Sunteți pe pagina 1din 66

JOB NO :- 0725MP

TECHNO ELECTRIC & ENGG. CO. LTD. DOC NO:-


ENGINEERS & CONSTRUCTORS,KOLKATA. 0725MP_GWLR_SUB_SWYD_E_DGN_07_001
400KV GWALIOR SUBSTATION

INDOOR ILLUMINATION DESIGN FOR COMBINED STATCOM STATION BUILDINGS

PROJECT : STATCOM Installations at: (i)400kV Lucknow and 400kV


Nalagarh Substations under Installation of STATCOMs in
Northern Region; and (ii) 400kV Gwalior substation
under Installation of STATCOMs in Western Region

CLIENT : POWER GRID CORPORATION OF INDIA LTD.

NOA No. : CC-CS/387-NR1/STATCOM-2120/3/G3/NOA-II/6978 dated 02.09.2016


CC-CS/387-NR1/STATCOM-2120/3/G3/NOA-IV/6980 dated 02.09.2016

SUBSTATION : 400 KV GWALIOR SUBSTATION

DOC. NO. : 0725MP_GWLR_SUB_SWYD_E_DGN_07_001

RXPE. REF. NO. : NR-RX-1-SE-PE-DG-0027

0 FIRST SUBMISSION P.B. 03.05.17 A.K.C. 03.05.17 S.B. 03.05.17

SIGN DATE SIGN DATE SIGN DATE


REVISION DESCRIPTION
PREPARED BY CHECKED BY APPROVED BY
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

Table of contents

GWALIOR STATCOM BUILDING


Table of contents 1
Luminaire parts list 3
18W DL LX LED based Recessed Luminaire
Luminaire Data Sheet 4
Prisma 45W , 2 x 2Ft LED based Recessed Luminaire
Luminaire Data Sheet 5
INSTA OMEGA 45W (2' x 2') Ceiling Light
Luminaire Data Sheet 6
CONTROL ROOM
Summary 7
Luminaires (layout plan) 8
Luminaires (coordinates list) 9
STATCOM -1
Summary 11
Luminaires (layout plan) 12
Luminaires (coordinates list) 13
Room Surfaces
Floor
Value Chart (E) 15
ACDB & DCDB ROOM
Summary 16
Luminaires (layout plan) 17
Luminaires (coordinates list) 18
BATTERY ROOM
Summary 19
Luminaires (layout plan) 20
Luminaires (coordinates list) 21
WATER COOLING ROOM 1
Summary 22
Luminaires (layout plan) 23
Luminaires (coordinates list) 24
AHU ROOM 1
Summary 25
Luminaires (layout plan) 26
Luminaires (coordinates list) 27
CONFERENCE
Summary 28
Luminaires (layout plan) 29
Luminaires (coordinates list) 30
STORE ROOM
Summary 31
Luminaires (layout plan) 32
Luminaires (coordinates list) 33
PANTRY
Summary 34
Luminaires (layout plan) 35
Luminaires (coordinates list) 36
GENTS TOILET
Summary 37
Luminaires (layout plan) 38
Luminaires (coordinates list) 39
LADIES TOILET
Summary 40

Page 1
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

Table of contents

Luminaires (layout plan) 41


Luminaires (coordinates list) 42
CORRIDOR 1
Summary 43
Luminaires (layout plan) 44
Luminaires (coordinates list) 45
Photometric Results 46
CORRIDOR 2
Summary 47
Luminaires (layout plan) 48
Luminaires (coordinates list) 49
Photometric Results 50
CORRIDOR 3
Summary 51
Luminaires (layout plan) 52
Luminaires (coordinates list) 53
Photometric Results 54
CORRIDOR 4
Summary 55
Luminaires (layout plan) 56
Luminaires (coordinates list) 57
Photometric Results 58
STATCOM -2
Luminaires (layout plan) 59
Luminaires (coordinates list) 60
WATER COOLING ROOM 2
Luminaires (layout plan) 62
Luminaires (coordinates list) 63
AHU ROOM 2
Luminaires (layout plan) 64
Luminaires (coordinates list) 65

Page 2
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

GWALIOR STATCOM BUILDING / Luminaire parts list

33 Pieces 18W DL LX LED based Recessed Luminaire See our luminaire catalog for an
Article No.: 18W DL LX image of the luminaire.
Luminous flux (Luminaire): 941 lm
Luminous flux (Lamps): 941 lm
Luminaire Wattage: 19.3 W
Luminaire classification according to CIE: 100
CIE flux code: 60 88 97 100 100
Fitting: 1 x LED (Correction Factor 1.000).

