Sunteți pe pagina 1din 40

MV electrical network management

MV substation control unit

Merlin Gerin Easergy range


Easergy T200 P

Users manual
Easergy T200 P Contents

Overview 2
General description 2
Mechanical specifications 5
Installation 6
Connecting the CPU card 6
Enclosure switchgear connection 7
Remote transmission equipment installation 9
Enclosure power supply 11
Commissioning 12
Software configuration 12
Tests 22
Operation 23
Control and indication 23
Control and indication - Automatic controls 24
Maintenance 25
Information display 25
Diagnostics 26
Power supplies 28
Card replacement 29
Appendix A: configuration parameters 30
Appendix B: general specifications 38

1
Overview General description

Functions
Easergy T200 P is designed to be installed with overhead switches remote
DE56214

controlled by the MV network. It contains all the functions required to monitor


The equipment is housed and control one or two MV switchgear devices.
in a stainless steel
enclosure designed Management of MV switch opening/closing electric control unit
for column mounting Triggered by actuation from the control station, by local operator control,
by means of a U-bolt or by internal automatic controls.
Measurement acquisition and processing
The T200 P can incorporate the following measurements and processing functions
for each channel:
b Current measurement on each phase,
b Calculation of the average load current,
b Homopolar current measurement,
1- or 2-channel enclosure b Single-phase or three-phase voltage measurement,
b Measurement of the phase deviation between the upstream/downstream voltages
for management of opening points,
b Calculation of active and RMS power (option),
b Calculation of active energy (option),
b Calculation of the power factor (option),
b Frequency measurement.
Monitoring, for the purposes of remote indication and/or local display,
of MV substation and T200 P information:
b Open/closed position of MV switch,
b locked state of MV switch,
b Phase-to-phase or phase-to-earth fault current detection,
b Voltage present,
b Automatic control ON/OFF position,
b Door open,
b Local/remote operating mode,
b Immediate alternating supply voltage shortage,
b Time-delayed alternating supply voltage shortage,
b Charger fault,
b Battery fault,
b External 12 V power supply shortage,
b Motorization supply voltage shortage.
Logs
Time-stamped chronological logging of events and measurements.
This information can be transmitted to the control centre and archived in logs
for consultation and local downloading (in the form of files), by connection
of a microcomputer.
Automatic controls
b SEC (Sectionalizer): automatic control for opening the MV switch following
detection of a number of fault currents in the source substation reset cycle.
b VT (Voltage Time): the detection of voltage loss (switch closed) causes channel
opening and then reclosing when the voltage returns.
Backup power supply
For all the control unit components, the transmission equipment and the switch
motorization with a battery life of several hours in the event of an AC supply outage.
Local communication or communication with the remote control centre
b One or two communication ports (option) are available for remote communication
with the control centre so as to manage two transmission channels. These ports can
be used redundantly (normal/backup), for repeater or maintenance applications.
The ports use either modems integrated in the COM card or external equipment
managed by the rack serial link.
b A choice of modem for each port allowing any type of mounting:
v Radio (600/1200 baud FSK or 1200/2400 FFSK),
v PSTN isolated at 8 kV (300 to 144400 bits/s -V32 bis),
v GSM / GPRS (dual-band 900 MHz 1800 MHz), SIM card accessible
on the front panel,
v LL isolated at 8 kV (1200 baud FSK),
v RS232 or RS485 isolated at 2 kV (19200 baud),
Note: in an RS232 link, port 1 is replaced by the RS232 port integral with
the COM card and accessible via the 9-pin connector on the right of the rack.
v a catalogue of communication protocols for communication with the control centre,
changing constantly:
IEC 870-5-101, DNP3, Modbus, Wisp+ and other proprietary protocols.

2
Overview General description (contd)

v an Ethernet communication port is available for communication with the control


centre or for access from the local PC consultation/configuration (Modbus IP protocol,
IEC 870-5-104). This port is accessible on the front of the COM card.
v a USB communication port is available for communication with the local PC
for consultation/configuration. This port is accessible on the front of the COM card.
Communication with local equipment (option)
A Modbus RS485 communication port (2 wires - isolated at 2 kV) and a CAN port
(CAN2.0 compatible) are available (on option) for dialogue with equipment
communicating with the T200 (e.g. Sepam, etc.).
Time synchronization of the equipment
Time setting for event dating can be performed:
b By the laptop PC for consultation/configuration of the T200
(manually or automatically via the PC time),
b By the control centre (if the protocol permits),
b By GPS sync (option). The precision of the time setting is in this case one second.

The enclosure
DE56212

1
The equipment is housed in a stainless steel enclosure 316L ensuring:
b Resistance to mechanical stresses,
b Resistance to environmental stresses,
b Compliance with EMC standards.
3
2 The enclosure is fitted with a key locking system.
Its main constituent parts are:
1) a sun visor to restrict the influence of high external temperatures
2) a 6-unit rack containing all the electronic modules
4 3) transmission equipment (radio, external modem, etc.)
4) a door switch
6 5 5) a lever type fuse holder for the AC power supply
6) a transformer for voltage measurement acquisition
7) a battery providing a backup power supply when the enclosure is no longer
powered by the AC supply
8 8) a connection part comprising plug-in connectors for connection
7 to the motorization units and the toroid sensors
9 9) an anti-intrusion plate under the enclosure providing protection against
any malevolent attempt at disconnection of the connection part cords.

Rack
DE56213

CONTROL COM POWER

The rack contains three functional modules:


b The control module (marked CONTROL)
The control module controls the overall operation of the T200 P and the exchange
Rack of information with the Power Supply and Communication modules.
This module implements several functions:
v interfacing with and monitoring and control of the MV switchgear,
v automatic control management,
v detection of fault currents on the MV line,
v detection of voltage loss,
v calculation of power (P, S, Q), energy, power factor, frequency,
v local operation.
b The Communication module (marked COM)
The communication card serves as an interface between the control module cards,
the local equipment communicating via Modbus and the control centre.
It centralizes, processes and archives information and transmits it in accordance
with the communications protocol adopted.

b The Power Supply module (marked POWER)


It supplies power to the enclosure, the battery charger and the associated
self-monitoring equipment.

3
Overview General description (contd)

Easergy T200 P block diagram

DE56201EN
Rack
Connector
RJ45-RS232
CONTROL COM POWER Ext 12 V
Control panel CPU card radio
and interface
4A
time-delay
Transmission
Voltage equipment
Meas. 0.8 A PSTN
RS232
card semi-time-lag or LL or FO
or or Radio
or GSM line
5A Modem 48 V
time-delay PORT1
Connection Modem 12 V
card PORT2 charger

SW1
SW2

PB.L
DO
DI
Door switch

Instrument
potential
transformer
2A
Radio antenna/
transmission
line input
4-pin
toroid
10-pin connector
connector
MV switch 12 V
Battery

Protection
plate

Digital Output DO
Digital Intput DI
or spare Mains input

Note: the various modules are connected via a rack backplane card not shown
in this diagram.

4
Overview Mechanical specifications

Identification Characteristics
Dimensions HxWxD 630 mm x 410 mm x 350 mm
Weight 40 kg
DE55679

Vibrations IEC 68-2-6 10 to 500 Hz;


1 g or 0.075 mn peak-to-peak
Climatic Working temperature 15C to +55C
Storage temperature 25C to +70C
Protection (IEC 60529) IP55

Enclosure opening
The enclosure is opened by two doors opening vertically (one upward and
one downward). Turn the central lock button located on the upper door
a quarter of a turn to the left and open the upper door and then the lower door.
Both doors can be locked in open position by means of blocking props.
To close the enclosure, first remove the props before closing the doors again.
The lower door can also provide support for a PC when it is locked in open position.
In the lock button, a lock or a padlock makes it possible to lock enclosure opening
completely.

Enclosure mounting
The enclosure weighs 40 kg in working order.
When installing the enclosure on the column, make sure not to conceal the air vent
inlets so as to enable good circulation of air.

Step 1: attach the U-bolt Step 2: : install the enclosure on the U-bolt. Step 3: fasten the enclosure to the U-bolt
to the column using strapping, Begin by placing the enclosures mounting bracket with the screws, washers and nuts contained
as shown in the following illustration. in position on the upper part of the U-bolt. in the bag attached to the U-bolt.
The enclosure is held in position by the mounting
bracket and can be released.
DE55145

DE56202

DE56203

x2

5
Installation Connecting the CPU card

2-channel CPU card (with voltage measurement)


The CPU card is located behind the control panel (front of the Control module).
It controls the equipments overall operation and permits the exchange of information
with the Power Supply and Communication modules.

This card incorporates several functions:


b Control CPU,
b Interface for connection,
b Interface for the switch and current and voltage inputs,
b Fault detection,
b Measurements relating to acquisition inputs.
DE56148EN

CPU card

Local control panel/CPU ribbon cable connection


Jumpers for current acquisition selection: W3
3 phases = position A W2
2 phases + homopolar = position B/C
1 homopolar toroid = position B/C
W2: channel 1 and W3: channel 2
Note: with PM6, position B/C required

Choice of control polarity


Position: +48V or Loop or 0V

Voltage measurement card

5 A time-lag fuse:
switch power supply

Connection card
SW1: connection to switch 1
(includes current and voltage inputs)
SW2: connection to switch 2
(includes current and voltage inputs)

DO: connection of the 3 digital outputs

DI: connection of digital inputs


(connectors DI 1 to 4 + DI 5 to 8)

PB + indicator lamp: connection of pushbutton


and lighting indicator lamp option

The Fault Detection and Voltage Measurement functions as well as the number
of channels (1 or 2) are options which can be incorporated in the CPU card
as requested.
The Connection card integral with the CPU card permits connection to the switch,
to the digital inputs/outputs, to the current inputs (toroid sensors) and to the voltage
inputs.
Jumpers on the card (W2 and W3) allow easy choice of current input acquisition
mode for each channel:
3 phase toroids (pos. A = I1, I2, I3) or 2 phase + homopolar toroids
or 1 homopolar toroid (pos. B/C = I1, I3, I0).
Note: switch PM6 imposes the choice in position B/C.

6
Installation Enclosure switchgear connection

Connecting the enclosure end


The T200 P is supplied with a plug-in connector to connect the connecting cable
to each MV switch.
d For the 2-channel T200 P, it is essential to first mount the polarizing pins,
in accordance with the diagram below. The polarizing pins are available
in a plastic bag attached inside the enclosure.

Position of the polarizing pins:


for 1-channel enclosure for 1- or 2-channel enclosure
(no polarizing pins) (cable end view)

DE55148EN
1 6 1 6 1 6

5 10 5 10 5 10
Polarizing pin

Channel 1 Channel 1 Channel 2

Access for connection


To access the connection part, the protection plate must be removed. To do this,
unscrew the wing screw inside the enclosure, in the bottom left-hand.

Bottom view, front panel facing upward


DE56204

1
2

View along A

5 A
6
6 7 8 7
8

1 4-pin plug-in connector: SW1 current


2 4-pin plug-in connector: SW2 current (option)
3 10-pin plug-in connector: Channel 1 switch control
4 10-pin plug-in connector: Channel 2 switch control (option)
5 CM18 P cable gland or N/BNC plug: transmission
(PSTN, LL or antenna cable line access)
6 CM18 P cable gland: spare or DI-DO inputs/outputs
7 CM12 P cable gland: mains voltage input
8 8 mm stud: earth terminal
9 Protection plate

Note: the above diagram is represented with the plug-in connection option.

