Automatic
Transfer
Switches

O-S ung E lectric M achinery CO., LTD.


Outstanding technology captivates the world!
Superior Quality satisfies our customers!

Contents
Information to Order 3
OSS - TN, TBN Type (60~600A) 4
Features / Application and Selection / Specification
Outline Dimension / Wiring Diagram
OSS - PC Type(800~6300A) 8
Features / Specification
OSS - PSO Type(400~6300A) 9
Features / Function of Overlapping Neutral Contact
Location needed for overlapping neutral contact
N-phase Transfer / Limits of 4P Transfer
Specification / Outline Dimension
OSS - PC, PSO Type 11
Outline Dimension / Wiring Diagram
Typical Operating Circuit
OSS-PCN Type(400~3200A) 18
Features / Specification
Outline Dimension/Wiring Diagram/Typical Operating Circuit
OSS-PSU Type(400~3200A) 24
Features / The feature of sensitive load by voltage sag
Uses / CBEMA Curve
Advantages / Specification
OSS-CTTS Type(400~3200A) 26
Features / Application
Transfer of Conventional ATS
Transfer of CTTS / Specification
OSS-PSU, CTTS Type(400~3200A) 28
Outline Dimension/Wiring Diagram
OSS-PSB Type 31
Features / Outline Dimension
ATS Controller(ACD21/ACSD/ACD ) 33
External View / Specification
Basic Function / In-phase Monitor
Ordering Information / Wiring Diagram
Outline Dimension

2 I Automatic Transfer Switches


Information to Order OSS - 6 - - P-
A B C D
A Rated Current B Type C Number of Poles D Operating Voltage
06 1 2 4 6 TN : TN-Type 2 : 2P A1 : AC 110V
TBN : TBN-Type 3 : 3P A2 : AC 220V
60A 100A 200A 400A 600A 4 : 4P D1 : DC 110V
D2 : DC 125V

OSS - 6 - - P - -
A B C D E
A Rated Current
04 06 08 10 12 16 20 25 32 40 50 63
400A 630A 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6300A

B Type C Number of Poles D Operating Voltage E Mounting System


PC : PC-Type 3 : 3P A1 : AC 110V F : Fixed
PCN : PCN-Type 4 : 4P A2 : AC 220V D : Draw out
PSO : PSO-Type D1 : DC 110V
PSU : PSU-Type D2 : DC 125V
CTTS : CTTS-Type

OSS - PSB - 6 - - P-
A B C D
A Rated Current
04 06 08 10 12 16 20 25 32
400A 630A 800A 1000A 1250A 1600A 2000A 2500A 3200A

B Type C Number of Poles D Operating Voltage


PSU : PSU-Type 3 : 3P A1 : AC 110V
CTTS : CTTS-Type 4 : 4P A2 : AC 220V
D1 : DC 110V
D2 : DC 125V

Automatic Transfer Switches I3


OSS - TN, TBN Type ATS(60~600A)

Features
Off position stop method Excellent Breaking Capacity
In case with the uninterrupted power system, it is recommended to stop at the Designed for suffciently large chamber to extinguish the arc when transferred.
OFF position set by tripping mechanism for the stable power. Instantaneous Arc-extinguishing area is designed for convenient inspection and maintenance.
transfer without stop can be also performed by operating signal.
A Off B, B Off A, and A Off A, B Off B Protection against the remaining power source
And also, instantaneous transfer can be performed by operating signal. Time delay to transfer is available so that the remaining power can not be
induced to the main power to protect the load.
One-Coil Application
One-coil is employed for the transfer to normal power source and emergency Construction for Safety
power source.
For safe operation, molded construction is employed on breaking parts. And
Compact & Lightweight Design also, latching indicator is prepared to indicate the operating condition.
Compact & lightweight design makes the minimized mounting space and
convenient installation.

Application and Selection


Applicable Standards For TN type ATS, Sequence setting is required so that closing or tripping order
IEC 60947-6-1 JEM 1038 UL 1008 KSC 4504 KSC 0703 should not supply in the same direction.
Control Order Control Circuit
It is recommended to give more than 0.5 sec for operation, though transfer ATS is designed so that operation current should be off by internal switch
time is completed within 0.3 sec. after completion of operation.
Interlock If operation current is off with auxiliary switch of the unit, it may cause a
Interlocking is required for control circuit so that control order should not malfunction.
suppy to both A power source side and B power source side simultaneously.

