Documente Academic
Documente Profesional
Documente Cultură
1. General ..................................................................................................................................... 10
1.1. ...................................................................................................................... 10
introduction ...................................................................................................................... 10
1.2. .................................................................................................................. 13
key point........................................................................................................................... 13
1.3. .............................................................................................................. 13
safety instruction .............................................................................................................. 13
1.4. ...................................................................................................................... 15
Nameplate ........................................................................................................................ 15
1.5. .............................................................................................................. 16
Compression process ....................................................................................................... 16
1.6. ...................................................................................................................... 18
rotor .................................................................................................................................. 18
1.7. .......................................................................................................... 18
Built-in volume ratio ........................................................................................................ 18
1.8. .................................................................................................. 19
Vi control ......................................................................................................................... 19
1.8.1. Vi .................................................................................................. 19
Vi control method .................................................................................................... 19
1.8.2. Vi .............................................................................................. 20
Vi control range........................................................................................................ 20
1.8.3. Vi ...................................................................................................... 21
Vi options ................................................................................................................. 21
Relation schema between manual Vi control rotary turn number and its
corresponding Vi .............................................................................................................. 22
2. Cooling oil ............................................................................................................................... 25
2.1. .............................................................................................................. 25
Oil circuit ......................................................................................................................... 25
2.2. .............................................................................................................. 27
Oil flow rate ..................................................................................................................... 27
2.3. .................................................................................................................. 29
lubricants .......................................................................................................................... 29
2.3.1. Lubricants(suitable for R22) .................................................................................... 30
1
SRS
2
SRS
5.2.1. ....................................................................................... 66
Motor thermistor ...................................................................................................... 66
5.2.2. INT69 SNY ................................................................................................... 67
5.2.3. ................................................................................................... 71
Oil flow switch ......................................................................................................... 71
5.2.4. ....................................................................................................... 72
Pressure differential switch ...................................................................................... 72
5.2.5. ................................................................... 73
Oil channel on/off sensor(normally open swich) ..................................................... 73
5.2.6. ........................................................................................... 74
Capacity position sensor .......................................................................................... 74
5.3. .............................................................................................................. 76
Power supply .................................................................................................................... 76
5.4. .................................................................................................. 78
Selectionofelectricalcomponents .................................................................................. 78
5.5. .............................................................................................................. 78
Electricaldata ................................................................................................................... 78
i. ...................................................................................................... 78
Freon motor electricaldata ...................................................................................... 78
ii. ................................................................... 80
Parameters of NH3 compressor synchronous frequency motor .............................. 80
5.6. ...................................................................................................... 80
Electricthreadspecification ............................................................................................. 80
i. ...................................................................................... 80
freon compressor threaded specification ................................................................. 80
ii. ................................................................................... 81
NH3 compressor thread specification ...................................................................... 81
6. ................................................................................................. 83
Model designation & technical data ........................................................................................ 83
6.1. .............................................................................................................. 83
Modeldesignation ........................................................................................................... 83
6.2. .............................................................................................................. 84
Technicaldata................................................................................................................... 84
6.2.1. ................................................................................... 84
Freon compressor technical parameters ................................................................... 84
6.2.2. ................................................................................... 86
NH3 compressor technical parameters .................................................................... 86
4
SRS
7 ............................................................................................................................................. 88
Extentofdelivery ..................................................................................................................... 88
7.1 .................................................................................................. 91
7.1.1 ....................................................................................................... 93
8 ......................................................................................................... 94
Overalldimensionandpacking ................................................................................................ 94
8.1 .......................................................................................................... 94
(Overalldimensionaldrawing) ......................................................................................... 94
8.1.1 ........................................................................................... 95
(Freon-use overalldimensionaldrawing) ................................................................ 95
8.1.2 ......................................................................................... 100
(NH3-use overalldimensionaldrawing) ................................................................ 100
8.2 ................................................................................................ 105
Compressorfeetdimension ........................................................................................... 105
8.3 .................................................................................................................... 106
packing ........................................................................................................................... 106
9 ................................................................................................................... 109
Performancedata................................................................................................................... 109
10 ................................................................................................................... 110
Applicationrange ................................................................................................................... 110
10.1 R22 ........................................................... 110
TheapplicationrangewithR22refrigerant ................................................................... 110
10.2 R404A ....................................................... 111
TheapplicationrangewithR404Arefrigerant ................................................................ 111
10.3 R507 .......................................................... 111
TheapplicationrangewithR507refrigerant .................................................................. 111
10.4 R134a ....................................................... 112
TheapplicationrangewithR134Arefrigerant ............................................................... 112
10.5 R717 ......................................................... 112
TheapplicationrangewithR717refrigerant ................................................................. 112
11 ................................................................................................................... 113
Additionalcooling .................................................................................................................. 113
11.1 ........................................................................................................ 113
Lubricantcooling ............................................................................................................ 113
11.2 ................................................................................ 113
Operationconditionstobeconsideredfortheoilcooling ............................................ 113
5
SRS
6
SRS
7
SRS
8
SRS
9
SRS
1. General
1.1.
introduction
SRS
Adopting SRM latest i profile, its efficientbility and running stability are superior to
existing profiles, which greatly improve the refrigeration efficiency of compressor. The adopting
optimal gear ratio 5+7 contributes to a more stable discharge and more even stress of rotors,
ensuring long-term efficient operation for compressor.
10
SRS
3 Step-less adjustable Vi
The compressor is integrated with multi-protection devices, like oil flow switch, oil pressure
differential switch, to keep compressor run efficient and safely at long-term. Built-in 10m level
oil filter, the housing design pressure is up to 28 bars, safety. High-precision, high load-carrying
bearing is adopted with 60000 design lifetime.
11
SRS
1-A SRS
Figure 1-A SRS series compressors structure chart
(capacity control with slide valve)
12
SRS
(caution)
Please pay attention to the above safety and caution notices occurred in the manual. SRM
More compressor performance data at different conditions, please use SRM selection software
(please contact Snowman to get the latest revision)
Please carefully read details instruction and usage points of this manual before running the
compressor.
Compressors are equipped with motor protection device. When the protection device works, it
means there exists overload, disallowed operation conditions or situation of wrong phase
sequence.Electrical connections should be in accordance with the wiring diagram. T1 and T2
terminals shall not connect with power supply or control power.
labels description
Cooling oil level shall be not lower than min. oil level.
13
SRS
3) ; are banned!
Touch switch with wet hands
5) maintenance.
14
SRS
1.4. Nameplate
The compressors adopt 3-phase asynchronous motor with 2 poles (2960 rpm at 50Hz). In
order to reduce start-up current, the compressors generally take star-delta or part-winding start.
When compressors are equipped with PM synchronous frequency aluminium winding motor,
the connection is star start and controlled by inverter.
Part winding
15
SRS
The rotors are located in a horizontal housing provided with a suction port(motor side) and a
discharge port. The extremely small clearances between the rotors and the housing are dynamically
sealed by an oil film, which is directly injected on the rotor profiles. The compression takes place
by a volume reduction resulting from the rotary motion; between rotors and the housing several
compression chambers are generated that decrease their volume and move along the axis at the
same time.
Basically the process can be divided into three phases (the below description is related to a
single lobe of the male rotor and a single flute of the male rotor):
suction
When the male rotor lobe and female rotor flute begin to unmesh, the compression chamber is
open to the suction side and a gas flow is led through the suction port, due to rotary motion the
chamber increase its volume and more gas is led into the chamber until this is not any longer open
to the suction side.
16
SRS
Compression
With a further rotation the volume of the compression chamber is reduced and at the same
time it is moved along the axis toward the discharge port, increasing the pressure of the refrigerant
contained in the chamber.
discharge
At a point, which is fixed by the housing geometry, the discharge port is uncovered and
connected to compression chamber along the rotors further motion and the compressed gas is
discharged thanks to the further meshing of the lobe and flute. Since the tooth ratio of SRS series is
5/7(5 lobes on the male rotor-7 flutes on the female rotor), there will be 5 discharge process when
17
SRS
male rotor make every rotary, and the rotor speed is close to 3000r/min, thus there are
30005=15000 discharge process every minute, resulting in a very slow gas pulsation (a
reciprocating compressor running at 1500 r/min should have 10 pistons to reach the same result).
1.6. rotor
The rotors,as shown in Picture, feature a 5/7 symmetric screw rotor profile is the latest i
profile from SRM, which has been proven to be better than existing profile on efficientibility and
operational stability, greatly improving the refrigeration efficiency of compressors. Picture shows
the correct revolving direction, too.
18
SRS
The dimension and geometry of the discharge port determine the so-called built-in volume
ratioVi, defined as the ratio between the chamber volume at the beginning and the end of
compression phase(It is worth noting that the end of compression is not same as the end of
discharge,compression end stops earlier).this ratio, that is not dependent upon the operating
conditions, corresponds to an ideal pressure ratio performing the maximum compressor efficiency:
namely the gas leaving the discharge port has the same pressure of the discharge side. Otherwise, if
the discharge pressure is different from the pressure of the gas leaving the discharge port, an over
compression or under compression takes place.
Therefore, choose the optimum Vi to ensure less and minimum energy loss for applications.
1.8. Vi control
1.8.1. Vi
Vi control method SRS-14~SRS-16
19
SRS
All models of SRS-14~SRS-16 series compressors are with Vi control function. Vi control
methods can be divided into manual and automatic, as shown below:
Manual control -- move the Vi piston to control Vi by rotating manual Vi control rod.
Automatic control-- move the Vi piston to control Vi by through solenoid valve on/off control
the oil in/outthe Vi is the maximum when the valve turn off.the Vi is the minimum when the valve
turn on.
20
SRS
1.8.3. Vi options
When Vi is able to be controlled, the corresponding condition point shall consider to have the
corresponding Vi, the major factor influencing the Vi selection is the pressure ratio of
suction/discharge.
Vi
As shown before, there will be different adiabatic efficiency for different Vi at fixed pressure
ratio, so it should have a optimum Vi for every pressure ratio.
Whereby, pc for condensing pressure, pe for evaporating pressure, k for insulation coefficient,
chart 1-B shows the valve got below:
Refrigerant k
R507 1.138
R22 1.196
R134a 1.13
R404a 1.139
R717 1.31
21
SRS
1.8.4. Relation schema between manual Vi control rotary turn number and its corresponding Vi
22
SRS
23
SRS
24
SRS
2. Cooling oil
2.1.