115 Pieces INSTA OMEGA 45W (2' x 2') Ceiling Light See our luminaire catalog for an
Article No.: INSTA OMEGA 45W (2' x 2') image of the luminaire.
Luminous flux (Luminaire): 3761 lm
Luminous flux (Lamps): 3761 lm
Luminaire Wattage: 46.0 W
Luminaire classification according to CIE: 100
CIE flux code: 58 86 96 100 100
Fitting: 1 x LED (Correction Factor 1.000).

52 Pieces Prisma 45W , 2 x 2Ft LED based Recessed Luminaire See our luminaire catalog for an
Article No.: Prisma 45W , 2 x 2Ft image of the luminaire.
Luminous flux (Luminaire): 2491 lm
Luminous flux (Lamps): 2491 lm
Luminaire Wattage: 40.3 W
Luminaire classification according to CIE: 100
CIE flux code: 59 88 97 100 100
Fitting: 1 x LED (Correction Factor 1.000).

Page 3
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

18W DL LX LED based Recessed Luminaire / Luminaire Data Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the luminaire.

Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table can be displayed for this
CIE flux code: 60 88 97 100 100 luminaire.

Page 4
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

Prisma 45W , 2 x 2Ft LED based Recessed Luminaire / Luminaire Data Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the luminaire.

Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table can be displayed for this
CIE flux code: 59 88 97 100 100 luminaire.

Page 5
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

INSTA OMEGA 45W (2' x 2') Ceiling Light / Luminaire Data Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the luminaire.

Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table can be displayed for this
CIE flux code: 58 86 96 100 100 luminaire.

Page 6
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CONTROL ROOM / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: 0.80 Values in Lux, Scale 1:167

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 405 253 542 0.624
Floor 10 369 221 460 0.600
Ceiling 50 45 36 129 0.790
Walls (4) 30 195 35 656 /

Workplane:
Height: 0.760 m
Grid: 11 x 9 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.516, Ceiling / Working Plane: 0.112.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 30 Prisma 45W , 2 x 2Ft LED based Recessed Luminaire (1.000) 2491 2491 40.3
Total: 74716 Total: 74716 1208.9

Specific connected load: 10.33 W/m = 2.55 W/m/100 lx (Ground area: 117.00 m)

Page 7
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CONTROL ROOM / Luminaires (layout plan)

Scale 1 : 88

Luminaire Parts List

No. Pieces Designation


1 30 Prisma 45W , 2 x 2Ft LED based Recessed Luminaire

Page 8
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CONTROL ROOM / Luminaires (coordinates list)

Prisma 45W , 2 x 2Ft LED based Recessed Luminaire


2491 lm, 40.3 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.600 12.300 3.000 0.0 0.0 0.0
2 2.100 12.300 3.000 0.0 0.0 0.0
3 0.600 8.400 3.000 0.0 0.0 0.0
4 2.100 8.400 3.000 0.0 0.0 0.0
5 0.600 5.100 3.000 0.0 0.0 0.0
6 2.100 5.100 3.000 0.0 0.0 0.0
7 0.600 3.000 3.000 0.0 0.0 0.0
8 2.100 3.000 3.000 0.0 0.0 0.0
9 6.900 12.300 3.000 0.0 0.0 0.0
10 6.900 8.400 3.000 0.0 0.0 0.0
11 6.900 5.100 3.000 0.0 0.0 0.0
12 6.900 3.000 3.000 0.0 0.0 0.0
13 8.400 12.300 3.000 0.0 0.0 0.0
14 8.400 8.400 3.000 0.0 0.0 0.0
15 8.400 5.100 3.000 0.0 0.0 0.0
16 8.400 3.000 3.000 0.0 0.0 0.0
17 0.600 0.900 3.000 0.0 0.0 0.0
18 2.100 0.900 3.000 0.0 0.0 0.0
19 6.900 0.900 3.000 0.0 0.0 0.0
20 8.400 0.900 3.000 0.0 0.0 0.0
21 0.600 10.500 3.000 0.0 0.0 0.0
22 2.100 10.500 3.000 0.0 0.0 0.0
23 6.900 10.500 3.000 0.0 0.0 0.0
24 8.400 10.500 3.000 0.0 0.0 0.0
25 4.500 12.300 3.000 0.0 0.0 0.0
26 4.500 8.400 3.000 0.0 0.0 0.0
27 4.500 5.100 3.000 0.0 0.0 0.0
28 4.500 3.000 3.000 0.0 0.0 0.0

Page 9
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CONTROL ROOM / Luminaires (coordinates list)

No. Position [m] Rotation []


X Y Z X Y Z
29 4.500 0.900 3.000 0.0 0.0 0.0
30 4.500 10.500 3.000 0.0 0.0 0.0

Page 10
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STATCOM -1 / Summary

Height of Room: 5.100 m, Mounting Height: 5.100 m, Light loss factor: 0.80 Values in Lux, Scale 1:142