Specification
606-TN, TBN 64-TN, TBN
TYPE 62-TN, TBN
61-TN, TBN 66-TN, TBN
Rated Operational Voltage Ue AC 600V, DC 125V
Rated Current Ie 60A, 100A 200A 400A, 600A
Neutral Phase Current 60A, 100A 200A 400A, 600A
Kind of Throw Double Throw
Connection Front(TN), Back(TBN)
Number of poles 2P 3P 4P 2P 3P 4P 2P 3P 4P
Weight 7kg 8kg 9kg 9kg 10kg 12kg 16kg 19kg 22kg
Rated Short-Time Withstand Current (1sec) Icw 5kA 10kA 12kA
Short-Circuit Making Capacity Icm 7.65kA 17kA 24kA
AC - 33B (6Ie making / 6Ie breaking cos = 0.5 )
Switching Capacity
DC - 31B (1.5Ie making / 1.5Ie breaking L/R = 1ms )
Switching Frequency 60Time / Hour
DC 110V ~ 125V 6A 6A 7A
Operating Current AC 100V ~ 110V 3A / 6A 3A / 6A 3.5A / 7A
rms/pick AC 200V ~ 240V 1.5A / 3A 1.5A / 3A 2A / 3.5A
Trip Coil Current DC 110V = 2.5A, AC 110A = 2.5A, AC 220V = 1.5A
Making 55 ms 55 ms 60 ms
A POWER
Breaking 20 ms 20 ms 25 ms
Operating Time
Making 80 ms 80 ms 90 ms
B POWER
Breaking 20 ms 20 ms 25 ms
Number of Operating Without Current 10,000
Cycles With Current 5,000
1. For complete operation, Be sure to provide control source for more than 0.5sec.
Cautions 2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.
3. Control Relay should be selected considering sufficient contact capacity to withstand against more than control current.

4 I Automatic Transfer Switches


OSS - TN, TBN Type ATS(60~600A)

Outline Dimension
60A, 100A 606-TN, 61-TN

200A 62-TN

400A, 600A 64-TN, 66-TN

* Arc space for main circuit


- 30mm for AC 220V
- 60mm for AC 660V

Automatic Transfer Switches I5


OSS - TN, TBN Type ATS(60~600A)

Outline Dimension
606-TBN~66-TBN

* Arc space for main circuit


- 30mm for AC 220V
- 60mm for AC 600V

PANEL CUTTING TERMINAL THICKNESS

6 I Automatic Transfer Switches


OSS - TN, TBN Type ATS(60~600A)

Wiring Diagram

Typical Operating Circuit

Standard Using a changeover switch

Using a timer Using a condensor tripping device

Automatic Transfer Switches I7


OSS - PC Type ATS(800~6300A)

Features
One coil mechanism Quick replacement of ATS
One coil mechanism is applied. If malfunction occurs, drawout type of ATS can be changed within 5 minutes.
Transfer indicator provided Perfect transfer mechanism
Transfer indicator is fitted to indicate the transfer status. By spring transfer mechanism, ATS can be completely and perfectly
transferred. There will be NO unattached position in any case.
Easier busbar arrangement
If the ATS is installed with the ACB in switchgear, Busbars can be easily Sufficient current capacity
arranged. Sufficient current carrying contacts are designed to withstand against over
current.
Fixed type & Drawout type available
Fixed type and Drawout type are available for customer's convenient Minimized opening & Closing impact
applicaion. Opening and closing impact is minimized.

Specification
TYPE 608-PC 610-PC 612-PC 616-PC 620-PC
Rated Voltage Ue AC 600V, DC 125V
Rated Current Ie 800A 1000A 1250A 1600A 2000A
Neutral Phase Current 800A 1000A 1250A 1600A 2000A
Kind of Throw Double Throw
Connection Back
Number of Poles 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
Fixed 55kg 65kg 55kg 65kg 60kg 70kg 65kg 75kg 90kg 110kg
Weight
Drawout 80kg 95kg 80kg 95kg 90kg 105kg 95kg 110kg 110kg 140kg
Rated Short-Time Withstand Curren (1sec) Icw 25kA 25kA 30kA 35kA 40kA
Short-Circuit Making Capacity Icm 52.5kA 52.5kA 63kA 73.5kA 84kA
AC-33B (6 Ie making / 6 Ie breaking cos = 0.5)
Switching Capacity
DC-31B (1.5 Ie making / 1.5 Ie breaking L/R=1ms)
Switching Frequency 60Time / Hour 20Time / Hour 10Time / Hour
DC 110V ~ 125V 45A 50A 65A
Operating Current
AC 100V ~ 110V 23A/45A 25A/50A 33A/65A
rms/pick
AC 200V ~ 240V 15A/30A 20A/40A 25A/50A
Change - over time 120 ms
Operating Time
Opening time 90 ms
Number of Operating Without Current 10,000 5,000
Cycles With Current 5,000 3,000
1. For complete operation, Be sure to provide control source for more than 0.5sec.
Cautions
2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.

