PowerTest Basic Concept

PONOVO POWER CO., LTD

No. 139 Jinghai Third Road, BDA, Beijing, China, 100176


Office TEL. +86 (10) 59089666
E-Mail Info@relaytest.com
Website www.relaytest.com

PowerTest

Basic Concept

VERSION: PowerTest Concept-AE-2.30


DATE: 16/01/2017

This manual is the publisher of PONOVO POWER CO., LTD. To make any kind of copy of this
manual please contact PONOVO POWER CO., LTD in advance.

This manual represents the technical status for the moment of publishing. The product information,
description and specifications mentioned in the manual do not have any contact binding force and
PONOVO POWER CO., LTD remains the right to make modifications to the technical
specifications and configurations without prior notice. PONOVO POWER does not take
responsibility to the possible error/mistakes in this manual.

1
PowerTest Basic Concept

Contents
Start page3 1.8.9 Recording window.15
I. Test Modules..4 1.8.10 Vector diagram.17
1.1 Basic..4 1.8.11 Manage test items 17
1.2 Protection.4 1.8.12 View windows.21
1.3 Advanced........4 1.8.13 Name for settings
1.4 Special..5 and variable.22
1.5 IEC61850......5 1.8.14 Bookmark23
1.6 New Modules...6 1.8.15 Recover task..23
1.7 How to select the test 1.8.16 Binary input
module......6 configuration..23
1.7.1 Single choice........6 1.8.17 Test equipment
1.7.2 Multiple information..24
choices.......7 1.8.18 Control test
1.8 Typical test page...8 process25
1.8.1 Test module...9 II. Setup.....26
1.8.2 Test template...10 2.1 System & IEC.26
1.8.3 Test module 2.2 AuxDC.33
Composition......11 2.3 Binary..34
1.8.4 How to generate 2.4License...35
test template......12 2.5 IP Set...35
1.8.5 Open test III. Test Manager.36
template..13 3.1 Templates..36
1.8.6 Output monitoring..13 3.2 Report.37
1.8.7 Test process 3.3 Test plan.38
Display.14 IV. Calibration............39
1.8.8 Test process V. Support........39
recording....14 GPS Instruction..39

2
PowerTest Basic Concept

Start page
The start page of PowerTest is the place where we can see the software menu and its selections
showing in the following figure.

3
PowerTest Basic Concept

I. Test Modules
The Test Modules include Basic, Protection, Advanced, Special, IEC61850 and New Modules.

1.1 Basic
User open the software, the basic interface is displayed. Customer can select one or more
modules in Test Modules at the same time and click OK button to enter into the test page.

1.2 Protection
Here users can open the Protection modules after authorized by PONOVO.

The grey part in left is not authorized while the right is authorized. The other modules are the same
except Basic Modules.

1.3 Advanced
Here we can open the Advanced modules after authorized by PONOVO.

4
PowerTest Basic Concept

1.4 Special
Here user can open the Special modules after authorized by PONOVO.

1.5 IEC61850
Here user can open the IEC61850 after authorized by PONOVO.

5
PowerTest Basic Concept

1.6 New Modules


Here we can open the New modules saved by customer in the place of customers selection. It
requires authorization from PONOVO.

1.7 How to select the test module


1.7.1 Single choice
In this situation, user only needs to select one test module at one time.

6
PowerTest Basic Concept

1.7.2 Multiple choices


User can select several test items in different Test Modules. For example, user can choose test
items both in Basic and Protection simultaneously.

Note: User should choose the test items either authorized or unauthorized by PONOVO. If
choosing the unauthorized items, users only can enter into the interface for demonstration, but
cant make tests. The software will instruct NOT BEEN AUTHROZIED.

7
PowerTest Basic Concept

1.8 Typical test page


The typical test page is shown bellow.

The test page provides the facilities for customer to manage the test process, such as

Managing test modules


managing test items and test points
editing relay settings
setting test parameters
displaying relay characteristic
displaying output vector diagram
displaying test process
control test process
display hardware operation status
managing test reports
managing test templates
managing the output monitoring function
managing the test process recording function

8
PowerTest Basic Concept

1.8.1 Test module


Test module is the basic test unit in PowerTest.

We can have access to test modules just from the start page.

For example in basic we can have the following test modules available.