7
Installation Enclosure switchgear connection
(contd)

T200 P CPU card


Connection to the switch
Marking on the 10-pin plug-in connector (Harting)
DE56205EN

SW1 (J6)
17 Neutral 1 Connector pin Marking Function
Voltage transformer
18 Phase 1 1 0V
1 1 20 I1 2 CF1 Channel closing control
Connection with: 2 2 4 I3 3 CO1 Channel opening control
b 2 phase toroids
and 1 homo. toroid 3 3 8 IH 4 O1 Open position
b or 1 homo. toroid 5 F1 Closed position
4 4 16 Common I
L3 L2 L1 6 + + 48 V
Harting
S1 4-pin
3 0V
8 8 6 PT1
+48V 7 ET1 Switch locked
3 4 6 ET
7 7 23 ET1
8 Free
1 2 1 0V
1 1 5 0V
9 DI AUX Auxiliary DI (SF6 missing)
2 CO CO1 10 COM External power supply common
M 3 3 1
5 O line for motorization control
4 4 21 O1
2 1
S3
4 F
5 5 22 F1
To establish connection, proceed as follows:
4 3 b Connect a 10 x 1.5 mm2 cable (U1000RO2V or equivalent) to the 10-pin plug-in
6 6 2 +48V
SF6
0V connector (cable not supplied),
9 9 7 MSF6/DI AUX
b Remove the steel protection plate, fastened by a wing screw inside the enclosure,
CF1
Lack of SF6
2 2 3 in the bottom left-hand,
PM6 pressure 10 10 11 COM b Connect the 10-pin plug-in connector to its base (Caution! on the 2-channel T200 P,
CO/CF
Connection Harting there are two polarized plug-in bases, one per channel),
to switch PM6 10-pin b Lock the connector to its base,
SW2 (J5) b Put back in place the steel plate and the wing screw.
Connection 1 1 20 I1
with 1 toroid Control polarity
per phase 2 2 12 I2
The switch(es) is (are) controlled via a relay contact (control duration 3 s) inside
3 3 4 I3 the T200 P enclosure.
4 4 16 Common I Depending on the position of the fuse on the Control module, the switch motorization
L3 L2 L1
Harting can be controlled:
4-pin
9 7 MSF6/DI AUX
b From the T200 internal power supply by a +V or 0V polarity,
b From an external power supply.
7 23 ET1
In factory, the fuse is positioned for a +V internal power supply.
5 22 0V +V
The standard voltage of the internal power supply is 48 V (although 24 V is possible
4 21 O1 on option).
8 6 PT1
Connection of digital inputs DI
CO1
3 1 Digital inputs are available on special connectors DI 1 to 4 and DI 5 to 8,
3 CF1 accessible on the Connection card under the rack on the left.
2
1 5 0V Note: the DIs are available spares.
6 2 +V Connection of digital outputs DO
0V
Other 10 11 COM 3 digital outputs are also available on a special DO connector accessible
CO/CF on the Connection card under the rack on the left.
Connection Harting
to other switch 10-pin DO (J4)
2
Other connections (wired in factory)
DO3 Connection of the contact for Door open indication.
1
4
Connection of DOs DO2
3
Toroid connection
6
DO1 Marking on the 4-pin + earth plug-in connector (Harting) for PM6
5
Connector pin Marking Function
DI 1-4 (J2) 1 Phase 1 Current phase 1
C Common
2 Phase 3 Current phase 3
1 DI1 3 Homopolar Homopolar current
2 DI2 4 Common 1 Current common
3 DI3 5 Earth Not used
4 DI4
Connection of DIs DI 5-8 (J3)
To establish connection, proceed as follows:
C Common b Connect a 4 x 1.5 mm2 cable (U1000RO2V) to the 5-pin plug-in connector
(cable not supplied),
5 DI5
b Remove the steel protection plate, fastened by a wing screw inside the enclosure,
6 DI6
in the bottom left-hand,
7 DI7 b Connect the 5-pin plug-in connector to its base (Caution! on the 2-channel T200 P,
8 DI8 there are two polarized plug-in bases, one per channel),
b Lock the connector to its base,
PB-L (J1)
+12V 2
b Put back in place the steel plate and the wing screw.
0V 1
Other connections
4
Door switch
3

8
Installation Remote transmission equipment
installation

60
Location
210
A transmission interface slot (LL or RS485/232, modem, optical fibre cable, radio
DE55159

and so on) is provided at the top right-hand side of Easergy T200 P. A slide-mounted
support offers various adjustment possibilities.
Available space (see illustration opposite)
220 b Height: 220 mm,
b Width: 60 mm,
b Depth: 210 mm.

Connecting the remote transmission equipment


to Easergy T200 P
The 12 Vdc supply for the remote transmission equipment is provided via
the connector on the right-hand side of the rack.
The RS232 serial link is provided on the RJ45 8-pin connector also located
on the right-hand side of the rack.
The Radio link is provided on the RJ45 8-pin connector located on the front
of the COM card.
Connection Cable attachment
of leased line LL
DE56206

RJ45 connector
LE

LR

12 Vdc output
(1 A max.)

+
Rack right-hand side +

LL equipment

d It is important to link the transmission cable shielding. The shields must


be earthed at one point in the line (preferably on the PC side of the remote
control station).

Connection to the radio transceiver Connection of RS232 external modem (PSTN, radio modem, GSM)
(accessible on the front of the COM card) accessible on RJ45 connector on the right of the rack.

T200 Radio T200 Modem T200 Modem


DE56215EN

DE56216EN

0V 1 1 Spare TX 1 3 RX TX 1 2 RX - Receive data


LF Rec 2 2 LF Receive RX 2 2 TX RX 2 3 TX - Transmit data
0V 3 3 Ground GND 8 5 GND GND 8 5 GND - Ground
0V 4 4 Spare RTS 6 7 RTS RTS 6 7 RTS - Request to send
LF Send 8 5 LF Send CTS 3 8 CTS CTS 3 8 CTS - Clear to send
Send Cd 5 6 Send command DTR 4 4 DTR DTR 4 4 DTR - Data terminal ready
Squelch 6 7 Squelch DSR 5 6 DSR DSR 5 6 DSR - Data set ready
NC 7 8 Spare DCD 7 1 DCD DCD 7 1 DCD - Data carrier detect
9 Spare
No CTS, DCT, DSR management CTS, DCT, DSR management
COM module

TX Radio link RJ45 connector


RX

9
Installation Remote transmission equipment
installation (contd)

RS232/RS485 interface
The interface is supplied mounted on the sliding grid. To perform connection and
position the microswitches, the grid can be loosened and removed.
RC 2F 4F 2-wire RS485 arrangement:
+5V

12V
b connect the 2 wires to terminals
DE56812

DE56831
GND A
2F 4F
A
+ B A and B (2F XV),
GND b connect the ground braid
RS485

B
GND A (GND terminal),

RS232
A
B
B
b set selection jumpers 2F/4F to 2F

4F

2F
GND GND
(on the right).
RC
4F

2F

+5V
GND
2F 4F 4-wire RS485 arrangement:
DE56832 A b connect the 2 Receive wires
B to terminals A and B (4F V),
GND b connect the ground braid
A (GND terminal),
B
b connect the 2 Transmit wires

4F

2F
GND
to terminals A and B (4F X),
b connect the ground braid
(GND terminal),
b set selection jumpers 2F/4F to 4F
(on the left).

d It is important to link the transmission cable shielding.


The shields must be earthed at one point in the line (preferably on the PC side
of the remote control station.

Ethernet and USB link


RJ45 connector
DE56207

for Ethernet link The USB and Ethernet links are available on the front of the COM card.
For linking with these transmission modes, the T200 complies with the connection
USB connector type B standard used (RJ45 and USB type B).
for USB link ON

GSM modem
The GSM modem is installed on the COM card of the T200.
The antenna connector and the SIM card are accessible on the front of the COM card.
b Attach the antenna to the wall of the substation (preferably outside),
SIM card case b Connect the antenna to the modem antenna connector,
b Insert the SIM card (T200 powered down).
COM

PSTN link
Connect the PSTN line to the terminals provided for the purpose on the DIN rail
TX
RX
alongside the mains fuse holder.

PSTN
output
Antenna
connector
Unlock button

PSTN line
input connection

10
Installation Enclosure power supply

Connecting an AC supply
d To prevent any risk of electric shock or burns, check that the mains supply
is disconnected before carrying out any work on the enclosure.
b Switch off the supply circuit by moving the central lever on the safety fuse located
in the centre to the down position. It is not necessary to remove the fuse.
b Insert the AC supply cable (2 x 2,5 mm 2) into the appropriate cable gland and
connect it using the shortest possible length of cable to the bottom screw terminals
on the safety fuse (phase on the right, neutral on the left).
b Check that the mains connector is correctly connected under the rack
(see illustration below).
d IMPORTANT: the AC supply input is insulated at 10 kV with respect to
the enclosure earth. It is important to ensure that the cable and its use outside
and inside the enclosure do not damage this insulation.

Earthing
d The equipment must be earthed to ensure EMC.
DE55160

For this purpose, a special stud of diameter 8 mm is provided under the enclosure.
Use an earth cable of cross-section greater than or equal to 16 mm 2.

Installing the battery


The battery is of 12 V - 38 Ah type. It is housed in the lower part of the enclosure
(see illustration opposite). It can be held in position by a strap with tightening buckle
(option).

Connecting the battery


d Note: the battery must only be connected to the enclosure
The battery is installed at the front of the enclosure when the equipment is powered up.
(lugs to the right) b Connect the battery to the equipment by plugging the connector into the base
under the power supply module (see illustration opposite).
b The connector is polarized.
DO NOT FORCE IT INTO POSITION.

Switching on the AC supply


DE56208

b Close the safety fuse inside the enclosure (see illustration opposite).

Normal use
When the operations described above have been performed, the normal power
supply to the equipment is resumed and the battery can be charged.
The normal service status is as follows (on the front panel):
b On the Power supply module:
v the AC supply OFF and Battery fault indicator lamps are off,
v the Rack 12 V present and Ext 12 V present indicator lamps are lit steadily,
v the 48 V present indicator lamp is lit steadily (after a 20 s time delay),
v the fault indicator lamps are off.
b On the Control module:
v the Local/Remote switch is set to Remote mode,
Mains connector v the indicator lamps reflect the indications, in particular the position of the cubicles.
b On the Communication module:
Battery connector v the ON indicator lamp is lit,
v the defect indicator lamp goes off quickly,
v the other communication indicator lamps remain off.

Instrumental Safety fuse


potential transformer

Plug in the battery connector below the rack

11
Commissioning Software configuration

An enclosure cannot be fully commissioned unless an auxiliary AC supply is present.


CONTROL COM POWER A dummy connector is also recommended to ensure that the many operations
DE56209

performed by the MV cubicle do not overload the battery.


ON
Easergy T200 P requires a configuration operation: this is performed from
AC OFF
U1 U2 Reset
+ the COM card (single access). It allows configuration of:
DI 1 DI 2 ON
b The parameters of the CPU card (date, fault detection, etc.).
1 DI 3 DI 4
b The parameters of the Communication card (com. parameters, alarms, etc.).
b The system parameters (variable management, class management, etc.).

Equipment required for T200 connection


TX For testing-maintenance configuration, the T200 requires:
RX
b A microcomputer operating under Windows 2000 or XP exclusively and including
Test
OFF ON Internet Explorer (version 5.5 or 6.0).
Reset b An USB port on this PC to perform connection with the T200.
TX

RX
An Ethernet port (RJ45) is available on the COM card for remote access to the T200
Reset
from an Ethernet network.
This port can also be used for direct connection of the T200 with the PC.
The Ethernet cable required for Ethernet network-T200 connection or PC-Ethernet
network connection is of the straight-through type.
DE55672

The Ethernet cable required for PC-T200 connection is of the cross-over type.
The USB cable required for PC-T200 connection is of the USB-A type on one side
and USB-B on the other.
A CD-ROM is supplied to the user for:
b Installation of the USB driver for connection with the T200.
b Installation of Java Runtime Environment 5.0 needed for port trace operation
(Supervisor frame analysis-T200).
d IMPORTANT: TCP/IP ports 1168 and 1169 must be accessible on the PC for
trace operation. Contact the network administrator if it is necessary to alter the PC
or network configuration to deactivate the Firewall on these ports.
Type B Type A Configuration of the T200 is performed directly from Internet Explorer. No other
connector connector additional software is needed to access the T200 testing-maintenance configuration
USB cable operations (apart from Java Runtime 1.5).