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 422 302 508 0.715
Floor 10 386 246 477 0.637
Ceiling 50 48 34 92 0.717
Walls (4) 30 209 43 685 /

Workplane:
Height: 0.760 m
Grid: 7 x 7 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.523, Ceiling / Working Plane: 0.114.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 30 INSTA OMEGA 45W (2' x 2') Ceiling Light (1.000) 3761 3761 46.0
Total: 112819 Total: 112827 1380.3

Specific connected load: 9.65 W/m = 2.29 W/m/100 lx (Ground area: 143.00 m)

Page 11
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STATCOM -1 / Luminaires (layout plan)

Scale 1 : 93

Luminaire Parts List

No. Pieces Designation


1 30 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 12
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STATCOM -1 / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 2.700 10.100 5.100 0.0 0.0 0.0
2 9.900 10.100 5.100 0.0 0.0 0.0
3 12.300 10.100 5.100 0.0 0.0 0.0
4 2.700 5.300 5.100 0.0 0.0 0.0
5 7.496 10.100 5.100 0.0 0.0 0.0
6 12.300 5.300 5.100 0.0 0.0 0.0
7 9.900 5.300 5.100 0.0 0.0 0.0
8 7.496 5.300 5.100 0.0 0.0 0.0
9 12.300 2.900 5.100 0.0 0.0 0.0
10 5.100 10.100 5.100 0.0 0.0 0.0
11 5.100 5.300 5.100 0.0 0.0 0.0
12 2.700 1.100 5.100 0.0 0.0 0.0
13 12.300 1.100 5.100 0.0 0.0 0.0
14 9.900 1.100 5.100 0.0 0.0 0.0
15 7.496 1.100 5.100 0.0 0.0 0.0
16 5.100 1.100 5.100 0.0 0.0 0.0
17 0.900 10.100 5.100 0.0 0.0 0.0
18 0.900 5.300 5.100 0.0 0.0 0.0
19 0.900 2.900 5.100 0.0 0.0 0.0
20 0.900 1.100 5.100 0.0 0.0 0.0
21 2.700 7.700 5.100 0.0 0.0 0.0
22 12.300 7.700 5.100 0.0 0.0 0.0
23 9.900 7.700 5.100 0.0 0.0 0.0
24 7.496 7.700 5.100 0.0 0.0 0.0
25 5.100 7.700 5.100 0.0 0.0 0.0
26 0.900 7.700 5.100 0.0 0.0 0.0
27 2.700 2.900 5.100 0.0 0.0 0.0
28 9.900 2.900 5.100 0.0 0.0 0.0

Page 13
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STATCOM -1 / Luminaires (coordinates list)

No. Position [m] Rotation []


X Y Z X Y Z
29 7.496 2.900 5.100 0.0 0.0 0.0
30 5.100 2.900 5.100 0.0 0.0 0.0

Page 14
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STATCOM -1 / Floor / Value Chart (E)

Values in Lux, Scale 1 : 93

Position of surface in room:


Marked point:
(0.000 m, 0.000 m, 0.000 m)

Grid: 9 x 9 Points

Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax


386 246 477 0.637 0.516

Page 15
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

ACDB & DCDB ROOM / Summary

Height of Room: 3.600 m, Mounting Height: 3.600 m, Light loss factor: 0.80 Values in Lux, Scale 1:136

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 305 202 360 0.662
Floor 20 285 193 336 0.679
Ceiling 80 71 56 161 0.792
Walls (4) 50 177 72 682 /

Workplane:
Height: 0.760 m
Grid: 21 x 9 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.613, Ceiling / Working Plane: 0.233.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 18 INSTA OMEGA 45W (2' x 2') Ceiling Light (1.000) 3761 3761 46.0
Total: 67692 Total: 67696 828.2

Specific connected load: 5.45 W/m = 1.79 W/m/100 lx (Ground area: 152.00 m)

Page 16
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

ACDB & DCDB ROOM / Luminaires (layout plan)

Scale 1 : 136

Luminaire Parts List

No. Pieces Designation


1 18 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 17
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

ACDB & DCDB ROOM / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.900 6.800 3.600 0.0 0.0 0.0
2 4.500 6.800 3.600 0.0 0.0 0.0
3 11.700 6.800 3.600 0.0 0.0 0.0
4 15.000 6.800 3.600 0.0 0.0 0.0
5 18.300 6.800 3.600 0.0 0.0 0.0
6 4.500 0.800 3.600 0.0 0.0 0.0
7 11.700 0.800 3.600 0.0 0.0 0.0
8 15.000 0.800 3.600 0.0 0.0 0.0
9 18.300 0.800 3.600 0.0 0.0 0.0
10 0.900 3.800 3.600 0.0 0.0 0.0
11 4.500 3.800 3.600 0.0 0.0 0.0
12 18.300 3.800 3.600 0.0 0.0 0.0
13 0.900 0.800 3.600 0.0 0.0 0.0
14 15.000 3.800 3.600 0.0 0.0 0.0
15 11.700 3.800 3.600 0.0 0.0 0.0
16 7.500 6.800 3.600 0.0 0.0 0.0
17 7.500 0.800 3.600 0.0 0.0 0.0
18 7.500 3.800 3.600 0.0 0.0 0.0

