69 kV
XLPE
Power
Cable
3
Section 2
Conductor material and size
Conductor material is a matter of both customer preference
and required current carrying capacity
69 kV Power Cables
Copper conductor common for larger loads
When both copper and aluminum conductors can meet your
requirements, the more economical solution will be a function
of the metal and the cable component costs
Insulation thickness
For cables with a radial moisture barrier, Southwire Standard
Wall reduced insulation thicknesses within the stress limits in
AEIC specification CS9 are recommended
Cables referred to by Traditional Wall insulation (650 mils)
follow the traditional insulation wall practice referenced in ICEA
standard S-108-720 appendix F as still specified by a number of
customers and utilities
For applications requiring smaller cable diameters,
specific designs are available upon request
Sheath material
Copper and aluminum corrugated sheaths offer the best
mechanical and moisture protection for your HV cable,
and copper will provide better short circuit performance
and improved connectability
Full wall cables with concentric neutrals are an economical
option for mostly dry environments
Composite laminate sheaths in both copper and aluminum
that offer excellent protection against moisture ingress
Jacket
Standard outer jacket: extruded LLDPE with a co-extruded outer
semi-conductive polyethylene layer for jacket integrity testing
Halogen Free Fire Retardant (HFFR) compounds are
available upon request for installations in cable trays and
ventilated troughs
4
69 kV Power Cables
69 kV XLPE
Copper
Conductor
Traditional Wall 650 mil XLPE Copper
Corrugated Sheath
Cable Construction
True Triple Extrusion and Dry Cured
Reverse Concentric Stranded Copper,
Firmly Bonded Insulation Shield
Compressed Conductor or Milliken
Welded Copper Corrugated Sheath
Super Smooth Conductor Shield
Polyethylene Jacket with Extruded
Super Clean XLPE Insulation
Semi-Conductive Outer Layer
Traditional Wall - 650 mil XLPE
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
5
Section 2
Conductor Size in
500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000
kcmil1
Dimensional Nominal
Conductor
in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21
Diameter
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1
Diameter over
69 kV Power Cables
in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 3.26 3.42 3.58 3.71
Insulation
mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 82.8 86.9 90.8 94.2
Diameter over
in 2.68 2.88 3.04 3.19 3.32 3.44 3.56 3.85 4.03 4.20 4.34
Sheath
mm 68.1 73.2 77.2 81.0 84.3 87.4 90.4 97.8 102.3 106.6 110.3
Overall Jacket
in 2.96 3.16 3.33 3.47 3.60 3.72 3.84 4.13 4.31 4.48 4.62
Diameter
mm 75.2 80.3 84.6 88.1 91.4 94.5 97.5 104.9 109.4 113.7 117.4
Total Weight lbs/ft 4.8 5.9 6.9 7.9 8.8 9.8 10.7 12.9 14.8 16.7 18.5
Min. Bending Radius
in 59/44 63/47 67/50 69/52 72/54 74/56 77/58 83/62 86/65 90/67 92/69
(install/perm.) in
Maximum Pulling
lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000
Tension
Typical Shipping Reel Size
Flange x Width in 126x95 126x95 126x95 126x95 126x95 126x95 150x95 158x95 150x95 150x95 150x95
Shipping Reel
ft 3,000 3,000 3,000 3,000 3,000 2,950 3,000 2,800 2,500 2,200 1,975
Capacity*
Electrical
Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410
Sheath kA 33.6 36.1 38.2 40 41.6 43.2 44.6 48.3 50.5 52.6 54.4
Conductor Resistance
DC @ 20o C /kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003
DC @ 90 C
o
/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003
Capacitance pF/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 76.5 81.5 86.2 90.3
Amps/
Charging Current 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.15 1.22 1.29 1.36
kft
Ampacity @ 90o C per circuit
Typical Single
Amps 600 740 820 960 1040 1110 1180 1390 1506 1595 1673
Ductbank4
Power Rating MVA 72 89 98 115 125 133 142 167 180 191 200
Typical Double
Amps 510 630 710 810 880 940 990 1181 1276 1432 1517
Ductbank4
Power Rating MVA 61 76 85 97 106 113 119 142 153 172 182
1
2500-4000 kcmil conductors are 5 segment Milliken conductors.
2
Increased shipping reel capacity can be accommodated on request.
3
Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current.