TYPE 625-PC 632-PC 640-PC 650-PC 663-PC


Rated Voltage Ue AC 600V, DC 125V
Rated Current Ie 2500A 3200A 4000A 5000A 6300A
Neutral Phase Current 2500A 3200A 4000A 5000A 6300A
Kind of Throw Double Throw
Connection Back
Number of Poles 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
Fixed 90kg 110kg 100kg 120kg 180kg 220kg 185kg 230kg 200kg 250kg
Weight
Drawout 110kg 140kg 125kg 155kg 220kg 275kg 245kg 305kg 245kg 305kg
Rated Short-Time Withstand Current (1sec) Icw 50kA 50kA 65kA 65kA 65kA
Short-Circuit Making Capacity Icm 105kA 105kA 143kA 143kA 143kA
AC-33B (6 Ie making / 6 Ie breaking cos = 0.5)
Switching Capacity
DC-31B (1.5 Ie making / 1.5 Ie breaking L/R=1ms)
Switching Frequency 10Time / Hour
DC 110V ~ 125V 65A 80A
Operating Current
AC 100V ~ 110V 33A/65A 40A/80A
rms/pick
AC 200V ~ 240V 25A/50A 33A/65A
Change - over time 120 ms
Operating Time
Opening time 90 ms
Number of Operating Without Current 5,000
Cycles With Current 3,000
1. For complete operation, Be sure to provide control source for more than 0.5sec.
Cautions
2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.

8 I Automatic Transfer Switches


OSS - PSO Type ATS(400~6300A)

Feature
In addition to every function of OSS-PC Type ATS, OSS-PSO Type ATS has
additional function of Overlapping Neutal Contact.

Function of Overlapping Neutral Contact


When general ATS will be transferred, Arc will be generated between fixed
contacts and moving contacts. Thus, current flows between contacts and arc will
be eliminated when current will be at zero level. Eliminating time of arc is 10~12
msec. Therefore, various device of load side can be protected when neutral
contacts should be opened 10~12 msec later than other 3-phases contacts. Load
side devices of general ATS cannot be sufficiently protected because opening
time gap between neutral contacts and other 3-pase contacts is less thant 10
msec. in order to solve this problem, Overlapping between neutral contacts of A-
power (Normal) and B-power (Emergency) during transfer of switch functions to
protect various devices of load side more safely.
In addition, Non-linear load increases the earth potential and potentional
difference is occurred between earth and neutral line.
When general ATS will be transferred, Neutral line is separated from load and
reference potential difference cannot be established. Thus, Floating is occurred
and electronic devices can be malfunctioned. When ATS with overlapping neutral
contact will be applied, Floating can be protected.

Location needed for overlapping neutral contact


Broadcasting system and telecommunication system Bank and computer center
Petrochemical plant Military communication system and radar facilities
Arc furnace Large harmonic load (Elevator & Escalator, etc.)

N-phase Transfer Limits of 4P Transfer


Opening neutral wire is forbidden.
The neutral is the common reference to 3-phases.

If N-phase will be opened, Ph/Ph voltage can go up to 400V.


For transfer of 4P, Overlapping of N-phase is necessary

Automatic Transfer Switches I9


OSS - PSO Type ATS(400~6300A)

Specification
TYPE 604-PSO 606-PSO 608-PSO 610-PSO 612-PSO 616-PSO
Rated Optional Voltage (VAC) Ue 600
Rated insulation Voltage (VAC) Ui 600
Rated impulse withstand Voltage (VAC) Uimp 8000
Rated Current Ie 400A 630A 800A 1000A 1250A 1600A
Neutral Phase Current 400A 630A 800A 1000A 1250A 1600A
Kind of Throw Double Throw
Connection Back
Number of Poles 4P
Fixed 70 75 80 85
Weight
Drawout 100 105 115 120
Rated Short-Time Withstand Current (1sec) Icw 25kA 30kA 35kA
Rated Short-Circuit Making Capacity Icm 52.5kA 63kA 73.5kA
AC-33B(10 le making/10 le breaking cos = 0.35)
Switching Capacity
DC-31B (1.5 Ie making / 1.5 Ie breaking)
Switching Frequency 60Time / Hour 20Time / Hour
DC 110V ~ 125V 45A 50A
Operating Current
AC 100V ~ 110V 23A/45A 25A/50A
rms/pick
AC 200V ~ 240V 15A/30A 20A/40A
Change - over time 120 ms
Operating Time
Opening time 90 ms

Number of Operating Without Current 10,000


Cycles With Current 5,000

Cautions 1. For complete operation, Be sure to provide control source for more than 0.5sec.
2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.