Page 18
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

BATTERY ROOM / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: 0.80 Values in Lux, Scale 1:65

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 154 57 243 0.371
Floor 10 134 83 176 0.618
Ceiling 50 21 13 107 0.627
Walls (4) 30 86 13 872 /

Workplane:
Height: 0.760 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.633, Ceiling / Working Plane: 0.133.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 5 Prisma 45W , 2 x 2Ft LED based Recessed Luminaire (1.000) 2491 2491 40.3
Total: 12453 Total: 12453 201.5

Specific connected load: 5.04 W/m = 3.27 W/m/100 lx (Ground area: 40.00 m)

Page 19
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

BATTERY ROOM / Luminaires (layout plan)

Scale 1 : 58

Luminaire Parts List

No. Pieces Designation


1 5 Prisma 45W , 2 x 2Ft LED based Recessed Luminaire

Page 20
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

BATTERY ROOM / Luminaires (coordinates list)

Prisma 45W , 2 x 2Ft LED based Recessed Luminaire


2491 lm, 40.3 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 1.500 4.400 3.000 0.0 0.0 0.0
2 3.900 2.300 3.000 0.0 0.0 0.0
3 7.500 4.400 3.000 0.0 0.0 0.0
4 1.500 0.500 3.000 0.0 0.0 0.0
5 7.500 0.500 3.000 0.0 0.0 0.0

Page 21
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

WATER COOLING ROOM 1 / Summary

Height of Room: 5.100 m, Mounting Height: 5.100 m, Light loss factor: 0.80 Values in Lux, Scale 1:97

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 432 243 554 0.562
Floor 10 374 230 467 0.614
Ceiling 50 70 54 117 0.772
Walls (4) 30 247 55 760 /

Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.614, Ceiling / Working Plane: 0.163.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 12 INSTA OMEGA 45W (2' x 2') Ceiling Light (1.000) 3761 3761 46.0
Total: 45128 Total: 45131 552.1

Specific connected load: 14.72 W/m = 3.41 W/m/100 lx (Ground area: 37.50 m)

Page 22
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

WATER COOLING ROOM 1 / Luminaires (layout plan)

Scale 1 : 51

Luminaire Parts List

No. Pieces Designation


1 12 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 23
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

WATER COOLING ROOM 1 / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.900 6.600 5.100 0.0 0.0 0.0
2 2.700 6.600 5.100 0.0 0.0 0.0
3 4.200 6.600 5.100 0.0 0.0 0.0
4 0.900 4.800 5.100 0.0 0.0 0.0
5 2.700 4.800 5.100 0.0 0.0 0.0
6 4.200 4.800 5.100 0.0 0.0 0.0
7 0.900 3.000 5.100 0.0 0.0 0.0
8 2.700 3.000 5.100 0.0 0.0 0.0
9 4.200 3.000 5.100 0.0 0.0 0.0
10 0.900 0.600 5.100 0.0 0.0 0.0
11 2.700 0.600 5.100 0.0 0.0 0.0
12 4.200 0.600 5.100 0.0 0.0 0.0

Page 24
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

AHU ROOM 1 / Summary

Height of Room: 5.100 m, Mounting Height: 5.100 m, Light loss factor: 0.80 Values in Lux, Scale 1:45

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 277 179 337 0.648
Floor 10 227 162 267 0.715
Ceiling 50 56 37 89 0.672
Walls (4) 30 180 40 553 /

Workplane:
Height: 0.760 m
Grid: 16 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.710, Ceiling / Working Plane: 0.202.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 5 INSTA OMEGA 45W (2' x 2') Ceiling Light (1.000) 3761 3761 46.0
Total: 18803 Total: 18805 230.1

Specific connected load: 13.15 W/m = 4.75 W/m/100 lx (Ground area: 17.50 m)

Page 25
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

AHU ROOM 1 / Luminaires (layout plan)

Scale 1 : 36

Luminaire Parts List

No. Pieces Designation


1 5 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 26
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