Oil circuit
In the SRS series compressors the cooling oil fulfills the following purposes:
For SRS-10~SRS-12 series compressors, lubrication oil doesnt work with refrigeration
capacity control.
Figure2Ashowstheoilcircuitandrelatedcomponents:
25
SRS
The lubricant is stored in an external oil separator. The compressor discharge come into oil
26
SRS
separator and the separation between oil and gas mixture conducts at the top of oil separator. The
separated lubricants flow down and store at the bottom of oil separator, and then flow back to
compressor again.
The oil circulation results from the pressure difference between oil separator (discharge
pressure) and the injection points (slightly higher than suction pressure). From the oil separator the
oil flows in the oil cooler, and then through oil filter to compressor. The oil is filtered by the
built-in oil filter and delivered to the bearing chamber at suction side, the injection points on the
rotor profiles and discharge bearing chamber as well as oil cylinders controlled by Vi slide valve
and capacity slide valve.
The oil leaving the slide valve control valve cylinder, the suction bearing and discharge
bearing is led to the suction side of rotors and it is then compressed and discharged through the
rotors together with refrigerant gas, and flow back to the oil separator through discharge pipe
connected to compressor.
Under the specified evaporating temperature conditions, the circulating oil has to be cooled
down by an oil cooler; however, under certain conditions direct refrigerant injection can also be
used as an alternative(choose one from above options, and shall confirm with Snowman if choose
direct refrigerant injection).
Since the oil circulation is generated by a pressure difference, the oil flow rate depends on the
pressure difference between discharge and suction; the calculation shall conform to below
equation:
V oil K Pd Ps
27
SRS
Where:
(Freon use)
SRS 08S 08M 08L 10S 10L 12S 12M 12L
SRS series
with Freon
K 9.1
SRS 14S 14M 14L 16S 16M 16L
SRS series
with Freon
K 10.7
(NH3 use)
SRS
The minimum oil flow rate to fulfill all purposes (lubrication, sealing, cooling, slide valve
control and Vi control) is ensured when the compressor operates with the fixed application range
and the oil filter is kept clean as well as all performance data of oil are with specification.
During the starting phase, there is no oil circulation due to pressure is always balanced in
compressor; therefore, bearings and rotors are designed to bear some seconds of dry operation
before necessary pressure difference is reached.
Caution!
Within 20 seconds after start the compressor must operate inside the
application range(minimum pressure difference)
In case of air-cooled condenser and low ambient conditions, generally the minimum pressure
difference is difficult to reach; it may need to take some special measures, like:
Set a pressure regulating valve between compressor and condenser, and must keep
compressor operate at minimum power running conditions (about 5 seconds).
2.3. lubricants
29
SRS
Caution!
All lubricants are hygroscopic and must not contact with air for long time.
It is forbidden to mixed use different type of lubricating oil, in order to avoid the
risk of the unknown.
30
SRS
1cSt 10 6 m 2 / s 1mm 2 / s
31
SRS
oil injection
Refrigerant Oil grade T cond. T evap. T disc.
temp.
R22 C100 4555 -50t0+5 Max.90
2.4.1. The standard scope of supply for oil separator (only for reference)
Oil heater
32
SRS
note
Nominal size is default for connection when order. Please contact Snowman for any other size
request.
PED EU 97/23-CE/
33
SRS
34
SRS
35
SRS
As illustrated in figure 2-C, the compressor is provided with a built-in replaceable high
efficiency oil filter. The oil filter is quite easy to disassemble (where SRS-08~SRS-10 series
compressors are not provided with oil filter. Instead external oil management kits can be option,
which includes oil flow protection, external oil filter etc.). More information please refer to
Chapter 8 8-overall dimension and packing
SRS-08~SRS-10
Oil filter shall be particularly clean to assure the correct oil feed to compressor. The cleanness
of the filter is determined by measuring the pressure difference on normal working condition,
pressure difference shall be less than 2 bars; when pressure difference exceeds 2 bars, the pressure
difference switch will alarm and stop the compressor. SRS-08~SRS-10 series compressor are not
provided with pressure difference switch and oil pressure measure points, the oil filter must be
provided on the piping of system.
If the refrigeration systems are not cleaned carefu lly, it may make dirt in filter soon in the
operation. Snowman recommends to order more oil filter for spare when order compressor.
Recommendation:
36
SRS
The SRS-12~SRS-16 compressor is equipped with oil sight glass to monitor oil level.
Through oil sight glass it can monitor the amount of refrigerants in lubricants. Without liquid
injection oil cooling, the bubble exists for long term means the attenuation of refrigerant in the oil.
The lubrication can be indirectly monitored by checking the discharge temperature: lack of
lubrication leads to an increase of that valve. SRS series compressors are provided with
temperature sensor (temperature signal can be inputted into electronic protection module
INT69SNY), installation position as shown in photo 2-B, to monitor the discharge temperature of
discharge temperature. When temperature goes to 140Cthe electronic protection module
switches off compressor through control circuit.
37
SRS
(Caution)
Oil cooling can not indirectly inspect compressor lubrication condition through
discharge temperature.
The correct circulation of oil is guaranteed by the fact that both the filter is clean and the
compressor operates in the admissible envelop of operation (see chapter 10-application range).
The oil level can be monitored by means of sight glass (installed on the position shown on
Figure 2-C)
For SRS-12~SRS-16 compressor, the oil flow switch(see chapter 5-electrical devices) can be
chosen as standard to monitor the oil flow of compressor( installed on the position shown on
Figure 2-C).
(Attention)
The most reliable protection method is to monitor the oil flow rate. If compressor
38
SRS
is not provided with oil flow monitor, it shall use oil pressure difference and
discharge pressure difference at the same time to monitor. Cannot start the
compressor without any monitor, otherwise it will damage the reliability of
compressor.
Oil flow switch has higher safety coefficient and sensitivity. It needs to prevent
the malfunction of oil flow switch in compressor electric control.
39
SRS
3. Capacity control
SRS series screw compressors permit to work at both full and partial load conditions.
SRS-08~SRS-12 series compressors are three steps capacity control, while SRS-14~SRS-16 series
are four steps and step-less control are available.
Provided with 2 pieces of solenoid valves and 3 steps capacity control (50-75-100%).
Refer to figure 3-A, 2 pieces of solenoid valves are corresponding to (20) and (21), each
control one piston, making it possible for compressor to run at 50%, 75% and 100% loads.
Figure 3-A: working principle of SRS-08~SRS-12S/M/L series compressor capacity control device
50% capacity
40
SRS
With reference to figure 3-B, both solenoid valves (20) (21) are power on. The piston
chamber connects with suction side, since the pressure of rotors chamber is higher (between HP at
discharge and LP at suction). As a result, the piston moves away from rotors and the by-pass
channel is open, 50% refrigerants are by-passed to suction side(as shown with arrow on picture),
the compressor starts to operate at 50% capacity.
75% capacity
With reference to figure 3-C, the solenoid valve (20) is power on. The opening of one by-pass
channel opened by upper piston makes 25% refrigerant flow back to suction side; the solenoid
valves (21) is power off, the below piston closes the another by-pass channel(as shown with arrow
on picture). Meantime, only 25% refrigerants flow back to suction side and 75% enter system,
leading compressor operates at 75% capacity.
41
SRS
100% capacity
With reference to figure 3-D, both solenoid valves (20) (21) are power off. Both 2 piston
chambers are connected with discharge side. Due to the pressure of discharge side is higher than
the medium pressure of rotor compressor chambers. Both pistons move towards rotors and the
by-pass channel is closed, all refrigerants compressed by rotors are discharged to discharge port,
the compressor starts to operate at 100% capacity.
42
SRS
The flowing of refrigerants can be controlled by the solenoid valves (20)(21) mounted on the
top of compressor housing. Figure 3-A shows the control logic of solenoid valve under step
control.
SRS-08S/M/L SRS-10S/L
SRS-12S/M/L
Figure 3-E: solenoid valves position on the SRS-08~SRS-12 series compressors with capacity
control
43
SRS
The cylindrical chamber of fixed screw rotor housing is provided on the bottom with a
longitudinal port whose opening is connected with suction side. The opening is regulated by a slide
valve for whether open towards suction side and the how large it opens (see picture 3-F). When the
port is is completely closed, the effective compression length is maximum, namely the whole rotor
length; when, on the other hand, the valve moves towards the discharge and the opening expands
longitudinally, the effective working length of the rotors is reduced and as a consequence a smaller
quantity of gas is processed. As a result, adjusting the volume taken in by the rotors make it
possible to control the mass flow processed and definitely the cooling capacity generated by the
compressor.
The slide valve is controlled by a hydraulic cylinder activated by the oil pressure and air
44
SRS
pressure together, the oil control circuit for the capacity control is characterized by
normally-closed solenoid valves: 14, 15 and 16, 17(see picture 3-F: solenoid valve 14/15/16/17).
The working principle of slide valve controlling capacity is to reduce suction volume. By
means of different combinations, it can be 4-step capacity control. The compressors are provided
with hydraulic capacity control device. According to solenoid valve unloading logic (power on
of solenoid valve = partial load operation), and each solenoid valve controls one capacity.
Snowman proposes that 25% capacity control should be only applied to st
period of compressor. Under any conditions, the compressor shall be started from minimum
capacity: it will always reduce the starting torque to minimum.
The slide valve is control by its connecting hydraulic piston. The piston can control slide
valve to stay at any one of four points from 100-75-50-25% (note: the actual refrigeration capacity
may be a little different from rated valve, which depends on the running conditions, and also differ
from compressor models).
45
SRS
25% capacity (only suitable for start-up and shut down period)
Refer to figure 3-G, solenoid valve (14) and (15) are power on, (16) and (17) are not power
on.
50% capacity
With reference to 3-H, solenoid valve (14) and (16) are power on, (15) and (17) are not.
46
SRS
75% capacity
With reference to figure 3-I, solenoid valve (14) and (17) are power on, (15) and (16) are not.
47
SRS
100% capacity
With reference to figure 3-J, solenoid valve (14)is power on, (15) (16) (17)are not.
The loading and unloading of oil inside oil cylinder is controlled by the 4 normally closed
solenoid valves mounted on the top of compressor housing(as figure 3-F), table 3-B shows the
control logic of solenoid valve for step control.
48
SRS
On Off On Off
25%
On Off Off Off
Infinite capacity control is recommended whenever the cooling capacity of the system has to
be controlled with a high degree of precision, while it is not very useful in systems featuring high
inertia, where step capacity control is more suitable.
