Measurements during
the Life Cycle of GIS
Presented originally at
HIGHVOLT Kolloquium 07
Dresden/Germany, May 14 15, 2007
Authors:
U. Schichler
E. Kynast
HIGHVOLT KOLLOQUIUM `07
Siemens AG
Power Transmission and Distribution, High Voltage
Berlin, Germany
Abstract: This report describes the different high- Development tests outside of the scope of the
voltage tests and measurements during the life standards, the routine tests at the manufacturers
cycle of GIS and the related impact to the works and the tests after installation are the most
dielectric failure rate in service. Intensive develop- important measures to ensure a GIS life-time with
ment tests, routine tests and commissioning tests high reliability and availability. Maintenance
are the basics for a reliable design and proven measures according manufacturer instructions
product quality. Insulation monitoring in service ensures the performance of the equipment.
may help to avoid unforeseen breakdowns. Insulation monitoring in service by PD measure-
ment gives information, which should avoid
INTRODUCTION breakdowns and shall be helpful for the asset
management. The results can be used for the
GIS have been in service for more than 40 years determination of the further operation or the
and they have shown a high level of reliability with equipments end of life-time. The benefits of PD
extremely small failure rates even for modern GIS monitoring are nowadays still under discussion.
showing a high compactness (Figure 1). This is
the result of quality assurance during development, Life Cycle Tests and Information
production, installation and commissioning as well Period Measurements for
as during service. Quality assurance consists of
different tests and measurements during the life Development
Research &
tests Design
cycle of GIS which give feedback to the Development
Type tests
manufacturer and user (Table 1). All return of
R&D
experience should be taken into account for the Production Routine tests Product Quality
continuous improvement of the product quality. Commissioning
Maintenance R&D
Production
Tests after
extension/repair Installation &
Service Commissioning
Monitoring
Asset management
(continuous,
periodic, Further operation
spontanuous) End of life-time
Disposal, Inspection
R&D
Recycling Material tests
An in-service breakdown in a GIS typically takes Figure 11 shows the flowchart of the proposed
more than a week to repair, and the costs of this, risk assessment procedure.
together with the consequent circuit disruption and
loss of supply in a single outage, usually far
outweigh the initial cost of high-performance PDM
systems.
Edelhard Kynast
Siemens AG
PTD H 321 H
Nonnendammallee 104
13623 Berlin
email: edelhard.kynast@siemens.com
Permission for use
The content of this paper is copyrighted by Siemens. Any inquiries regarding
permission to use the content of this paper, in whole or in part, for any
purpose must be addressed to Siemens directly.
Disclaimer
This document contains forward-looking statements and information that is,
statements related to future, not past, events. These statements may be
identified either orally or in writing by words as expects, anticipates,
intends, plans, believes, seeks, estimates, will or words of similar
meaning. Such statements are based on our current expectations and certain
assumptions, and are, therefore, subject to certain risks and uncertainties. A
variety of factors, many of which are beyond Siemens control, affect its
operations, performance, business strategy and results and could cause the
actual results, performance or achievements of Siemens worldwide to be
materially different from any future results, performance or achievements that
may be expressed or implied by such forward-looking statements. For us,
particular uncertainties arise, among others, from changes in general
economic and business conditions, changes in currency exchange rates and
interest rates, introduction of competing products or technologies by other
companies, lack of acceptance of new products or services by customers
targeted by Siemens worldwide, changes in business strategy and various
other factors. More detailed information about certain of these factors is
contained in Siemens filings with the SEC, which are available on the
Siemens website, www.siemens.com and on the SECs website, www.sec.gov.
Should one or more of these risks or uncertainties materialize, or should
underlying assumptions prove incorrect, actual results may vary materially
from those described in the relevant forward-looking statement as anticipated,
believed, estimated, expected, intended, planned or projected. Siemens does
not intend or assume any obligation to update or revise these forward-looking
statements in light of developments which differ from those anticipated.
Trademarks mentioned in this document are the property of Siemens AG, it's
affiliates or their respective owners.