4
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded
6
69 kV Power Cables
69 kV XLPE
Copper
Conductor
SW Standard Wall XLPE Copper
Corrugated Sheath
Cable Construction
Reverse Concentric Stranded Copper, True Triple Extrusion and Dry Cured
Compressed Conductor or Milliken Firmly Bonded Insulation Shield
Super Smooth Conductor Shield Welded Copper Corrugated Sheath
Super Clean XLPE Insulation Polyethylene Jacket with Extruded Semi-
430 mil XLPE minimum Conductive Outer Layer
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
7
Section 2
Conductor Size in
500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000
kcmil1
Dimensional Nominal
Conductor
in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21
Diameter
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1
Insulation
69 kV Power Cables
mils 520 490 470 450 450 440 430 430 440 450 450
Thickness
mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 10.9 11.2 11.4 11.4
Diameter over
in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 2.82 2.92 3.1 3.23
Insulation
mm 49.5 52.5 55.4 57.7 60.7 63.0 65.0 71.6 74.2 78.7 82.0
Diameter over
in 2.39 2.51 2.63 2.73 2.87 2.96 3.05 3.35 3.44 3.64 3.78
Sheath
mm 60.7 63.8 66.8 69.3 72.9 75.2 77.5 85.0 87.4 92.5 96.0
Overall Jacket
in 2.67 2.80 2.91 3.01 3.15 3.24 3.33 3.63 3.72 3.92 4.06
Diameter
mm 67.8 71.0 73.9 76.5 80.0 82.3 84.6 92.1 94.5 99.6 103.1
Total Weight lbs/ft 4.2 5.2 6.1 6.9 7.9 8.8 9.6 11.7 13.3 15.3 17
Min. Bending
Radius (install/ in 53/40 56/42 58/44 60/45 63/47 65/49 67/50 73/54 74/56 78/59 81/61
perm.)
Maximum Pulling
lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000
Tension
Typical Shipping Reel Size
Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 126x95 150x95 150x95 158x95
Shipping Reel
ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,750 2,400 2,100
Capacity2
1
2500-4000 kcmil conductors are 5 segment Milliken conductors. Declared values for 30 mils copper sheath. Thicker sheath can
3
2
Increased shipping reel capacity can be accommodated on request. accommodate more current.
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf,
4
69 kV XLPE -
Aluminum
Conductor
Traditional Wall 650 mil XLPE
Aluminum Corrugated Sheath
Cable Construction
Reverse Concentric Stranded Aluminum, True Triple Extrusion and Dry Cured
Compressed Conductor Firmly Bonded Insulation Shield
Super Smooth Conductor Shield Welded Aluminum Corrugated Sheath
Super Clean XLPE Insulation Polyethylene Jacket with Extruded Semi-
Traditional Wall - 650 mil XLPE Conductive Outer Layer
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
9
Section 2
Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000
Dimensional Nominal
Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9
Diameter over Insulation in 2.21 2.39 2.53 2.67 2.79 2.90 3.00
69 kV Power Cables
mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2
Diameter over Sheath in 2.78 2.98 3.15 3.30 3.43 3.55 3.67
mm 70.6 75.7 80.0 83.7 87.1 90.2 93.2
Overall Jacket Diameter in 3.06 3.26 3.43 3.58 3.71 3.83 3.95
mm 77.7 82.8 87.1 90.8 94.2 97.3 100.3
Total Weight lbs/ft 3.2 3.6 4.1 4.5 4.9 5.3 5.7
Min. Bending Radius
in 61/46 65/49 69/51 72/54 74/56 77/57 79/59
(install/perm.)
Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000
Typical Shipping Reel Size
Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 150x95 150x95
Shipping Reel Capacity 1
ft 3,000 3,000 3,000 3,000 2,950 3,000 3,000
Electrical
Electrical Stress @ Uo
Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3
Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8
Typical Double Ductbank3 Amps 400 500 580 650 710 770 820
1
Increased shipping reel capacity can be accommodated on request.
2
Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current.
3
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded
10
69 kV Power Cables
69 kV XLPE -
Aluminum
Conductor
SW Standard Wall XLPE Aluminum
Corrugated Sheath
Cable Construction
Reverse Concentric Stranded Aluminum, True Triple Extrusion and Dry Cured
Compressed Conductor Firmly Bonded Insulation Shield
Super Smooth Conductor Shield Welded Aluminum Corrugated Sheath
Super Clean XLPE Insulation Polyethylene Jacket with Extruded Semi-
430 mil XLPE minimum Conductive Outer Layer
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
11
Section 2
Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000
Dimensional Nominal
Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9
Insulation Thickness mils 520 490 470 450 450 440 430
69 kV Power Cables
mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9
Diameter over Insulation in 1.95 2.07 2.18 2.27 2.39 2.48 2.56
mm 49.5 52.6 55.4 57.7 60.7 63.0 65.0
Diameter over Sheath in 2.47 2.61 2.73 2.83 2.96 3.06 3.15
mm 62.7 66.3 69.3 71.9 75.2 77.7 80.0
Overall Jacket Diameter in 2.75 2.89 3.01 3.11 3.24 3.34 3.43
mm 69.9 73.4 76.5 79.0 82.3 84.8 87.1
Total Weight lbs/ft 2.7 3.0 3.4 3.7 4.1 4.4 4.7
Min. Bending Radius
in 55/41 58/43 60/45 62/47 65/49 67/50 69/51
(install/perm.)
Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000
Typical Shipping Reel Size
Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95
Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000
Electrical
Electrical Stress @ Uo
Conductor Shield kV/mm 4.5 4.5 4.5 3.4 4.5 4.5 4.5
Insulation Shield kV/mm 2.1 2.4 2.6 1.8 2.8 2.9 3.0
Short Circuit for 0.5s 2
1
Increased shipping reel capacity can be accommodated on request.
2
Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current.
3
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded
12
69 kV Power Cables
69 kV XLPE -
Copper
Conductor
Traditional Wall 650 mil XLPE
Copper Concentric Neutrals
Cable Construction
Reverse Concentric Stranded Copper, True Triple Extrusion and Dry Cured
Compressed Conductor or Milliken Firmly Bonded Insulation Shield
Super Smooth Conductor Shield Copper Concentric Neutrals
Super Clean XLPE Insulation Polyethylene Jacket with Extruded
Traditional Wall - 650 mil XLPE Semi-Conductive Outer Layer
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
13
Section 2
Conductor Size in
500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000
kcmil1
Dimensional Nominal
Conductor
in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21
Diameter
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1
Diameter over
69 kV Power Cables
in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 3.18 3.34 3.5 3.63
Insulation
mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 80.8 84.9 88.9 92.2
Diameter over
in 2.56 2.74 2.88 3.02 3.14 3.25 3.35 3.53 3.69 3.84 3.98
Neutrals
mm 65.0 69.6 73.2 76.7 79.8 82.6 85.1 89.6 93.7 97.6 101.1
Overall Jacket
in 2.86 3.04 3.18 3.32 3.44 3.55 3.66 3.83 3.99 4.15 4.28
Diameter
(mm) 72.6 77.2 80.8 84.3 87.4 90.2 93.0 97.4 101.4 105.4 108.7
Total Weight lbs/ft 4.2 5.2 6.1 7.1 8.0 8.9 9.8 11.6 13.4 15.2 17
Min. Bending
Radius (install/ in 57/43 61/46 64/48 66/50 69/52 71/53 73/55 77/57 80/60 83/62 86/64
perm.)
Maximum Pulling
lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000
Tension
Typical Shipping Reel Size
Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 150x95 150x95 150x95 150x95
Shipping Reel
ft 3,000 3,000 3,000 3,000 3,000 3,000 2,950 3,000 2,700 2,400 2,150
Capacity2
1
2500-4000 kcmil conductors are 5 segment Milliken conductors.
2
Increased shipping reel capacity can be accommodated on request.
3
Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current.
4
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded
14
69 kV Power Cables
69 kV XLPE -
Aluminum
Conductor
Traditional Wall 650 mil XLPE Copper
Concentric Neutrals
Cable Construction
Reverse Concentric Stranded Aluminum, True Triple Extrusion and Dry Cured
Compressed Conductor Firmly Bonded Insulation Shield
Super Smooth Conductor Shield Copper Concentric Neutrals
Super Clean XLPE Insulation Polyethylene Jacket with Extruded
Traditional Wall - 650 mil XLPE Semi-Conductive Outer Layer
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
15
Section 2
Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000
Dimensional Nominal
Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9
Diameter over Insulation in 2.21 2.39 2.53 2.67 2.79 2.90 3.00
69 kV Power Cables
mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2
Diameter over Neutral in 2.56 2.74 2.88 3.02 3.14 3.25 3.35
mm 65.0 69.6 73.2 76.7 79.8 82.6 85.1
Overall Jacket Diameter in 2.86 3.04 3.18 3.32 3.44 3.55 3.66
mm 72.6 77.2 80.8 84.3 87.4 90.2 93.0
Total Weight lbs/ft 3.1 4.1 4.5 4.9 5.2 5.6 6.0
Min. Bending Radius
in 57/43 61/46 64/48 66/50 69/52 71/53 73/55
(install/perm.) in
Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000
Typical Shipping Reel Size
Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95
Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000
Electrical
Electrical Stress @ Uo
Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3
Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8
Short Circuit for 0.5s 2
1
Increased shipping reel capacity can be accommodated on request.