We can select one or more test modules at the same time according to our test requirement.

9
PowerTest Basic Concept

1.8.2 Test template


Test template is composed by one ore test modules.

Test template is used to test a complete protective relay system where different relay tests are
required.

10
PowerTest Basic Concept

1.8.3 Test module composition


The typical composition for distance module is
shown bellow.

The association of the above diagram


components to the software is shown bellow.

11
PowerTest Basic Concept

1.8.4 How to generate test Step 4


Select the two modules
template

Step 1
Select test modules to be included in the test Step 5
template from the start page and enter into the We can also change the module name. To do
test page. In our example here we are going to it we can right click the mouse button and
generate a test template which contains select Rename. Then we see the pop-up
Ramp and Distance(R,X) modules. dialog box.

Step 2
In the Task List area of test page right click
the mouse button and we see the pop-up
selection page
Step 6
Enter the new name for the module.

Step 7
Make relay settings for these two modules
accordingly.

Step 8
Step 3 In the Task List area right click the mouse
Click the Disable multi-select option to button and select Save as Template File and
make it active. After this operation we will be we will be asked to select the folder where we
able to select more test modules at the same want to save the template.
time.

Step 9

12
PowerTest Basic Concept

Select the folder we want to save the template


and give the name for the template.

Open template from report

If we have save the test report in PowerTest


format with the extension of rpt we can also
open the template through opening this report
in any module.

rpt format test report can be opened in the test


1.8.5 Open test template module. At the same time the template
information contained in the report will also be
There are three ways to open the test opened.
templates.

Open template from start page 1.8.6 Output monitoring


Click the Templates button in the start page This function is used to monitor the output
and select the template file from the folder waveform and value during the test process
where the template file is saved. Then we will
enter into the test page automatically with test This function is used to monitor the output
modules containing in this template. The test
parameters and relay settings in the saved Customer can activate this monitoring function
template will also be uploaded here. by clicking the quick control button

During the test process we can see the output


waveform and output value from this
Open template from test page monitoring window.

We can also open the template from the test


page.

In the test page drop-down menu select


Template and select open. Then we need to
select template file from the place where its
saved.

13
PowerTest Basic Concept

1.8.7 Test process display 1.8.8 Test process recording


For some test modules, such as RAMP, This function is used to record the test process
QuickTest, we can view the test process on after test is over. The binary input/output
test page during test process. status during the test process is also recorded.

Click the control button to switch among When test is over we can click the recording
different display windows button to activate the recording operation.

Example: recording of ramping process for


pick-up and drop-off test

In this example we show a ramping process.


The current will increase with set step value
and step duration. When relay trips the current
will decrease until relay drops.

----------------------------------------------
Here we can also view the binary input/output Note: The recording button will be
status during the test process. We can also activated only after test is over
see the output or tripping values by moving ----------------------------------------------
cursor to the position we need.

We can enlarge it by using two cursors along


time axis.

14
PowerTest Basic Concept

1.8.9 Recording window


The recording window provides some simple
tools to better view the recording display.

Instantaneous and RMS value


The instantaneous, RMS and harmonic values
for voltages and currents at the cursor place
can be displayed at the same time.

----------------------------------------------
Note: To view the value display at a cursor
position drag the cursor to the position.
----------------------------------------------

15
PowerTest Basic Concept

Adjust display scale Example: one typical recording display

The instantaneous, RMS and harmonic values


for voltages and current

Through these settings we can set the


maximum range for displaying the voltages
and currents for better view.

Time between cursors


The time difference between two cursors and
also the absolute time for each cursor position
are also be displayed. Export COMTRADE file
The recorded waveform and binary
input/output status can be exported to
COMTRADE format file.

Move mouse pointer to the waveform display


area and right click the mouse button. Then we
see the following menu will appear.
T1: the absolute time counted from the start
point to the position of cursor 1

T2: the absolute time counted from the start


point to the position of cursor 2

dT: the time difference between T1 and T2

Select Save As Comtrade to export the


current waveform and binary input/output
status display as COMTRDE file.

16
PowerTest Basic Concept

1.8.10 Vector diagram 1.8.11 Manage test items


For a test process we can view the output Before starting a test customer needs to
vector diagram (calculation value). manage the test items/points according to test
requirement
By click the quick control button we can open
this display window.

