The line impedance is converted to the secondary side of the instrument transformers wit h
the formula
VT prim CT sec
= 7.2204 79.075
F = 50Hz
CHAPTER-IX
Where
Z1 = Positive sequence impedance
Iprim./sec. = 1200 / 1 A
Maximum permissible reach of the start relay Zma x = 0.5*96.16 = 48.08 Ohms
The starter relay setting is determined by the Zo ne-3 reach and the load impedance. The
radius of the start relay circle is determined by setting the Zo ne-3 reach by over
reaching about 35%.
2. ZONE-1 SETTING:
In case of numerical relays the value calculated shall be programmed directly In the case of
static/ magnetic relays the relay manual shall be referred for setting the calculated values by
wa y of selections
2. ZONE-2 SETTING:
Zone-2 settings =100% of the line + 50% of the adjacent shortest line
According to the relay manual the settings are to be adopted for the Zone-2 reach. Similar to
the Zo ne-1 the numerical relays shall be fed wit h the value.
3. ZONE-3 SETTING:
The relay can be set wit h Zone 3 in reverse looking blocking mode or on
forward reach,
As per relay manual the relay settings shall be calculated for the selection of relay
constants for the value calculated above. For the numerical relays the value calculated shall be
programmed directly.
The above setting shall be programmed in case of numerical relays. If the relay is of
static type, the availability of reverse zone shall be detected first and setting shall be set as per
procedure given by the manuf acturer.
Starter reach :
= 1.35 x 23.5941 79.17 ohm / phase
= 31.8521 79.17 ohm / phase
CHAPTER-IX
= 0.109 -1.9667
In normal scheme, where Zone-4 elements will be reverse looking , the Zo ne-5 forward reach
should be set to the starter forward reach , and the Zone-4 reverse reach , should be set to the
reverse reach.
Zone- 4 reversereach
Zone-5 forward reach + Zone 4 reverse reach
= 1.7329 = 0.65156
31.852+1.7329
Zone-1 accuracy is +5% for System Impedance Ratios (SIR) of upto 30 and +10% for SIR of
upto 60. If +5% of accuracy of Zo ne-1 is required, then the operate in voltage for earth faults
and phase faults need to be more than the minimum required voltage of the relays.
9. TIME LAG