2
Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current.
3
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded
16
69 kV Power Cables
69 kV XLPE -
Copper
Conductor
TRADITIONAL WALL 650 MIL XLPE Copper neutrals
with copper composite Laminate sheath
Cable Construction
Reverse Concentric Stranded Copper, True Triple Extrusion and Dry Cured
Compressed Conductor or Milliken Firmly Bonded Insulation Shield
Super Smooth Conductor Shield Copper Concentric Neutrals with Copper
Super Clean XLPE Insulation Composite Laminate Sheath
Traditional Wall - 650 mil XLPE Polyethylene Jacket with Extruded
Semi-Conductive Outer Layer
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
17
Section 2
Conductor Size in
500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000
kcmil1
Dimensional Nominal
Conductor
in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.78 1.98 2.08 2.21
Diameter
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 45.2 50.2 52.8 56.1
Diameter over
69 kV Power Cables
in 2.21 2.39 2.54 2.67 2.79 2.90 3.00 3.18 3.34 3.5 3.63
Insulation
mm 56.1 60.7 64.5 67.8 70.9 73.7 76.2 80.8 84.8 88.9 92.2
Diameter over
in 2.59 2.77 2.92 3.06 3.18 3.29 3.39 3.59 3.75 3.91 4.04
Sheath
mm 65.8 70.4 74.2 77.7 80.8 83.6 86.1 91.2 95.3 99.3 102.6
Overall Jacket
in 2.91 3.09 3.24 3.38 3.50 3.61 3.71 3.91 4.07 4.23 4.36
Diameter
mm 73.9 78.5 82.3 85.9 88.9 91.7 94.2 99.3 103.4 107.4 110.7
Total Weight lbs/ft 4.5 5.5 6.5 7.4 8.4 9.3 10.2 12.1 13.8 15.7 17.5
Min. Bending
Radius (install/ in 58/44 62/46 65/49 68/51 70/53 72/54 74/56 78/59 81/61 85/63 87/65
perm.)
Maximum Pulling
lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000
Tension
Typical Shipping Reel Size
Flange x Width in 126x95 126x95 126x95 138x95 138x95 138x95 150x95 150x95 150x95 150x95 150x95
Shipping Reel
ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,650 2350 2100
Capacity2
Electrical
Electrical Stress @ Uo
1
2500-4000 kcmil conductors are 5 segment Milliken conductors.
2
Increased shipping reel capacity can be accommodated on request.
3
Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current.
4
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded
18
69 kV Power Cables
69 kV XLPE -
Copper
Conductor
SW Standard Wall XLPE Copper neutrals with
copper composite laminate sheath
Cable Construction
Reverse Concentric Stranded Copper, True Triple Extrusion and Dry Cured
Compressed Conductor or Milliken Firmly Bonded Insulation Shield
Super Smooth Conductor Shield Copper Neutrals with Copper Composite
Super Clean XLPE Insulation Laminate Sheath
430 mil XLPE minimum Polyethylene Jacket with Extruded
Semi-Conductive Outer Layer
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
19
Section 2
Conductor Size in
500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000
kcmil1
Dimensional Nominal
Conductor
in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.78 1.98 2.08 2.21
Diameter
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 45.2 50.2 52.8 56.1
Insulation
69 kV Power Cables
mils 520 490 470 450 450 440 430 430 440 450 450
Thickness
mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 10.9 11.2 11.4 11.4
Diameter over
in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 2.74 2.92 3.1 3.23
Insulation
mm 49.5 52.5 55.4 57.7 60.7 63.0 65.0 69.6 74.2 78.7 82.0
Diameter over
in 2.33 2.45 2.56 2.66 2.78 2.87 2.95 3.16 3.41 3.51 3.64
Sheath
mm 59.3 62.2 65.0 67.4 70.5 72.8 74.9 80.3 86.6 89.1 92.5
Overall Jacket
in 2.65 2.77 2.88 2.98 3.10 3.19 3.27 3.48 3.73 3.83 3.96
Diameter
mm 67.3 70.4 73.2 75.7 78.6 80.9 83.0 88.4 94.7 97.2 100.6
Total Weight lbs/ft 4.9 6.0 6.3 7.1 8.0 8.9 9.7 11.7 13.5 15.4 17.1
Min. Bending
Radius (install/ in 53/40 55/42 58/43 60/45 62/46 64/48 65/49 70/52 75/56 77/57 79/59
perm.)