With reference to picture 3-F, the step-less configuration is performed through the solenoid
valve (14) as oil supply loading function to load compressor. Any one of the solenoid valves (15) ,
(16), (17) can be used to discharge oil from oil cylinder to unload compressor, thus the minimum
refrigeration capacity compressor can achieve is 25%, 50% and 75% separately.
When the compressor runs under step-less control mode, the on/off of solenoid valve shall
follow the control logic requirements from table 3-C, 3-D and 3-E.
49
SRS
50
SRS
10075% (steplesscontrol)
51
SRS
The capacity delivered by the compressor is controlled by using a control device that, in
response to a variation in the load required by the system (figure 3-K), output the loading or
unloading pulse signal to control solenoid valve. As regards the control device input signal, the
chosen parameter should be sensitive to the variation in the load required by the system. For
instance the suction pressure or air/water temperature etc.
The solenoid valve energized must be controlled by temperately impulse signal (T1=0.5 1S).
Generally, the energize time for solenoid valve (14) shall be a little bit shorter than (15) or (16) or
(17).
The time interval between two impulses (T0) must be optimize the control, according to the
inertia of system. It shall be longer for time interval T0 with large inertia system.
For system with quite high thermal inertia, it needs to carry out more tests to finds the
continous period of impulse energize and the optimal settings of impulse time interval for solenoid
valve.
Caution:
1) 50%
Strongly recommend to carry out careful and widely tests with a capacity below
50%. Should avoid compressor continous running with a capacity below 50% and
also avoid following points:
Motor superheating caused by low power under low load (especially power supply
voltage exceeds rated voltage).
52
SRS
2) Since the motor cooling can not be guaranteed with a capacity of 25%, the
minimum capacity step only can be used for start-up and shut down.
Suggestion:
Not to operate with a capacity below 50% for longer than around 5 minutes, so as
to avoid excessive overheating of motor.
Not to switch directly from full load to minimum load condition, but rather to
remain for a minimum time of 3 minutes at 50%. Otherwise liquid may enter the
compressor cause liquid hammer.
Check and if necessary adjust the control parameters when the avariation in the
compressor load is not in line with compressor capacity control.
To limit the peak current when starting, the electric motors are started in the part-winding
configuration, or alternatively with the windings connected in the star configuration. This, however,
means also a drop in the starting torque, and as a result the resisting torque needs to be reduced in
order to start the compressor without excessively overloading the electric motor. For this purpose,
Snowman recommends to start the compressors at the minimum capacity step.
So as to stop and start the compressor at the minimum capacity step for around at least 25
seconds.
The starting and stopping procedure indicated in picture 3-L has to be followed for all the
screw compressors, both in the step and in the stepless version, as this avoids the temporary
53
SRS
reverse rotation caused by large refrigerant return flow at shut down period.
By working at part load, the discharge temperature increased caused by motor overheating (it
is mandatory not to exceed specified range), and the efficiency is slightly lower than full load.
54
SRS
4. Components
SRS series compressors are fitted with a suction filter that can be inspected and cleaned by
simply dismantling the suction shut-off valve (Picture 4-A). The filtration precision of suction
filters is 70 microns.
SRS series compressors, excluding SRS-08~SRS-10, are all provided with oil filter and can
be checked and cleaned by disassembling the head of oil filter (figure 4-B). The filtration precision
of oil filter is 10um.
55
SRS
The SRS series compressors are fitted with a safety valve that when necessary opens a
passageway from the high to low pressure sections. The valve is sized in accordance with the
European standard EN 60335-2-34. The safety valve opens when the pressure differential reaches
30 bars, and closes again automatically.
56
SRS
To avoid the backflow of the refrigerant gas from condenser when the compressor stops,
make rotors reversal rotation to balance pressure. The compressor is fitted with a check valve
installed immediately upstream of the discharge shut-off valve, see picture 4-D.
Attention
When the compressor stops, following the balancing of the pressure, there is a
temporary reverse rotation of the rotors, which produces a typical noise. If this noise
lasts more than 3 seconds, check and if necessary replace the check valve.
Picture 4-E below shows the assembly method of the rubber vibration dampers.
The exact tightness of the self-locking bolt is achieved when the deformedvibration damper
57
SRS
bushing is around 0.5 mm less than its size when relaxed. The integration of rubber vibration
dampers and components please refer to below description, the correct assembly method as shown
on figure 4-F.
58
SRS
59
SRS
The SRSL series compressors, excluding SRS-08~SRS-10, are fitted with one built-in oil
shut-off valve (shown as figure 4-G) and oil on/off sensor. The oil shut-off valve opens and the
filtered oil are supplied to all parts of compressor when compressor runs at stable conditions;
during the shut down period, the shut-off valve is closed to avoid extra oil flow into internal
compressor. Note: the oil shut-off valve should be used together with oil on/off sensor, please refer
to the Chapter 5- electric device for description of oil on/off sensor.
Attention:
It is not recommend using pump for oil supply when compressor operates
normally. If oil pump must be used, please consult to Snowman.
5. Electric device
Freon motor usually adopts part winding or star -delta start for the purpose of reducing starting
60
SRS
current. The electric motors provided for SRS-08~SRS-10 series compressor are standard
three-phase asynchronous two-pole motors (2960 rpm at 50 Hz) part-winding (PW)The electric
motors provided for SRS-12~SRS-16 series compressor are standard three-phase asynchronous
two-pole motors (2960 rpm at 50 Hz) star/delta (Y/) version, applicable power supply is 400V/
three-phase/50Hz or 460V/ three-phase/60Hz. If request special voltage or non-standard starting
method, please contact with Snowman.
The stator of motor is fixed on compressor housing with screw and key. So it is not necessary
to use special tool to replace motor. The design and test of motor conform to European standard
EN603335-2-34.
The running current and input power for different working conditions ca n be calculated by
selection software. The main electric parameters (like maximum start current L.R.A and the
maximum working current F.R.A) also can refer to the following technical specification.
Depending on the compressor model there are two different types of PW motors which differ
from each other for the connection of the three phases: star or delta type. In any case at the
compressor starting only a part of the windings is powered, while in normal operation all are
powered.
As regards the mains connections, there is no difference between the two PW motor
configurations. Pictures 5-A and 5-B below show the internal connections of the phases, depending
on the configuration of the electrical motor.
61
SRS
PART-WINDING CONFIGURATION
Caution
62
SRS
Picture 0-A: internal winding connections for the motors with part-winding configuration;
STAR-DELTA CONFIGURATION
Caution
With reference to picture 5-A, measuring the electrical resistance between
terminals 1-2-3 and 7-8-9, the star-delta version has the following values: continuity
between terminals 1 and 8, 3 and 7, 2 and 9, and insulation between terminals 1 and
2/3/7/9, 2 and 1/3/7/8, 3 and 1/2/8/9, 7 and 1/2/8/9, 8 and 2/3/7/9, 9 and 1/3/7/8.
Picture 5- B: internal winding connections for the motors with star-delta configuration;
63
SRS
By starting the electrical motor either in part -winding configuration or with the windings in
star connection for the electrical motor in star-delta configuration there is a reduction in the
starting current LRA and starting torque. To achieve a reduction in the resisting torque and
consequently start the motor without overloading it, the compressor needs to be started at the
minimum capacity step.
caution
Then with the screw compressors no by-pass system between the high and low
pressure is required for reducing the resisting torque on starting.
Pictures 5-C and 5-D show how does the electrical motor connect to th e three-phase line for
both the star-delta configuration and the part-winding one. It also gives the time sequence for the
contactors. The compressor therefore starts as follows:
In the PW motors, the delay in closing the run contactor K2 from when the starting contactor
K1 closes must be 1 second maximum (recommended value 0.6 sec).
In the star-delta configurati on, on the other hand, the starting duration in star configuration
(closing of contactors K1 and K3) must not exceed 1.5 sec (recommended value 0.8/1 sec); while
when switching to delta configuration (closing of contactors K1 and K2), contactor K2 must be
closed with a delay of 35-50 msec from the instant when contactor K3 is opened, see picture 5-C
again.
64
SRS
Picture 5- C: connection diagrams to the three-phase network in the two compressor starting
Remarks:
65
SRS
NH3 compressors usually adopt PM synchronous frequency aluminium motor with star
starting, and controlled by inverter. The electric motors provided for SRS-08~SRS-16 series
compressor are standard three-phase synchronous six-pole motors (3000 rpm at 150 Hz, 3600 rpm
at 180 Hz) , please refer to chapter 5.52 for motor control parameters.
To protect the motor against high temperatures six PTC thermistors connected in series are
inserted in the motor windings. Three thermistors are positioned on the intake side of the motor
(suction side) and have an activation temperature of 100C, while the other three are positioned on
the opposite side of the motor (discharge side) and have an activation temperature of 130C.
The resistance of the chain of thermistors when cold (temperature less than 40C) must be
less than 1800 Ohm; but even if just one of the thermistors reaches the critical temperature, the
resistance of the chain will increase exponentially, with the consequent activation of the INT 69
VS electronic module (INT 69 RCY as an option), which cut off the power supply to the motor.
The resistance can be measured between terminals T1 and T2 on the terminal block.
66
SRS
caution
When measuring the resistance of the thermistors chain, never apply a voltage
higher than 3V.
This electronic protection module INT69SNY is supplied as standard with the compressor. It
carries out the following functions:
67
SRS
AC 50/60Hz 115-240V-15...+10%
Dynamic
3VA automatic lock
reset
Power (delay)
supply 5min1min
AC 50/60Hz 24V-15...+10% 3VA Default
10/24h automatic
phase
lock
-30...+70 LED Please
Ambient LED code refer to below table for flash
temperature code
Max.AC 240Vmax.2.5AC300
PTC DIN 44081/082 NOC
Test loop
Output capacity
1-9 -AgNi 90/10 Min.>24V AC/DC>20mA
Nr. Of sensors
- R 25total <1.8k
Lifetime About 1 million times
6.3mm
- R reset 2.75k20% Connection
6.3mm connect to flat terminal
terminal
- <30m PA66/PA6
68
SRS
Max.Lengt Housing
h material
PTC
PTC short
<30
circuit Fixed type Flat fixed
monitor
system
3 AC 50/60Hz 200-690V 10% Size [mm] 76.581.535LWH
Phase-sequ
ence t0+1s......t0+6s Weight 200g
monitoring
EN 61000-6-2
Automatic lock
Phase fault
EN 61000-6-3
Frequency Not suitable
converters
<3/30s Standard EN 61010-1
Switching
frequency
oversteppin
g
The flash code combine recycle red light and orange light flash, and the current status decide
the number of impulse.
