hour


5

Fig. 4: Leakage location using ultrasound system cost-management (Fig. 5a to Ready

e). The more users introduce transpar-


case, it is not enough to simply re-equip ency into their air cost structure, search Fig. 5d: Compressed air consumption
the central compressed air supply.
The pipe work that has transported SIGMA AIR CONTROL plus Contact / Service SIGMA AIR CONTROL plus Contact / Service

air of lower quality will have to be


Settings Settings
System status Network pressure System status Specific power
Current system pressure Current system

cleaned or renewed. In the latter case,


pressure Actual value 5.22 kW/m/min Average 5.32 kW/m/min
System data Actual pressure 6.24 bar Average 6.38 bar Reference
System data 5.85 kW/m/min Minimum 5.14 kW/m/min
Event history value
Required pressure 6.15 bar Minimum 6.14 bar Event history Time 11:44:50
local air treatment that can supply
Process data history Process data history
pt Pressure
5.95 bar 99.6 %
performance
Spec. power / kW/m/min

the quality required is recommended.


Network pressure Pressure (bar) Network pressure
Air delivery Max. display value: 6.3 kW/m/min Accept
Air delivery Time 20.04.15 14:19:10

Airflow through local treatment devices


Specific power Specific power 7.00
6.70
Compressor status Compressor status

should be limited.
6.60
Load/idle/ Load/idle/ 6.50
Total power Total power
6.50

This ensures that an increase in


Analogue inputs Analogue inputs -
Progress over time 6.40 Progress over time 6.00
Analogue inputs

demand above that for which the


Analogue inputs -
Cumulative display 6.30
Cumulative display
5.50
Costs 6.20

devices are intended does not result in


Costs
Data recall Data recall
6.10
5.00

degradation of air quality. 6.00

5.90
4.50

13:00:00 11:30:00 11:45:00 12:00:00 12:15:00 12:30:00 Time 11:05:00 11:30:00 11:45:00 12:00:00 12:15:00 12:30:00 Time
15.06.10
20.04.11

2.4 Monitoring leaks Y Zoom - X 1 hour 15.06.15 11:05:00


5

0
Y Zoom + X 1 hour
5

Leakages occur in every compressed Ready Ready

air distribution network and can lead


to considerable energy losses. The Fig. 5b: Pressure curve Fig. 5e: Specific power requirement

36 37
Practical tips
Tips 1 - 7
www.kaeser.com

Tip 1

Savings with optimised pressure

The efficiency of a compressed air Pressure at the


system doesnt just depend on the air-consuming
correct working pressure. Even equipment
6.0 bar/4.0 bar Counter-balance 6 bar
small measures can often have a
large effect.
Pressure at the
6.1 bar take-off points:
In many cases, the connection to the Tool not in
compressed air tools looks as follows: operation
At rest, the pressure at the mainte- Spiral
nance unit is 6.1 bar and 6.0 bar at the Shut-off valve hose
tool. However, this pressure is not the
7.5 to 9.5 bar
same as the pressure when air is being
used. Maintenance unit with pressure regulator

Pressure drop at the tool Caption: Tool connection with spiral hose 6.0 bar pressure with zero compressed air consumption.
what to do? 4.0 bar when tool in operation = 2 bar pressure drop when tool in operation: only 54 % of full perfor-
mance capacity!
Pressure measurement on a working
tool often shows a considerable pres-
sure drop. In the following example, Counter-balance
this drop is 2 bar; in other words the 6.0 bar
tool delivers only 54 % of its potential
performance. 8 to 10 bar network pressure reduced
6.1bar Tool not in
The causes for this can often be easily operation A waste of energy, pure and simple: higher compression than necessary, with pressure reductions at the air-consuming equipment...
remedied:

a) Insufficient connection diameter: Shut-off valve Smooth


Use a quick-coupling with a larger flow hose Pressure at the
passage. air-consuming
equipment 6 bar
Maintenance unit with pressure regulator
b) Incorrectly adjusted pressure
Pressure regulator
regulator: Open it further. Water separators and spiral hoses are energy wasters: instead, dry compressed air centrally and use
opened further
smooth hoses
c) System pressure too low: Increase
the pressure in the air-main or install Saving energy with the right turn defective due to insufficient tool pres-
pipework with a larger diameter. Pressure regulators affect the efficiency sure and the compressors run longer
of compressed air usage to a greater than necessary. On the other hand, the
d) Spiral hose is too small: Use a extent than is often realised. In this desired savings can be easily and pain-
larger spiral hose or preferably a example, the compressed air system lessly achieved by not only reducing
smooth hose. is operating between 8 and 10 bar. The the system pressure, but also by using
pressures of 7.5 and 9.5 bar, respec- smooth hoses, removing superfluous
e) Pressure drop in the decentralised tively, at the take-off points are reduced water separators and further opening
water separator: Dry compressed to 6 bar by a pressure regulator. To the pressure regulators on the air-con-
air centrally (makes the separator save energy, the system pressure is suming equipment.
superfluous). reduced to between 6.8 and 7 bar. This
These are simple steps to restore means that a pressure of 6.1 bar is
optimal tool pressure (6 bar, in this available at the network take-off points,
case) and performance at 100 % of but only 4 bar is available to the tools. 6.8 to 7.0 bar network pressure reduced
capacity. This configuration has consequences:
work takes longer, work results may be ...instead, reduce system pressure and open the pressure regulator further

40 41
www.kaeser.com

Tip 2

Correct pressure at the air connection

The compressor station pressure is nents, the problem can only be in the Furthermore, a specialised nomo-
actually correct, but pressure is too pipe network. This is divided into three gram can also be used; please see
low at the air-consuming equipment. sections: the main line, distribution Appendix 1, pg. 54 f.
Whats the cause? line and connection line (Fig.1). In an
optimised compressed air system, the Ensure correct connections
In this case, hoses, quick couplings following pressure drops are reason- To prevent disruptions and damage
and pressure regulators are commonly able from an efficiency perspective: due to potential moisture, the con-
the offending components. But often nection between the distribution and
the pressure at the take-off point in the Main line (1): 0.03 bar connection lines should be designed as
system is too low: for example, of the Distribution line (2): 0.03 bar a flow-optimised swan neck (Fig. 2):
6.8 to 7 bar originally available for the Connection line (3): 0.04 bar a direct downward pipe should only be
tools, a mere 5 bar remains. Additionally: used if the possibility of condensate for-
Dryer (4): 0.2 bar mation in the pipeline can be excluded
Operators often turn to a quick fix: Maintain. unit/hose (5) 0.5 bar with 100 % certainty (Fig. 3).
Lets just set the station pressure 1 Total: 0.8 bar The optimised connection, which has
bar higher, who cares! But this is prob- a maximum pressure drop of 1 bar
lematic, because for every pressure Eliminate bottlenecks between compressed air discharge at
increase of 1 bar, the energy con- Upon closer inspection, it often the compressor and the compressed
sumption of the compressor station becomes apparent that although the air tool, is illustrated on page 40.
increases by 6 % and the leakage main line and distribution lines have
rate also sharply increases. Its there- the correct dimensions, the connec-
fore advisable to identify the causes tion lines are too narrow. For these,
and implement an appropriate solution. the pipe width should not be less than
DN 25 (1). For precise determina-
Pipe network as the source of the tion of the cross-section, KAESER Fig. 1: Main components of a compressed air distribution system: Air-main (1), Distribution piping (2), Connection piping (3), Dryer (4), Maintenance unit/hose (5)
problem KOMPRESSOREN offers a convenient
When the pressure directly downstream on-line tool:
of the compressor is correct and there www.kaeser.com/Online_Services/
is no disproportionately large reduction Toolbox/Pressure_drop/.
due to downstream treatment compo-

