Coordinate mode
Boiler follow mode
Turbine follow mode
Manual mode
Coordinate mode- In this mode the target load is set through CMC
unit demand. Unit load demand is fed to Boiler Master to generate
Boiler demand i.e. Air & Fuel requirement and to Turbine Control
to set Turbine demand i.e. MW. In this mode both Boiler Master
and Turbine Control are put in Auto and unit load demand is fed
to both Boiler and Turbine to compute their individual load
demands. The load demand signal will be added or subtracted
according to the actual throttle pressure (as pressure correction)
before going to EHG (1kg/cm2=1MW) & Boiler Master.
Boiler follow mode: In this mode, the Turbine takes lead and
the boiler follows. It is adopted when Turbine control
(EHG) is in Manual. The turbine sets the MW load and the
boiler controls throttle pressure as a follower. Whenever
capabilities of TG are exceeded or limited, the boiler shall
follow the turbine load.
Turbine follow mode: In this mode Boiler takes lead and the
Turbine follows. MW is controlled by the Boiler while throttle
pressure is maintained by the turbine. The load demand signal
will be added by Throttle pressure difference before going to
EHG. This mode maybe used for run back action.
Note :- Run Down, Run UP & Run Back will work only when machine
is in CMC Mode.
PROCEDURE FOR PUTTING INTO CMC Mode
MS PR SP
U
N
I
T
L BOILER MASTER
O
A
D
S
P