The green cursor indicates that the current


item/point is active.

The vector diagram window is show bellow Add and remove test item/point
Click Add and Remove buttons in the
parameter setting area to add or delete the
test point in a test item.

Each test item/point has its own parameter


setting screen.

If the newly added test item/point may have


different parameters, wiring, report setting, or
assessment customer can make setting just in
the parameter setting area.

All test items/points share the same group of


relay setting values, general parameters,
binary input configuration and relay
characteristic.

17
PowerTest Basic Concept

Add wiring and test information


Right click on the item table a pop-up screen
will appear and we can see Message option
there.

Select test item/point

For all test items/points listed in the table


customer can decide which items/points will be
tested. Simply click the items/points in the
column of Sel to enable or disable it.

Click Message the following screen will


appear

Status of test item/point


When test is over the status for each tested
item/point will be displayed

Here we can edit the wiring information for the


selected test items/points. In the message box
we can also edit necessary notice/instructions.

18
PowerTest Basic Concept

The following is one example

With this selection and when we start test the


setting page will pop-up first. And after we click
OK button the test will then start.

Set test item parameters


For each test item/point we can set test
parameters in the item parameter setting area.

Example: Parameter setting area for


Under-frequency module

For each test item/point it has its own test


When this is selected the software will Parameter, Assessment, and Wiring
compare the message of this test item/point
with that of the last test item/point. If there is
any difference the current popping box will
----------------------------------------------
appear before test starts. And test will start Note: The layout and content of parameter
after click the OK button. setting area may differ from module to module
----------------------------------------------
Set parameter with direct setting value

With this selection and after the current test is For test parameters which require setting
completed a pop-up dialog box will appear. values we can put in the direct setting values
Customer needs to click the OK button to start according to our test requirement.
the next test.
Example: direct setting in distance module
----------------------------------------------
Note: This facility can be used to manually
observe each test item/point
----------------------------------------------

19
PowerTest Basic Concept

Set test parameters with variables Wiring diagram


When one module is opened parameters
related to settings will be expressed with Click Wiring button we can view the wiring
variables. diagram. The wiring diagram is made based
on the information we put in Message.
Example: setting with variables in distance Example: wiring diagram based on the
module information we put in Message (see page 15)

Set group settings

In the above example the variable RE1 and Click to enter into the group setting
XE1 represents the relay setting RE1 and page
XE1.
For different test modules the group setting
If RE1 setting is 3 ohm then the expression of page may be different.
0.95*RE1 is equal 0.95*3=2.85 ohm
Example: group setting page for
Under-frequency module
----------------------------------------------
Note: For more details about variables
please refer to Name for settings and variables
on page 17
----------------------------------------------
----------------------------------------------
Note: The settings here will be applicable
to all test items/points
----------------------------------------------

20
PowerTest Basic Concept

Set group parameters 1.8.12 View windows


Click to enter into the group 4 control buttons are provided to switch over
parameter page among different view windows.

For different test modules the group parameter


page may be different.

Depending on the module these 4 control


Example: group parameter page for buttons may bring different view windows,
Under-frequency module such as relay characteristic, vector diagram,
wiring, relay settings, test process, etc.

Example: a view window which shows the


vector diagram and output settings.

----------------------------------------------
Note: The parameters here will be
applicable to all test items/points
----------------------------------------------

Set group binary input


For some modules group binary setting is
applicable.

In these modules the group binary setting


button will be activated

----------------------------------------------
Note 1: for more information about binary
input configuration please refer to page 21 Example: click we can view the relay
---------------------------------------------- settings/parameters

----------------------------------------------
Note 2: The set binary input configuration
will be applicable to all test items/points
----------------------------------------------

21
PowerTest Basic Concept

1.8.13 Name for settings and By click button we can view the
setting/parameter names and their variables at
variables the same time.

The settings/parameters in all modules have Example: setting/parameter names and


been assigned to a dedicated name. And for variables for differential module
each setting/parameter a dedicated variable
name has also been assigned for setting
purpose purpose.

By select button we can view the


setting names and their variables.

Example: setting names and variables for


differential module

By select button we can view the


parameter names and their variables.