Principle of the T200 on-board server


DE55673

The T200 includes an on-board server which is initialized automatically as soon as


connection is established with the T200.
The data displayed by the T200 through this on-board server appears in the form
of HTML pages.
Various pages and sub-pages can be accessed by the user depending on the rights
available to him. The HTML pages are refreshed in real time every three seconds
so as to update the states reported by the T200.
Access and connection are secured by a Login and password. Several levels of
access to the HTML pages can be configured, provided one has the required rights.
From the on-board server, it is possible to:
b Configure the fault detector, communications and automatic control parameters
or system parameters (management of variables, classes, rights, etc.),
Cross-over or straight-through Ethernet cable depending on
type of link access
b View the states managed by the T200 (TSS, TSD, routine faults,
remote measurements, etc.),
b Save or load the T200 parameter configuration from files already backed up
on the PC,
b Send remote control orders to the T200,
b Transfer the diagnostic logs in the form of Excel-compatible files,
b Load a new software version of the T200 application.
The on-board server can be accessed both by the USB port and by the Ethernet port.
There is no difference in operation according to the type of port used.

Initialization of T200 connection


The T200 incorporates by default IP addresses necessary for local connection from
a PC. It is important to know these addresses in advance in order to start a connection
(these addresses are indicated on the Com card):
b USB port: default address on the T200 = 212.1.1.10
b Ethernet port: default address on the T200 = 172.16.0.5
Note: the USB address cannot be modified by the user. The Ethernet address,
on the other hand, can be modified (if the rights so permit) so as to correspond to
the local area network, which does not necessarily use the same network addresses
and masks. For the T200 link via Ethernet, the first two steps indicated below are not
necessary. In that case, go directly to stage 3.

12
Commissioning Software configuration (contd)

Step 1 - Installing Java Runtime Environment 5.0


b Insert the CD-Rom supplied with the T200 into the PC drive, then double-click
PE55880FR

on the jre-1_5_0-windows-i586.exe installation file on the CD-Rom.


b Software installation begins, click on the option I accept the terms
and then on Next.
b Choose the Default installation type and click on Next.
Wait until installation is completed, then click on Terminate.
PE55881FR
PE55882FR

13
Commissioning Software configuration (contd)

Step 2 - Installing the USB driver


At first connection with the T200 via the USB port, Windows detects the new
PE55189FR

hardware and asks you to install the driver.


Carry out the following operations to install the USB driver:

Under Windows 2000


PE55883FR

b Select the option Search for an appropriate driver,


b Select the option Specific location.
b Then insert the CD-Rom supplied with the T200 and indicate to Windows the path
to obtain access to the corresponding driver (file: sb_usb_port.inf on the CD-Rom).
b Windows detects the driver. Continue with installation.
Driver installation then takes place automatically and ends with the appearance
of an Installation Completed - SORHODEL BARDIN Communication Module screen.
The driver is installed.

Under Windows XP
b Select the option Install from a list or a specified location,
b Select the option Do not search. I shall select the driver to install,
b Select the USB bus controller hardware type,
PE55884FR

b Click on the Disk provided button.


b Then insert the CD-Rom supplied with the T200 and indicate to Windows the path
to obtain access to the corresponding driver (file: sb_usb_port.inf on the CD-Rom).
Windows detects the Communication Module (SORHODEL BARDIN) driver.
b Start installation of the driver.
Windows then indicates that the driver is not validated. Continue with installation.
Driver installation then takes place automatically and ends with the appearance of
an Installation Completed - SORHODEL BARDIN Communication Module screen.
The driver is installed.
d IMPORTANT: it is recommended to always use the same USB port on the PC
for connection to the T200, so as to avoid having to reinstall the driver for the second
port.
PE55885FR

Note: step 2 is no longer necessary after the first connection performed with
the T200. In that case, go directly to stage 4.
PE55886FR
PE55887FR

14
Commissioning Software configuration (contd)

Step 3 - Creation of the USB remote network connection


Once the USB driver has been installed, a remote network connection
PE55888FR

must be created for the USB link (this is not necessary for the Ethernet link).

With Windows 2000


b Click on the Windows Start button,
b Click on Settings,
b Click on Network connection and remote access,
b Click on Establish a new connection,
b Select the option Connect directly to another computer,
b Select the Guest option,
b Select the last COM port created on the PC corresponding to
Communication Port (COM X),
b Select the option For all users,
b Give a name to the USB network connection (e.g. T200 connection),
PE55889FR

b When the connection window is displayed on screen, give a user name


or login password (none recommended),
b Click on the Log in option,
b The USB connection between the PC and the T200 is initialized. A USB connection
status icon is then inserted in the Windows toolbar.
It is recommended to create a shortcut for the T200 Connection USB network
connection (e.g. on the desktop of your PC, in order to be able to call it up again later).

With Windows XP
b Click on the Windows Start button,
b Click on Control Panel,
b Click on Network connection and internet,
PE55890FR

b Click on Network connections,


b Click on Create a new connection,
b Select the option Configure an advanced connection,
b Select the option Direct connection to another computer,
b Select the Guest option,
b Give a name to the USB network connection (e.g. T200 connection),
b Select the last COM port created on the PC corresponding to
Communication Port (COM X),
b Select the option For all users,
b Click on Add a shortcut to this connection on my desktop then on End,
b When the connection window is displayed on screen, give a user name or login
PE55891FR

password (none recommended),


b Click on the Log in option.
Note: step 3 is no longer necessary after the first connection performed with
the T200. In that case, go directly to stage 4.
PE55892FR

15
Commissioning Software configuration (contd)

Step 4 - Starting connection with the T200


PE55893FR

By USB access
b With the T200 being powered up without a Fault indicator lamp lit on the COM
card, connect the USB cable to the PC and to the COM card,
b Start the USB remote network connection created earlier (=> step 3),
b Click on Log in, and connection is established,
b Start Internet Explorer,
b Enter the IP address (212.1.1.10) in the Address field, then click on Ok,
b The home page of the on-board server appears on screen,
b Enter the language to use, then click on Ok,
b Enter a User name and a Password (by default: Easergy, Easergy)
then click on Ok,
b Access to the HTML pages is activated according to the rights related to this user.
d IMPORTANT: after powering up or a Reset of the T200, it is important
to wait for completion of initialization of the COM card before connecting
the USB cable, otherwise the connection is likely not to work.
When the T200 is powered up, the red Fault indicator lamp should flash
for approximately 5 s and then stay lit steadily for 1s before going out.
PE55196FR

Only then is connection of the USB cable possible.


Note: to stop the USB connection to the T200, the following operations should be
performed (in the respective order):
b Stop the T200 connection by double-clicking on the T200 connection shortcut
on the PC desktop, then click on the Disconnect option.
PE55197FR

b Then disconnect the USB cable from the PC and the T200.

By Ethernet access via a local area network


b With the T200 powered up, connect the PC to the Ethernet connector of the COM
card on the T200 using the appropriate cable (straight cable),
b Start Internet Explorer,
PE55894FR

b Enter the IP address of the T200 corresponding to Ethernet access (by default:
172.16.0.5) in the Address field, then click on Ok,
b The home page of the on-board server appears on screen,
b Enter the language to use, then click on Ok,
b Enter a User name and a Password (by default: Easergy, Easergy),
then click on Ok,
b Access to the HTML pages is then activated according to the rights related to
this user.
Note: if the default IP address of the T200 cannot be used on the local area network,
it must be changed in the specific T200 configuration HTML page, for an address
acceptable for the network (see section on IP address configuration).
For this purpose, the only way to access the HTML pages for configuration
PE55895FR

of the T200 is to use the USB connection.

By direct Ethernet access to the T200


b With the T200 powered up, connect the PC to the Ethernet connector
of the COM card on the T200 using the appropriate cable (cross-over cable),
b Open the Windows Control Panel, then open Network connection,
b Note the name marked in the Name column corresponding to
the Local area network in the Type column,
b Insert the CD-Rom supplied with the T200 into the PC drive,
b Copy the file Ip_T200.bat onto the hard disk of your PC (e.g. to C:\),
b Open the file Ip_T200.bat on C:, using the Windows Notepad,
b Recopy the name of the network connection (noted earlier) into the file
Ip_T200.bat, following the set interface= entry,
b Save the file, then double-click on the file Ip_T200.bat,
b Internet Explorer starts with the T200 automatic connection, reallocating the PCs
Ethernet connection parameters for correct operation of the connection with the T200,
b The home page of the on-board server appears on screen,
b Enter the language to use, then click on Ok,
b Enter a User name and a Password (by default: Easergy, Easergy),
then click on Ok,
b Access to the HTML pages is then activated according to the rights related to
this user.
Note: the Windows Notepad does not manage accented characters. Accordingly,
if the name of the Windows local area network connection contains accented
characters, this connection should be renamed in Windows and in the file
IP_T200.bat, to replace the accented characters with non-accented characters.
d IMPORTANT: once connection with the T200 is completed, you should click
again on the file Ip_T200.bat to retrieve the previous PC settings concerning
the Ethernet connection.

16
Commissioning Software configuration (contd)

Operation on the T200 on-board server


Once access to the on-board server has been identified by user name and password,
all the HTML pages can be consulted by simply clicking on the tabs or the associated
drop-down lists when they are available:
Details of the settings for each page are given in Appendix A.

Home page
PE55896EN

This page is displayed at connection to the T200. It enables definition of the


language to be used for displaying the pages. It also allows definition of user access
rights by login and password.
The users and passwords that can be accessed depend on the configuration defined
in the Maintenance page and the Users sub-menu.
By default, the Easergy user and Easergy password allow access as Administrator
to the on-board server.
A wrong user or password automatically opens access inViewing mode.

Monitoring page
This page can be used to consult the T200 states:
b TSS: state of digital inputs, T200 internal faults, voltage presences,
current faults, etc.
b TSD: open or closed state of switch, automatic control, digital outputs
b TM: measurements of currents, voltages, frequency, etc.
Home page b Counters: number of operations or energy.
Note: some displayed data is calculated and deduced by the T200:
v Active, reactive, apparent power,
PE55897EN

v Phase difference between channels (deduced from the phase 1 voltages


of each channel),
v Power factor or Cos ,
v Active power,
v Neutral and average current (neutral current deduced in the case of
a type A arrangement - 3 phase toroids),
v Phase-to-phase or phase-to-ground voltage (3-wire arrangement: phase-to-phase
voltages measured and phase-to-ground voltages deduced. 4-wire arrangement:
phase-to-ground voltages measured and phase-to-phase voltages deduced).
The page is displayed by class (e.g. State of channels, System, Automatic Control,
etc.).
Each class covers a category of information so as to facilitate viewing on screen.
The states of the indications or measurements are refreshed every 3 seconds
automatically.
The presentation, quantity of data displayed and content of this page may vary from
Monitoring page one application to another.

Control page
PE55899FR

This page allows local control orders to be sent from the PC to:
b the switches (change of position by CO/CF),
b the operation and energy counters (counter initialization),
b the automatic controls (switching ON/OFF),
b the digital outputs (forced setting open or closed),
b the fault detector (fault memory resetting).
The controls on the TSDs make it possible to go to the state complementary
to that displayed by the T200.
The controls on the counters enable them to be initialized at a value predefined
by the user.
For safety reasons, each control must be confirmed by the user.
The state of a control in progress is displayed in orange (default colour).
The state of the control is refreshed on screen automatically as soon as it is completed.
Note: the colours of the states displayed can be modified by configuration.