69
SRS
PTC 2.75k Can manually restart motor during this process Recycle of 1 red and 3
Time delay after Cut off the power supply due to over orange
motor overheat heat of motor, and PTC lower than
2.75k
PTC PTC PTC PTC 14
PTC short circuit or Cut off power PTC return normal Recycle of 1 red and4
circuit break PTC short circuit failure, PTC switch supply of motor orange
off or not good connetion with
module
phase sequence failure The sequence failure of motor power Cut off power Correct phase sequence Recycle of 2 red and 1
supply L1L2L3 supply of motor The motor was locked, must be manually reset (after orange
adjust the correct phase sequence, power on the
module again 5 seconds after power off)
L1L2L3
Lack of phase or phase Cut off power Phase sequence return 5min1min Recycle of 2red and
imbalance Motor power supply L1, L2, L3least one supply of motor normal 2orange
phase lost,or three phase voltage appear the first - ninth phase fault occur within 24 hours, the
bigger difference module will restart automatically after 5min1min.
70
SRS
the first - ninth phase fault occur within Phase sequence return Can manually restart motor during this process Recycle of 2 red and 4
24 hours normal orange
LN
Too low power supply L, N voltage is lower than normal module Voltage return to normal Recycle of 3 red and 1
of scope orange
Generally, the motor protection module is installed inside the terminal box of compressor.
However, for the below situations the module can also be installed in the mian control box which
is far away from compressor, but you need to note below:
Carefully check the connection cable to motor terminal with phase sequence.
L1 connects to T1; L2 connects to T2; L3 connects to T3; thus it can detect the rotation
direction of rotors.
The connection from module to PTC sensor should use separate shield cable or twist pair to
prevent magnetic field induction.
The oil flow switch mounted on compressor housing, excluding SRS-08~SRS-10, to take
real-time monitoring of correct circulation of oil lubrication, see figure 5-G. the output signal of oil
flow switch is monitored by unit electric control.
71
SRS
temperature O-ring
Max. 10 W IP 67
Power IP grade
K04PU-02SG 2m
Electrical Cable parameter 2m straight Connector of M12*1
cable type 4-pin
The pressure differential switch is mounted on the bearing box of compressor or housing
except SRS-08~SRS-10, to real-time monitor the pressure difference before and after the oil filter.
Through the pressure drop of oil filter we can detect its block situation. When the pressure drop
exceeds 2 bars, the switch will alarm and start compressor protection, see figure 5-H.
Type DG041-31
Sealing material NBR
72
SRS
Pressurelimit Operatingvoltage
Figure5H:thediagramofpressuredifferenceswitch
The pressure differential switch is mounted on the bearing box of compressor or housing
except SRS-08~SRS-10, to real-time monitor the on/off of the oil channel on/off senso. When the
oil shut-off valve closes during compressor stop, the contact switch indicates light on; when the oil
shut-off valve opens during compressor starts, the contact switch indicates light off, see figure 5-I.
Specification:
40 bar Max. 150
Working
Pressure limit
temperature
Power Max. 10 W Voltage Max. 100 V AC/DC
Current Max. 0.5 A AC/DC Capacitance Max. 0.3 pF
Min. 1000 M
Insulation
IP grade IP 68
resistance
73
SRS
SRS-16 series compressors can be provided with capacity position sensors, which can be anti-
electronic interference, please see table 5-B for specification. Please see figure 5-J for outer
appearance and component name of capacity position sensor and figure 5-K for assembly.
-20 70 116 mA
Operation temperature Max. current
range
950 mW 50 nF
Max. power Max. capacitance
1 mH IP 65
Max. inductance IP Grade
Operation
T5
temperature code
Table5B:parametersofpositionsensor
74
SRS
1. Thermal insulating
IP65);
disc; 2. Plug ( 3. cable gland;
4. Aluminum nameplate 5. Stainless steel pipe sensor; 6. PTFE slidingring; 7. Aluminum pipe
Figure 5-J: outer appearance and component name of capacity position sensor
Snowman will calibrate the position sensor before factory delivery and mount capacity
positionsensorontheoilcylinder.Chargegasintooilcylindertomake,makemovementofpiston
tocalibratepositionsensor.Calibrationmethodcanbedescribedasbelow:
Powersupplyvoltage:1228V
Beforecalibration,atleastsupplypowerfor5minutes.
Presscalibrationswitchfor5secondstomakesensorentercalibrationmode.Redindicator
75
SRS
changesfromnormalflashintopoweron,allbuttonsasshownonbelowfigure5L:
Moveslidevalveto0%position.Andthenpresscalibrationbutton,theredindicatorwilllight
forsomeseconds.Whenredlightstartstoflash,itindicatesfinishthecalibrationofequipon0%
position.
Move slide valve to 100% position and push the calibration button for twice. The red
indicatorwillflashquickly,thencalibrationcompletes.
After calibration, the capacity position sensor will have the normal signal output. For the
movingpartaluminumpipe,thesignalbecomessmallwhenitmovesinoppositedirection,the
outputcurrentis420mA.
Figure5L:indicationdiagramofcalibrationbutton
Caution
For the direction of rotation of the rotors see chapter 1-General. If the
motor turns in the opposite direction the compressor can be seriously damaged.
powersupplyrequirement
400V-3 -50Hz/460V-3 -60Hz
76
SRS
Freon motorpowersupplyforstandardversion(partwindingandstardelta):
400V3phases50Hz/460V3phases60Hz (otherpowersupplyonrequest);
NH3 motor power supply for standard version (star): the client supplies the inverter, the
controller
wire voltage
is more
than
400V.
Permissiblevoltagerange:10%ofratedvoltage;
PermissiblevoltageunbalancebetweenL1L2L3:2%;
Maximumvoltagedropduringthestartingphase:10%ofratedvoltage;
Permissiblecurrentunbalance:5%RSTthreephaseunbalancecurrent,12%6pcs
123789unbalancecurrent
Calculationofcurrentunbalance:
Asfollow:
I R I1 I 7 I S I 2 I8 IT I 3 I 9
I R I S IT
IM
3
MAX I R , I S , I T I M
SB3% 100
IM
77
SRS
SB3% 5%
SB6% 12%
5.4. Selectionofelectricalcomponents
The various
electrical
components:
cables,
fuses
and contactor
etc.
mustbesizedconsidering
themaximumcurrentthatcanbeabsorbedbytheelectricalmotorduringnormaloperation,i.e.
theFLA.
in Part Winding configuration the contacts on the motor contactors must be sized for a
currentequaltoatleast65%ofthemaximumoperatingcurrent(FLA).
Ontheotherhand,forthestardeltaconfigurationthedeltaandcontactorsmustbesizedfor
acurrentequaltoatleast75%oftheFLA.Starmustbesizedforacurrentequaltoatleast40%of
theFLA.
5.5. Electricaldata
50Hz
HP/kW 25/18.5 30/22 35/26 40/30 50/37 60/45 70/52 75/55
Nominalmotorpower
PW Y/
Standardmotortype
78
SRS
SRS
14S 14M 14L 16S 16M 16L
CompressormodelSRS
50Hz
HP/kW 90/66 100/75 110/82 125/90 140/105 150/112
Nominalmotorpower
400V/3/50Hz460V/3/60Hz 10%
Powersupply 400V/3/50Hz or 460V/3/60Hz, voltagevary10%
Y/
Standardmotortype
Note:LRAstartcurrent;FLAMax.runningcurrent;noconfiguration
79
SRS
5.6. Electricthreadspecification
M825 M1016
Terminalscrewspec.
M635 M1060
Earthstudspec.
Terminalspec.And -- 7SC50-10
quantity
80
SRS
M1016 M1220
Terminalscrewspec.
M1060 M1060
Earthstudspec.
6SC120-12
7SC50-10
Terminalspec.Andquantity +SC120-10
M12 M16
Terminalscrewspec.
M6 M10
Earthstudspec.
1SC50-10
Terminalspec.And 3RNB14-12
+3SC120-16
quantity
81
SRS
SRS
14S 14M 14L 16S 16M 16L
CompressormodelSRS
M16 M16
Terminalscrewspec.
M10 M10
Earthstudspec.
1SC50-10 1SC50-10
Terminalspec.Andquantity +3SC120-16 +3SC120-16
Note:
1SC5010incolumnofTerminalspec.andquantitymeans:terminalquantityis1pcs;
2
SC50isthespecificationofterminal,namelythesectionareaofconnectingwireis50 mm
10showsthenominalsizeofterminalthreadhole;
2
RNB14-12: section area of terminal is 14 mm ;12isthenominalspecificationofterminalthreadhole
82
SRS
6.1. Modeldesignation
1SRS-14LMAL = snowman rotor Semi-hermetic
2SRS-14LMAL = 140mm (rotor diameter is about 140mm)
(model)08/10/12/14/16
3SRS-14LMAL
L (long)
M (middle)
S (short)
4SRS-14LMAL
Aautomatic SRS-14~SRS-16
Automatic control (applicable to SRS-14~SRS-16 )
Mmanual SRS-14~SRS-16
Manual control (applicable to SRS-14~SRS-16 )
H high Vi SRS-08~SRS-12
Fixed high Vi (applicable to SRS-08~SRS-12), may be omitted.