TYPE 620-PSO 625-PSO 632-PSO 640-PSO 650-PSO 663-PSO


Rated Optional Voltage (VAC) Ue 600
Rated insulation Voltage (VAC) Ui 600
Rated impulse withstand Voltage (VAC) Uimp 8000
Rated Current Ie 2000A 2500A 3200A 4000A 5000A 6300A
Neutral Phase Current 2000A 2500A 3200A 4000A 5000A 6300A
Kind of Throw Double Throw
Connection Back
Number of Poles 4P
Fixed 110 120 220 230 250
Weight
Drawout 140 155 275 305 305
Rated Short-Time Withstand Current (1sec) Icw 40kA 50kA 65kA
Rated Short-Circuit Making Capacity Icm 84kA 105kA 143kA
AC-33B(10 le making/10 le breaking cos = 0.35)
Switching Capacity
DC-31B (1.5 Ie making / 1.5 Ie breaking)
Switching Frequency 10Time / Hour
DC 110V ~ 125V 65A 80A
Operating Current
AC 100V ~ 110V 33A/65A 40A/80A
rms/pick
AC 200V ~ 240V 25A/50A 33A/65A
Change - over time 120 ms
Operating Time
Opening time 90 ms

Number of Operating Without Current 5,000 3,000


Cycles With Current 3,000 1,500

Cautions 1. For complete operation, Be sure to provide control source for more than 0.5sec.
2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.

10 I Automatic Transfer Switches


OSS - PC Type

Outline Dimension 800~1600A Fixed


unit : mm

OSS-608~610-PC

OSS-612-PC

OSS-616-PC

Automatic Transfer Switches I11


OSS - PC, PSO Type

Outline Dimension 400~3200A Fixed


unit : mm

OSS-604~616-PSO

OSS-604~610-PSO

OSS-612~616-PSO
OSS-620~625-PC,PSO

OSS-620~625-PC

OSS-620~625-PC, PSO

OSS-632-PC, PSO

OSS-632-PC

OSS-632-PC, PSO

12 I Automatic Transfer Switches


OSS - PC, PSO Type

Outline Dimension 4000~6300A Fixed


unit : mm

OSS-604-PC, PSO

OSS-640-PC

OSS-640-PC, PSO
OSS-650~663-PC, PSO

OSS-650~663-PC

OSS-650~663-PC, PSO

Automatic Transfer Switches I13


OSS - PC Type

Outline Dimension 800~1600A Draw Out


unit : mm

OSS-608~610-PC

OSS-612-PC

OSS-616-PC

14 I Automatic Transfer Switches


OSS - PC, PSO Type

Outline Dimension 400~3200A Draw Out


unit : mm

OSS-604~616-PSO

OSS-604~610-PSO

OSS-612~616-PSO

OSS-620~625-PC, PSO

OSS-620~625-PC

OSS-620~625-PC, PSO
OSS-632-PC, PSO

OSS-632-PC

OSS-632-PC, PSO

Automatic Transfer Switches I15


OSS - PC, PSO Type

Outline Dimension 4000~6300A Draw Out


unit : mm

OSS-640-PC, PSO

OSS-640-PC

OSS-640-PC, PSO

OSS-650~663-PC, PSO

OSS-650-663-PC

OSS-650-663-PC,PSO

16 I Automatic Transfer Switches


OSS - PC, PSO Type

Wiring Diagram
AC 110V, AC 220V DC 110V, DC 125V

Typical Operating Circuit


Standard Using a changeover switch Using a timer

Wiring Diagram
AC Operating and Control DC Operating and Control

Caution : More than 2.5mm2 power cable used for less than 1,600A ATS.
More than 4.0mm2 power cable used for more than 2,000A ATS.

Automatic Transfer Switches I17


OSS-PCN Type ATS(400~3200A)

Features
Neutral position is functioned to cut off both power sources
In case UPS is applied, It is available to transfer to neutral position by tripping mechanism after checking
circuit stability and safety instaneous transfer as follows. A Off B, B Off A and A Off
A, B Off B instaneous transfer can be avaiable also by operating signal.
Sufficient contact capacity against accidental current.
(20 times of operating current)
On-load break and make type.
Easy busbar arrangement.
Prevent the simultaneous closing by complete mechanical and electrical tripping mechanism
Current carrying capacity of of N-phase is 100% same as other phases.
N-phase is closed earlier and opened later.

Specification
TYPE 604-PCN 606-PCN 608-PCN 610-PCN 612-PCN
Rated Operational Voltage (VAC) Ue 600
Rated insulation Voltage (VAC) Ui 600
Rated impulse withstand Voltage(VAC) Uimp 8000
Rated Current le 400A 630A 800A 1000A 1250A
Neutral Phase Current 400A 630A 800A 1000A 1250A
Kind of Throw Double Throw
Connection Back
Number of poles 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
Fixed 60 70 60 70 65 75 65 75 70 80
Weight (kg) 130 145 130 145 135 150 135 150 145 160
Drawout
Rated Short-time Withstand Current(1sec) Icw 20kA 25kA 30kA
Rated Short-circuit Making Capacity Icm 40kA 52.5kA 63kA
AC-33B(10 Ie making/10 Ie breaking cos = 0.35)
Switching Capacity
DC-31B(1.5 Ie making/1.5 Ie breaking)
Switching Frequency 50A 60A
DC 110V~125V 50A 60A
Operating Current
AC 100V~110V 25A / 50A 30A / 60A
rms / pick
AC 200V~240V 20A / 40A 25A / 50A
Making 120ms
"A"Power
Breaking 90ms
Operating Time
Making 150ms
"B"Power
Breaking 90ms
Number of Without Current 10,000
Operating Cycles With Current 5,000
1. For complete operation, Be sure to provide control source for more than 0.5sec.
Cautions 2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.