Maximum Pulling
lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000
Tension
Typical Shipping Reel Size
Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 138x95 150x95 150x95 150x95
Shipping Reel
ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,800 2,500 2,200
Capacity2
Electrical
Electrical Stress @ Uo
Conductor Shield kV/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1
1
2500-4000 kcmil conductors are 5 segment Milliken conductors. Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield.
3
2
Increased shipping reel capacity can be accommodated on request. Larger wires can accommodate more current.
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf,
4
69 kV XLPE -
Aluminum
Conductor
Traditional Wall 650 mil XLPE Copper neutrals
with aluminum composite laminate sheath
Cable Construction
Reverse Concentric Stranded Aluminum, True Triple Extrusion and Dry Cured
Compressed Conductor Firmly Bonded Insulation Shield
Super Smooth Conductor Shield Copper Neutrals with Aluminum
Super Clean XLPE Insulation Composite Laminate Sheath
Traditional Wall - 650 mil XLPE Polyethylene Jacket with Extruded
Semi-Conductive Outer Layer
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
21
Section 2
Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000
Dimensional Nominal
Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9
Diameter over Insulation in 2.21 2.39 2.54 2.67 2.79 2.90 3.00
69 kV Power Cables
mm 56.1 60.7 64.4 67.8 70.9 73.7 76.2
Diameter over Sheath in 2.60 2.78 2.93 3.06 3.18 3.29 3.39
mm 66.0 70.5 74.3 77.7 80.7 83.5 86.1
Overall Jacket Diameter in 2.92 3.10 3.25 3.38 3.50 3.61 3.71
mm 74.1 78.7 82.4 85.8 88.9 91.7 94.2
Total Weight lbs/ft 3.7 4.2 4.7 5.1 5.5 5.8 6.2
Min. Bending Radius
in 58/44 62/46 65/49 68/51 70/52 72/54 74/56
(install/perm.)
Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000
Typical Shipping Reel Size
Flange x Width in 126x95 126x95 126x95 138x95 138x95 138x95 150x95
Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000
Electrical
Electrical Stress @ Uo
Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3
Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8
Short Circuit for 0.5s 2
Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.
2
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded
3
22
69 kV Power Cables
69 kV XLPE -
Aluminum
Conductor
SW Standard Wall XLPE copper neutrals
with aluminum laminate sheath
Cable Construction
Reverse Concentric Stranded Aluminum, True Triple Extrusion and Dry Cured
Compressed Conductor Firmly Bonded Insulation Shield
Super Smooth Conductor Shield Copper Neutrals with Aluminum
Super Clean XLPE Insulation Composite Laminate Sheath
430 mil XLPE minimum Polyethylene Jacket with Extruded
Semi-Conductive Outer Layer
Cable Data
Voltage Characteristics (kV)
Max Voltage Rating 72.5
BIL Rating 350
Temperatures ( C)
o
Nominal Conductor 90
Max. Emergency Conductor 105
Short Circuit Conductor 250
Minimum Installation -10
Design Characteristics
Design Standards AEIC, IEC
Typical Test Voltages 120 kV / 15 min.
XLPE Loss Factor 0.0005
Relative Permittivity 2.3
23
Section 2
Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000
Dimensional Nominal
Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61
mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9
Insulation Thickness mils 520 490 470 450 450 440 430
69 kV Power Cables
mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9
Diameter over Insulation in 1.95 2.07 2.18 2.27 2.39 2.48 2.56
mm 49.5 52.5 55.3 57.7 60.7 63.0 65.1
Diameter over Sheath in 2.34 2.46 2.57 2.66 2.78 2.87 2.95
mm 59.4 62.4 65.2 67.5 70.6 72.9 75.0
Overall Jacket Diameter in 2.66 2.78 2.89 2.98 3.10 3.19 3.27
mm 67.5 70.5 73.3 75.7 78.7 81.0 83.1
Total Weight lbs/ft 3.3 3.7 4.0 4.3 4.7 5.0 5.3
Min. Bending Radius
in 53/40 56/42 58/43 60/45 62/46 64/48 65/49
(install/perm.)
Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000
Typical Shipping Reel Size
Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 138x95 138x95
Shipping Reel Capacity 1
ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000
Electrical
Electrical Stress @ Uo
Conductor Shield kV/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5
Insulation Shield kV/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0
Short Circuit for 0.5s2
Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4
Sheath kA 41 41.2 41.5 41.7 42 42.2 42.4
Conductor Resistance
Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.
2
4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded
3
24