5SRS-14LMAL
A (refrigerant):R717
F R404AR407cR507AR410R22
Common used for Freon applicable to R404AR407cR507AR410R22
6SRS-14LMAL
L=220V AC50/60Hz (electrical attachment)
M=110V AC50/60Hz (electrical attachment)
Y=24V AC50/60Hz (electrical attachment)
U= UL 220V AC50/60Hz
220V AC50/60Hz electrical attachment has been verified by UL
83
SRS
6.2. Technicaldata
Nominal HP/kW 25/18.5 30/22 35/26 40/30 50/37 60/45 70/52 75/55
motorpower
3
Displacement m /h 85/102 100/120 120/144 140/168 168/202 210/252 230/276 250/300
at50/60Hz
weight kg 190 200 210 245 250 365 370 375
mm 42 42 42 42 42 54 54 54
Discharge line,
inch 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8
internal
mm 54 54 54 54 54 80 80 80
Suctionlineinternal
inch 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 3-1/8 3-1/8 3-1/8
mm/inch 3/8SAE 22/M261.5
channelconnection
Capacitycontrol step)100%-75%-50%
Protectionmodule INT69SNY
400V/3/50Hz 460V/3/60Hz
Standardmotor 1
PW
PW/DOL
A 140/215 175/271 200/308 277/398 303/406 262/422 280/459 351/580
PW(2)Start current
PW/DOL
-
Y/DOL
A 71/215 90/271 103/308 133/398 135/406 139/422 159/459 193/580
Stardelta 2
StartcurrentY/DOL
84
SRS
mm 67 67 67 80 80 80
Discharge line,
inch 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-1/8
internal
Oil
mm 22/M261.5
channelconnection
(step)100%75%50%25% (stepless)10025%
Capacitycontrol
canprovideasrequest
Protectionmodule INT69SNY
400V/3/50Hz 460V/3/60Hz
Standardmotor 1
PW/DOL
PW(2) A 462/693 462/693 635/953 584/876 770/1155 770/1155
Startcurrent
PW/DOL
Y/DOL
A 224/693 224/693 318/953 276/876 354/1155 354/1155
Stardelta 2
StartcurrentY/DOL
85
SRS
Note:
10%
Allowancevoltagedeviationrange10%
Rated motor kW 22 27 33 45 45 54 62 72
power
Rated line V 379 378 395 374 374 348 335 307
voltage
Non-loaded
line counter V 330 324 328 310 310 287 274 251
electromotive
force
Dischargeline, mm 42 42 42 42 42 57 57 57
internal
Suctionlineinternal mm 57 57 57 57 57 76 76 76
mm 22/M261.5
Oilchannel 10 (ferrule-type)
86
SRS
connection
Capacitycontrol
Protectionmodule INT69SNY
SRS
14S 14M 14L 16S 16M 16L
CompressormodelSRS
Non-loaded line
counter V 221 221 236 299 299 299
electromotive
force
Dischargeline, mm 65 65 65 76 76 76
internal
Oil
mm 22/M261.5
channelconnection
Capacitycontrol
Protectionmodule INT69SNY
87
SRS
7 Extent of delivery
Thestandarddeliveryincludes:
SRS-
Serial SRS-12 SRS-14 SRS-16
Parts 0810
No.
Compressor
Stepcapacitycontrolkits
400V10%-3-50Hz/460V10%-3-60Hz
3
400V10%350Hz/460V10%360Hzmotor
4
Terminalbox,IP54
5 Electricalassessories,230V150/60Hz
standardvoltage
6 Motorwith6internalPTCtemperature
sensors
7
PTCdischargetemperaturesensors
Motorprotectionmodule
8
INT69SNY(monitormotoranddischarge
temperature,rotationdirection,andphase
sequencefailure)
9
ProtectionwithNitrogencharge
10
Builtinsafetyvalve
11
Checkvalve
88
SRS
12
Suctionshutoffvalve
13
Dischargeshutoffvalve
14 Suction filter
15
Rubbervibrationdamper
16
Replaceableoilfilter
17
Oilinconnection
18
Oilsightglass
19
ManualVicontroldevice
20
Oilflowswitch
21
Oilshutoffvalve
22
Oilchannelon/offsensor
Partscanbeprovidedasrequest
1
Motorwithspecialvoltage
2
AutomaticVicontroldevice
3
Capacitypositionsensor
4
Pressuredifferenceswitch
5
Liquidinjectionconnection
89
SRS
Economizerconnectionwithshutoffvalve
7
Lubricants
Note:
1)
meansoffer
2)
If need assessories, please note it when order.
90
SRS
7.1 Suctionanddischargebushingdiameter
Standardconnection Recommendedconnectionforoption
Models Items
Bushing Connection Connection Connection Connection
Bushingcode Bushingcode
Internal pipesize pipematerial Internal pipesize pipematerial
Disch. 42.2 510570 1-5/8
Coppertube Coppertube
port
SRS-08S/M/L
Suction 54.1 513470 2-1/8 58.0 519969RS 57
Coppertube Coppertube
port
Disch. 42.2 510570 1-5/8
Coppertube Coppertube
port
SRS-10S/L
Suction 54.1 513470 2-1/8 58.0 519969RS 57
Coppertube Coppertube
port
Disch. 54.1 513470 2-1/8 58.0 519969RS 57
SRS-12S/M/L Coppertube Coppertube
port
91
SRS
Note:
1) Thewallthicknessofconnectionpipeshallbedefinedbysystempressureandprocessrequirement.
2) Standardconnectioniscoppercoatingsteeltube;noncoppercoatingsteeltubeforoptions.
3) Itisdefaultforstandardconnectionwhenorder.Optionsneedtobeconfirmedbymutualsides.
92
SRS
7.1.1Bushingsize
Bushing A B C D E F G H -
No.
510500 80 48 86 104.5 104.5 87 10 70 -
510560 77 48 86 104.5 104.5 87 10 70
510570 42.2 25 37.8 52.7 57 49 11.5 42.5
513470 54.1 28 59.5 72 86 60 13 48 -
513480 67 28 59.5 72 86 73 13 48 -
517880 90 52 98 115.5 115.5 97 11 75
519899 110 52 111 130 130 118 11 75
519969 58 28 59.5 72 86 64 13 48
Bushing A B C D E F G H M
No.
513500 92.5 25 99 115.5 52 99.8 11 75 92
519239 105.5 25 111 130 52 114.6 11 75 104.8
93
SRS
8 Overalldimensionandpacking
8.1 (Overalldimensionaldrawing)
94
SRS
8.1.1(Freon-use overalldimensionaldrawing)
95
SRS
96
SRS
98
SRS
99
SRS
100
SRS
101
SRS
102
SRS
103
SRS
104
SRS
8.2 Compressorfeetdimension
Figure8K:dimensiondrawingofcompressorfeet
SRS-08S/M/L 315 40
SRS-10S/L 365 50
SRS-12S/M/L 400/346 50
SRS-14S/M/L 400 50
SRS-16S/M/L 380/490 70
Table8A:dimensiontableforcompressorfeet
105
SRS
8.3 packing
Figure8L:packingdimensiondrawing
Amm Bmm Cmm
Models
SRS-08S/M/L 906 586 578
Freon-use
SRS-10S/L( ) 1100 670 650
Freon-use
SRS-12S/M/L( ) 1196 736 668
Freon-use
SRS-14S/M/L( ) 1446 756 707
Freon-use
SRS-16S/M/L( ) 1481 946 833
Freon-use
106
SRS
107
SRS
Theweightofcompressorsshownastabletable8C(excludingtheweightofoil)
Freon-use
190 200 210 245 250 365 370 375
compressor
weight
NH3-use
190 195 205 240 260 355 360 365
compressor
weight
Freon-use
505 510 515 680 690 700
compressor
weight
NH3-use
505 510 515 670 675 680
compressor
weight
108
SRS
9 Performancedata
For the refrigerants like R407C, R404A and R507 etc., the above mentioned
performance data are based on DEW. This is valid also for those substances
characterized by a glide during the change of phase. The relationship
between DEW and average temperature as below:
Averagecondensingtemperature:theaveragevalueofcalculationbetween
saturationtemperatureandDEWundercondensingpressure.
109
SRS
10 Applicationrange
TheapplicationrangeofSRSseriescompressorsadoptingrefrigerantsR22R404AR507
R134awillbegivenasbelow:
Thebelowapplicationrangeappliesforthecompressorsrunningunderfullloadcondition.
Asregardpartialloadcondition,pleasecontactSnowmanfordetailsapplicationrange.
TheuseralsocantakeSRSseriescompressorsselectionsoftwaretoconfirmdesigncondition
andlimitedconditionsmeetapplicationrangeornot,andchecktheapplicationcondition.
10.1 TheapplicationrangewithR22refrigerant
110
SRS
R404A
10.2 TheapplicationrangewithR404Arefrigerant
R507
10.3 TheapplicationrangewithR507refrigerant
111
SRS
R134a
10.4 TheapplicationrangewithR134Arefrigerant
R717
10.5 TheapplicationrangewithR717refrigerant
note
Tccondensing temperature
Teevaporating temperature
112
SRS
11 Additionalcooling
11.1 Lubricantcooling
Hard operating conditions (high condensation and /or low evaporation) require the oil
cooling. The application limits with each refrigerant have to be considered (consult the chapter
10applicationrange).WiththeC100(oilforR22refrigerant),thedischargetemperaturehasto
bemaintainedunder80;asforB170,thedischargetemperaturehastobemaintainedunder
100.forA055(oilforR717refrigerant),thedischargetemperaturehastobemaintainedunder
100.Anyway, this limit is different according to the different applications and lubricants (any
questionpleasecontactwithSnowman)
In addition, cooling by direct liquid injection is possible but with limitations due to risk of
excessiveoildilutioncausedbytoomuchrefrigerantliquid,resultingintothedecreaseofviscosity
ofcoolingoil(maximumcoolingcapacityhastobe10%oftotalrefrigerationcapacity).
11.2 Operationconditionstobeconsideredfortheoilcooling
Refrigerantstype
Min.evaporatingtemperature/max.condensingtemperature
Max.suctionsuperheating
Partialloadrunning
WithECOoperation
113
SRS
11.3 Generalrecommendationaboutoilcooler
Installation under the level of oil separator / compressor, to prevent the possible
lubricantsfillwithcompressororflowbacktooilseparator,leadingtogasenteringoilcooler
andinsufficientlubricationduringnexttimestart.
Oilpressuredrop<0.5barduringnormaloperation
Oil solenoid valve in the oil line must be mounted closed to the compressor to avoid
backflowingoroilenteringcompressorduringshutdownperiod.
Manualshutoffvalves(orboatvalve)recommendedonbeforeandafteroilcoolerfor
servicepurpose.
It must control the operation of oil cooler (temperature sensitive bag locates on the
dischargeline);controlmethodandtemperaturesettingasbelow:
Adopttemperatureregulatortocontroloiltemperature
temperature
R134a
Note:thesettingtemperatureinthetableisnotapplicabletoR134a
Note: oil cooler temperature also can be controlled according to temperature of oil entering
compressor,butpleasecontactwithSnowman.
Forbelowsuitations:oiltemperatureinoilcoolerclosesto20 orsolventlevelsinoil
coolerandoilpipeexceed25L,werecommendtoaddoneoilcoolerbypasslineorheatoil
cooler during shut down period. In fact, in these two situations the oil flow drops are too
muchduetooilflowresistance.Addingoneoilcoolerbypasslineorheatoilcoolerduring
shutdownperiodisgoodforoilquicklyheatinginoilcircuitandreducingthepressuredrop
duringcoldlubricantsstatus.