Example: parameter names and variables for


differential module

22
PowerTest Basic Concept

1.8.14 Bookmark 1.8.16 Binary input


PowerTest software provides the facility for
configuration
advanced report template editing (optional).
The binary inputs will be used to sense the
relay operation during the test.
To edit the report template we need to use the
bookmarks associated to settings/test
Properly configure the binary input is important
parameters in the software.
for successful relay test.
Click we can see the bookmarks for the
The selection of binary input type, potential
module customer is using.
free or potential as while as the setting of
threshold for potential contact, can be found
Example: bookmarks for differential module
on page 10.

In the test module what we do is to configure


the logic combination of binary input and
decide which one will be used to sense the
relay operation.

----------------------------------------------
Note: To know more about the optional
report editing tool please contact the
manufacture
----------------------------------------------
We can assign binary input with following
names.
1.8.15 Recover task
Not used: This binary input is not used
Use the context menu Resume last test task Start
on the Test template menu to resume last Trip
unfinished test plan, so that accidental Trip LA
power-off wont affect the whole test plan Trip LB
Trip LC
Sig.1 Sig.8

These names will be associated with the


report.

We can also modify these names according to


our own wish in the column of Display Name

For the selected binary inputs we can


configure them as OR logic or AND logic.

23
PowerTest Basic Concept

OR logic 1.8.17 Test equipment


Indicating OR logic. When any of the selected
binary input meets with the trigger condition information
the current test process will be terminated.
When the communication between test
equipment and external PC is setup we can
select from drop-down menu Help the option
of About Test Set to get some basic hardware
information of test equipment in use.

In above example binary 1 and 2 are defined


as OR logic. Any trigger operation of binary 1
or 2 will terminate the current test process.

AND logic Then we can see the following message


Indicating AND logic. When all of the selected screen.
binary input meets with the trigger condition
the current test process will be terminated.

In above example binary 1 and 2 are defined


as AND logic. Only when both of them meet
the trigger condition then the current test
process will be terminated.

24
PowerTest Basic Concept

1.8.18 Control test process State control button

This button is used in some modules where we


We can use the follow 4 quick control buttons use this button to manually switch from one
to control the test process
state to the next one
----------------------------------------------
Note: More detailed information will be
provided on the use of this button in modules
where this button is used.
Start the test
----------------------------------------------
Stop the test
Used in some modules to switch Pause the test
from one state to the next one We can temporally stop the test by pressing
Pause the test and click again the this pause button. Then the button will have
resume the test the following look

Start the test

After test is started one message will pop-up to At the same time a message will pop-up
indicate the current test status

If we press this button again the test will be


Stop the test resumed
After test is started the stop button will be
activated for stop action.
----------------------------------------------
button is activated Note: More detailed description on
is available in the module where this control
If we press this button we will stop the test and button will be used
the button will become inactivated. ----------------------------------------------

button becomes inactivated

25
PowerTest Basic Concept

Voltage (LL)
II. Setup
The System & IEC, AuxDC, Binary, License Here we need to give the nominal secondary
and IP Set are located in this menu. voltage of PT which is connected to the relay
voltage input.

If we know the L-N voltage we can get the L-L


voltage with the following calculation.

V ( LN ) = V ( LL) / 3

Current
Here we need to give the nominal secondary
current of CT which is connected to the relay
current input.

2.1 System & IEC Frequency

In the start page we can set some basic Here we need to define the system frequency
system settings which will be applicable for all
test modules. Debounce time
This time will be used to filter the bouncing of
Click to enter into output contact of the relay under test.
the setting page.
Example:

In above example the relay contact is


experiencing bouncing process. The duration
of T1-T4 are all less than 3ms. So these T1-T4
bouncing will not be sensed by our test
software. The T5 sensed by the test software
because its duration is longer than 3ms.

26
PowerTest Basic Concept

By default we set 3ms here. Customer needs Set Type


to make necessary modification if this setting
can not meet the test requirement.
All of PONOVO kits output analog except PWF
The setting range is 0-25ms and POM2 serial relay testers.
When test is over we will consider this PWF only outputs digital.
debounce time in our tripping time calculation POM2 ouputs both analog and digital.
So that no extra error will be added to tripping
time result.