Control page

17
Commissioning Software configuration (contd)

Diagnostic pages
These pages allow consultation of the logs recorded in real time by the T200.
PE55202EN

The event dating is 1 ms.


Each log allows consultation of the history of states occurring on the T200
with a description of the states.
All the information present in the logs is time-and-date stamped by the T200s internal
Drop-down list Diagnostic pages clock.
The logs are as follows:
b Alarm log: (storage capacity: 100)
PE55201EN

Alarms can be generated and transmitted spontaneously to the control centre


after an information change of state, provided that this state has been configured
as alarmed.
A box associated with each alarm is checked when the control centre
has acknowledged this alarm.
Note: information configured as alarmed automatically implies the generation
of an associated event (in the events log).
b Event log: (storage capacity: 500)
Every change of state generates an event, provided that the use of events
for this state has been configured.
b System log: (storage capacity: 300)
The equipment also incorporates a function for recording additional information
to facilitate operation and maintenance.
v storage of transmission events (to determine the origin of a recurring
communication fault)
Alarm log Diagnostic pages v indication of transmission errors (CRC error, collisions, PSTN line out of order,
switchover to redundancy, etc.)
v indication of system events (T200 start-up, T200 reset, change of configuration,
etc.).
PE55203EN

b Measures log: (storage capacity: 1500)


The measurements managed by the T200 (phase current, mains voltage, frequency,
power factor, etc.) can be saved in a log, provided that their use has been configured.
The measurements can be recorded in several ways:
v periodically (sampled or averaged value with configurable period),
v upon exceeding a threshold (configurable high or low threshold),
v upon variation or dead band (configurable variation %),
v upon periodic recording of Min. and Max. values (configurable values and period).

For all the logs, when the storage capacity is reached, the most recent event
occurring erases the oldest event on the list.
A Files download sub-menu allows these logs to be saved to the PC in the form
of Excel-compatible files (.scv files).
These files can be consulted or transferred, to enable the establishment of statistics
or reviews.
Files download Diagnostic pages

18
Commissioning Software configuration (contd)

Maintenance pages
Several pages can facilitate maintenance of the T200, by giving information or allowing
PE55900EN

configuration of the T200 application:

1 General informations
Specific sub-pages provide information concerning the T200 application, namely:
b Substation page: information concerning the current application
(version No. of the application and fault detector, date and time of last configuration,
name of substation, etc.)
b Communication software page: information concerning the software used
Drop-down list Maintenance pages by T200 (version, date and time of compilation, size and CRC32).
The T200 is capable of storing two different software versions in memory.
It is possible to switch from one software version to another by mere selection
(if two versions are available).
PE55901EN

It is also possible to load a new software version from a file available on the PC
or from a floppy disk or CD-Rom.
b Clock page: allows the T200 date and time to be configured manually
or automatically from the time on the PC.
b IP parameters page: allows consultation or possibly configuration of the Ethernet
and USB interface parameters (IP addresses, sub-network masks, etc.).
CAUTION: it is dangerous to modify the Ethernet IP parameters, with a risk of
no longer being able to access the T200. Call on competent authorities to modify
these parameters.
b User page: allows creation, modification or deletion of users and management
of rights (login, password, access rights).

2 Port 1 and 2 traces (provided that the Java Runtime Environment software
has been installed; see section on Initialization of T200 connection)
Communication software information Maintenance pages A page allows viewing of communication exchanges between the control centre
and the T200, for each port available (hexadecimal frames).
This trace is displayed on screen in decoded form to facilitate reading
PE55206EN

of the frames content:


Column 1: time-and-date stamping of the frame (in hour:minute:second.thousandth
of second format).
Column 2: direction of dialogue RTU V PC or PC V RTU with associated address
Nos of the PC and RTU.
Column 3: hexadecimal frame + brief description of the content of the frame.

3 Save/Restore configuration
This page allows all the current T200 configuration parameters to be saved to a file.
It is also possible to load from a file available on your PC or from a floppy disk
or CD-Rom the T200 configuration parameters coming from a preceding backup
Port 1 traces Maintenance pages
or coming from another substation.
This file can be used to configure one or more other substations in the same way
without being obliged to reconfigure all the parameters one by one.
PE55207EN

In case of problems, a default configuration of the equipment (factory configuration)


can also be configured on the T200.
Note: during loading from a file, the data integrity is verified automatically
so as to ensure the compatibility of application versions.

Save/Restore configuration Maintenance pages

19
Commissioning Software configuration (contd)

Configuration pages
Configuration of the T200 is performed from pages grouped together in several
PE55902EN

different categories:

1 Communication
Several pages allow you to configure the specific communication parameters
of the T200:
b Operating Modes page: for each communication port available on the T200,
it is possible to determine:
v the protocol available,
v the type of transmission medium to be used (Radio, PSTN, GSM),
Drop-down list Configuration pages
Important: a non-configured or poorly configured medium generates a fault
on the COM card.
v the way in which the port will be managed:
PE55903EN

Normal: main transmission channel,


Backup: backup channel in case of loss of the Normal channel
(for normal/backup operations),
Backup auto return: same as Backup with return to Normal channel
as soon as it is available,
Exact copy: channel which is an exact copy of the Normal channel
(the two channels both transmit and receive the information),
Different copy: same as Exact copy with differences relative to the main channel
(e.g. different medium, protocol or speed),
Repeater: the messages received on the main channel are re-sent over the second
channel toward another T200,
Maintenance: backup link for transmission of information to a maintenance
supervisor, without disturbing dialogue on the Normal channel.
b Protocol Parameters page: this page is used to configure the parameters specific
to the protocol used:
Protocol Parameters Configuration pages
v max. number of send operations,
v collision avoidance system,
v Scada address configuration,
PE55904EN

v frame size,
v etc.
Note: each type of protocol has its specific configuration page.
b Ports 1 and 2 page: this page is used to configure the parameters
of the communication port (modem):
v baud rate (e.g. 19200 baud),
v parity, stop bit, etc.
v time-out management (e.g. RTS-CTS, CTS-message, etc.),
v etc.
Note: the parameters displayed in this page depend on the type of transmission
medium configured in the Operating modes page.

2 Control Module No. x


Some parameters of the T200 are managed by the Control module(s) of the T200.
Two pages allow this configuration:
Control and Automation Configuration pages b Control and Automation page: this page can be used to configure
the parameters related to electrical control of the switch and automation
management:
v type of switch (PM6, RL27, CI2 or other),
PE55905EN

v control execution time,


v change of position waiting time,
v etc.
b Measurements and FPI configuration page: this page allows configuration
of all the T200 analogue information, namely:
v mains frequency,
v current and voltage measurement parameters,
v fault detection parameters.

Measurement and FPI configuration Configuration pages

20
Commissioning Software configuration (contd)

3 Variable management
All the information managed by the T200 must be configured separately to define
PE55906EN

its operation and how it will be managed by the on-board server:


b Variable configuration page: the complete list of information (variables)
managed by the T200 is displayed in this page, under various categories.
Depending on the type of variable, the parameters displayed can vary from
one configuration page to another. There is therefore a specific type of page for:
v controls (e.g. TCD, reset FPI, reset counters, etc.),
v indications (e.g. TSD, DI, faults, etc.),
v measurements (e.g. I, U and P measurements),
v counters (e.g. reset operations or power),
The parameters to be configured for each variable are (for example):
v variable name,
v type of access (operator session, administrator session, etc.),
v assignment class,
v logical addresses, internal and external,
v measurements, events and alarms management,
Variable configuration Configuration pages v type of recording for measurements (periodic, upon exceeding high or low threshold,
upon % variation or indication of min. and max. values per period),
v etc.
Note: the parameters to be configured depend on the type of page displayed.
PE55907EN

b Classes configuration page: the variables created can be grouped


together by classes, so as to facilitate the management and display of variables.
Each variable can be assigned to one of these classes by configuration.
This page can be used to create, modify or delete the classes managed by
the on-board server and determine those that will be visible in the Viewing page.

Classes configuration Configuration pages

21
Commissioning Tests

During the tests, a microcomputer designed for configuration of the T200


can remain connected to the Communication module. It can be used to monitor
the status of the equipment, time-stamped events and communications sent over
the internal Modbus link.
Commissioning sheet ref. NT00004 can be used.

Local/Remote switch
set to Local (wiring check)
See Operation for a more detailed description b Check that the PC has taken the local equipment information into account.
of Easergy T200 P operation. b Check that the MV cubicle switchgear is operating correctly, for example
that each channel can open and close and that the positions of the switches
correspond to the status of the indicator lamps.
b Locked information (earthing switch) check:
Check that the equipment has taken the locked inputs into account.
See Operation for a more detailed description of Easergy T200 P operation.

Local/Remote switch
set to Remote
See Operation for a step-by-step description of the various b Check that the switch status is correctly displayed on the control station.
transmission stages indicated by the indicator lamps b Check that the switch connecting cables are correctly marked and disconnect them:
on the front panel of the Communication module. a remote alarm is generated after a one-minute time-out.
b Check that the HA10 switch connectors are fitted with polarizing pins.
If you have dummy devices, install them on the HA10 connectors to ensure
that neither the battery nor the MV cubicle is overloaded.
b Remote control order check:
v check that each order processed by the remote control station is correctly
transmitted and executed by the equipment, for example that each channel
can open and close.
v check that the switch position information received at the remote control station
corresponds to the status of the indicator lamps.
b Digital inputs check:
Check that the equipment has taken the Digital inputs into account and
that the indications have been forwarded to the remote control station.
b Internal fault current detection function check:
The Test pushbutton on the Control module activates the indications corresponding
to those channels for which the Current Measurement option is installed.
Note: a current simulator supplied as an optional extra can be used for this check.
It performs a complete test of the acquisition system.
Disconnect the dummy devices and reconnect the switch connecting cables
to their HA10 connector (polarization).
b Remote control order check:
v check that each order processed by the remote control station is correctly
transmitted and executed by the equipment, for example that each channel can open
and close.
v check that the switch position information received at the remote control station
corresponds to the status of the indicator lamps.
b Locked information (earthing switch) check:
Check that the equipment has taken the Locked inputs into account and
that the notifications have been forwarded to the remote control station.
b AC supply OFF alarm check:
Open the AC supply fuse block. The remote alarm is generated immediately,
or after the configured time-out.
b Measurement checking:
Check that the equipment takes into account the measurements performed
(currents, voltages, frequency, power, etc.) according to the options installed
on the T200 and retransmits them to the remote control station.

d IMPORTANT: these tests can store time-stamped events.

22
Operation Control and indication

Operating mode
Easergy T200 P can be used locally via the Control module or remotely from
a remote control station, depending on the position of the Local/Remote switch.
An indicator lamp showing the status of the equipment is located at the top
of the control panel (front panel of the Control module).
A PC can be connected to the COM module to provide further information about
the status of Easergy T200 P and its operating history.

Ethernet connector
DE56210EN

for network access


Equipment fault CONTROL COM POWER Communication module
powered
Communication module
Automatic control reset fault
USB connector
Voltage present ON (local connection with a PC)
AC OFF
U1 U2 Reset The AC supply to the unit
Automatic control locked +
is cut off
Switchgear neutralization
indication DI 1 DI 2 ON

Channel no. 1 2 DI 3 DI 4 Loss of battery capacity


(2nd channel on option) or charge fault

Switchgear position
Switchgear selector, Rack 12 V supply present
Local mode Telecommunications
equipment (radio, etc.)
Status of digital inputs 12 V supply available

Fault current storage 48 V or 24 V supply


Incoming MV identification present
location
TX Spare (CAN 2.0 port
Selected switchgear or accessory equipment)
RX
open/closed confirmation GSM connection status
OFF ON Port 1 sends data
Test
Fault detector and indicator (for other than RS232)
lamp self-test control Reset
Stored fault Port 1 receives data
erase button (for other than RS232)
TX
Not used
RX T200 P reset
Automatic control Reset
operating service
Port 2 sends data
OFF (left LED)
or ON (right LED)
Port 2 receives data
Automatic control
ON/OFF switching
Local operation (left LED)
or Remote operation (right LED) switch
COM

Note 1:
The above rack shows a complete COM card
with:
b 2 communication ports on the front panel
ON
(e.g. port 1 = GSM and port 2 = radio),
b or port 2 on the front panel (e.g. GSM) and
RS232 port in the transmission compartment
on the right of the rack.

