NC -NORMALLY CLOSED
-SLOPE DIRECTION
12x8 -RADIUS TEE
CRU-1 BASEMENT (COLLECTIONS) 0 0 0 17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS,
DIFFUSERS, LOUVERS AND OTHER AIR DISTRIBUTION DEVICES.
NO -NORMALLY OPEN -FLEX CONNECTION
CRU-2 1ST LEVEL (COLLECTIONS) 0 0 0
18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH
NTS -NOT TO SCALE CRU-3 2ND LEVEL (COLLECTIONS) 0 0 0 FAN, AIR HANDLING UNITS, AND FAN COIL UNITS.
OA -OUTSIDE AIR -O.S.&Y. GATE VALVE
-HYDRONIC REHEAT COIL AHU-1 1ST LEVEL (OFFICES/LABS) 25 20 500 19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF
OAL -OUTSIDE AIR LOUVER
-THREE-WAY CONTROL VALVE
-RECTANGLE-TO-ROUND TAKE-OFF
1ST LEVEL (EXHIBT #2) 60 15 900 FLEX DUCTS TO BE CONNECTED.
PRV -PRESSURE REDUCING VALVE 20. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER
PRS -PRESSURE REDUCING STATION
-THERMOMETER
-DOOR GRILLE AHU-2 1ST LEVEL (LABS) 70 20 1,400 THAN NORMAL OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH
INTERRUPTIONS TO SERVICES SHALL NOT BE MADE WITHOUT THE PRIOR WRITTEN
PSI -POUNDS PER SQUARE INCH -STANDARD BRANCH TAKE-OFF
UC
AHU-3 2ND LEVEL (EXHIBT #1) 200 15 3,000 CONSENT OF THE OWNER'S REPRESENTATIVE AND PROPER COORDINATION WITH
EQUIP.
PSIG -PSI GAUGE - P-TRAP
-SPIN-IN TAKE-OFF
-UNDERCUT DOOR AHU-4 2ND LEVEL (OFFICES/LABS) 80 20 1,600
OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE SHUTDOWN
PERIOD AS BRIEF AS POSSIBLE.
PVC -POLYVINYL CHLORIDE PIPE
RA -RETURN AIR -TWO-WAY CHECK VALVE 21. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL REMAIN PROPERTY OF
-ACCESS DOORS, VERTICAL OR HORIZONTAL THE OWNER OR DISPOSED OF LEGALLY, AS DIRECTED BY OWNER.
RHC -REHEAT COIL
MV
-CEILING DIFFUSER, ROUND NECK
RHP -ROOFTOP HEAT PUMP -MANUAL VENT (CEILING DIFFUSERS ARE 4-WAY THROW UNO) TOTALS 435 7,400 22. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING,
EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS,
RPM -REVOLUTIONS PER MINUTE -STAINLESS STEEL DUCTWORK TO ALLOW FOR INSPECTIONS OF RATED WALLS.
-ROUND DIFFUSER NOTE: THESE OUTSIDE AIR QUANTITIES ARE MINIMUMS BASED ON
RS/L -REFRIGERANT SUCTION & LIQUID LINES
OCCUPANCY, AND DO NOT INCLUDE ADDITIONAL MAKE-UP AIR 23. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 10'-0" CLEAR FROM ALL
-PRESSURE GAUGE PLUMBING VENTS AND EXHAUST AIR DISCHARGE LOCATIONS. LOWEST POINT OF
RTU -ROOFTOP AIR HANDLING UNIT -FLEXIBLE CONNECTION REQUIREMENTS FOR FUME HOODS.
-CEILING RETURN EACH OUTSIDE AIR INTAKE ON ROOF SHALL BE A MINIMUM OF 24" ABOVE ROOF.
SA -SUPPLY AIR -RELIEF VALVE
SP -STATIC PRESSURE
12x8 -FLAT OVAL DUCT
24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
FM -FLOW METER -CEILING EXHAUST
TSP -TOTAL STATIC PRESSURE
25. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED
UNO -UNLESS NOTED OTHERWISE M -WATER METER -CEILING DIFFUSER, RECTANGULAR OR 5 PSI.
SQUARE NECK (CEILING DIFFUSERS -INLINE CENTRIFUGAL FAN
V/PH -VOLTS/PHASE 26. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE
ARE 4-WAY THROW UNO)
DESIGN CONDITIONS
-INLINE PUMP INDEPENDENTLY PIPED FULL SIZE TO THE NEAREST PLUMBING DRAIN.
VAV -VARIABLE AIR VOLUME
-INLINE PUMP -SUPPLY REGISTER OR GRILLE 27. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.