AHU ROOM 1 / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 1.200 2.600 5.100 0.0 0.0 0.0
2 2.700 2.000 5.100 0.0 0.0 0.0
3 4.200 2.600 5.100 0.0 0.0 0.0
4 1.200 0.800 5.100 0.0 0.0 0.0
5 4.200 0.800 5.100 0.0 0.0 0.0

Page 27
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CONFERENCE / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: 0.80 Values in Lux, Scale 1:79

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 450 349 511 0.777
Floor 10 382 244 459 0.640
Ceiling 50 56 47 142 0.835
Walls (4) 30 221 41 884 /

Workplane:
Height: 0.760 m
Grid: 7 x 7 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.549, Ceiling / Working Plane: 0.126.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 11 Prisma 45W , 2 x 2Ft LED based Recessed Luminaire (1.000) 2491 2491 40.3
Total: 27396 Total: 27396 443.3

Specific connected load: 14.42 W/m = 3.21 W/m/100 lx (Ground area: 30.75 m)

Page 28
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CONFERENCE / Luminaires (layout plan)

Scale 1 : 42

Luminaire Parts List

No. Pieces Designation


1 11 Prisma 45W , 2 x 2Ft LED based Recessed Luminaire

Page 29
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CONFERENCE / Luminaires (coordinates list)

Prisma 45W , 2 x 2Ft LED based Recessed Luminaire


2491 lm, 40.3 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.600 5.559 3.000 0.0 0.0 0.0
2 2.400 5.559 3.000 0.0 0.0 0.0
3 4.200 5.550 3.000 0.0 0.0 0.0
4 0.600 2.259 3.000 0.0 0.0 0.0
5 4.200 2.250 3.000 0.0 0.0 0.0
6 0.600 0.453 3.000 0.0 0.0 0.0
7 2.400 0.453 3.000 0.0 0.0 0.0
8 4.200 0.450 3.000 0.0 0.0 0.0
9 0.600 4.059 3.000 0.0 0.0 0.0
10 4.200 4.050 3.000 0.0 0.0 0.0
11 2.400 3.150 3.000 0.0 0.0 0.0

Page 30
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STORE ROOM / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: 0.80 Values in Lux, Scale 1:65

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 277 148 358 0.534
Floor 10 233 152 274 0.653
Ceiling 50 37 27 118 0.728
Walls (4) 30 148 24 713 /

Workplane:
Height: 0.760 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.604, Ceiling / Working Plane: 0.135.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 6 Prisma 45W , 2 x 2Ft LED based Recessed Luminaire (1.000) 2491 2491 40.3
Total: 14943 Total: 14943 241.8

Specific connected load: 9.67 W/m = 3.49 W/m/100 lx (Ground area: 25.00 m)

Page 31
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STORE ROOM / Luminaires (layout plan)

Scale 1 : 36

Luminaire Parts List

No. Pieces Designation


1 6 Prisma 45W , 2 x 2Ft LED based Recessed Luminaire

Page 32
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STORE ROOM / Luminaires (coordinates list)

Prisma 45W , 2 x 2Ft LED based Recessed Luminaire


2491 lm, 40.3 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.600 4.100 3.000 0.0 0.0 0.0
2 4.200 4.100 3.000 0.0 0.0 0.0
3 0.600 2.300 3.000 0.0 0.0 0.0
4 0.600 0.500 3.000 0.0 0.0 0.0
5 4.200 0.500 3.000 0.0 0.0 0.0
6 4.200 2.300 3.000 0.0 0.0 0.0

Page 33
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

PANTRY / Summary

Height of Room: 3.600 m, Mounting Height: 3.600 m, Light loss factor: 0.80 Values in Lux, Scale 1:39

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 165 102 206 0.617
Floor 10 115 89 132 0.774
Ceiling 50 30 18 40 0.607
Walls (4) 30 98 21 377 /

Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.672, Ceiling / Working Plane: 0.181.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 1 INSTA OMEGA 45W (2' x 2') Ceiling Light (1.000) 3761 3761 46.0
Total: 3761 Total: 3761 46.0

Specific connected load: 8.52 W/m = 5.18 W/m/100 lx (Ground area: 5.40 m)

Page 34
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

PANTRY / Luminaires (layout plan)

Scale 1 : 21

Luminaire Parts List

No. Pieces Designation


1 1 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 35
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

PANTRY / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.900 1.500 3.600 0.0 0.0 0.0

Page 36
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

GENTS TOILET / Summary

Height of Room: 3.600 m, Mounting Height: 3.600 m, Light loss factor: 0.80 Values in Lux, Scale 1:39

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 139 74 193 0.534
Floor 10 103 70 127 0.679
Ceiling 50 17 11 21 0.624
Walls (4) 30 65 12 142 /

Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.497, Ceiling / Working Plane: 0.123.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 1 INSTA OMEGA 45W (2' x 2') Ceiling Light (1.000) 3761 3761 46.0
Total: 3761 Total: 3761 46.0

