TRANSMISSION CONNECTORS SECTION TA

DEADENDS
T1C BOLTED
QUADRANT STRAIN CLAMP
ALUMINUM
ALUMINUM

SD TA
For high tension transmission line construction with all
aluminum, ACSR or aluminum alloy conductor.

Material: Body and Keeper356-T6 aluminum alloy


Hardwaregalvanized steel
Sockets and Clevisesductile iron, galvanized
Cotter Pin#302 stainless steel

DIMENSIONS INCHES (MM)


CATALOG
NUMBER L W H C K PD
9-1/16 3/4 6-3/4 5-1/8 1-1/4 5/8
SD-57 (230.19) (19.05) (171.45) (130.18) (31.75) (15.88)
10-1/4 15/16 8-3/8 6-1/2 1-1/4 5/8
SD-70 (260.35) (23.81) (212.73) (165.10) (31.75) (15.88)
11-1/4 1-1/16 9-5/8 7-3/8 1-1/4 5/8
SD-86 (285.75) (26.99) (244.48) (187.33) (31.75) (15.88)
13-1/8 1-3/8 11-1/2 8-1/4 1-3/8 3/4
SD-112 (333.38) (34.93) (292.1) (209.6) (34.33) (19.05)
14 1-7/16 13-1/8 9-1/2 1-1/2 3/4
SD-130 (355.6) (36.51) (333.38) (241.3) (38.10) (19.05)
15-1/2 2 15-3/4 12-3/8 1-1/2 3/4
SD-155 (393.70) (50.8) (400.05) (314.32) (38.10) (19.05)
17 1-7/8 18 12-3/8 1-1/2 1
SD-185 (431.80) (47.63) (457.20) (314.32) (38.10) (25.40)

FITTING CLAMPING RANGE U-BOLTS


ULTIMATE
BODY SIZE APPROX.
CATALOG INCHES STRENGTH INCHES WT. EACH
NUMBER TYPE CAT. NO. ACSR ALUMINUM (MM) LBS. (KG) NO. (MM) LBS. (KG)
SD-57-N None -- #4-6/1 #4-7 Str. 3.2 (1.45)
.20-.64 1/2
SD-57-S Socket SA-04 To To (5.08-16.26) 15,000 (6,804) 3 (12.70) 4.4 (2.00)
SD-57-C Clevis CA-04 266.8-26/7 300-37 Str. 4.8 (2.63)
SD-70-N None -- #2-7/1 #1-7 Str. 4.7 (2.14)
.30-.75 1/2
SD-70-S Socket SA-06 To To 20,000 (9,072) 4 6.0 (2.72)
(7.62-19.05) (12.70)
SD-70-C Clevis CA-06 397.5-18/1 397.5-37 Str. 6.4 (2.90)
SD-86-N None -- #3/0-6/1 3/0-19 Str. 5.4 (2.45)
.46-.94 1/2
SD-86-S Socket SA-07 To To 25,000 (11,340) 4 6.8 (3.09)
(10.16-23.88) (12.70)
SD-86-C Clevis CA-06 556-26/7 650-61 Str. 7.1 (3.22)
SD-112-N None -- #3/0-6/1 40-19 Str. 30,000 (13,608) 8.4 (3.81)
.50-1.20 1/2
SD-112-S Socket SA-10-13 To To 30,000 (13,608) 5 9.9 (4.5)
(12.80-30.48) (12.70)
SD-112-C Clevis CA-10-13 954-54/7 1033.5-61 Str. 25,000 (11,340) 10.4 (4.73)
SD-130-N None -- 336.4-26/7 397.5-19 Str. 35,000 (15,876) 13.2 (6.00)
.70-1.39 5/8
SD-130-S Socket SA-10-13 To To 30,000 (13,608) 5 15.3 (6.95)
(17.78-35.30) (15.88)
SD-130-C Clevis CA-10-13 1272-54/19 1431-61 Str. 25,000 (11,340) 15.5 (7.04)
SD-155-N None -- 1,033.5 (36/1) 1,100-91 Str. 35,000 (15,876) 15.5 (7.00)
1.18-1.52 5/8
SD-155-S Socket SA-16-13 To To 30,000 (13,608) 5 17.3 (7.85)
(29.97-38.61) (15.88)
SD-155-C Clevis CA-16-13 1510.5 (54/19) 1,700-127 Str. 25,000 (11,340) 17.3 (7.85)
SD-185-N None -- 1,192.5 (45/7) 1,272-61 Str. 50,000 (22,680) 21.0 (9.53)
1.30-1.85 5/8
SD-185-S Socket SA-14-17 To To 30,000 (13,608) 5 22.7 (10.30)
(33.02-46.99) (15.88)
SD-185-C Clevis CA-15-17-033 2,156 (84/19) 2,500-127 Str. 30,000 (13,608) 22.3 (10.11)

NOTES: (1) Recommended torque on U-bolts; 1/2--480 in.-lbs., 5/8--720 in.-lbs.