TYPE 616-PCN 620-PCN 625-PCN 632-PCN


Rated Operational Voltage (VAC) Ue 600
Rated insulation Voltage (VAC) Ui 600
Rated impulse withstand Voltage(VAC) Uimp 8000
Rated Current le 1600A 2000A 2500A 3200A
Neutral Phase Current 1600A 2000A 2500A 3200A
Kind of Throw Double Throw
Connection Back
Number of poles 3P 4P 3P 4P 3P 4P 3P 4P
Fixed 75 85 105 125 105 125 110 130
Weight (kg)
Drawout 150 165 165 195 165 195 180 210
Rated Short-time Withstand Current(1sec) Icw 35kA 40kA 50kA
Rated Short-circuit Making Capacity Icm 73.5kA 84kA 105kA
AC-33B(10 Ie making/10 Ie breaking cos = 0.35)
Switching Capacity
DC-31B(1.5 Ie making/1.5 Ie breaking)
Switching Frequency 20Time /Hour 10Time /Hour
DC 110V~125V 60A 65A
Operating Current
AC 100V~110V 30A / 60A 33A / 65A
rms / pick
AC 200V~240V 25A / 50A 25A / 50A
Making 120ms
"A"Power
Breaking 90ms
Operating Time
Making 150ms
"B"Power
Breaking 90ms
Number of Without Current 10,000 5,000
Operating Cycles With Current 5,000 3,000
Cautions 1. For complete operation, Be sure to provide control source for more than 0.5sec.
2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.

18 I Automatic Transfer Switches


OSS-PCN Type ATS(400~3200A)

Outline Dimension 400~1600A Fixed


unit : mm

OSS-604~610- PCN

OSS-612-PCN

OSS-616-PCN

Automatic Transfer Switches I19


OSS-PCN Type ATS(400~3200A)

Outline Dimension 400~1600A Draw Out


unit : mm

OSS-604~610-PCN

OSS-612-PCN

OSS-616-PCN

20 I Automatic Transfer Switches


OSS-PCN Type ATS(400~3200A)

Outline Dimension 2000~3200A Fixed


unit : mm

OSS-620~625-PCN

OSS-632-PCN

Automatic Transfer Switches I21


OSS-PCN Type ATS(400~3200A)

Outline Dimension 2000~3200A Fixed


unit : mm

OSS-620~625-PCN

OSS-632-PCN

22 I Automatic Transfer Switches


OSS-PCN Type ATS(400~3200A)

Wiring Diagram

AC 110V, AC 220V DC 110V, DC 125V

Typical Operating Circuit

AC Operating and Control DC Operating and Control

Automatic Transfer Switches I23


OSS-PSU Type ATS(400~3200A)

Features
OSS-PSU Type is a UPS-class uninterruptible transfer switch. Differently from the
ATS of other products, switching is done within 8ms with synchronization and the
possible accidents caused by contact during switching in open state may be basically
prevented.

Switching speed: within 8ms


The feature of sensitive load by voltage sag
Several suppliers and organizations conducted the tests on the features of voltage
sag of the devices using signal generators to generate voltage sag with various
voltages and duration time. Such features of the voltage sag of susceptible devices
are used as the industrial standards.

Uses
When power cut is noticed in advance by the Nomal Power
When there has been no notice of power cut by the Nomal Power but momentary
power failure is expected
When Nomal Power recovered its function and switching is required from the
generator to Nomal Power
When there has been no notice of power cut by the Nomal Power but it is
required to test a generator or other equipment

Patent No. 10-0730045


Patent No. 10-0804506

CBEMA Curve
CBEMA (Computer Business Equipment Manufacturers Association) curve is suggested in ANSI/IEEE Standard 446-1987, IEEE Recommended
Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications and this curve is applied in the manufacturing
industry of computers susceptible to voltage change.

Advantages
As switching is done in the state that the power
qualities of both sources are stabilized, the generator
may be protected with extension of its lifetime.
(Momentary inrush current may damage the generator.)

Motor: 6 times / transformer: 20 times / other loads: 5


times

The duration of time to use UPS and batteries is


reduced resulting in trouble reduction and lifetime
extension.