Fig. 3: Direct downward pipe

Fig. 2: Swan neck

42 43
www.kaeser.com

Tip 3

Ecient compressed air distribution

There are essentially three ways to Designing the air-main


distribute compressed air from the The function of a compressed air
compressor system to the point of systems air-main is to connect the
use: via branch line, ring main or separate air distribution lines for var-
distribution network. As to which
ious operational facilities (buildings)
system is most suitable depends
with the compressed air installation
on the company concerned. When
looking at efficient use of com- (generation).
pressed air, it is important not only
to focus on energy-saving air pro- The dimensions and capacity of an
duction, but to also consider the air-main are dictated by the total air
most effective method of air distri- delivery of the compressors within the
bution. Read on to find out how compressed air system. Care should
also be taken to ensure that the pres-
Branch line sure drop does not exceed 0.03 bar.
Installation of a branch line with var-
ious outflow connections that lead to Fig. 1: Compressed air branch line Air from a single compressor Fig. 3: Compressed air distribution network with pipeline grid
the individual air consumers (Fig. 1) package
is relatively straightforward. The length If a single compressed air package
of piping required for the branch line supplies air to several operational facil-
is comparatively short, but must have ities (e.g. production halls), then the
sufficient capacity to meet the systems feed lines, and therefore the air-mains
entire compressed air demand. for the individual areas, should be
This means that the pipe diameter has able to deliver the maximum volume
to be significantly larger in comparison of compressed air required by that
to ring main or distribution network area. Once again, the pressure drop
piping. The connection lines to the air should not exceed 0.03 bar. Pipelines
consumers also have to be larger, due bundled together in a collector within
to the increased distance from the main the compressed air station provide
compressed air supply. In addition, this the advantage of being able to easily
solution does not allow individual sec- shut off entire work areas as required.
tions of the system to be shut-down in Furthermore, with the addition of flow
order to facilitate system expansion or rate measuring equipment, the air con-
cleaning work for example. Branch line Fig. 2: Compressed air ring main sumption of individual areas can be Fig. 4: Compressed air supply with a central compressed air station for multiple production areas
systems are therefore best suited to easily determined (Fig. 4).
small businesses.
included in the ring main design, as this system to install, but any additional Air from multiple compressor
Ring main allows certain sections of piping to be effort is more than rewarded through the packages
Installation of a ring main taken out of operation for cleaning and advantages that it brings. The network If several compressor packages supply
(Fig. 2) is more complex but has system expansion purposes, leaving structure provides a reliable and ener- the compressed air for a large air-main
one considerable advantage the rest of the air installation to operate gy-efficient supply of compressed air system, then the piping must have suf-
over a branch line system: if using as normal. to large production halls with no need ficient capacity to be able to deliver
consumers each with the same com- for excessively large pipe dimensions. the maximum air volume from the
pressed air demand, the connection Distribution network On the contrary: pipe dimensions can largest compressor package of each
pipe length and volume can be reduced A distribution network is perfect for be kept to a similar size as those in a production area. Again, the pressure
by half. As a result, smaller diameter companies with large facilities. The ring main system installed in a small or drop between the individual packages
piping can be used and the capacity design is very similar to a ring main, medium sized business. The system should not exceed 0.03 bar, otherwise
remains the same. The connection lines but includes additional longitudinal and has the further advantage that indi- installation of complicated and expen-
are very short and are seldom installed cross connections that transform the vidual sections can be shut-down as sive regulating systems becomes
any larger than DN 25. Sufficient num- system into a true pipe network (Fig. 3). required. necessary (Fig. 5).
bers of shut-off units should also be Of course, this is the most complicated Fig. 5: Compressed air supply with two stations and central regulation for multiple production areas