Note 2:
A reduced-scale COM card also exists
with port 2 on the front panel (e.g. GSM) and TX
RS232 port in the transmission compartment RX
on the right of the rack.

23
Operation Control and indication
Automatic controls

Switch control
The switches can only be controlled via the Control module if:
b The Local/Remote switch is set to Local,
DE55166

DI 1 DI 2 b The 48 V voltage is present.


1 2 DI 3 DI 4 When an order is implemented, the switch moves to the additional position.
b If a switch is off, a switch-on order can be given.
b If a switch is on, a switch-off order can be given.

Channel 1 to 2 selection Fault currents


On the Control module, a stored fault current is shown by a red indicator lamp
included in each channel block diagram.
b A Test pushbutton is used to trigger the simultaneous testing of the acquisition
systems and control panel indicator lamps. The corresponding indicator lamps light
up if the test is positive for as long as the pushbutton remains pressed, then remain
lit after the Test pushbutton is released.
Test
OFF ON b The Reset pushbutton is used to erase stored faults.
Confirmation
Reset
Other orders
The Power supply module is used to reset the power supply:
b It can reinstate the Telecoms supply when this output has been cut off
due to over-consumption,
b It can reinstate the supply to the equipment after it has been switched off
To ensure that a switch cannot be activated or deactivated
accidentally and that no operations are performed at the wrong due to an excessive drop in the 12 V supply.
time, an order cannot be implemented locally unless
the pushbutton corresponding to the channel to be controlled
and the confirmation pushbutton are pressed simultaneously.
Time-stamped events (logs)
As a result of the monitoring operations performed by the equipment, time-stamped
events that can be used to track the various operating phases (operating mode,
transmission of orders to the MV switches, self-testing, and so on) are stored.
The events are dated by the equipments internal clock or by GPS sync.
The system can be set from the configuration PC, or from the remote control station
if this function is available, or by GPS sync (if the option is present).

SEC automatic control (Sectionalizer)


Current The purpose of this automatic control is to open the MV switch following a failed slow
reset of the outgoing circuit-breaker. T200 must detect a fault current notification
MT10076EN

Operating time
confirmed by the loss of the T200 supply voltage (MV) before the SEC automatic
control can give this opening order (it must therefore be equipped with this function).
Id
It can be configured to:
Voltage dip b select the automatic control action in the voltage dip of a slow 4th, 3rd, 2nd
or 1st reset,
In
b program the automatic control reset time-out (must be greater than the total time
for the source substation reset cycle),
b assign the SEC automatic control channel by channel.
The SEC function can be activated or deactivated from the control panel or by
Time
a remote control order. The switches can be controlled manually in Local mode.
Configurable parameters, SEC automatic control: d IMPORTANT: if the SEC automatic control is associated with a channel,
b Valid/invalid automatic control, the latter shall mandatorily be configured with a remote alarm.
b Number of faults: 1 to 4, The enclosure shall mandatorily be powered from a LV source coming from
b Operating time: 20 s to 4 min in 5 s increments. the MV line on which the component is installed.

present VT (Voltage Time) automatic control


DE55675EN

Voltage With the switch closed, detection of voltage loss causes opening of the channel,
absent after a time-out t0 (confirmation of voltage OFF).
t1 t2 t1 t2 When voltage return is detected, a time-out t1 (closing time-out) is activated.
Switch closed As of the end of this time-out, closing of the cutoff component takes place
automatically, thus activating a time-out t2 (monitoring time-out).
Switch open If a new voltage loss appears during this time-out t2, the automatic control function
t0 t0 t0
is blocked and causes the automatic control locked red indicator lamp to light
on the local control panel.
Locked To unlock the automatic control function, the Reset automatic control pushbutton
on the local control panel must be pressed. Automatic control can then operate again.
Unlocked Automatic control can also be unlocked by the automatic control unlocking
command from the control centre.
Configurable parameters, VT automatic control:
b t0: voltage off time-out, The VT function can be activated or deactivated from the control panel or by
b t1: closing time-out, a remote control order. The switches can be controlled manually in Local mode.
b t2: monitoring time-out.

24
Maintenance Information display

General
The equipment does not require regular maintenance.
The integrated battery test keeps users informed of the battery availability status.
Note: replacement fuses are provided in the accessories bag attached inside
the basic enclosure.
The T200 has certain tools to perform maintenance or fault finding on the equipment.
This requires a PC-compatible microcomputer with Internet Explorer (or an equivalent
software) installed. It is then possible to read the internal states of the equipment and
the events stored in memory by the T200 (see also section on Commissioning).
The tools available for maintenance and fault finding are as follows:

Monitoring page
PE55897EN

The screen on the left shows an example of a 1-channel Easergy T200 P,


with internal fault detector option, provided with a current acquisition card
and a transformer for voltage measurement.
This menu allows viewing of all the states and information managed by the T200:
b The switch state Open, Closed or Locked,
b Stored fault currents: I Max et I Max transient on each phase,
b Current measurement on each phase, average current and neutral current,
b Voltage measurement phase-to-ground and phase-to-phase,
b Power measurement active, reactive and apparent,
b Frequency and power factor measurement,
b The operation and energy counter values,
b The automatic control status, On or Off,
b Equipment faults,
b The operating mode: local or remote,
b AC supply Off, Delayed AC supply Off,
b The state of digital inputs 1 to 8,
Monitoring page b The state of digital outputs 1 to 4.
Note: the indications are refreshed every three seconds.

Consulting the logs


PE55214EN

The various logs available (events, alarms and system) make it possible to know
the history of everything that has occurred on the T200.
This can be useful to find the cause of a fault during fault finding.
b All the events displayed in the logs are time stamped so as to know the date
of origin of a fault.
b The number of time-stamped events recorded (300 for the system log,
100 for alarms, 500 for events and 1500 for measurements) makes it possible
to go sufficiently far back in time to retrace the cause of a problem.
When the maximum number is exceeded, the oldest event on the list is erased
by the most recent one.
b The logs can be saved on PC in the form of Excel-compatible files so as to be able
to perform fault finding, reviews or statistics later.
b The logs can be transferred by e-mail so as to be able to forward the report
on a problem to an accessory department or person or possibly to exchange
an opinion with the manufacturer of the T200.
Event log
Indicator lamp indications
The T200 provides a certain amount of information via the indicator lamps on the
front panel of the rack modules (see section on Operation Control and indication).
These indicator lamps provide information concerning the operating state
of the T200 and concerning the presence of any fault, where applicable.
Note: a diagnostic through the state of the indicator lamps on the front panel
is not always adequate to find the cause of a fault. A lit indicator lamp indicates
the presence of a fault, but it is often necessary to consult the logs or the Viewing
page to determine precisely the cause of a fault.
For more information, consult the diagnostic table below.

25
Maintenance Diagnostics
via the front panel indicator lamps
and logs

Symptoms Possible causes Solutions Log *


The Equipment Easergy T200: Replace the Control module and/or the Communication module Modbus
fault LED on the no communication between communication
Control module is lit the Control module and fault
(you are advised the Communication module
to connect a PC The battery charger output Check the charger and the battery. If necessary, Charger fault
to the Control module voltage is too high or too low replace the Power Supply module and/or the battery
to determine the No power supply See 48 V LED OFF in the symptom column below Motorization
cause of the fault: to the switchgear power supply
Equipment States failure
menu)
Loss of battery capacity See Battery fault LED ON in the symptom column below Battery fault
or charge fault
No telecommunications See External 12 V LED OFF in the symptom column below Accessory
power supply equipment power
(Radio or Modem) supply failure
Problem on the Control module Connect the PC to the COM module and consult the logs. Configuration loss
Configuration loss: reconfigure the T200. or memory fault or
Other faults: perform resetting on the power supply card. program error or
If the fault persists, replace the CPU card parameter error
The Control module software Press the Reset button on the Power Supply module. If the LED
is faulty does not go out after a few seconds, replace the CPU card
The AC supply AC supply fuse blown Replace the gF type 2 A HPC fuse, 10 x 38 mm, Power supply
OFF LED on the in the lower enclosure panel failure
front panel of the No supply to the enclosure Connect the AC supply
Power Supply Enclosure power supply cut off Check the cause of the AC supply outage.
module is ON automatically due to prolonged If the AC supply remains OFF, run another supply cycle
AC OFF AC supply outage by pressing the Reset button on the Power Supply module.
If the power supply does not restart, change the Power Supply
module and/or the battery.
Temporary AC supply outage Wait for the AC supply voltage to be reinstated Power supply
(the enclosure is now running on battery) failure
The Battery fault Loss of battery capacity Check that AC supply is ON and that the charger Battery fault
LED on the front or charge fault is supplying 12 V. To do this, disconnect the battery
panel of the Power and measure the voltage on the rack battery connector.
Supply module If the voltage is null, replace the Power Supply module.
is ON Otherwise, after reconnecting the battery,
reset the Power Supply module to trigger
a battery test; if the problem recurs after charging
for 24 hours, replace the battery.
The Rack 12 V Fuse blown Replace the 5 x 20 mm, 0.8 A semi time-lag fuse
LED on the front on the Power Supply module
panel of the Power If the AC supply OFF LED is lit, Check the cause of the AC supply outage.
Supply module the enclosure supply has been If the AC supply remains OFF, run another supply cycle
is OFF cut off automatically due to by pressing the Reset button on the Power Supply module.
a long AC supply outage If the power supply does not restart, change the Power Supply
module and/or the battery.