Model
The PowerTest software can be used by
different model of our relay test sets. Before GOOSE Subscription
we enter into the test page customer needs to
select the model he is going to use

----------------------------------------------
Note: GOOSE Subscription and publish are
optional.
----------------------------------------------
The tester has to subscribe GOOSE
Set Com information when it receives the tested relays
GOOSE signal. The GOOSE can subscribe
Here we need to define the communication some information under the MAC address.
port of the relay test set. By default Ethernet When subscribing, the following specifications
will be set here. have to be set: 1) GOOSE control reference; 2)
GOOSE ID; 3) Application ID;4) MAC Address,
or only MAC Address is set to receive GOOSE
information.
Map GOOSE data such as the data for tripping
signal to the Binary Input on the tester. When

27
PowerTest Basic Concept

the tester receives GOOSE information, the


change of information status will be reflected
on the related binary input. The testing
software will judge the operation status
according to the binary situation.
Data SB. means the sequence of the Dataset
Click Open to
of the testing data. The number begins with enter into
figure 1. software interface
as 1-8
GOOSE Subscription includes manual setting
and auto setting.
Manual setting
If there are no setting documents of the Fig. 1-17 selecting SCL document
tested relays, it needs manual setting.
1) Get GOOSE configuration
information by capturing tool such as
MMS ETHEREAL and input it to the
related configuration frame.
2) Map by GOOSE data and binary:
Input Data SB., put the cursor after
binary and left-click Map.

Automatic setting
Click lead-in SCL document in the GOOSE
Subscription interface, open the tested relays
SCL (SCD, ICD, CID) setting documents.
According to the software configuration
Fig.1-18 Select IED (Intelligent electric device)
interface, the substation binary information
can be subscribed, and the GOOSE
information (GOOSE control reference,
GOOSE ID, Application ID, MAC Address) is
set automatically. The operation is executed
according to software showing in the figures
1-17~1-20

28
PowerTest Basic Concept

GOOSE parameter is relative to the


Indicating the subscribed parameter. The GOOSE
IED has GOOSE parameter and GOOSE Data structures
information
Double-click to show must comply with the configuration of the
the configuration relays.
information as figure
1-23
The meaning of GOOSE parameters:

After confirmation, the GOOSE Control Reference: Goose


GOOSE subscription
parameter will be set
Control Block reference (Object
automatically showing as Reference), data NR with maximum 65
figure 1-24 bits.
GOOSE ID:The GOOSE Identifier (string),
data NR with maximum 65 bits.
Fig.1-19 select configuration information APPID:GOOSE application identifier
MAC address: range 01-0C-CD-01-00-00
To 01-0C-CD-01-01-FF
GOOSE Publish Time Allowed to Live: Unit: millisecond
DatSet: data NR with maximum 65 bits
NdsCom: boolean
Test: Boolean, Specifies the status of the
GOOSE test bit (0=False, 1=True = Test
Mode )
VLANVirtual Local Area Network
VLAN Priority
When the tester connects with switchboard,
VLAN and VLAN priority need to set. The
manufacturer has to provide the values.

The type of GOOSE Data:

There are six kinds of editable data in GOOSE


The tester can also analog other intelligent publication data: BOOLEAN, Unsigned Integer,
device to publish GOOSE information. For UTCTime, BitString, Float and dual-position
example, if it is going to test the reclosing remote signal, shown in the table 1-3.
time, the tester has to analog intelligent
operation box to publish GOOSE signal of
circuit breaker to meet the reclosing
requirements.
GOOSE information will be transmitted in
substation by multicasting. When receiving
GOOSE information, it has to confirm if the

29
PowerTest Basic Concept

Table 1-3 the expression ways of data completed automatically. The configuration
type process is shown in the Fig.1-21~1-24.

Data type Expression ways


True or False or out1
(2, 3, 4)
If the data is OUT1, it
Boolean maps with binary
output. The value is
controlled by binary Click Open and
enter into the
output. interface as 1-28
Decimalinteger such
Unsigned Integer
as 12
UTC Time UtcTime
[Data NR. With 1,0]
BitString Fig. 1-21 Select SCL document
(such as:[110000])
Float mm.yy(such as 1.2)
[10] occlusion position
Dual-position
[01] Lane place
remote
[11] Fault status Select IED device.
signal
[00] Maintenance status

The two ways of getting GOOSE parameter Click OK to enter


and GOOSE Dataset structure: into interface as
1) Provided by protection device Figure 1-29
manufacture or substation.
2) Getting by capturing GOOSE
document (These GOOSE message
are sent by other intelligent device. Fig.1-22 Select IED
The device may be other protective
device or intelligent operation box.)