Specific connected load: 4.79 W/m = 3.45 W/m/100 lx (Ground area: 9.60 m)

Page 37
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

GENTS TOILET / Luminaires (layout plan)

Scale 1 : 23

Luminaire Parts List

No. Pieces Designation


1 1 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 38
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

GENTS TOILET / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 1.500 1.500 3.600 0.0 0.0 0.0

Page 39
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

LADIES TOILET / Summary

Height of Room: 3.600 m, Mounting Height: 3.600 m, Light loss factor: 0.80 Values in Lux, Scale 1:39

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 165 102 206 0.617
Floor 10 115 89 132 0.774
Ceiling 50 30 18 40 0.607
Walls (4) 30 98 21 377 /

Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.672, Ceiling / Working Plane: 0.181.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 1 INSTA OMEGA 45W (2' x 2') Ceiling Light (1.000) 3761 3761 46.0
Total: 3761 Total: 3761 46.0

Specific connected load: 8.52 W/m = 5.18 W/m/100 lx (Ground area: 5.40 m)

Page 40
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

LADIES TOILET / Luminaires (layout plan)

Scale 1 : 21

Luminaire Parts List

No. Pieces Designation


1 1 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 41
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

LADIES TOILET / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.900 1.500 3.600 0.0 0.0 0.0

Page 42
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 1 / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: 0.80 Values in Lux, Scale 1:58

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 173 103 208 0.594
Floor 10 130 83 154 0.640
Ceiling 50 22 18 59 0.793
Walls (4) 30 81 16 646 /

Workplane:
Height: 0.760 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.523, Ceiling / Working Plane: 0.128.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 7 18W DL LX LED based Recessed Luminaire (1.000) 941 941 19.3
Total: 6585 Total: 6585 134.8

Specific connected load: 9.11 W/m = 5.26 W/m/100 lx (Ground area: 14.80 m)

Page 43
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 1 / Luminaires (layout plan)

Scale 1 : 58

Luminaire Parts List

No. Pieces Designation


1 7 18W DL LX LED based Recessed Luminaire

Page 44
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 1 / Luminaires (coordinates list)

18W DL LX LED based Recessed Luminaire


941 lm, 19.3 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.300 0.950 3.000 0.0 0.0 0.0
2 1.500 0.950 3.000 0.0 0.0 0.0
3 2.700 0.950 3.000 0.0 0.0 0.0
4 3.900 0.950 3.000 0.0 0.0 0.0
5 5.100 0.950 3.000 0.0 0.0 0.0
6 7.500 0.950 3.000 0.0 0.0 0.0
7 6.300 0.950 3.000 0.0 0.0 0.0

Page 45
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 1 / Photometric Results

Total Luminous Flux: 6585 lm


Total Load: 134.8 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m]
direct indirect total
Workplane 151 22 173 / /
Floor 110 20 130 10 4.15
Ceiling 0.90 21 22 50 3.53
Wall 1 56 20 76 30 7.26
Wall 2 71 19 90 30 8.60
Wall 3 63 19 82 30 7.82
Wall 4 69 19 87 30 8.35

Uniformity on the working plane


u0: 0.594 (1:2)
Emin / Emax: 0.495 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.523, Ceiling / Working Plane: 0.128.

Specific connected load: 9.11 W/m = 5.26 W/m/100 lx (Ground area: 14.80 m)

Page 46
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 2 / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: 0.80 Values in Lux, Scale 1:79

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 178 128 213 0.716
Floor 10 144 94 175 0.654
Ceiling 50 24 18 56 0.764
Walls (4) 30 88 19 379 /

Workplane:
Height: 0.760 m
Grid: 17 x 5 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.560, Ceiling / Working Plane: 0.136.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 8 18W DL LX LED based Recessed Luminaire (1.000) 941 941 19.3
Total: 7526 Total: 7526 154.0

Specific connected load: 8.35 W/m = 4.68 W/m/100 lx (Ground area: 18.45 m)

Page 47
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 2 / Luminaires (layout plan)

Scale 1 : 42

Luminaire Parts List

No. Pieces Designation


1 8 18W DL LX LED based Recessed Luminaire

Page 48
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 2 / Luminaires (coordinates list)

18W DL LX LED based Recessed Luminaire


941 lm, 19.3 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.600 5.700 3.000 0.0 0.0 0.0
2 0.600 3.900 3.000 0.0 0.0 0.0
3 2.400 5.700 3.000 0.0 0.0 0.0
4 2.400 3.900 3.000 0.0 0.0 0.0
5 0.600 2.100 3.000 0.0 0.0 0.0
6 2.400 2.100 3.000 0.0 0.0 0.0
7 0.600 0.600 3.000 0.0 0.0 0.0
8 2.400 0.600 3.000 0.0 0.0 0.0