44 45
www.kaeser.com

Tip 4

Pipework in the compressed air station

The pipe network not only distributes Correct connection size Fig. 3a (1)
compressed air within a companys The air-main collector should have at
facilities, but also connects the com- Fig. 1.1 least a connection in order to pre-
pressors and other components vent unnecessary back-pressure.
of the compressed air installation
to the whole system. In order to
Connection from above
ensure best possible efficiency and
reliability, several important factors The air-main collector should be con-
should be taken into consideration nected to the condensate lines from
when installing the system. above so that the drainage points do
Flow diffuser not influence one another (Fig. 3a (1)).
The pipe network should usually be laid
out in such away that the pressure loss Sloping, pressure-free line
caused by the piping remains below The condensate collector should always
0.01 bar at full flow capacity. It is also be installed at a gradient and should Fig. 3a: Connection of refrigeration dryer and
advisable to use only metal piping, as not be under pressure. Condensate condensate drain (from above)
it can cope with differing thermal loads drains from various system compo-
nents (e.g. centrifugal separator, air
Connection of compressed Fig. 1.2 receiver, refrigeration dryer, air filters)
air distribution piping operating at different pressure levels
The best way to connect the piping from Fig. 1: Compressed air station with collector line should discharge only into a system like
the compressor station to the air distri- this. If this is not possible, then various
bution network is to use a collector. The connection points on the condensate
collector acts as a central feed-off point Compressor connection treatment equipment (Aquamat) should
for all distribution lines (Fig. 1.1). and, Flexible connections should be used be used.
if necessary, allows the compressed to connect the compressors to the air Fig. 2.1
air supply to be shut down for specific distribution network in order to avoid Multiple treatment units
operating areas. transmission of vibrations. Hose con- If, due to large volumes of condensate,
nections are suitable for pipe widths it is necessary to use several treatment Fig. 3b: Vibration-dampening compressor
Installation in the moist air sector < DN 100 (Fig. 4). A vibration-absorbing units, then the main condensate line connection with axial compensators
Installation of a condensate collector in fastening is attached between the hose Water trap should be connected via a flow distrib-
the so-called moist air sector, i.e. the and the first pipe bend to ensure that utor (Fig. 1.2).
piping sections located downstream these forces are not transferred to the
from the compressors and upstream piping (Fig. 4.1). For pipe diameters System pressure above 15 bar
from the air dryers, should be avoided > DN 100, axial compensators must For systems with pressures above
if at all possible. Otherwise, the piping be used instead of hoses (Fig. 3b) to 15 bar, a separate high-pressure relief Fig. 4.1
must slope towards the condensate implement the vibration-dampening Fig. 2: Line with water
ter trap and condensate drain chamber should be used before the
collector, which must be drained via a connection between the compressor condensate is drained into the treat-
specifically dedicated condensate drain and pipeline system. lems can be easily avoided however, by ment unit.
(Fig. 2). following the simple tips below:
Correct condensate drainage
Correct component connection Reliable condensate removal is essen- Shut-off the condensate drain
The individual components of the com- tial to ensure optimised compressed air Condensate drains should be able to be
pressor station (compressors, dryers system performance and availability. shut-off on either side via a ball valve
etc.) should be connected to the main There are a few errors worth avoiding, so that they can be easily removed Fig. 4: Vibration-dampening compressor
air line from above. Connection from particularly when it comes to installing from the compressed air system should connection with a hose
the side is also possible with pipe diam- compressed air lines. Despite todays maintenance work need to be carried
eters from DN 100 (Fig. 3 a/b). advanced drainage technology, the out (Fig. 2.1).
connection lines used to connect these
condensate treatment systems are
often incorrectly installed. These prob-

46 47
www.kaeser.com

Tip 5 Tip 6

Correct compressor installation Compressed air station ventilation (intake)