If power failure is made within 8.33ms, the PC does not recognize the power failure.

24 I Automatic Transfer Switches


OSS-PSU Type ATS(400~3200A)

Specification
TYPE 604-PSU 606-PSU 608-PSU 610-PSU 612-PSU
Rated Optional Voltage (VAC) Ue 600
Rated insulation Voltage (VAC) Ui 600
Rated impulse withstand Voltage (VAC) Uimp 8000
Rated Current Ie 400A 630A 800A 1000A 1250A
Neutral Phase Current 400A 630A 800A 1000A 1250A
Kind of Throw Double Throw
Connection Back
Number of Poles 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
Fixed 70 80 70 80 70 80 70 80 80 90
Weight
Drawout 95 120 95 120 95 120 95 120 110 125
Rated Short-Time Withstand Current (1sec) Icw 25kA 35kA
Rated Short-Circuit Making Capacity Icm 52.5kA 73.5kA
AC-33B(10 le making/10 le breaking cos = 0.35)
Switching Capacity
DC-31B (1.5 Ie making / 1.5 Ie breaking)
Switching Frequency 60Time / Hour 20Time / Hour
DC 110V ~ 125V 65A
Closing
Operating Current AC 100V ~ 110V 33A/65A
coil
rms/pick AC 200V ~ 240V 25A/50A
Trip coil DC110~125V=15A, AC100~110V=15A, AC200~240V=7A
A Making 100 ms
Power Breaking 60 ms
Operating Time
B Making 100 ms
Power Breaking 60 ms
Number of Operating Without current 10,000
Cycles With current 5,000

Cautions 1. For complete operation, Be sure to provide control source for more than 0.5sec
2. When control source will be provided to A side and B side simultaneously,Coil may be damaged.

TYPE 616-PSU 620-PSU 625-PSU 632-PSU


Rated Optional Voltage (VAC) Ue 600
Rated insulation Voltage (VAC) Ui 600
Rated impulse withstand Voltage (VAC) Uimp 8000
Rated Current Ie 1600A 2000A 2500A 3200A
Neutral Phase Current 1600A 2000A 2500A 3200A
Kind of Throw Double Throw
Connection Back
Number of Poles 3P 4P 3P 4P 3P 4P 3P 4P
Fixed 80 90 95 115 95 115 105 125
Weight
Drawout 110 125 115 145 115 145 130 160
Rated Short-Time Withstand Current (1sec) Icw 35kA 40kA 50kA
Rated Short-Circuit Making Capacity Icm 73.5kA 84kA 105kA
Switching Capacity AC-33B(10 le making/10 le breaking cos = 0.35) DC-31B (1.5 Ie making / 1.5 Ie breaking)
Switching Frequency 20Time / Hour 10Time / Hour
DC 110V ~ 125V 65A 100A
Closing
coil AC 100V ~ 110V 33A/65A 50A/100A
Operating Current
AC 200V ~ 240V 25A/50A 35A/70A
rms/pick
Trip coil DC110~125V=15A, AC100~110V=15A, AC200~240V=7A
A Making 100 ms
Operating Time Power
Breaking 60 ms
B Making 100 ms
Power Breaking 60 ms

Number of Operating Without current 10,000 5,000


Cycles With current 5,000 3,000
Cautions 1. For complete operation, Be sure to provide control source for more than 0.5sec. 2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.

Automatic Transfer Switches I25


OSS-CTTS Type ATS(400~3200A)

Closed Transition Transfer Switch (ATS)

Feature
CTTS permits the transfer of electrical loads under overlapping condition within
50ms without power interruption. The switch transfers in a make-before-break
mode if both sources are within acceptable parameters.
When normal power will be failed, Switch will be transferred as conventional
non-overlapping mode.
Functioned to withstand the inrush overvoltage.

Application
Transfer without power interruption against previous notice of power failure.
Transfer without power interruption against expected instantaneous power
failure.
Retransfer from emergency power source to normal power source.
Testing of generator without power interruption.

Patent Application #2007-0074372

Transfer of Conventional ATS Transfer of CTTS

26 I Automatic Transfer Switches


OSS-CTTS Type ATS(400~3200A)