Enclosure power supply cut off Check the charger and the battery. If necessary,
automatically due to a drop in replace the Power Supply module and/or the battery
the 12 V voltage
Power Supply module failure Replace the Power Supply module

(*) The events can be consulted in one or more of the various logs available:
b events log,
b alarms logs,
b system log.
In these logs, the information appears in the form TSSxx - Information (log column) - Fault

26
Maintenance Diagnostics
via the front panel indicator lamps
and logs (contd)

Symptoms Possible causes Solutions Log *


The Rack 12 V Fuse blown Replace the 5 x 20 mm, 0.8 A semi time-lag fuse Accessory
LED on the front on the Power Supply module equipment
panel of the Power Consumption on output Check the transmission equipment and reinstate the supply power supply
Supply module is > 1.3 A 0.3 A for 3 min by pressing the Reset button on the Power Supply module failure
OFF If the AC supply OFF LED is lit, Check the cause of the AC supply outage.
the enclosure supply has been If the AC supply remains OFF, run another supply cycle
cut off automatically due to by pressing the Reset button on the Power Supply module.
a long AC supply outage If the power supply does not restart, change the Power Supply
module and/or the battery

Enclosure power supply cut off Check the charger and the battery. If necessary,
automatically due to a drop in replace the Power Supply module and/or the battery
the 12 V voltage
Power Supply module failure Replace the Power Supply module Accessory
equipment
power supply
failure
The 48 V present Fuse blown Replace the 5 x 20 mm, 5 A time-lag fuse on the CPU card Motorization
LED on the front of the Control module in the left-hand part of the enclosure power supply
panel of the Power failure
Supply module If the AC supply OFF LED is lit, Check the cause of the AC supply outage.
is OFF the enclosure supply has been If the AC supply remains OFF, run another supply cycle
cut off automatically due to by pressing the Reset button on the Power Supply module.
a long AC supply outage If the power supply does not restart, change the Power Supply
module and/or the battery.
Enclosure power supply cut off Check the charger and the battery. If necessary,
automatically due to a drop replace the Power Supply module and/or the battery
in the 48 V voltage
T200 CPU card failure Replace the T200 CPU card Motorization
Power Supply module failure Replace the Power Supply module power supply
failure
All the Control The equipment is not Power up the equipment
module indicator powered up
lamps are OFF Supply fuse blown Replace the 5 x 20 mm, 0.8 A semi time-lag fuse
on the Power Supply module
Control module failure Replace the Control module
The card program Reset by pressing the Reset button on the Power Supply module
is no longer running
The Communication The equipment Power up the equipment
module ON LED is not powered up
is extinguished Supply fuse blown Replace the 5 x 20 mm, 0.8 A semi time-lag fuse
on the Power Supply module
The Communication Problem on the Communication Connect the PC to the Communication module. Check the conformity
module Fault module of the T200 configuration (for example: compatibility of the configured
LED is lit modem with that installed on the Communication card).
If the fault persists, replace the Communication module
The Communication The Communication module Stop the USB driver, disconnect the USB cable from Reset
module Fault software is faulty the Communication module, then press the Reset key
LED is flashing on the Power Supply module. If the LED does not go out
rapidly after a few seconds, replace the Communication module
The Communication The Communication module With the USB cable disconnected and the USB driver stopped,
module Fault software is faulty press the Reset key on the Power Supply module.
LED is flashing If the LED does not go out after a few seconds,
slowly replace the Communication module

Other diagnostics
Events Possible causes Solutions
Operation orders The switch order Check:
not executed was not executed b the position of the Local/Remote switch,
b the validity of the order issued,
b the connection between Easergy T200 and the switches.

27
Maintenance Power supplies

Powering down the equipment


b Switch off the AC supply outside the equipment or on the safety fuse block within
the enclosure.
b Disconnect the supply to the battery circuit:
Unplug the battery connector under the rack.
All the LEDs on the front panels of the rack should now be extinguished.
The Easergy T200 P enclosure is now powered down.

Toroid safety precautions


The toroid connectors are IP2x; switching off the current sensors temporarily
(< 10 min) involves no particular danger.
d IMPORTANT: there is no need to alter the cables when connecting
the toroid and power supply cables to the cubicle. The cables must never
be modified.

Battery maintenance
DE55061

Replacing the battery


Before carrying out any work on the battery, disconnect it from the equipment
by unplugging the connector from the base under the rack.
Remove the battery by sliding it outwards, raise the terminal covers and undo
the two terminal nuts, then disconnect the Faston lugs from the connecting cord.
To install a new battery, repeat this sequence in the reverse order.

Servicing and storing the batteries


d IMPORTANT: Sealed lead batteries are used. The advantages of this type of battery include the
b Use batteries having recent production dates fact that there is no risk of explosion, no acid leakage and no servicing requirement.
(less than three months old).
b Do not store more than 6 months without However, this type of battery has its limitations:
recharging. b Limited number or recharging cycles,
b Do not throw the batteries away. b Average service life of 10 years, with ageing accelerated by temperatures outside
the recommended range,
b Ageing during storage (do not store for more than 6 months without recharging,
as this type of battery does not withstand a total discharge),
b Difficult to predict the end of the battery service life.
The Power Supply module is designed to optimize the characteristics of the battery.
A battery fault alarm informs the remote control system of an imminent discharge.

Replacing fuses
DE56211

Replacement fuses are provided in the accessories bag attached inside the basic
enclosure.
b AC supply fuse
This fuse is located in the lower panel of the enclosure.
External 12 V It is a gG type HRC fuse of rating 2 A, 10 x 38 mm.
supply fuse b Rack power supply fuse
The fuse protecting the power supply to all the electronic modules is located
Rack power supply on the Power Supply module card.
fuse
It is a 5 x 20 mm, 0.8 A semi-time-lag fuse.
48 V supply fuse b Fusible external 12 V supply fuse
The fuse is located on the Power Supply card.
It is a 5 x 20 mm, 4 A time-lag fuse.
AC supply fuse b 48 V supply fuse
(safety fuse)
The fuse is located on the CPU card of the Control module.
This card is located in the left-hand part of the rack. It is accessible
after removing the control panel (front of the Control module).
It is a 5 x 20 mm, 5 A time-lag fuse.
To replace the fuses:
a) Power down the enclosure,
b) Replace the defective fuse,
c) Power up the enclosure.

28
Maintenance Card replacement

Replacing the Power Supply module


The 0.8 A fuse located on the Power Supply card protects a) Power down the enclosure (see the previous page) and disconnect the Battery
the 12 V supply to the entire rack. and Mains connectors on the underside of the card,
b) Release the two locking screws from the Power Supply module and remove it
from its housing,
c) Insert the new module, locking it in position,
d) Reconnect the Battery and Mains connectors to the underside of the card
and power up the enclosure.

Replacing the Communication module


a) Power down the enclosure (see the previous page),
b) Release the two locking screws and remove the Communication module
from its housing,
c) Insert the new module, locking it in position,
d) Power up the enclosure.
d IMPORTANT: remember to configure the module;
T200 CPU card see Commissioning.
DE55681

C
O
N
Replacing and connecting the control panel
T

U
1
R
O
L or T200 CPU card
U
2
Purpose: replacing the control panel or the T200 CPU card
1 or adding/replacing the voltage measurement card.
2 R
es
a) Power down the enclosure (see the previous page),
et
D
I1 b) Release the two locking screws from the front panel of the Control module,
D
I3
D
I2
c) Disconnect the ribbon cable from the rear of the front panel by separating
D
I4
the two levers on each side of the connector base,
d) If necessary, remove the T200 CPU card from its slot after loosening its locking
screw (at the bottom left-hand, on the front of the card) and disconnecting
all the connectors from the Connection card (under the rack).
Te
s
Installing the T200 CPU card
t
R
es
et
e) Push the new T200 CPU card firmly home and tighten its locking screw again
(at the bottom left-hand, on the front of the card),
O
F
F f) Reconnect all the connectors to the Connection card (under the rack),
O
N
g) Attach the end of the 26-pin ribbon cable from the control panel to the connector
on the T200 CPU card,
h) Screw the control panel firmly into position,
i) Power up the enclosure.
Connection card Meas. card Installing the voltage measurement card
e) Plug the measurement card into the T200 CPU card and secure it with the screws,
Control panel f) Install the T200 CPU card and the control panel (see above),
g) Power up the enclosure.
d IMPORTANT: remember to configure the module;
see Commissioning

29
Appendix A Configuration parameters 0

White colour: accessible for Viewing, as Operator or Administrator


Yellow (or light grey) colour: accessible exclusively as Operator or Administrator
Green (or medium grey) colour: accessible exclusively as Administrator
Dark grey colour: not accessible or non-existent

Home Page
Sub-page Section Parameters / button Config. ranges Default config. Comments
Choice Language Franais/English Franais Confirm by OK
of language
User User name No restriction Easergy Confirm by OK
Password No restriction Easergy Confirm by OK
An incorrect user or password opens
a User session

Viewing Page
Sub-page Section Parameters / button Config. ranges Default config. Comments
Classes Channel state Access to the corresponding class states
Automatic controls Access to the corresponding class states
Digital I/Os Access to the corresponding class states
System Access to the corresponding class states

Control Page
Sub-page Section Parameters / button Config. ranges Default config. Comments
Channel state Operation counter reset Between 0 0 Counter value to be initialized
and 9999999
Operation counter preset Allows the counter reset value
to be taken into account
OK allows the T200 to be initialized to this value
Energy counter reset Between 0 0 Counter value to be initialized
and 9999999
Energy counter preset Allows the counter reset value
to be taken into account
OK allows the T200 to be initialized to this value
F-O control Allows the switch status to be changed
DDEF reset control Allows resetting of fault detector storage
in memory
Automatic ON/OFF control Allows the automatic control status
controls to be changed
Digital I/Os Control of digital outputs Allows the state of digital outputs 1 to 3
1 to 3 to be changed

Diagnostic Page
Sub-page Section Parameters / button Config. ranges Default config. Comments
Alarms log Ack. The box is checked when the Scada
has acknowledged the alarm
Consultation of the log exclusively:
no action possible
Events log Consultation of the log exclusively
System log Consultation of the log exclusively
Measurements log Consultation of the log exclusively

File transfer Alarms.csv Transfers the alarms log in Excel file form
Save saves the file to the PC
Open opens the file under Excel without
saving it
Events.csv Same as for the events log
System.csv Same as for the system log
Measures.csv Same as for the measurements log

30
Appendix A Configuration parameters (contd) 0

Maintenance Page
Sub-page Section Parameters / button Config. ranges Default config. Comments
Terminal General Name of terminal No restriction No restriction At the users choice
Date format DD/MM/YYYY DD/MM/YYYY Defines the date format to be displayed
MM/DD/YYYY in the logs
YYYY/MM/DD
Other parameters Consultation exclusively
Save Takes into account the change
Software Software All parameters Consultation exclusively
information Software 1 Checked or not Not checked Selection of software 1
Software 2 Checked or not Checked Selection of software 2
Download software Allows the T200 software to be updated
Clock Terminal Date Consistent date None
date/time format (year > 2000)
Time Consistent time None
format
Update Allows the T200 date and time to be updated
manually
Synchronization Allows the T200 date and time to be updated
automatically by the PC
IP parameters Ethernet Mac address Unique identification address for each T200,
interface set in factory. Consultation exclusively
DHCP Active Inactive Defines whether the server of the Ethernet
Inactive local area network can allocate automatically
on connection an IP address to the T200 (active)
or not (inactive)
IP address Consistent IP address 172.16.0.5 Ethernet IP address of the T200
Sub-network mask Consistent mask 255.255.255.0 The mask enables (0) or inhibits (255) the choice
of accessible IP address values
Gateway addresses Consistent IP address 172.16.0.1 IP address of the servers Ethernet gateway.
The gateway centralizes all the network IP
accesses
Primary DNS server Consistent IP address 172.16.0.1 IP address of the primary DNS server
(Domain Name Server).
The DNS enables the IP
Secondary DNS server Consistent IP address 0.0.0.0 IP address of the secondary DNS server
(Domain Name Server).
Backup DNS server
USB interface Server IP address 212.1.1.10 IP address allocated to the Web server on-board
the T200 for USB access.
Not modifiable: consultation exclusively
Client IP address 212.1.1.11 IP address allocated to the PC connected via
USB to the on-board Web server.
Not modifiable: consultation exclusively
Save / Cancel Allows changes to be saved/cancelled
Users User No restriction None User name for the session
Password Password None Password for the session
Type Administrator Administrator The Administrator has full access
Operator The Operator has restricted access
Save Saves the new session
Recycle bin Check box to select a session to be deleted
Delete Deletes an existing session if the corresponding
box is checked
Port Traces Trace options Start / Stop Start / Stop acquisition of the T200 PC frame
1 and 2
Filtered Allows filtering of frames exclusively intended
for the local T200
Backup/ Saves Arrow T200 V PC Allows the configuration to be saved on the PC
Restoral the terminal in file form
configuration
Loads Arrow PC V T200 Enables the configuration to be loaded on the PC
the terminal from a file
configuration
Recovery Arrow T200 V T200 Loading of a default configuration
default (factory configuration)
configuration