The installation location and the Appropriate compressor system


environmental surroundings of a ventilation not only enhances com-
compressed air system greatly influ- pressed air availability, but also
ence compressed air production helps to minimise maintenance
efficiency and reliability. Here are costs. Heres how its done:
three rules worth remembering...
1. Correct location of ventilation
openings
1. Keep the compressed The location of ventilation openings is
air installation clean Fig. 2a: Bag air filter (intake side) Fig. 2b: Bag air filter (compressor side) extremely important for effective ven-
The level of cleanliness for many com- tilation of a compressor system. To
pressed air systems leaves a lot to be condensate in the lines would freeze, ment to shut-down and the compressed ensure optimum system reliability, air
desired, even if it doesnt look like the resulting in operational disruptions. air supply system to completely fail. that is drawn in from outside should
Secondly, the lubrication performance All of these problems can be avoided be affected as little as possible by the
of the oils and bearing lubricants used simply by maintaining a moderate weather. Therefore, it is advisable to
in compressed air systems is signifi- temperature in the compressor room. install weather-protected ventilation
cantly reduced at temperatures below This can be guaranteed year-round openings in the lower half of the instal- Fig. 2: Compressed air station with supply air system
+ 5 C. Needless to say, this can also via cooling systems, which automat- lation locations external wall, which
lead to system failures. During the ically regulate the heat balance in the ideally should not directly face the It is important to take note of the term A ventilation system generally com-
summer months however, as 100 % of compressor station via thermostatically sun. free diameter. Weather protection prises (Fig. 1) a bird protection screen,
the electrical energy used to power the controlled ventilation (Fig. 3). screens, louvres and in dusty envi- a weather protection screen, a (motor
compressor is converted into heat, it is 2. Protect the system from ronments filters all considerably operated) flow adjustment flap and, if
Fig. 1: Neglected compressed air station important to ensure as far as possible 3. Maintenance-friendly station dust and contamination reduce the diameter of the ventilation necessary, ventilation filters. For com-
that the compressor room does not Although modern compressors and The compressor system should be opening: Depending on the quality of pressed air systems comprising several
one shown in Fig. 1. Above all, clean- exceed the outside ambient tempera- treatment components require signifi- exposed to as little dust and contam- the selected ventilation system, the compressors, it is advisable to install
liness means protecting the equipment ture. Otherwise, motors and electrical cantly less maintenance than older ination as possible. This includes all diameter is reduced by between 30 a thermostatically controlled ventila-
from exposure to dust. If care is not components are liable to overheat and equipment, they are not completely aggressive, or flammable, materials and and 60 percent. It is therefore best to tion system and to divide the openings
taken, the compressor intake filters will the dryer may become overloaded due maintenance-free. Therefore, the sys- emissions from combustion engines. use flow-optimised ventilation systems. according to the position and power of
quickly clog up, which not only increases to insufficient re-cooling. Once again, tems must be installed in such a way as Trucks and heavy vehicles in particular Whatever the case, compensation the individual units (Fig. 2).
maintenance requirement and reduces this leads to condensate accumula- to ensure easy, reliable access to all should not be allowed to enter the com- should always be made for reductions
performance, but also adversely affects tion and degraded performance of service-relevant areas. Optimum com- pressor systems air intake zone. If in diameter caused by protection and 4. Also ventilate water-cooled
air cooling. Subsequent consequences air-consuming equipment. In a worst- pressed air system reliability and per- high levels of dust or contamination are control devices. compressors
may include costly downtime due to case scenario, insufficient ventilation formance can be achieved only if all unavoidable, then appropriate protec- Water-cooled compressors also require
overheating, decreased dryer power can result in a build up of heat, which three of these points are closely ob- tion measures should always be taken. adequate ventilation, as they are usu-
and, as a result, condensate accumu- causes all compressor / dryer equip- served. Moderate levels of dust and contamina- Weather protection ally powered by air-cooled motors,
lation. This in turn can cause serious tion can be alleviated using cooling air screen Bird protection which radiate heat. Approximately 20
damage to air-using equipment and filters. In extreme cases, so-called dust screen percent of a water-cooled compres-
can negatively impact product quality. traps can be used. sors power is converted to heat, which
Therefore, if dust exposure cannot be needs to be removed by the cooling air.
avoided by finding a dust-free installa- 3. Correctly size and equip Appropriately dimensioned ventilation
tion location, then a bag filter should the ventilation openings openings should therefore be installed
be used to clean the intake air (Fig. 2a, The size of the ventilation openings accordingly.
2b). depends on the power of the air-cooled
compressors that are installed. As a
2. Ensure moderate temperatures rule of thumb, the free diameter of the
Firstly, the compressed air system ventilation opening should be between
should not be exposed to sub-zero 0.02 and 0.03 m for every kilowatt of
temperatures, as this leads to produc- a compressors rated power. This is Inlet air filter Motor-controlled air
tion and transport of moist compressed equivalent to a cooling air volume of inlet shutter
air before it reaches the air-using 130 to 230 m/h.
equipment; in the event of frost, the Fig. 3: Compressed air station with thermostatically-controlled air ducting Fig. 1: Supply air system (design)

