Sunteți pe pagina 1din 2

M-01-SDS-0001

Specification Sheet

Project Name HVFO/HFO Tank and Associated


System design
Client HNG FLOAT GLASS LTD

Document Number SDS-01-M-001

Document Revision 01

Document Title Specification Sheet for Inline Heater


For Truck Unloading

Project Number P160001

Document type Specification Sheet

Tag No 100-E-101 A/B

8-Jun-16 01 ISSUED FOR REVIEW PS AT AT


Prepared Checked Approved
DATE REV Description
By By By
NOTE : After approval on this document it will be submitted to vendor(s), further vendor document document will be submitted along with this data to
client.
Heavy Fuel Oil Inline Heater
NOTE: APPLICABLE TO INQUIRY (X ) PURCHASE ( ) AS BUILT ( )

Service: Inline Electrical Heater for Tanker unloading pump Item No.: 100-HE-101 A/B

Fluid IOCL heavy Fuel Oil

Flow 17 m3/hr

Duty Note 15 KW

Inlet Temperature 25 C

Outlet Temperature Note 2 & 15 C

Supply pressure Nor 3.1 barg

Design Pressure 7 barg

Design Temp 150 C

Density 1010 kg/m3

Viscosity 180-385 cst

Notes
1.Consider Min Flow 5 m3/hr.
2. Heater fouling factor will be subjected for approval.
3. Heater outlet temp vary from 55 deg C to 75 deg C.
4. Vendor to provide all controls and instrumentation for operation of system.
5. Expected Nozzle Connections are :
Heater Inlet - 6"
Heater Outlet - 6"
6. Two unit shall be supplied, one working and one stand by. Both unit shall be on skid.
7. Max pressure drop in shell is 0.5 bar.
8. MOC : SAE 516 Gr 60
9. Baffled heater to be considered.
10. Flamproof encloser to be considered.
11. Certificate : ATEX Directive 94/9/EC
12. Minimum weather proof protection IP67.
13. Epoxy primer with two coats after sand blasting at inside and outside of heater shell.
14. Area Classification Class I, Div 2 Gr D, T3.
15. A. Tanker unloading temperature range in/out is 25 to 55 deg C. Heat load for unloading mode is 340 KW.
B. Tanker circulation temperature range in/out is 55 to 75 deg C. Heat load for unloading mode is 227 KW.
C. Heater will be operated either for unloading or circulation at a time.

Client: HNG Float Glass LTD Project: HFO System Engineering Services

Client's Project No.: P16001 Plant Location: Vadodara

S-ar putea să vă placă și