31
Appendix A Configuration parameters (contd) 0

Configuration Page
Sub-page Section Parameters / button Config. ranges Default config. Comments
Operating modes Communication Port 1 or 2 mode Master / Master Consultation exclusively
Parameters Port 1 link Not used Normal b Port not available
Normal b Main transmission port
General Backup b Backup port upon loss of main port
communication Backup auto return b Ditto + return to main port if available
parameters Exact copy b Exact copy of the main port.
The ports transmit identically
Different copy b Same as Exact copy with different type
of medium, protocol or speed
Repeater b Repeater: the frame on the Normal channel is
sent again over the second port (V other T200)
Maintenance b Maintenance: transmission of parallel info
to a maintenance Scada
Port 2 link Same as Port 1 Not used Same as Port 1. At least one Normal port
is required. There cannot be two ports configured
as Normal
Port 1 medium Direct RS232 (internal) Radio (external) b RS232 modem integral with COM card
Radio (external) b For external radio with integral modem
Radio FSK (internal) b FSK radio modem on COM card
LL FSK (internal) b FSK radio modem on COM card
PSTN (external) b For external PSTN modem accessible
by Hayes command
PSTN (internal) b Internal PSTN modem on COM card
GSM (external) b For external GSM modem accessible
by Hayes command
GSM (internal) b Internal GSM modem on COM card
Port 2 medium Same as Port 1 None Same as Port 1
Save Allows the configuration to be taken into account
Protocol General TL 0 to 255000 ms 20000 ms Maximum response waiting time
parameters Max. number of send 1 to 255 or limited 3 Maximum number of repetitions during
Protocol operations the maximum response waiting time
parameters
Collision avoidance Disabled Disabled b Collision avoidance system disabled
(radio exclusively) Standard (Squelch) b The Squelch indicates radio occupancy
Standard (CD) b The CD indicates radio occupancy
Specific (Squelch) (Standard = MG collision avoidance algorithm)
Specific (CD) (Specific = protocol collision avoidance algorithm)
Collision avoidance On or off Off Enables the collision avoidance system or not
(Direct RS232
or LL exclusively)
Standard Priority 0 to 10 0 Defines a T200 call priority upon the occurrence
parameters of an alarm. The smaller the figure, the greater
the priority
Port 1 or 2 Min. random time-out 0 to 1500 ms 0 ms In 5 ms increments. Minimum random time-out
for sending an alarm to the Scada.
(RS232 or radio
Max. random time-out 10 to 60000 ms 500 ms In 1 ms increments. Maximum random time-out
only)
for sending an alarm to the Scada. The time
before sending an alarm is defined randomly
between the min. and max. random time-outs
Squelch protection Yes or No No Allows squelch operation to be validated or not
Active squelch level High or low Low Defines the level on which the squelch should
be defined as active
Tsqu (squelch protection) 0 to 255000 ms 10000 ms In 100 ms increments. Time for forced setting
of sending if still active after this time-out
Standard First test 1 s to 1 min 1s Time-out before first alarm sending test
parameters Second test 1 min to 5 min 1 min Time-out before second alarm sending test
or random if first test fails
Port 1 or 2
Third test 1 min to 10 min 2 min Time-out before third alarm sending test
or random if second test fails
(PSTN or GSM
only)
Save Allows the configuration be be taken into account

32
Appendix A Configuration parameters (contd) 0

Configuration Page (contd)


Sub-page Section Parameters / button Config. ranges Default config. Comments
Port 1 or 2 Direct RS232 Baud rate 200 to 38400 baud 1200 baud Frame transmission rate
or Radio 9600 baud (GSM) 9600 baud (PSTN
Transmission or PSTN or GSM)
or GSM line 600 to 1200 baud
or LL (radio FSK or LL FSK)
Stop bits 1 or 2 1 Stop bit in frame
Delay before response 0 to 10000 ms 0 ms In 10 ms increments. Upon reception, wait before
sending the response to avoid overlapping
RTS (or CTS) - 0 to 1000 ms 400 ms Request To Send. In 10 ms increments.
to message delay Delay between rise of RTS (or CTS if managed)
and sending the message
Message to RTS delay 0 to 10000 ms 20 ms In 10 ms increments. Delay between end
of message and RTS drop by the T200
Direct RS232 Parity None Even Transmission parity
or Radio Space
or PSTN Even
or LL Odd
Frame error on noisy Yes or no Yes The start of the frame can be filtered or not
outgoing feeder to avoid reading any noise
Frame error on line Yes or no No Any holes in the frame can be filtered or not
at rest
Direct RS232 CTS management Checked or not Not checked Clear To Send. The modem enables the CTS
or Radio (ext.) as soon as ready after RTS enabling by the T200
RTS to CTS delay 20 ms Delay between receiving the RTS and sending
the CTS by the modem
LL Type of line 2-wire or 4-wire 2-wire Choice of type of leased line, 2-wire or 4-wire
Direct RS232 DTR management Checked or not Not checked Data Terminal Ready. The modem causes
the DTR to rise after powering up or when
it is Clear To Send
DSR management Checked or not Not checked Carrier Detect. The carrier can be used by
the modem to detect reception of a message
PSTN or GSM Telephone No. (normal) 0 to 9, P, T or space None Main telephone No. to be used in case of alarm
retransmission
Telephone No. (backup) 0 to 9, P, T or space None Backup telephone No. to be used in case
of alarm retransmission if main No. not free
PSTN Type of dialling Pulse or voice Pulse dialling Type of dialling used for alarm retransmission
frequency
Modem init. sequence No restriction. &B1&A0&K0E0Q0V AT commands necessary to initialize the PSTN
Record consistent AT 1&C1&D2X4S0=2 modem. With internal PSTN mode, default AT
commands S2=255 commands not modifiable
GSM Calling party call delay 1 to 600 s 30 s Allows the call to be released when the T200
is called after the configured delay
Called party call delay 1 to 600 s 60 s Allows the call to be released when the Scada
is called after the configured delay
PIN code 0000 to 9999 None PIN code of the GSM card
SMS service centre No. 0 to 9, P, T or space None Telephone No. of the SMS service centre
(gateway for SMSs)
User SMS No. 0 to 9, P, T or space None Telephone No. of the user for sending SMSs
Save Allows the configuration to be taken into account

33
Appendix A Configuration parameters (contd) 0

Configuration Page (contd)


Sub-page Section Parameters / button Config. ranges Default config. Comments
Cntrl/Auto. Controls Type of control Other Other b Other = separate CO/CF controls
Ctrl PM6 b PM6 = single CO/CF control on CO
CI2 b CI2 = control execution time at 100 ms
Automatic RL27 b RL27 = specific cubicle connection
control Automatic control Type of automatic control None Voltage time b No automatic control
No.x Channel x Voltage time b Opening on mains loss
Sectionalizer b Opening on voltage dip due to fault
Automatic control Voltage failure time-out 0 to 327000 ms 200 ms In 100 ms increments
Voltage time Waiting time following voltage disappearance
before opening the channel
Closing time-out 0 to 327000 ms 200 ms In 100 ms increments
Waiting time following voltage return before
reclosing the channel
Monitoring time-out 0 to 327000 ms 200 ms In 100 ms increments
Time for monitoring non-disappearance
of the voltage following voltage return.
If this is the case during this time, the channel
opens and automatic control is blocked
Automatic control Reset time-out 20000 to 240000 ms 30000 ms In 5000 ms increments
Sectionalizer fault counter Maximum time to wait to see the number of faults
configured before automatic control reset
No. of faults 1 to 4 2 Number of faults to be taken into account before
authorized opening upon automatic control action
Save Allows the configuration to be taken into account
Measurements/ MV network Frequency 50 or 60 Hz 50 Hz Mains frequency
fault detector characteristics
Voltage Voltage input U21 U21 Choice of type of voltage measurement
measurement U21_U32 Depends on the type of setup (star or delta)
Measurement and configuration U21_U32_U13
fault detector No.x V1
configuration V1_V2
V1_V2_V3
Primary 100 to 36000 100 Primary transformation ratio of voltage
transformation ratio transformer
Secondary 100, 110, 115, 120 100 Secondary transformation ratio of voltage
transformation ratio 100/3, 110/3, transformer
115/3, 120/3
200, 220, 230, 240
200/3, 220/3,
230/3, 240/3
Voltage rating 20 to 36000 V 230 V Rated network voltage U
U presence threshold 70 to 120% 90% Min. threshold for taking into account U presence
U absence threshold 5 to 95% 80% Max. threshold for taking into account U absence
Voltage present time-out 100 to 180000 ms 100 ms In 10 ms increments.
Minimum U presence time for taking into account
U presence
Voltage absent time-out 100 to 180000 ms 100 ms In 10 ms increments.
Minimum U absence time for taking into account
U absence
Current Current sensors I1,I2,I3 or I1,I3,I0 I1,I2,I3 Type 2 setup (3 phase - RL27 type) or type 3
measurement (2 phase + homopolar - type RM6)
configuration
Fault detection Maximum I threshold 40 to 800 A 100 A Max. I fault detection threshold
configuration Threshold I0 20 to 160 A 50 A Homopolar fault detection threshold
Reset upon voltage Checked or not Not checked Reset of fault detection storage upon voltage
return return or not
Validation by supply Checked or not Not checked Use of supply voltage shortage or voltage loss
voltage shortage for fault detector reset
Validation time-out 1 to 70 s 2s Waiting time to validate fault presence
Inrush time-out 0 to 70 s 2s Current peak filtering time after closing the head
circuit-breakers
Auto detector reset 1 to 12 h 2h Time to reset the fault stored in memory
automatically, if still present
Imax time-out 40 to 800 ms 100 ms Time for taking into account Imax fault
I0 time-out 20 to 800 ms 40 ms Time for taking into account I0 fault
Rapid Imax time-out 20 to 800 ms 40 ms Time for taking into account rapid faults on Imax
Hysteresis 70 to 100% 95% Percentage of detection threshold for taking
into account disappearance of the fault
Save Allows the configuration to be taken into account

34
Appendix A Configuration parameters (contd) 0

Configuration Page (contd)


Sub-page Section Parameters / button Config. ranges Default config. Comments
Variable General Variable name No restriction Default name Name given to variable
configuration parameters of variable
Type Single or double Double TCD = double control only
Control
Access Administrator Operator Access right for this variable.
configuration
Operator A session with (at least) this access right
Viewing will allow viewing of this variable
Order Reverse or normal Normal Reverse gives an order with control
complementarity (e.g. CO/CF)
Class (complete list (depends on Allows a variable to be assigned to a class
of all classes) the variable)
Logical address TCDxx (e.g. TCD3) TCD No. assigned automatically by the website
Internal address x,x (e.g. 0,0) Internal address for the COM-CPU link
Associated logical TSD1 to TSD40 --- (none) No. of the TSD associated with the TCD used
address TS or none by the website for reading the state
External address format x (e.g 1) - (none) External address used by the Scada for this TCD