The bypass valve in oil cooler bypass pipeline shall obtain control fuction. The demand of
controlling solenoid valve requires temperature controller having high sensitivity and small
switchvalvedifference(efficienttemperaturevaryrang<10K).
Note:
Thecoolingloadofoilcoolercanbecalculatedwithselectionsoftware.
PleasecontactwithSnowmanforspecificationofoilcooler.
Examplesofoilcoolerapplication
115
SRS
Temperatureiscontrolledbymeansofthermostaticwaterregulator(dischargetemperature
settingupto100).Atposition13,waterregulatorwithinputsignalsofdischargetemperature
controlstheoilcoolerwaterbymeansofreceivingdischargetemperaturesignal,andthencontrol
oiltemperaturewithinrange.
At any time as long as possible, the oil cooler should be mounted on the position lower than
injection point of compressor and outlet of oil separater, to prevent the would be lubricants filling
the compressor or flowing back to oil separator during standstills, resulting into gas entering oil
cooler which will cause harmful lubrication when restarting. Otherwise, oil pipeline should be
higher.
Figure11A:layoutdiagramofwatercooledoilcooler
Note:1)compressor;2)oilinsightglass;3)solenoidvalve;4)oilflowswitch
5)oilfilter;8)oilseparator(withoilheaterandoillevelcontroller);
9)condenser12)watercooledoilcooler
13)waterregulator(controlbydischargegastemperature)
Temperature control
bymeansofthermostaticswitchinginoroutorsteplessspeedcontrol
ofthecoolerfans(temperaturesettingupto100).Intheposition6thereisathreewaymixing
valve that should have a modulating control function thermostatically controlled with high
sensitivityandaneffectivetemperaturerangelessthan10K.
116
SRS
Since this type of oil cooler has certain level, the outlet of oil cooler should be lower than the
insight glass of oil separator and oil injection point of compressor. If oil cooler is too high
compared to oil separator, it may cause oil flowing back to oil separator during standstills. And it
may cause shortage of oil supply when restart. The oil level difference between oil cooler and oil
separator can be tolerated (it needs to follow the structure of system), but the oil level in oil
separator shall be reduced correspondingly. Meantime it shall set an oil by-pass in the oil line to
quickly supply oil when start the compressor.
Figure11B:layoutdiagramofaircooledoilcooler
Note:1)compressor;2)oilinsightglass;3)solenoidvalve;
4)oilflowswitch5)oilfilter6)threewaymixingvalve
7)aircooledoilcooler
8)Oilseparator(withoilheaterandoillevelcontroller);9)condenser
11.5 Directrefrigerantinjection
A relatively
simple
and cheap
way to provide
additional
cooling
is a liquid
injection
at
intermediate pressure. When the additional cooling capacity exceeds 10% of the compressor
coolingcapacity,itisrecommendedtouseoilcoolingonly.
117
SRS
Figure11C:layoutdiagramofdirectrefrigerantinjection
Note:1)compressor2)oilinsightglass3)solenoidvalve
4)Oilflowswitch5)oilfilter
8)Oilseparator(withoilheaterandoillevelcontroller);9)condenser
10)Liquidinjectionvalve11)dryfilter
On figure 11C, for the liquid injection valve on position 10, in real application it can be
relaced by the liquid injection expansion valve specially designed by the discharge temperature
variation. Those expansion valves include Danfoss TEAT20Alco series 935101B,Sporlan Y103
etc.
No matter liquid injection expansion valve or other liquid injection valve adopted, the
thermostaticbagfordischargetemperatureshouldbefixedtightlytodischargelineandthermal
insulation. For liquid injection expansion valve, the contact surface between pipeline and
thermostatic bag should be cleaned (clean metal), and coat the heatconducting glue and use
special clip (special for thermostatic) to clamp thermostatic bag. Keep thermostatic bag warm.
The contact point between pipeline and thermostatic bag should be 1020cm from discharge
shutoffvalve.
118
SRS
In order to secure the refrigerant liquid in liquid supply injection valve (or orifice) without
anybubble,theiquidsupplylineforliquidinjectionshallcomefromhorizontalsectionofmain
liquidlineandbenddownfirst.
Theinstallationpositionofliquidinjectionexpansionvalveshallbe1520cmhigherinjection
port. The pipeline move towards down and fix together with compressor (expansion
valve/solenoidvalvealsofixed).Topreventpossiblewaterhammercausedbythemovementof
oil and refrigerant and damage to compressor, the injection pipeline starting from compressor
injection port shall be towards up. (Figure 11D not shows the position of luqid injection
expansion valve)
Whenselecttheliquidinjectionexpansionvalve,themediuminjectionpressureisabout
1.53.5bar higher suction pressure (R22R404A). We recommend not selecting too big liquid
injectionexpansionvalvetoavoidoveramountliquidrefrigerant.Mediuminjectionpressurecan
becalaculatedwithSnowmanSRSseriescompressorselectionsoftware.
As shown on figure 11C, we recommend to install a solenoid valve in liquid injection line
(opens during compressor running) and a liquid insight glass. Due to injection port directly
connectstorotorchamber,soitneedstoinstallaprecisionfilter(maximumprecison25um).
1) SRS16S/M/L Compressorsareprovidedwithliquidinjectionconnectionadaptor
2) It also can take the defined orifice kits to replace liquid injection expansion valve with
thermostatic,pleasecontactwithSnowmanfordetails.
119
SRS
Figure11D:thelayoutofliquidinjectionpipeline
Caution:
Toomuchrefrigerantliquidinjectedwillcausethereductionofviscosityof
lubricants,makingbadlubricationperformance.
Toomuchrefrigerantliquidinjectedwillcausethemovementoflubricants
andmakelubricantsentersystem.
Liquidinjectionwillleadtoriseofmotorpower.Moreserious,itwillmake
motoroverload.
Forbidtouserefrigerantliquidinjectionandeconomizeratthesametime.
120
SRS
12 Econimizer
The system with subcooling economizer will increase COP. If necessary, we can offer the
performance data of system with economizer. Please contact Snowman for specification
subcoolingheatexchanger.
By SRS series compressor selection software we can calculate the performance data of
compressorwitheconomizer.
12.1 Workingprinciple
It is therefore possible to transport an additional gas flow rate without relevant effects on
thesuctionvolume,andanadditionalsubcoolingcircuitcanbeaddedtotherefrigerantsystem.
Thisresultsinastrongincreaseofthecoolingcapacity,duetothehighersubcooling,withasmall
increaseofthepowerinputcausedbythetransportofanadditionalmassflowrate;theincrease
ofthesystemefficiencycanbeexplainedconsideringthattheadditionalcompressionworktakes
placefromahighersuctionpressure,thereforewithahigherefficiency.
Infigure12Aaneconomizercircuitisshown.Aheatexchanger(position14)subcoolsthe
liquid leaving the condenser (position 9) with the heat rejected in the counterflow by the
121
SRS
refrigerantthatisdrawnoutfromtheliquidlineandexpandedinanexpansionvalve(13)tothe
intermediate injection pressure. The superheated vapour leaving the exchanger (position 14) is
injectedthroughtheeconomizerportandismixedtothesuctiongas,alreadyslightlycompressed,
whichcomesfromtheevaporator.Andongoingfurthercompression.
Figure12A:subcoolingsystemwithEconomizercircuit
Note:
1.compressor 2.insightglass
3.solenoidvalve 4.oilflowswitch
5.oilfilter 8.oilseparator
9.condenser 11.dryfilter
12.heatexchanger(oilcooler) 13.expansionvalve
14.heatexchanger(ECO) 15.suctionfilter
122
SRS
Shellandtubeheatexchanger,coaxialtypeandplateheatexchangercanbeadopted.The
capacity of subcooler is the difference between the compressor with economizer and without
economizer. The subcooling liquid temperature shall be at least 10k higher than saturation
temperaturecorrespondedbymediumpressure.
Inputdataofsubcoolerdesignselection:
Subcoolerload:basedonSRSselectionsoftwarecalaculation,wecandefinethedifferenceon
refrigerationcapacitybetweencompressorwitheconomizerandwithouteconomizer.
Liquidoulettemperature:calculationbasedonSRSselectionsoftware
Forplateheatexchanger,italsoneedstodefinetherefrigerantdrynessofafterthrottleand
offerforplateheatexchangerfactory.
Expansion valve
In order to avoid wet operation happens when opens the subcooler circuit, we recommend to
use expansion valve special for liquid injection design. Its superheating settings is ahout 10K.
Refrigerant type
123
SRS
Expansion valve load: based on SRS selection software calaculation, we can define the
difference on refrigeration capacity between compressor with economizer and without
economizer.
Select the expansion valve with superheat can be set at about 710K.
Caution!
12.3 recommendation
The sub-coolers should be installed below the compressor in order to avoid possible
backflows of oil or liquid refrigerant to the compressor during standstill periods.
As the compressor may expel a certain quantit y of oil through the economizer port when the
operating conditions have not yet stabilised or alternatively when the sub-cooling circuit is
disabled, the injection pipe should be fitted with an elbow as illustrated in picture 11-D in Chapter
124
SRS
The economizer port leads directly to the rotors; therefore a fine mesh filter (max 25 m)
should be installed. Please refer to table 12-A and 12-B for standard economizer connection flange.
The diameter of the injection pipe should be selected to be same as economizer connection size on
compressor.
616097 614558
ECO flange code
614558 616067
ECO flange code
125
SRS
A B H
ECO flange /mm /mm /mm
code
616097 22 16 36
614558 26 21.6 36
616067 34 25 38
Compressors can be equipped with option ECO connection kits with shut-off valve, as shown
on below table 12-C
Code
Seria
Parts Qty
l No.
Freon-use NH3-use
1 O-ring 691219 691229 1
4 592360 592360 1
Teflon gasket
5 614475 614479 1
Shut-off valve
126
SRS
304311 [SRS-10S/L&SRS-12S/M/L&SRS-14S/M/L
(Freon-use)]
304311A [SRS-10S/L&SRS-12S/M/L&SRS-14S/M/L
(NH3-use)]
Code
Seria
Parts Qty
l No.
Freon-use NH3-use
2 592360 592360 1
Teflon gasket
3 691208 691208 1
Flange gasket
5 614475 614479 1
Shut-off valve
303150 [SRS-16S/M/L (Freon-use)]
303150A [SRS-16S/M/L (NH3-use)]
Code
Serial
Parts Qty
No.