VFD -VARIABLE FREQUENCY DRIVE
(VERTICAL MOUNT, SIDEWALL) -PACKAGED TERMINAL AIR CONDITIONER (PTAC) PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN CHILLED WATER AND HOT
WATER PIPING.
1 -REVISION REFERENCE -VALVE ON RISER COOLING (ASHRAE 1% CONDITION) 94F DB/79F WB
1 -DETAIL REFERENCE: TOP-DETAIL#, -CAP
-RETURN/EXHAUST REGISTER OR GRILLE HEATING (ASHRAE 99% CONDITION) 28. MAXIMUM LENGTH OF ALL FLEX DUCT TO BE 8'-0". IF LONGER RUNS ARE REQUIRED
M-1 BOTTOM-DRAWING# SHOWN ON (VERTICAL MOUNT, SIDEWALL) PROVIDE SHEET METAL EXTENSIONS WITH SNAP LOCK FITTINGS.
-CONNECTION, BOTTOM
T -THERMOSTAT/TEMPERATURE SENSOR
H -HUMIDISTAT/HUMIDITY SENSOR -CONNECTION, TOP INSIDE SETPOINT (COLLECTIONS) 75F DB (55% MAX RH)
INSIDE SETPOINT (EXHIBIT SPACES) 70F DB (45% WIN/55% SUM RH)
-DUCT SMOKE DETECTOR
-COUPLING
INSIDE SETPOINT (ALL OTHER SPACES) 75F DB (60% MAX RH)
-ELBOW, 90
-CONNECT TO EXISTING
-ELBOW, 45
-DEMOLISH TO POINT INDICATED
-ELBOW, TURNED DOWN
DIFFUSER AIR THROW LEGEND WALL U-VALUE 0.118 BTU/HR-SQFT-F HVAC DESIGN REQUIRES: YES NO
M -MOTORIZED CONTROL DAMPER
ROOF U-VALUE 0.046 BTU/HR-SQFT-F
-ELBOW, TURNED UP
NOTE: ALL CEILING DIFFUSER AIR THROW PATTERNS ARE FOUR-WAY UNLESS OTHERWISE INDICATED ON PLAN DRAWINGS IN ACCORDANCE WITH THE SYMBOLS SHOWN BELOW
GLASS U-VALUE/SHADING COEFFICIENT 0.32 BTU/HR-SQFT-F / 0.42 DUCT SMOKE DETECTORS
TS -TEMPERATURE SENSOR
-TEE, OUTLET DOWN FIRE DAMPER(S)
-PRESSURE SENSOR
P
-TEE, OUTLET UP
1W 2C SMOKE DAMPER(S)
-CEILING DIFFUSER, ONE-WAY THROW, -CEILING DIFFUSER, TWO-WAY CORNER THROW,
D D ARROW INDICATES DIRECTION OF ARROWS INDICATE DIRECTION OF AIR THROW. FIRE RATED ENCLOSURE
-45 PIPE RISE (R) / DROP (D) AIR THROW.
FIRE RATED ROOF/FLOOR
-SHUT OFF VALVE
CHILLED WATER DEMAND CEILING ASSEMBLY
FIRE STOPPING
SMOKE CONTROL
3W
2W -CEILING DIFFUSER, TWO-WAY THROW, -CEILING DIFFUSER, THREE-WAY THROW, CONDITIONED AREA: 38,000 SQFT
ARROWS INDICATE DIRECTION OF ARROWS INDICATE DIRECTION OF
BUILDING LOAD T. MARK KIRBY
AIR THROW. AIR THROW. 1,500 MBH MECHANICAL
COIL TEMP. DIFF: 14 F (BASED ON EXISTING PLANT) 45276
PEAK FLOW 215 GPM
M:\102014\01\ M001.dwg 11/06/02 14:26 vince.briones-1798
HVAC LEGENDS,
SYMBOLS AND
NOTES
M001
VFB
TMK
INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER
THAN NORMAL OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH
INTERRUPTIONS TO SERVICES SHALL NOT BE MADE WITHOUT THE PRIOR WRITTEN
AHU-3 2ND LEVEL (EXHIBT #1) 200 15 3,000 CONSENT OF THE OWNER'S REPRESENTATIVE AND PROPER COORDINATION WITH
AHU-4 2ND LEVEL (OFFICES/LABS) 80 20 1,600
OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE SHUTDOWN
PERIOD AS BRIEF AS POSSIBLE.
24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
25. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED
5 PSI.
26. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE
DESIGN CONDITIONS 27.
INDEPENDENTLY PIPED FULL SIZE TO THE NEAREST PLUMBING DRAIN.
FIRE DAMPER(S)
SMOKE DAMPER(S)
FIRE RATED ENCLOSURE