Page 49
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 2 / Photometric Results

Total Luminous Flux: 7526 lm


Total Load: 154.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m]
direct indirect total
Workplane 156 22 178 / /
Floor 123 21 144 10 4.59
Ceiling 0.83 23 24 50 3.84
Wall 1 64 20 84 30 8.04
Wall 2 74 20 94 30 9.00
Wall 3 76 20 96 30 9.15
Wall 4 60 21 80 30 7.68

Uniformity on the working plane


u0: 0.716 (1:1)
Emin / Emax: 0.599 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.560, Ceiling / Working Plane: 0.136.

Specific connected load: 8.35 W/m = 4.68 W/m/100 lx (Ground area: 18.45 m)

Page 50
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 3 / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: 0.80 Values in Lux, Scale 1:65

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 164 115 207 0.698
Floor 10 140 87 172 0.625
Ceiling 50 20 15 51 0.742
Walls (4) 30 80 14 272 /

Workplane:
Height: 0.760 m
Grid: 5 x 5 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.553, Ceiling / Working Plane: 0.126.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 12 18W DL LX LED based Recessed Luminaire (1.000) 941 941 19.3
Total: 11288 Total: 11288 231.0

Specific connected load: 6.42 W/m = 3.91 W/m/100 lx (Ground area: 36.00 m)

Page 51
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 3 / Luminaires (layout plan)

Scale 1 : 52

Luminaire Parts List

No. Pieces Designation


1 12 18W DL LX LED based Recessed Luminaire

Page 52
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 3 / Luminaires (coordinates list)

18W DL LX LED based Recessed Luminaire


941 lm, 19.3 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.600 4.400 3.000 0.0 0.0 0.0
2 3.600 4.400 3.000 0.0 0.0 0.0
3 0.600 3.200 3.000 0.0 0.0 0.0
4 0.600 2.000 3.000 0.0 0.0 0.0
5 0.600 0.500 3.000 0.0 0.0 0.0
6 3.600 3.200 3.000 0.0 0.0 0.0
7 3.600 2.000 3.000 0.0 0.0 0.0
8 3.600 0.500 3.000 0.0 0.0 0.0
9 6.600 4.400 3.000 0.0 0.0 0.0
10 6.600 3.200 3.000 0.0 0.0 0.0
11 6.600 2.000 3.000 0.0 0.0 0.0
12 6.600 0.500 3.000 0.0 0.0 0.0

Page 53
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 3 / Photometric Results

Total Luminous Flux: 11288 lm


Total Load: 231.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m]
direct indirect total
Workplane 147 17 164 / /
Floor 122 18 140 10 4.44
Ceiling 0.65 20 20 50 3.25
Wall 1 53 17 70 30 6.67
Wall 2 82 17 99 30 9.45
Wall 3 58 18 76 30 7.25
Wall 4 66 17 83 30 7.90

Uniformity on the working plane


u0: 0.698 (1:1)
Emin / Emax: 0.555 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.553, Ceiling / Working Plane: 0.126.

Specific connected load: 6.42 W/m = 3.91 W/m/100 lx (Ground area: 36.00 m)

Page 54
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 4 / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: 0.80 Values in Lux, Scale 1:49

Surface [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 166 93 206 0.559
Floor 10 125 82 151 0.652
Ceiling 50 21 15 58 0.693
Walls (4) 30 77 15 651 /

Workplane:
Height: 0.760 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.511, Ceiling / Working Plane: 0.127.

Luminaire Parts List

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 6 18W DL LX LED based Recessed Luminaire (1.000) 941 941 19.3
Total: 5644 Total: 5644 115.5

Specific connected load: 8.49 W/m = 5.12 W/m/100 lx (Ground area: 13.60 m)

Page 55
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 4 / Luminaires (layout plan)

Scale 1 : 49

Luminaire Parts List

No. Pieces Designation


1 6 18W DL LX LED based Recessed Luminaire

Page 56
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 4 / Luminaires (coordinates list)

18W DL LX LED based Recessed Luminaire


941 lm, 19.3 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.300 1.100 3.000 0.0 0.0 0.0
2 1.500 1.100 3.000 0.0 0.0 0.0
3 2.700 1.100 3.000 0.0 0.0 0.0
4 3.900 1.100 3.000 0.0 0.0 0.0
5 5.100 1.100 3.000 0.0 0.0 0.0
6 6.300 1.100 3.000 0.0 0.0 0.0

Page 57
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

CORRIDOR 4 / Photometric Results

Total Luminous Flux: 5644 lm


Total Load: 115.5 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m]
direct indirect total
Workplane 145 21 166 / /
Floor 106 19 125 10 3.98
Ceiling 0.85 20 21 50 3.35
Wall 1 49 19 69 30 6.57
Wall 2 68 18 86 30 8.17
Wall 3 62 18 80 30 7.63
Wall 4 65 18 83 30 7.92

Uniformity on the working plane


u0: 0.559 (1:2)
Emin / Emax: 0.449 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.511, Ceiling / Working Plane: 0.127.