Specification
TYPE 604-CTTS 606-CTTS 608-CTTS 610-CTTS 612-CTTS
Rated Optional Voltage (VAC) Ue 600
Rated insulation Voltage (VAC) Ui 600
Rated impulse withstand Voltage (VAC) Uimp 8000
Rated Current Ie 400A 630A 800A 1000A 1250A
Neutral Phase Current 400A 630A 800A 1000A 1250A
Kind of Throw Double Throw
Connection Back
Number of Poles 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
Fixed 70 80 70 80 70 80 70 80 80 90
Weight
Drawout 95 120 95 120 95 120 95 120 110 125
Rated Short-Time Withstand Current (1sec) Icw 25kA 35kA
Rated Short-Circuit Making Capacity Icm 52.5kA 73.5kA
AC-33B(10 le making/10 le breaking cos = 0.35)
Switching Capacity
DC-31B (1.5 Ie making / 1.5 Ie breaking)
Switching Frequency 60Time / Hour 20Time / Hour
DC 110V ~ 125V 65A
Closing
Operating Current AC 100V ~ 110V 33A/65A
coil
rms/pick AC 200V ~ 240V 25A/50A
Trip coil DC110~125V=15A, AC100~110V=15A, AC200~240V=7A
A Making 100 ms
Power Breaking 60 ms
Operating Time
B Making 100 ms
Power Breaking 60 ms
Number of Operating Without current 10,000
Cycles With current 5,000

Cautions 1. For complete operation, Be sure to provide control source for more than 0.5sec
2. When control source will be provided to A side and B side simultaneously,Coil may be damaged.

TYPE 616-CTTS 620-CTTS 625-CTTS 632-CTTS


Rated Optional Voltage (VAC) Ue 600
Rated insulation Voltage (VAC) Ui 600
Rated impulse withstand Voltage (VAC) Uimp 8000
Rated Current Ie 1600A 2000A 2500A 3200A
Neutral Phase Current 1600A 2000A 2500A 3200A
Kind of Throw Double Throw
Connection Back
Number of Poles 3P 4P 3P 4P 3P 4P 3P 4P
Fixed 80 90 95 115 95 115 105 125
Weight
Drawout 110 125 115 145 115 145 130 160
Rated Short-Time Withstand Current (1sec) Icw 35kA 40kA 50kA
Rated Short-Circuit Making Capacity Icm 73.5kA 84kA 105kA
Switching Capacity AC-33B(10 le making/10 le breaking cos = 0.35) DC-31B (1.5 Ie making / 1.5 Ie breaking)
Switching Frequency 20Time / Hour 10Time / Hour
DC 110V ~ 125V 65A 100A
Closing
coil AC 100V ~ 110V 33A/65A 50A/100A
Operating Current
AC 200V ~ 240V 25A/50A 35A/70A
rms/pick
Trip coil DC110~125V=15A, AC100~110V=15A, AC200~240V=7A
A Making 100 ms
Operating Time Power
Breaking 60 ms
B Making 100 ms
Power Breaking 60 ms
Without current 10,000 5,000
Number of Operating
Cycles With current 5,000 3,000
Cautions 1. For complete operation, Be sure to provide control source for more than 0.5sec. 2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.

Automatic Transfer Switches I27


OSS-PSU, CTTS Type ATS(400~3200A)

Outline Dimension 400~3200A Fixed


unit : mm

OSS-604~616-PSU, CTTS

OSS-620~625-PSU, CTTS

OSS-632-PSU, CTTS

28 I Automatic Transfer Switches


OSS-PSU, CTTS Type ATS(400~3200A)

Outline Dimension 400~3200A Draw Out


unit : mm

OSS-604~616-PSU, CTTS

OSS-620~625-PSU, CTTS

OSS-632-PSU, CTTS

Automatic Transfer Switches I29


OSS-PSU, CTTS Type ATS(400~3200A)

Wiring Diagram

30 I Automatic Transfer Switches


OSS-PSB Type

Feature
The bypass and isolation features of By-Pass ATS allows switch to be inspected, tested
and maintained without any interruption of power to the load.

Patent Registration #2006-0075750

Normal Operation By-Pass Switch Closed


Manual By-Pass Switch Manual By-Pass Switch

CTTS CTTS
Normal operation with CTTS Parallel operation without power interruption with the direction
to CTTS closing by manual By-Pass Switch.

Maintenance & Checking of CTTS Competely drawn CTTS without


power interruption
Manual By-Pass Switch Manual By-Pass Switch

CTTS CTTS
Maintenance & checking of CTTS without power interruption Maintenance & checking of CTTS without power interruption
under completely drawn CTTS by manual By-Pass Switch.

Automatic Transfer Switches I31


OSS-PSB Type

Outline Dimension
unit : mm

32 I Automatic Transfer Switches


ATS Controller ACD21/ACSD

External View
B-power source indicating LED for Emergency
A-power source indicating LED for Utility
ATS A-power transfer status indicating LED
SYC(In-phase Monitor) indicating LED
Selection switch of A-power source
Selection switch of B-power source
ATS B-power transfer status indicating LED
Selection switch of automatic or manual

Specification
Rated operating voltage : 220VAC
Frequency : 50 / 60Hz
Contacts capacity for ATS control : AC250V, 10A
(No-load contacts)
Contacts capacity for Abnormal power source : AC250V, 10A (No-load contacts)