Freon-use NH3-use
1 613840 613840 1
Alu gasket
3 592360 592360 1
Teflon gasket
System with economizer running is the priority for low temperature condition. For R22
refrigerant, when evaporating temperature is below -30 or compression ratio is larger than 10, it
should consider mode with economizer first.
Due to the compression of the additional mass flow and the consequent overloading of the
motor, the operating limits with the economizer are partially more restricted than the standard
conditions for the normal operation of the compressor, the maximum allowance evaporating
temperature and condensing temperature will go down together.
For running at high condensing temperature condition, motor specification should be bigger
(contact with Snowman for details).
Attention!
ECO
The sub-cooling circuit with economizer can be used only on full load
conditions.
During systemstart up (low load condition), the subcoolingcircuit has to remain closed until
working conditions is stable (the use of a time relay to turn on the circuit of ECO is
recommended).
128
SRS
The parallel compounding of 2 or more compressors with one common oil separator is
possible (up to 6). The following schematic picture shows a 2-compressors circuit (parallel
operation with common oil separator).
All single discharge lines should ensure a sufficient fall, in this way we have a free drainage
in the oil separator. The common discharge line should be fitted horizontally like picture 13-A with
a right angle. The optimal layout is to make single discharge line go up along main discharge line
129
SRS
and bend about 135 degree and then connect with main discharge line (as shown figure 13-A).
Examples of parallel compounding with common oil separator and common water oil cooler
(see later content for code explanation):
Examples of parallel compounding with common oil separator and common air oil cooler(see
later content for code explanation):
Figure 13-C: parallel compounding with common air oil cooler and oil separator
130
SRS
Examples of parallel compounding for different suction pressure(see later content for code
explanation):
131
SRS
Examples of parallel compounding with common oil separator and common air oil cooler and
oil pump(see later content for code explanation):
Figure 13-E: Examples of parallel compounding with common oil separator and common air
oil cooler and oil pump
132
SRS
5. oil filter; 6. mixing valve; 7. air cooled oil cooler; 8. oil separator(with oil heater and
oil level controller)
9. condenser; 10. water regulation valve; 11. dry filter; 12. water cooled oil cooler
13. expansion valve; 14. economizer heat exchanger; 15. suction filter 16.condensing pressure
regulation valve
17. shut-off valve; 18. solenoid valve (by-pass during standstill); 19. oil pump; 20. check valve
In principle, the distance between compressor and oil separator, oil cooler should be as short
133
SRS
as possible. The oil pump need if oil channel pressure drop is too big.
3) Oil cooler provided for group, especially for parallel compounding system for different suction
pressure.
134
SRS
The screw compressor can be incorporated into the system in a similar way to reciprocating
compressor. Only the specific features of oil circuit require special attention.
Due to features of screw compressor structure, it is not sensitive to liquid compression during
operation and shows good reliability. However, measure must be taken to keep no lubricant or
refrigerant liquid flooding in compressor during standstill. The flooding of lubricant or
refrigerant liquid in compressor will make uncontrolled liquid pressure during start-up and
will damage the bearing, compressor and oil channel solenoid valve under extreme conditions.
Compressor must be prevented from the pollution of dirty. The cleanness of oil and refrigerant
have an important impact on the reliability and lifetime of compressor.
For the situation of short oil return pipeline, the size of pipeline is mainly decided by the
nominal size of shut-off valve. But for the pipelines with many branches, like low temperature
system, parallel system, and also the system with large load variation as well as up-leg of pipeline,
it needs to specially calculate size. Generally the calculation principle is based on flow rate (oil
return) to define pipeline diameter.
135
SRS
Considering the flow rate problem of return-gas duct with oil, the gas flow speed inside
horizontal pipe should be 4m/s, for vertical pipeline, it should be 8m/s
For longer up-leg pipe, there should be one oil loop at every 4m (the length of oil loop must
be as short as possible to avoid accumulating too much oil); for the single compressor (or parallel
system) running at partial load, it shall set two-rise tube to secure oil return, like figure 14-A.
Figure 14-A: the oil return diagram of evaporator under partial load and for longer up-leg
pipe.
When adopt flooded evaporator with HCFC/HFC refrigerant, it needs to set a separate oil
return point on evaporator or low-pressure liquid reservoir. The oil return point (it is best for more
than one) shall be set within liquid level range. Oil return pipe shall connect to suction pipe. The
refrigerant in oil return pipe can be treated by the heating method of heat exchanger. Firstly it
needs to evaporate the refrigerant and enter suction pipeline. For the liquid with strong variation,
136
SRS
like liquid pump system, the oil drainage point shall be set at lowest point or after circulating
pump.
Prevent compressor from accumulation of oil and liquid and starting with liquid
The pipe layout and system construction must be considered so that the compressor cannot be
flooded with oil or liquid refrigerant during off periods. For this purpose the discharge and suction
lines should at first be led downwards from the compressor.
Assitional measure must be taken for the system with direct expansion to prevent compressor
starting with liquid.
3) A solenoid valve should also be fitted in the liquid line directly before the expansion valve.
Figure 14-B: pipe layout evaporator port for preventing compressor starting with liquid
137
SRS
Due to the low level of vibration and the small discharge gas pulsation the suction and
discharge lines can usually be made without a flexible element or muffler. The pipes must be
however sufficiently flexible and must not exert any strain on the compressor. Critical pipe section
lengths should be avoided (also dependent upon operating conditions and refrigerant).
An oil heater is situated in the oil separator to prevent high refrigerant dilution of the oil
during off periods. This is controlled by means of a thermostat, the temperature setting is 70
Please see position14 and 15 of figure 2-A in chapter 2- cooling oil management
A check valve must be set on the outlet of oil separator to reduce the gas return to condenser
and quickly balance the suction and discharge pressure during the by-pass of standstills. Note: the
built-in check valve inside compressor can not replace this chech valve to complete the dissolution
of refrigerant in the oil during standstills and by-pass period.
A off cycle bypass id recommended which reduces the pressure in the oil separator to suction
pressure during of cycle and thus reduces refrigerant saturation. Apart from this an additional start
138
SRS
unloading is also achieved. A check valve and a balance pipe are necessary after the oil separator
and an equalizing line controlled by a solenoid valve between oil separator and the suction line
(only open during off cycle). With parallel compounded compressors the solenoid valve may only
be open when all compressors are switched off.
Please see position 8 and 9 of figure 2-A in chapter 2- cooling oil management
caution
The bypass of shut down is not allowed to be used for external by-pass
unloading start from high pressure to low pressure (the common method adopted
by piston compressor), otherwise the compressor will be damaged.
The bypass of shut down only can have some extent of fuction for unloading.
Adopting TX valve or crankcase pressure regulator can achieve starting unload
for low temperature running, but only for single compressor and parallel system
with experience.
The compressor must be protectd against contamination with dirt (scale, rust and phosphate
deposits). For widely branched pipe system which are difficult to inspect for contamination the use
of a suction side fine filter (max. 25um) is necessary. In addition, a generously dimension good
quality filter drier is required to provided the system with a high degree of dehydration and
chemical stability.
14.2.1 The layout of oil separator position, discharge pipeline and oil injection pipeline.
139
SRS
The pipe layout of oil separator locating below compressor level (optimal layout).
Figure 14-C: The pipe layout of oil separator locating below compressor level
The pipe layout of oil separator oil locating at oil injection port (better layout)
140
SRS
Figure 14-D: The pipe layout of oil separator level locating at oil inection port
The pipe layout of oil separator oil level higher than oil injection port (should be avoid and not
suitable for parallel system)
141
SRS
Figure 14-E: The pipe layout of oil separator oil level higher than oil injection port
The layout of discharge line and oil injection line for parallel compounding system
142
SRS
Figure 14-F: the layout of discharge line and oil supply line for parallel compounding system
2)
The layout of main oil pipeline
The same pipe diameter shall be adopted for the whole length for main oil pipe. Oil supply
branch should be unity and as short as possible.
One common oil filter with reasonable specification (locating on main oil line) can be adopted
to replace the oil filter on all branches.
Note:
We recommend to set shut-off valve on oil supply branch for service (using ball valve can
obtain smaller pressure drop).
143
SRS
Whenever if possible it should install oil cooler below the compressor injection port and oil
separator port, to prevent the possible lubricants filling compressor or flowling back to oil
separator which leading to bad lubrication during next starting due to gas entering oil cooler.
Otherwise, it should raise oil pipe.
Due to the certain height of such kind of oil cooler, the port of oil cooler during installation
should be bothly lower than sight glass of oil separator and oil injection port of compressor. If oil
cooler is higher than oil separator, it may cause oil flow back to oil separator during off periods,
while there will be shortage of oil supply if compressor start again. The small oil level distance
between oil cooler and oil separator is allowed (need to conform to structure), but the oil level in
oil separator shall reduce correspondingly; meantime oil bypass should be installed in oil line for
quick oil supply during compressor start.
144
SRS
Unreasonable pipeline layout in parallel system will produce extreme bad influence. In
system design, the general situation is to consider the installation of oil separator first, and the
system usually allows suction line working position to be lower than compressor surface. This
layout provides the maximum safety.
Note: for hot gas defrost system or system with unbalanced pressure and shut down for long
time, the serious liquid hammer can not be completed dismissed.
By reasonable design of suction line, it can have gas/lliquid separator. Hence, suction line
inlet shall be designed with baffle plate. The flat suction line shall be designed up and connecting
to compressor. At same time separate oil return pipe should be adopted, like figure 14-H.
145
SRS
Figure 14-H: the layout of suction line for parallel compounding system (The flat suction line
with individual oil return pipe)
Figure 14-I shows another design layout of suction line, the flat suction branch is cut with 30
degree wedge shape and inserted into the bottom of suction line. Thus the suction branch also
works with oil return, and it is no necessary to set separate oil return pipe.
Figure 14-I: the layout of suctionbranch for parallel compounding system (wedge shape
suction branch)
For the parallel compounding system of two compressor, even under partial load condition,
146
SRS
the oil return of system is quite easier and the pipe layout is more easier, like shown on figure 14-J.
Figure 14-J: layout of suction line for parallel compounding system of two compressors
The suction branch of parallel compounding system can also be extended from the side of
suction line, like figure 14-K; it is not allowed to extend suction branch from the bottom of suction
line, like figure 14-K.
Figure 14-K: the side connection between suction branch and suction line of parallel
compounding system.