Two kinds of configuration methods:


automatic setting and manual setting
Automatic setting

In the GOOSE publication interface (Fig.1-16),


click lead-in SCL document to open the
configuration documents of tested SCL (SCD,
ICD, CID). Select the tested IED according to
software indication. The data system of
GOOSE parameter and GOOSE Dataset are

30
PowerTest Basic Concept

Double click and


show the Fiber interface
configuration
Indicate the IED
information in Figure
has GOOSE
1 30
information

Fiber-electric converter
Click OK, and the
GOOSE publication
parameter sets
automatically showing in
Fig. 1-26 Wiring diagram of GOOSE fiber
Figure 1-31 interface

Fig. 1-23 Select configuration information

Manual setting
Data

Manual setting includes manual setting


GOOSE parameter and GOOSE publication
data. We take reclosing time as an example.
In order to get GOOSE configuration Fig. 1-27 GOOSE message
parameter and GOOSE Dataset, MMS
1) Set GOOSE parameter manually
Ethereal tool can be used to get GOOSE
message sent by intelligent operation box. If Manually set GOOSE parameter and
the GOOSE interface is electricity interface GOOSE dataset structure (including
number of data member and type) in
such as RJ45, the wiring diagram is the Fig.
publication interface (shown in Fig. 1-16)
1-25. If it is fiber interface, the wiring diagram
is the Fig. 1-26. The captured GOOSE according to captured GOOSE message.
2) Edit GOOSE dataset
message is shown in Fig.1-27. It clearly shows
Edit every data value in the GOOSE
the GOOSE parameter and data system (16
BOOLEAN style data). dataset according to testing requirement.
If it is BOOL type data, the data can be
Electricity interface mapped with binary output and the data
value (0 or 1) is controlled by binary
output (close or open).
We take a test as an example (shown in
Electricity Figure 1-28) to indicate. Click GOOSE
converter or Hub publication data and click lead-in, the
GOOSE dataset structure will be
Fig. 1-25 Wiring diagram of GOOSE electricity displayed in the data edition window
interface (Figure 1-29) and the data is separated by

31
PowerTest Basic Concept

comma. User can edit publication data at


the related position of this window.
We cite two examples to explain the
edition methods. GOOSE
publication

Analog intelligent operation box to send


circuit breaker position signal (Suppose
the breaker is closed.)
It is known from the message of intelligent
operation box that it sends out 16
BLOOEAN type data, and the first data is
the breaker position signal from the relay
user manual (True means that the breaker Fig.1-28 General test(4V,3I)
is closed. False means it is opened.)
Other 15 signals also have specified
meaning. To be short, all of them are set
as False. See the edited data in Fig.
1-29.
Analog other GOOSE information sent by
IED
Suppose that the IED send out 5 data, in
which the first two are BOOLEAN, the
third is integral number, the fourth is
BitString type and the fifth is standard
time, UTC time type. Fig.1-29 GOOSE data edition window
Instruction of data edition: The first data is
controlled by binary output 1 (variable Users refer to the instruction for output form of
SMV in User Manual-IEC61850-EN.
name is OUT1), and the value (0 or 1) is
confirmed by binary output status (open or
close). The second, third and fourth data
are set as True, 66, 110000 randomly.
The fifth data is set as UTCtime (the tester
will send the current time of the system.)
See the data in Figure 1-30.

32
PowerTest Basic Concept

2.2 AuxDC Drag the cursor to the setting position and click
OK to confirm the setting.

Here we can set the Auxiliary DC for driving


the relay which requires DC power supply. To stop the auxiliary DC output we need to
enter into the above setting page and set drag
Here we can set the Auxiliary DC for driving the cursor to OFF position.
the relay which requires DC power supply.

The auxiliary DC voltage will be generated


at the moment we start the test and will
remain active when we change from test
module to test module.

We can also set the auxiliary DC in the test


page by selecting AuxDC in Settings of
drop-down menu

Click OK button to confirm this operation.

Then we can see the setting page as shown


bellow.