48 49
www.kaeser.com

Tip 7

Compressed air station ventilation (exhaust)

In order to safeguard compressed vres are necessary to properly connect the system (take note of manufacturers
air availability and keep maintenance the compressors. When closed, they specifications). Otherwise, exhaust air Changeover flap
costs to a minimum, compressed prevent warm air from flowing back into from this unit would flow back into the
air stations must be equipped with the station when the given compressor installation room. Additional fans are
appropriate exhaust ventilation. If the
is not in operation. Motor-actuated needed if there is insufficient residual
ambient temperature falls to below +
louvre flaps reduce pressure loss and thrust. The louvres should be automat-
5 C, then recirculated air should be
used to keep the installation room at can be activated in conjunction with the ically controlled via room thermostats
an appropriate temperature for com- Motor running signal. Baffles should and compressors. Monitoring with a
pressed air system operation. be installed to minimize pressure master control system (e.g. SIGMA
losses in the collective exhaust air dis- AIR MANAGER) is also recommended
1. Manage exhaust air charge duct. in order to be able to quickly identify
Air exhaust ducts perform an important potential problems with the louvres and
role in compressor installations: They 3. Use recirculated air to maintain to forward any alarm messages to a
remove the warmed cooling air, as well the temperature in the installation centralised control system.
as the exhaust heat from the motor room
and the heat radiated by the compres- Air recirculation flaps should be 6. Special cases Water cooling Canvas duct joint
sors (Fig. 1). With modern machines, installed in areas where temperatures As water-cooled compressors emit the
the exhaust heat from these various fall to below + 5 C. These should be equivalent of 20 % of their input power
sources leaves the unit via a single active from + 10 C, whereby they open as radiant heat, these systems also
air discharge opening (Fig. 1, circle). to a greater or lesser extent according require sufficient ventilation.
This must be flexibly connected to the to the temperature (Fig. 1). If the com- Fans
air exhaust ducting via a canvas neck pressor system is completely shut down
connection (Fig. 2). For ambient tem- every once in a while, then a supple-
peratures above + 10 C, all of the air mentary heating system should be Fig. 1: Exhaust air system with individual ducting for each compressor
warmed with exhaust heat is removed used to ensure that the temperature in
from the compressor installation room. the installation room remains above +
As older compressors often have sep- 5 C.
arate air discharge openings, it may
therefore be necessary to install indi- 4. Ventilate refrigeration dryers
vidual ducting accordingly. Refrigeration dryers generate approxi- Collective exhaust
mately four times as much heat energy ducting
than they consume as electrical energy.
They should therefore have their own
exhaust system equipped with a ther-
mostatically controlled fan (Figs. 1
and 3). If the compressor installation
includes several refrigeration dryers,
then the fan should have a pacing
control system that is activated from
+ 20 C. As this exhaust system isnt
in continuous operation, the ducting
doesnt need to be installed directly on
Fig. 2: Compressor ventilation connection with the dryer.
canvas duct joint
5. Correctly design and
2. Install collective ducting manage exhaust systems
If installation of individual exhaust air All exhaust systems should be designed Fans
ducting is not possible, then a col- to ensure that any pressure drop they
lective exhaust air discharge duct induce is smaller than the residual thrust
(Fig. 3) must be provided. Check lou- delivered by the smallest machine in Fig. 3: Exhaust air system with collective exhaust ducting for all compressors

50 51
Appendices
Appendices 1 - 2
www.kaeser.com

Appendix 1

Nomogram to determine required internal pipe


diameter

Pipe length in [m]