Basic Function
Automatic or manual ATS control
Indicating lights for A-power (Utility), B-power (Emergency) and ATS transfer status
- Power source : A-power (Green LED), B-power (Red LED)
(Displayed when voltage is above 85%)
- Transfer status : A-power (Green LED), B-power (Red LED)
Manual operation buttons
- For A-power(Utility) : Green
- For B-power(Emergency) : Red
- Note : Built-in LED is on for selective button
Setting for automatic transfer time
- Time setting at rear side to avoid unnecessary setting change
- Variable time settings (0~30sec)
While timer is working, indicating lamp for transferable ATS is flickering
Detection for open phase of Utility power source
(For 3 4W, 220/380VAC only)
Detecting the power failure, low voltage and abnormal condition of Utility source, the ACD sends the engine
starting signal to the Generator.

n
Optio
In-phase Monitor
On & Off of In-Phase Monitor can be selected by selection switch
- When In-Phase Monitor is selected, Transfer is made manually or automatically when synchronized.
- When In-phase Monitor is not selected, synchronizing indication lamp is not on.
When synchronized, Yellow LED is flickered.
When synchronized more than 3 cycles, Tranfer will be made.
Under the manual mode, when the selection button is selected for Utility or Generator, Built in LED will be
flickering until synchronized.

Ordering Information
ACD21 (ATS control device) : Basic Function
ACSD (ATS control synchronizing device) : Built-in In-phase Monitor

Automatic Transfer Switches I33


ATS Controller ACD21/ACSD

Wiring Diagram
3 4W 380/220V 3 4W 220/127V 3 3W 220V

OSS - T, TB Type

OSS - TN, TBN Type

C_R~C_N A-power source


G_R, G_N B-power source
AP1, AP2 Operating signal of ATS A-power side
BP1, BP2 Operating signal of ATS B-power side
a1, a2 Aux a contacts of ATS A-power side
b1, b2 Aux a contacts of ATS B-power side
SS1, SS2 Starting signal of Generator
ADJ1 Delayed time setting of Utility side under Auto (0~30sec)

OSS - PC Type ADJ2 Delayed time setting of Emergency side under Auto (0~30sec)
SYC, S/W ON/OFF selection of In-phase Monitor (Option)
Aux contacts(a1a2, b1b2) of ATS should be connected. If not connected, automatic transferring
function will NOT work.

Outline Dimension

34 I Automatic Transfer Switches


ATS Controller ACD Controler

Specification Wiring Diagram


Rated operating voltage : 220VAC
Frequency : 50 / 60Hz OSS - PC Type
Contacts capacity for ATS control : AC250V, 10A
(No-load contacts)
Contacts capacity for Abnormal power source : AC250V, 10A
(No-load contacts)
Fitment : Front Type

Basic Function OSS - TN, TBN Type


Automatic or manual ATS control
Built-in indicator for A-power (Utility), B-power (Emergency)
and ATS transfer status
- Power source : A-power (Green LED), B-power (Red LED)
(Displayed when voltage is above 85%)
- Transfer status : A-power (Green LED), B-power (Red LED)
Manual operation buttons
- For A-power(Utility) : Green
- For B-power(Emergency) : Red OSS - T, TB Type
- Note : Built-in LED is on for selective button
Setting for automatic transfer time
- Transferring time setting is available at rear side to avoid
unnecessary touch.
- Variable time settings (0~30sec)
While timer is working, indicating lamp for transferable ATS
is flickering
Detection for open phase of Utility power source
(For 3 4W, 220/380VAC only)
Monitering for power failure, and low voltage of A power
and B power .
1 2W/220V

KA, KB A-power source


GA, GB B-power source
a1, a2 Aux a contacts of ATS A-power side
b1, b2 Aux a contacts of ATS B-power side
A1, A2 Operating signal of ATS A-power side
B1, B2 Operating signal of ATS B-power side
A-POWER TIME Delayed time setting of Utility side under Auto (0~30sec)
A-POWER TIME Delayed time setting of Emergency side under Auto (0~30sec)
FUSE Fuse of ATS A-power & B-power
S/W ON/OFF Selection of A-power & B-power
Be sure to connect the Aux contact (a1a2,b1b2) of ATS.
If not connected, automatic transfer of ATS cannot be proceed.

PANEL CUTTING : W157 H131 (unit:mm)


Automatic Transfer Switches I35
O-S ung E lectric M achinery CO., LTD.
Head Office & Factory :
111-3, Yeoungtae-ri, Wollong-myeon, Paju-si, Gyeonggi-do, Korea
Printed in June. 2010

Tel : (82-31)944-3521/3, (82-2)332-6151


Fax : (82-31)944-3525, (82-2)332-6152
Website : http://www.osemco.com
Catalog No. ATS-1005
E-mail : ousung@chol.com

S-ar putea să vă placă și