33
PowerTest Basic Concept

2.3 Binary Example: setting potential contact

Suppose the potential contact has a threshold


Here we can set binary input forms (dry of 90V. Bellow 90V the potential contact is to
contact or threshold and power level) be regarded as closed status in the software.
When the contact status changes the voltage
For relay test set with adjustable threshold we applied to the binary input will jump to 220V.
need to configure the binary input We can set any one of the 8 binary inputs. In
characteristic and/or threshold here. this example we are going to set binary input
1.
Click Binary to enter into the setting page.

----------------------------------------------
Note: We can increase the threshold
setting to avoid possible electromagnetic noise
at the site. For example we can set 110V in
this example
----------------------------------------------

Potential Free
For potential free contact customer needs to In the example above the low status voltage is
select the potential free box for the binary input 90V, lower than the threshold setting of 110V.
to be used. In that case the setting for When potential status changes the voltage will
threshold will be prohibited. jump to 220V and this status will be regarded
as open status in the software.
Threshold
For potential contact customer needs to set The AC signal can be injected in the binary
the threshold here. input, but the triggering voltage should be set
based on the peak value.
The threshold is the point where potential For example: when the triggered AC voltage is
contact changes from high status to low status 220V, the required value is
or from low status to high status. 110*1.4142=155.56V. Please type in trigger
voltage 115V.
Close status Considering the error, the triggering voltage is
For potential free or potential contact customer suggested to be decreased by 10% to avoid
can associate its actual status with that to be the mal-function. For example: in the DC 110V,
displayed in the software. For example, we the injected voltage is 108V that is normal in
can define the high status of potential contact the protection system, but in the kits, it does
as the closed status in the software, or vice not meet the trigger voltage and not trigger.
versa.

34
PowerTest Basic Concept

License
It is used to check the authorization
information of all test templates.

This is used to check information of modules


authorization.

Example:

Step1: Press in the main


interface and select the modules.

Step2: Check modules authorization.

35
PowerTest Basic Concept

Open template from test page


III. Test Manager
We can also open the template from the test
page.

In the test page drop-down menu select


Template and select open. Then we need to
select template file from the place where its
saved.

Open template from report

If we have save the test report in PowerTest


3.1 Templates format with the extension of rpt we can also
open the template through opening this report
There are three ways to open the test in any module.
templates.
rpt format test report can be opened in the test
module. At the same time the template
Open template from start page information contained in the report will also be
opened.
Click the Templates button in the start page
and select the template file from the folder
where the template file is saved. Then we will
enter into the test page automatically with test
modules containing in this template. The test
parameters and relay settings in the saved
template will also be uploaded here.

36
PowerTest Basic Concept

3.2 Report Example: distance test report in word format


There are two type of report formats in
PowerTest software.

Report in rpt format


This type of report does not allow any editing
operation. And it contains also the template
information of the module used. When we
open this report in any module both content of
the report and all settings/test parameters
weve set for that test will be uploaded.

Report in Word format


Work format report is allowed for any editing
operation.

Report generation User defined logo in the report


To use his own company logo in the report
To generate rpt format report click customer can simply replace the bmp format
logo file in the installation directory of
To generate word format report click PowerTest with his own logo file with same file
format and name.

Example: distance test report in rpt format

37
PowerTest Basic Concept

Report head setting 3.3 Test Plan


In the drop-down menu we can select Setting This part is reserved.
to configure what is to be included in the report
head.

The follow setting screen will the appear

Select the items we want to include in the


report and click OK to confirm the operation.

38
PowerTest Basic Concept

IV. Calibration GPS Instruction


In this part, it is optional. Users can consult
with PONOVO for detailed information. GPS: Test state will be switched to the next
one if GPS pulse signal is received. GPS
signal trigger condition means the end of the
current state (after output 50ms) and begin of
next state.
V. Support
GPS is usually used in the ends of line
differential protection to make online test. It
requires the current as 0 before
synchronization output. If the GPS is set as the
first state (before fault), there should not be
current output. If the first state has current
output, it will make the first state protection trip
since the outputs of both sides is not
synchronized.

Example:
The line differential protection is made by
simulating phase A fault in State Sequence.
The following is the parameter setting.

Users press to get related


documents and press to
enter into PONOVO website seeking online
support.

39
PowerTest Basic Concept

It is waveform output.

From the waveform, there is a 50mS state


waveform output after receiving GPS signals.
The waveform is synchronized at both ends at
this time.

40