Clear
pipe diameter [mm]
10 Pipe length in [m]
500 Pressure drop
20 [bar] Clear
Free air delivery 400 pipe diameter
0.03
[m/h] [m/min] 350 10 [mm]
50
300 System 0.04
500 Pressure drop
pres-
100
10000
250 sure 0.05 20 [bar]
100 [bar (g)]
0.07 Free air delivery 400
200 1 5000 200
4 0.03
3000 50 175 2
[m/h] [m/min] 350
0.1 50
2000 150
500 30 3 300 0.04
125 System
20 2 4 0.15 10000 0.05
1000
1000
7 100 8 5 6 100 250 pressure
10 6 0.2
100 [bar (g)]
500
2000 80 7 5000 200 0.07
200
300 5
65 10 5 0.3

5000 200 3 15 0.4


3000 50 175 2
2.5 20
0.1
50
0.5 2000 150
100 30
500 3
A 40
E 125
O 32
0.7
1000
20 4 0.15
1000 5
25
1.0 100 0.2
10 6
500
20 1.5 2000 80 7
C D F F 300 5
65 10
0.3

5000 200 15 0.4


2.5 20
50
100 0.5
The required internal pipe diame- the C-axis. Finally, mark the minimum attain an intersection point on the D-ax-
A 40
E
ter for compressed air lines can be
calculated using this nomogram:
system pressure and the desired maxi-
mum pressure loss on the E- and G-ax-
is showing the required pipe diameter.
O 32
0.7
Mark the A- and B-axes according to es. The straight line between these two
the pipe length and the delivery vol- points intersects the F-axis. By con- 1.0
ume. Draw a straight line between necting both intersection points on the 25
both points, extending it to intersect C- and F-axes with a straight line, you
20 1.5

C D F F

54 55
www.kaeser.com

Appendix 2

Questionnaire examples regarding the Energy


Saving System Service

Energy Saving System Service Energy Saving System Service

1. What free air delivery do the compressors need to provide? 2. Are compressors already in use?
No
1.1 Air consumption of tools and machines used

Yes
Tools, Air consumption No. of Load / duty Simultaneity Actual calculated
machines per tool, tools, cycle factor air consumption
machine machines % % m/min Operators Manufacturer Model Pressure Free air delivery Continued
m/min designation bar(g) m/min use
planned?
x x x = Yes No
+
x x x =
+
x x x =

+
x x x =

+
x x x =

+
x x x =

Air consumption of all tools = VTools m/min


+
Total free air delivery of existing compressors that will continue to be used
1.2 Other consumers VOther m/min
+ = VExisting m/min
1.3 Compressed air network leakages VLeakage m/min
+ Existing compressed air treatment components:
1.4 Reserve VReserve m/min Type/model Manufacturer Designed for Remarks
(dryer, filter, drain etc.) m/min bar(g) e.g. Incorrectly sized

Min. req'd free air delivery from the = VTotal m/min


compressors

56 57
www.kaeser.com
www.kaeser.com

KAESER The world is our home


As one of the worlds largest manufacturers of rotary screw compressors, KAESER KOMPRESSOREN is represented throughout
the world by a comprehensive network of branches, subsidiary companies and authorised partners in over 100 countries.
With innovative products and services, KAESER KOMPRESSORENs experienced consultants and engineers help customers
to enhance their competitive edge by working in close partnership to develop progressive system concepts that continuously
push the boundaries of performance and compressed air efficiency. Moreover, the decades of knowledge and expertise from
this industry-leading system provider are made available to each and every customer via the KAESER groups global computer
network.
These advantages, coupled with KAESERs
KAESSER s worldwide
wo service
serrvicce organisation,
se orga
organnisa on,, ensure
satitio en
nsu e that
sure at all
tha a l products
al oducts operate
p od
pr ope
p rate at the peak of their
de maximum
performance at all times and provide maxxim
imumm availability.
um avail
vailab
abi
bililit
ilitty.y.

P-2010ED.10/15 Specifications are subject to change without notice


KAESER KOMPRESSOREN SE
P.O. Box 2143 96410 Coburg GERMANY Tel +49 9561 640-0 Fax +49 9561 640130
e-mail: productinfo@kaeser.com www.kaeser.com

S-ar putea să vă placă și