Save Allows the configuration to be taken into account


Cancel Enables return to the preceding configuration
Variable Overall Variable name No restriction Default name Name given to variable
configuration parameters of variable
Type Single or double (depends on TSD = double information
Indications the variable) TSS = single information
configuration
Logical address TSSxx or TSDxx TSD No. assigned automatically by the website
(e.g. TSD1)
Class (Complete list (depends on Allows a variable to be assigned to a class
of all classes) the variable)
Access Administrator (depends on Access right for this variable. A session with
Operator the variable) (at least) this access right will allow viewing
Viewing of this variable
Internal address x,x (e.g. 0,0) Internal address for the COM-CPU link
External address format x (e.g. 2) - (none) External address used by the Scada
for this variable
Active state definition (1) No restriction Closed Name displayed for an active state
of the variable
Active state colour (1) Black, blue, green Blue Display colour for an active state
or red colour of the variable
Inactive state definition (0) No restriction Open Name displayed for an inactive state
of the variable
Inactive state colour (0) Black, blue, green Green Display colour for an inactive state
or red colour of the variable
Other undefined state No restriction Problem Name displayed for an undefined state
of the variable
Undefined state colour Black, blue, green Red Display colour for an undefined state
or red colour of the variable
Record Enable Checked or not (depends on Enabling of the record or not upon change
configuration the variable) of state of this variable in the events log
Upon change of state Checked or not (depends on Recording of the event upon change of state
(or upon active) the variable) of the variable (or upon active)
Upon loss of closing Checked or not (depends on Recording of the event upon disappearance
(or upon inactive) the variable) of variable closing (or upon inactive)
Alarms Enable Checked or not (depends on Enabling of the alarm or not upon change of state
Configuration the variable) of this variable in the alarms log
Upon change of state Checked or not (depends on Enabling of the alarm and recording of alarm upon
(or upon active) the variable) change of state of the variable (or upon active)
Upon loss of closing Checked or not (depends on Enabling of the alarm and recording of alarm
(or upon inactive) the variable) upon disappearance of variable closing
(or upon inactive)
Alarm level 1 to 3 1 Several possible actions in the event of
a retransmission of alarm depending on the level
Time-delayed alarm Checked or not Not checked Enables a delay for sending the alarm
Delay value 0 to 99 0 Number of hours, minutes or seconds for
the delay before sending the alarm to the Scada
Hours or Minutes Checked according Hours checked Choice of unit for the value of the alarm delay
or Seconds to choice
Save Allows the configuration to be taken into account
Cancel Enables return to the preceding configuration

35
Appendix A Configuration parameters (contd) 0

Configuration Page (contd)


Sub-page Section Parameters / button Config. ranges Default config. Comments
Variable General Variable name No restriction Default name Name given to variable
configuration parameters of variable
Correction coefficient Direct or raw or Direct/10 Conversion for display of the variable value
Measurements Direct/10 to 10000 or
configuration Direct*10 to 10000
Logical address TMxx TM No. assigned automatically by the website
(e.g. TM1)
Class (Complete list (depends on Allows a variable to be assigned to a class
of all classes) the variable)
Access Administrator (depends on Access right for this variable. A session with
Operator the variable) (at least) this access right will allow viewing
Viewing of this variable
Internal address x,x (e.g. 0,0) Internal address for the COM-CPU link
External address (Scada) Format x (ex. 2) - (none) External address used by the Scada
for this variable
Unit No restriction None Unit for display of the variable
Max. value Integer 0 Max. measurement display value or max. value
for Scada transmission
Min. value Integer 0 Min. measurement display value
Value format Absolute + sign Complement at 2 Format for sending measurement to Scada
Complement at 2 Depends on the method of processing by Scada:
b Absolute + sign = sending of absolute value
of measurement + sign
b Complement at 2 = sending of binary value
complemented by addition of least significant bit
Regular Recording Checked or not Not checked Enabling of regular recording of the measurement
processing in the measurements log or not
Period 15 min, 30 min or 1 h (depends on Measurement recording period
the variable)
Type Averaged or Averaged Way of calculating the measurement
sampled for recording in the measurements log
Event Checked or not Not checked Enabling of regular recording of the measurement
in the events log or not
Call Checked or not Not checked Enabling of regular sending of the alarm to Scada
and recording in the alarms log or not
Period 15 min, 30 min or 1 h (depends on Event or call recording period
the variable)
Processing Recording Checked or not Not checked Enabling of recording of the measurement
on threshold in the measurements log or not upon exceeding
threshold
Event Checked or not Not checked Enabling of recording of the measurement
in the events log or not upon exceeding threshold
Call Checked or not Not checked Enabling of sending of the alarm to Scada
and recording in the alarms log or not upon
exceeding threshold
High threshold Checked or not Not checked Enabling of high threshold or not
Low threshold Checked or not Not checked Enabling of low threshold or not
High threshold value No restriction 0 Value for enabling exceeding of the high
measurement threshold
Low threshold value No restriction 0 Value for enabling exceeding of the low
measurement threshold
Dead band Recording Checked or not Checked Enabling of recording of the measurement
in the measurements log or not through variation
Event Checked or not Checked Enabling of recording of the measurement
in the events log or not through variation
Call Checked or not Not checked Enabling of sending of the alarm to Scada
and recording in the alarms log or not following
measurement variation
Value as % 0 to 255 10 % variation of the measurement for dead band
Min. and Max. Active minimum Checked or not Checked Recording or not of the minimum measurement
recording reached over the period configured
Active maximum Checked or not Checked Recording or not of the maximum measurement
reached over the period configured
Period 1, 7 or 14 days 1 day Calculation period for min. and max. value
Save Allows the configuration to be taken into account
Cancel Enables return to the preceding configuration

36
Appendix A Configuration parameters (contd) 0

Configuration Page (contd)


Sub-page Section Parameters / button Config. ranges Default config. Comments
Variable General Variable name No restriction Default name Name given to variable
Configuration parameters of variable
Type Direct or raw or Direct/10 Conversion for display of the variable value
Counters Direct/10 to 10000 or
Direct*10 to 10000
Logical address CNTx CNTx No. assigned automatically by the website
(e.g. CNT1)
Class (Complete list (depends on Allows a variable to be assigned to a class
of all classes) the variable)
Access Administrator (depends on Access right for this variable.
Operator the variable) A session with (at least) this access right
Viewing will allow viewing of this variable
Internal address x,x (e.g. 0,0) Internal address for the COM-CPU link
External address format x (e.g. 5) - (none) External address used by Scada for this variable
Unit No restriction None Unit for display of the variable
Max. value scale Integer 0 Max. measurement display value
Min. value scale Integer 0 Min. measurement display value
Value format Absolute + sign Complement at 2 Format for sending measurement to Scada.
Complement at 2 Depends on the method of processing by Scada:
b Absolute + sign = sending of absolute value
of measurement + sign
b Complement at 2 = sending of binary value
complemented by addition of least significant bit
TCD reset address TCD1 to 40 (depends on Address for the counter reset command
the variable)
Regular Recording Checked or not Not checked Enabling of regular recording of the counter
processing in the measurements log or not
Period 15 min, 30 min or 1 h (depends on Counter recording period
the variable)
Event Checked or not Not checked Enabling of regular recording of the counter
in the events log or not
Call Checked or not Not checked Enabling of regular sending of the alarm to Scada
and recording in the alarms log or not
Processing Recording Checked or not Not checked Enabling of recording of the counter
on threshold in the measurements log or not upon
exceeding threshold
Event Checked or not Not checked Enabling of recording of the counter in the events
log or not upon exceeding threshold
Call Checked or not Not checked Enabling of sending of the alarm to Scada
and recording in the alarms log or not upon
exceeding threshold
High threshold value No restriction 0 Value for enabling exceeding of the high counter
threshold
Dead band Recording Checked or not Checked Enabling of recording of the counter in the
measurements log or not through variation
Event Checked or not Checked Enabling of recording of the counter in the events
log or not through variation
Call Checked or not Not checked Enabling of sending of the alarm to Scada
and recording in the alarms log or not following
counter variation
Value as % 0 to 255 10 % variation of the measurement for dead band
Save Allows the configuration to be taken into account
Cancel Enables return to the preceding configuration
Class Recycle bin Coche ou non Not checked Selection of class to be deleted or not
management Viewing Coche ou non (depends on Selection or not of class display
the classe) in the Viewing page
Class name No restriction None Class name to be displayed
Save Allows a modification or a creation
to be recorded for each class
Delete Allows a class that has been selected earlier
to be deleted

37
Appendix B General specifications

Capacity
Controllable switch 1 channel (2 channels on option)
Indication inputs Open door + 8 free digital inputs
Output loops Enclosure lighting + 3 digital outputs
Number of TMs Management of a max. of 82 TMs per 4-channel module
Power supply
AC supply Characteristics 90 to 240 Vac, 50 Hz, 120 VA max., output 91 W
Protected by a gG type HRC fuse of rating 2 A, 10 x 38 mm
Power supply Charger 12 V 7A
Rack power supply 12 Vdc (10.8 V to 14.8 V). Protected by a 0.8 A fuse
Telecommunications 12 Vdc (10.8 V to 14.8 V) 1 A continuous-duty, 7 A max.
Protection if consumption > 1.3 A for more than 3 min
Motorization 48 V (or 24 V on option) By 12/48 V converter (12/24 V on option)
48 Vdc (44.8 V to 59 V) max. 6 A during 12 s and 15 A during 50 ms
Battery Type Sealed lead maintenance-free type
Charging time 10 h to 24 h
Capacity 12 Vdc - 38 Ah
Power reserve at 20C Up to 16 h + 10 O/C cycles (in radio communications)
Lifetime at 20C 10 years
Characteristics
Dielectric AC supply input IEC 255-4 Insulation (50 Hz / 1 min): 10 kV
Impulse wave (1.2 / 50 s): 20 kV
Toroid input IEC 255-4 Insulation (50 Hz / 1 min): 2 kV
Impulse wave (1.2 / 50 s): 5 kV
Electromagnetic Rapid transients IEC 1000-4-4 Level 4: 4 kV (mains and sensors),
2 kV (other circuits)
Electrostatic discharges IEC 1000-4-2 Level 3; 6 kV on disconnected 8 kV contact
Radiated electromagnetic IEC 1000-4-3 80 MHz 1 GHz 10 V/m
field
Radio frequency on FSM IEC 1000-4-6 0.15 MHz to 80 MHz 10 Vrms
Damped oscillatory waves IEC 1000-4-12 2.5 kV common mode, 1 kV differential mode
Pulsed magnetic field IEC 1000-4-9 1000 A/m peak
Impulse waves IEC 1000-4-5 Coupling between line wires 1 kV, between wire and frame earth 2 kV
50 Hz magnetic fields IEC 1000-4-8 30 A/m continuous-duty and 300 A/m 1 to 3 s
Climatic Temperature 25C to +55C
Relative humidity IEC 68-2-3 Less than 95% at 40C
Salt spray test IEC 68-2-11 336 h
Storage temperature IEC 68-2-14 40C to +70C
Mechanical Enclosure material Stainless steel 316 L
Vibrations IEC 68-2-6 10 to 500 Hz; 1 g or 0.075 min peak-to-peak
Dimensions HxWxD 630 mm x 410 mm x 350 mm
Weight 40 kg
Protection IEC 60529 IP55
Measurements (options)
Current measurement Phase-to-phase fault threshold Configurable for 40 to 800 A in increments of 1 A
and fault detection Earth fault threshold Configurable for 2 to 160 A in increments of 1 A
Fault duration 40 to 800 ms in increments of 20 ms
Values restored 3I, Imean, Io
Precision from 10C to 55C 1.6% from 20 to 800 A
Voltage measurements Values restored 3 U and 3 V
Precision from 10C to 55C 1.2% (0.5% at +20C)
Other measurements Power from 10C to 55C P, S, Q: precision 2.8%
Energy from 10C to 55C Precision 2%
Power factor from 10C to 55C Precision 1.7%
Frequency Mean value over 10 periods; precision 0.1%
Measurement of phase shift from 10C to 55C Expressed in degrees; precision 3C
between two U measurements
General specifications Digitizing 12 bits

Note: the tolerances indicated for the voltages are applicable only on the voltages measured.

38
Schneider Electric Industries SAS
Postal address: As standards, specifications and designs develop from time to time, always ask for confirmation
Easergy of the information given in this publication.
F-38050 Grenoble Cedex 9
This document has been
Tel.: +33 (0)4 76 57 60 60 printed on ecological paper
Fax: +33 (0)4 76 57 60 61
http://www.schneider-electric.fr Publishing: Schneider Electric
http://www.merlin-gerin.com Design, production: Graphme
http://www.easergy.com Printing:

NT00113EN-edition 1 04/2005

S-ar putea să vă placă și