(a) correct (b) incorrect
147
SRS
It should be avoid to layout pipe of suction line higher than compressor surface, this layout
only can be considered when the space size is not enough to meet the above mentioned space, like
figure 14-L:
Figure 14-L: layout of suction line (sution line higher than compressor surface)
Left: suction line of two compressors
Middle: wedge shape suction branch
Right: individual oil return line
As figure 14-M, for the situation of suction line higher compressor surface, unallowed pipe
layouts between suction branch and suction line are listed below:
Figure 14-M: unallowed layout of suction line (suction line higher than compressor surface)
148
SRS
Only the compressor is running with specified range and oil filter is kept clean, all
performance data are with index range can ensure lubricants to meet the required minimum flow
for all funtions (sealing, lubrication, cooling and slide valve control). When condensing pressure is
lower or reduces quickly, the following problems will occur:
149
SRS
Condensing pressure dropping quickly will produce large bubble and the movement of oil, as a
result, oil monitoring system will cut the power supply of compressor.
Delay occurs due to low or high condensing pressure, the minimum oil pressure difference
can not be kept, as a result, oil monitoring system will cut the power supply of compressor.
Therefore, it needs to have small variation step control and stepless control
for condensing pressure, to keep high efficiency of oil separator and normal supply
pf lubricants.
For below conditions, it needs to mount pressure regulator on discharge line (after oil
separator)
Long time shut down under extreme partial load condition or condenser mounted in low
ambient temperature.
When start, the liquid temperature of heat exchanger on high pressure side is quite low, sution
pressure is quite high.
It also can adopt crankcase pressure regulator to quickly reduce suction pressure to quick build
the minimum oil supply pressure difference.
150
SRS
Apart from pressure regulator, it also can use condenser air fan delay start to quickly build
minimum oil pressure difference.
For the position of pressure regulator, please see position 16 of figure 13-B, 13-C, 13-D in
chapter 13-parallel compounding system.
For the systems which can not balance the temperature and pressure, special attention should
be paid to the movement of refrigerant. In addition, for the systems with hot gas defrost or reserve
cycle, it needs to take measures to prevent the strong liquid hammer and too much oil entering
cycle.
If compressor locates in low ambient temperature and the temperature is quite high during off
periods, the oil separator needs to be heat insulation to reduce the dissolution of refrigerant in oil.
In order to prevent too much refrigerant in compressor, suction line or gas/liquid separator
during shut down, the system take vaccum cycle(Pump down cycle). The start pressure of low
pressure controller must be lower than the lowest temperature may arrive.
For flooded evaporator, the solenoid valve cooperating with crankcase pressure regulator
should be mounted on the position higher than suction line port, and close during standstills.
During standstills, the over high pressure can be released by refrigerant to high pressure side to be
avoided (pay attention to capacity of liquid reservoir)
151
SRS
The refrigerant will move during standstills, and there will be lack of refrigerat when next
restart; for water chiller, it may lead to frozen of evaporator
There may exist the risk of larger refrigerants movement when some circuit closes. Below
measures can be taken:
Special measures should be taken to prevent the strong liquid hammer to compressor or too
much oil entering cycle. Below measures can be taken:
1 Keep the oil temperature in conditions changing and subsequent operation always higher
condensing temperature at least 30
2 Set pressure regulator after oil separator to limit the pressure drop or drastic change;
3 Switch off compressor power supply for short time before condition changing and restart
the compressor after pressure balanced.
152
SRS
Note: ensure to build minimum pressure difference with 20 minutes after starting
compressor at any time.
153
SRS
15 Operation instruction
SRS series compressor only can use refrigerants approved by Snowman and oil recommended.
Prohibit compressing air or other any kind of gas, or using lubricants without Snowman approval.
Prohibit starting compressor when the suction and discharge shut-off valve are not completed
open. Prohibit starting compressor when the terminal box are not correct installed and fixed.
Only allow to use N2 or Co2 gas to keep pressure for refrigeration cycle system. Prohibit
keeping pressure with O2 and acetylene.
154
SRS
The temperature of the environment where the compressor operates and is stored must be
between -15C and +50C.
For the compressor the range of admissible suction superheat temperatures is: R22515K
155
SRS
The user must ensure also that the balanced pressure does not exceed the maximum value
specified by Snowman. If user wants to test the tightness of compressor, must pat attention to
following points:
The compressors are designed and tested according to the European standards EN 60335-2-34.
In order to generate a starting torque greater than the resisting one, the balanced system
pressure (pressure inside the compressor during standstill periods) must not exceed 21 bars.
The compressor can be started a maximum of 6 times per hour (1 start every 10 minutes).
156
SRS
The compressor must operate for a minimum time of three minutes. In addition, it must be
started and stopped at minimum capacity (minimum step). The transients at minimum load must
last 25 seconds at least.
15.9 Installation
The compressor must be installed horizontally. To prevent the compressor from transmitting
vibrations to the structure, the vibration damper kit should be used. Flexible pipes are not required
on the suction or discharge lines, so that these do not exert any force on the compressor.
Please use pipes and components that are extremely clean and dry inside, without slag, swarf,
rust and phosphate coating.
157
SRS
15.10 Testing
Note:
The compressors are supplied with a protective nitrogen charge (0.5-1 bar
above atmospheric pressure) to prevent air from entering inside.
Perform the leak test on the refrigerant circuit with dry nitrogen; if the circuit is tested with
dry air, the compressor must be bypassed. Empty the entire circuit, including the compressor and
the sections isolated by the valves, both on the suction side and on the discharge side. The vacuum
required is at least 1.5 mbar (with isolated vacuum pump); if necessary repeat the operation more
than once. After emptying, add the oil to the compressor, if the oil charge is supplied separately,
and switch on the oil heater.
As regards the compressor, this has already been tested for leaks under pressure, and therefore
this test does not need to be performed by the user. If the leak test does need to be repeated by the
user, make sure the design pressures reported on the compressor rating plate are never exceeded
Never subject the compressor to pressure higher than the design values
indicated on the rating plate;
Never start the compressor under vacuum.
158
SRS
To identify the correct discharge temperature, use the SRS selection software.
15.11 starting
Start preparation:
After discharging the protective nitrogen charge, connect the compressor to the plant, making sure
that the shut-off valves are closed. This avoids contact between the humidity of the air and the oil.
However if the oil comes into contact with the humidity, it must be for not longer than 30 min;
Make all the electrical connections as given in the wiring diagram on chapter 5: Electrical
devices ;
2 Oil level;
Turn on the oil heater at least 24 hours before each first seasonal start-up. The oil inside the
separator must have a temperature at least 15K higher than the ambient temperature;
Open the suction and discharge shut off valves, start the compressor while checking the correct
motor rotation in the following way (even if some protection electroni
3 If the compressor screws rotate correctly, the suction pressure will drop promptly. The
electronic protection intervention or a suction pressure increase implies the wrong rotors rotation.
In this case, switch two of the power supply phases in the terminal plate.
Start
Re-start the compressor and open slowly the suction shut-off valve;
160
SRS
Make sure that the oil level is visible through the sight glass. Presence of foam is normal as
long as the working conditions are not stable. The discharge temperature must be about 30K
higher than the condensing temperature;
1 Evaporating pressure;
2 Condensing pressure;
4 Discharge temperature;
6 Contingent unbalanced electrical absorbed currents on all the 6 wires connected to the
electricity grid.
161
SRS
thermistors embedded
in the motor windings
(cut out 100/120 C)
To protect the
Discharge gas
lack of lubrication compressor from lack of INT 69 RCY
temperature sensor
lubrication
(cut out 120 C)
To prevent compressor
Oil flow shortage Oil flow switch
lack of oil INT 69 RCY
The pressure
difference of
Built-in safety
suction and safety hazard INT 69 RCY
valve
discharge is too
high
Discharge
To prevent too high Manual pressure System electric
pressure is too
pressure for switch control protection
high
compressor
162
SRS
Pressure drop of
To keep oil filter Pressure difference System electric
oil filter is too
clean switch (2 3.5bar control protection,
high
switch off ) (option part).
Discharge
Ensure bearing Oil cooling (liquid System electric
temperature is too
lifetime injection/external control protection
high
oil cooling)
See chapter 10
Compressor can Capacity control solenoid valve damage Contact with Snowman
not loading or abnormal working, the problem of
solenoid valve control system.
164
SRS
Motor
Water exists in motor winding Contact Snowman
insulation
damage
The acid cooling oil will damage Contact Snowman
insulation
Motor burns
166
SRS
Bearing damage
Contact snowman
167
SRS
Motor
protection Compressor running conditions are not check
device fault or withing application range;
motor burning Low oil level
Too frequent of start number Check the matching of
electric control system or
refrigeration system
Contact snowman
168
SRS
Evaporator damages
169
SRS
check
See chapter 2
See chapter 3
170
SRS
16 Maintenance
Switch off power supply before maintenance, non-professional guys are not allowed
to open terminal box.
Lubricants
The lubricants have high thermal and chemical stability: if installation is performed correctly,
the oil normally does not need to be changed. Periodically test the acidity of the oil to prevent
damage to the motor or the compressor and, if necessary, perform the following operations:
Purge the system from the highest point on the discharge side.
The oil can be drained through the service valve and the plug on the bottom of the suction
cover. The oil can be recharged through the service valve, creating a vacuum inside the
compressor.
Bearing
The bearings in the compressor are designed to ensure 60,000 hours of operation with correct
lubrication (oil filter clean and oil pressure within the limits. Any alteration of the
above-mentioned conditions and excessive changeability of the load may bring a drastic reduction
in the effective working life. The bearings must be replaced by qualified personnel in a specially
equipped workshop.
171
SRS
If the reverse rotation, which occurs when the compressor stops to balance the pressure, lasts
more than 3 seconds, the check valve located underneath the discharge shut-off valve may be
damaged, and consequently must be replaced. In any case, the reverse rotation must not last more
than 5 seconds to avoid damage to the compressor and the unwanted activation of the INT 69 RCY
protection module.
Oil filter
SRS-12~16S/M/L series compressors have their oil filter inside compressor. At normal
conditions, the pressure drop before and after oil filter is lower 2 bars. It needs to replace the oil
filter element if exceeds this rang, as figure 16-A shown:
As shown below:
S= replace ; C= check
172
SRS
C/S S
Oil filter
C C C C C S
Lubricants
Suction C C C C
filter
Solenoid C C C C C
valve
S
bearing
C C C C C
Check valve
Protection C C C C C
module
C C C C C C
Input voltage
Motor contact C C C C C
points
173