Specific connected load: 8.49 W/m = 5.12 W/m/100 lx (Ground area: 13.60 m)

Page 58
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STATCOM -2 / Luminaires (layout plan)

Scale 1 : 93

Luminaire Parts List

No. Pieces Designation


1 30 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 59
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STATCOM -2 / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 2.700 10.100 5.100 0.0 0.0 0.0
2 9.900 10.100 5.100 0.0 0.0 0.0
3 12.300 10.100 5.100 0.0 0.0 0.0
4 2.700 5.300 5.100 0.0 0.0 0.0
5 7.496 10.100 5.100 0.0 0.0 0.0
6 12.300 5.300 5.100 0.0 0.0 0.0
7 9.900 5.300 5.100 0.0 0.0 0.0
8 7.496 5.300 5.100 0.0 0.0 0.0
9 12.300 2.900 5.100 0.0 0.0 0.0
10 5.100 10.100 5.100 0.0 0.0 0.0
11 5.100 5.300 5.100 0.0 0.0 0.0
12 2.700 1.100 5.100 0.0 0.0 0.0
13 12.300 1.100 5.100 0.0 0.0 0.0
14 9.900 1.100 5.100 0.0 0.0 0.0
15 7.496 1.100 5.100 0.0 0.0 0.0
16 5.100 1.100 5.100 0.0 0.0 0.0
17 0.900 10.100 5.100 0.0 0.0 0.0
18 0.900 5.300 5.100 0.0 0.0 0.0
19 0.900 2.900 5.100 0.0 0.0 0.0
20 0.900 1.100 5.100 0.0 0.0 0.0
21 2.700 7.700 5.100 0.0 0.0 0.0
22 12.300 7.700 5.100 0.0 0.0 0.0
23 9.900 7.700 5.100 0.0 0.0 0.0
24 7.496 7.700 5.100 0.0 0.0 0.0
25 5.100 7.700 5.100 0.0 0.0 0.0
26 0.900 7.700 5.100 0.0 0.0 0.0
27 2.700 2.900 5.100 0.0 0.0 0.0
28 9.900 2.900 5.100 0.0 0.0 0.0

Page 60
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

STATCOM -2 / Luminaires (coordinates list)

No. Position [m] Rotation []


X Y Z X Y Z
29 7.496 2.900 5.100 0.0 0.0 0.0
30 5.100 2.900 5.100 0.0 0.0 0.0

Page 61
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

WATER COOLING ROOM 2 / Luminaires (layout plan)

Scale 1 : 51

Luminaire Parts List

No. Pieces Designation


1 12 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 62
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

WATER COOLING ROOM 2 / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 0.900 6.600 5.100 0.0 0.0 0.0
2 2.700 6.600 5.100 0.0 0.0 0.0
3 4.200 6.600 5.100 0.0 0.0 0.0
4 0.900 4.800 5.100 0.0 0.0 0.0
5 2.700 4.800 5.100 0.0 0.0 0.0
6 4.200 4.800 5.100 0.0 0.0 0.0
7 0.900 3.000 5.100 0.0 0.0 0.0
8 2.700 3.000 5.100 0.0 0.0 0.0
9 4.200 3.000 5.100 0.0 0.0 0.0
10 0.900 0.600 5.100 0.0 0.0 0.0
11 2.700 0.600 5.100 0.0 0.0 0.0
12 4.200 0.600 5.100 0.0 0.0 0.0

Page 63
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

AHU ROOM 2 / Luminaires (layout plan)

Scale 1 : 36

Luminaire Parts List

No. Pieces Designation


1 5 INSTA OMEGA 45W (2' x 2') Ceiling Light

Page 64
GWALIOR STATCOM BUILDING
03.05.2017

Operator
Telephone
Fax
e-Mail

AHU ROOM 2 / Luminaires (coordinates list)

INSTA OMEGA 45W (2' x 2') Ceiling Light


3761 lm, 46.0 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation []


X Y Z X Y Z
1 1.200 2.600 5.100 0.0 0.0 0.0
2 2.700 2.000 5.100 0.0 0.0 0.0
3 4.200 2.600 5.100 0.0 0.0 0.0
4 1.200 0.800 5.100 0.0 0.0 0.0
5 4.200 0.800 5.100 0.0 0.0 0.0

Page 65