(2) For corona free application, add suffix -CRF. Example, SD-130-N-CRF.
(This includes spherical or acorn type nuts or a combination of both.)
(3) Clamp may be furnished with bolt, nut and cotter pin by adding BNK suffix to catalog number.

TA-5
September 2001
Printed in USA
POWER SYSTEMS

STRAIN CLAMPS
RECOMMENDED APPLICATION CHART OF ANDERSON ALUMINUM CLAMPS FOR T-2 CONDUCTOR
CONDUCTOR DATA RECOMMENDED CLAMPS

DUAL
CONDUCTOR
OUTSIDE
DIMENSIONS
INCHES STRAIGHT LINE
LARGE STRAIGHT LINE DEAD-END, SPRING STRAIGHT LINE
T2 CONDUCTOR QUADRANT DOUBLE DEAD-END, LOADED, SIDE OPEN DEAD-END,
ULTIMATE DEAD-END GROOVE STRAIN CLAMP (STRAIGHT SPRING LOADED, SMALL LARGE
CONDUCTOR SIZE STRENGTH DOUBLE-GROOVE DEAD-END (WAVE SEAT CONTOURED SIDE OPEN QUADRANT QUADRANT
CODE WORD (QTY.) AWG LBS KEEPER (SEE NOTE 2) DESIGN) GROOVE) STRAIN CLAMP DEAD-END DEAD-END
T-2 IRIS (2) 2-7 STR. AAC. .292 x .584 2532 ADE-60 ADS-60 PG-70 SD-70

STRAIN AND SUSPENSION CLAMPS


T-2 SPARROW (2) 2-6/1 ACSR .316 x .632 5580 ADE-70 ADS-88 ADEZ-88 PG-70 SD-70
T-2 RAVEN (2) 1/0-6/1 ACSR .398 x .796 8560 SDT2-86 AR2-025 ADE-86 ADS-116 ADEZ-88 PG-86L SD-86
T-2 QUAIL (2) 2/0-6/1 ACSR .447 x .894 10,690 SDT2-86 AR2-025 ADE-98 ADS-130 ADEZ-116 PG-100L SD-86
T-2 PIGEON (2) 3/0-6/1 ACSR .502 x 1.004 13,350 SDT2-112 AR2-025 ADS-130 ADEZ-116 PG-100L SD-112
T-2 PENQUIN (2) 4/0-6/1 ACSR .562 x 1.126 16,840 SDT2-112 AR2-025 ADS-130-T2 ADEZ-116 PG-130 SD-112
T-2 PARTRIDGE (2) 266.8-26/7 ACSR .642 x 1.284 22,500 SDT2-185 AR2-050 ADE-155 ADS-130-T2 PG-130 SD-130
T-2 LINNET (2) 336.4-26/7 ACSR .721 x 1.442 28,100 SDT2-185 AR2-050 ADE-155 SD-155
T-2 CHICKADEE (2) 397.5-18/1 ACSR .743 x 1.486 20,080 SDT2-185 AR2-050 ADE-155 SD-185
T-2 IBIS (2) 397.5-26/7 ACSR .783 x 1.566 32,380 SDT2-185 AR2-050 ADE-155 SD-185
T-2 PELICAN (2) 477.0-18/1 ACSR .814 x 1.628 23,740 SDT2-185 AR2-100 SD-185
T-2 MISTLETOE (2) 556.5-37 STR.AAC .858 x 1.716 19,660 SDT2-185 AR2-100 SD-185 (1)
T-2 HAWK (2) 477.0-26/7 ACSR .858 x 1.716 38,860 SDT2-185 AR2-100 SD-185
T- 2 OSPREY (2) 556.5-18/1 ACSR .879 x 1.758 27,700 SDT2-185 AR2-100 SD-185
T-2 HEN (2) 447.0-30/7 ACSR .883 x 1.766 46,600 AR2-100
T-2 DOVE (2) 556.5-26/7 ACSR .927 x 1.854 44,800 AR2-100
T-2 GROSBEAK (2) 636.0-26/7 ACSR .990 x 1.980 50,000 AR2-100
T-2 TERN (2) 795.0-45/7 ACSR 1.063 x 2.126 45,800 AR2-100
T-2 RAIL (2) 954.0-45/7 ACSR 1.165 x 2.330 53,800 AR2-150
T-2 BLUEJAY (2) 1113.0-45/7 ACSR 1.259 x 2.518 61,800 AR2-150

(1) RECOMMENDATION BASED ON 556.5-18/1 TEST VALUES IN LIEU OF 556.5-37 STR. AAC.
(2) RECOMMENDATION FOR LOW TENSION APPLICATION. REFER TO CATALOG FOR CLAMP ULTIMATE STRENGTH RATING.