Documente Academic
Documente Profesional
Documente Cultură
1 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
Force Distribution
This section applies to lange forces on moment connections only. Please see Required Flange Forces to see how
RISAConnection calculates the lange forces when moment and axial loads are present.
Shear connections are assumed to carry all axial load through the connecting elements.
Moment Arm
The depth of the moment arm between lange forces (dc) is described below. RISAConnection assumes these to be
applied at the centroid of the beam lange (for End Plate and Direct Weld Moment Connections) or that of the lange
plates (for Flange Plate Moment Connections).
Flange plate moment connections: This is taken as the Top Column Dist (from the Loading input section)
minus half of the thickness of the lange plate. This is the location where the centroid of the top lange plate
transmits its force into the column.
End plate moment connectionsand Direct Weld moment connections: This is taken as the Top Column Dist
(from the Loading input section) plus half of the thickness of the beam lange. This is the location where the
2 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
centroid of the top lange transmits its force into the column.
Note that we always assume the top lange is in compression for these moment connections, or we assume that the
moment can be reversed.
k and N Assumptions
The AISC 360-10 speciication speciies k as the distance from outer face of the column lange to the web toe of the illet.
Table 1-1 from the 14th Edition Steel Manual list both a kdet and a kdes value. RISAConnection assumes k = kdes for this
value.
N is deined as the bearing length of the applied force. Therefore this value differs based on the weld type speciied to
connect the beam lange to the column or end plate. RISAConnection uses the following assumptions when calculating
this value:
3 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
Note:
This is only checked in Shear Connections if the connection includes a tensile axial load.
4 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
This check contains some complicated geometry to approximate the yield line pattern. Below are graphical explanations
of some of the more complicated terms:
5 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
Some End Plate connections do not have column yield line formulas speciically listed in the design guides.
Note:
The column yield lines for the 8 bolt (unstiffened) connection is not given in the design guides. But, can be found
in section 4.4.5.5 and Figure 4-15 of Emmett Sumner's PhD thesis, Uniied Design of Extended End-Plate Moment
Connections Subject to Cyclic Loading.
The column yield lines for the MRE1/3 connection is not given in the design guides. But, can be found in section
4.4.5.6 and Figure 4-16 of Emmett Sumner's PhD thesis, Uniied Design of Extended End-Plate Moment
Connections Subject to Cyclic Loading.
The 2 bolt lush end plate connections will have the same yield lines as the Yp values in table 3-2 of AISC Design
Guide 16. The only difference is that bp (plate width) is replaced with bcf (column lange width), tp (plate
thickness) with tcf(column lange thickness). In addition "s" is used instead of Pf for the distance to the top yield
line unless a transverse column stiffener is present in which case the distance between this stiffener and the top
row of bolts is used in place of Pf.
6 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
The 4 bolt lush end plate connections will have the same yield lines as the Yp values in table 3-3 of AISC Design
Guide 16. The same differences mentioned in the bullet point above for the 2 bolt lush connection also apply to
the 4 bolt lush connections.
This is only checked in Shear Connections if the connection includes an axial load.
7 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
Expand this section of the design report and RISAConnection will provide you with the exact equation, code reference,
listed variables, as well as the code check value and pass or failure notiication. See the Moment Arm section for more
information on how this value is calculated.
Note:
For lush end plate connections, the spread of the axial force is not addressed in any of the design guides.
Therefore, a value between the two formulas is used (5.5k + N +1.0*tp). This is rational because it assumes a
spread of load on one side is the same as the end plate connection, but on the other side it is assumed to be the
same as the direct weld connection.
In the case of lush end plates with double illet welds, the plates are extended the distance of the weld leg + an
extra 1/16th of an inch for any weld legs greater than 0.25".
8 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
There are three equations that come into play for this check. When the concentrated compressive force to be resisted is
applied at a distance from the member end that is greater than or equal to dcol/2 use equation J10-4. If this distance is
less than dcol/2, then use either J10-5a or J10-5b. Please see the Concentrated Force Location section for more
information on how this location is calculated.
The differentiation between equations J10-5a and J10-5b depends on the ratio of bearing length to overall depth of the
beam (N/d). See the Column Moment Checks topic for information on calculating N. If N/d <= 0.2, then equation J10-5a
is used. If N/d > 0.2, then equation J10-5b is used.
The program will perform all of these dimensional checks and use the appropriate equation automatically.
Note:
This is only checked in Shear Connections if the connection includes a compressive axial load.
There are three equations that come into play for this check. When the concentrated compressive force to be resisted is
applied at a distance from the member end that is greater than or equal to dcol/2 use equation J10-4. If this distance is
less than dcol/2, then use either J10-5a or J10-5b. This location where this compressive force occurs is deined earlier in
this topic.
The differentiation between equations J10-5a and J10-5b depends on the ratio of bearing length to overall depth of the
beam (N/d). See information earlier in this topic for information on calculating N. If N/d <= 0.2, then equation J10-5a is
used. If N/d > 0.2, then equation J10-5b is used.
The program will perform all of these dimensional checks and use the appropriate equation automatically.
9 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
Note:
Technically this check is only valid when there column web is restrained at both langes (i.e. when there is a
moment connection on both sides of the column). However, RISAConnection does not currently have a method to
determine if this is the case. Therefore, the connection is always checked for column web buckling.
These forces cause a shear to the web panel zone that we are checking here.
10 of 11 11/8/17, 4:13 PM
Column Connection Checks https://risa.com/risahelp/risaconnection/Content/Design Checks/Colu...
There are four equations from the AISC 360-10 speciication that are used, equations J10-9, J10-10, J10-11 and J10-12.
The program assumes that the effect of panel-zone deformation on frame stability is not considered in the analysis, thus
equations J10-11 and J10-12 are never used. Whether to use J10-9 or J10-10 depends on the axial force in the column at
the location of the connection. This force is input in the Loading section. If this force is <= 0.4*Pc then J10-9 is used. If Pr
> 0.4*Pc, then J10-10 is used.
Story Shear
The actual demand panel zone shear that occurs can be reduced by the story shear coming into the panel zone.
This story shear is also an input in the Loading section. If there is story shear, then the program calculates an Mequivas
the design demand. This is a reduced demand based on a reduced panel zone shear due to this story shear. Because the
code checks are based on converting the capacities into equivalent moment capacities, the same must be done for the
moment demand in this case.
RISAConnection will take all of the inputs, perform the applicable checks and use the appropriate equation.
11 of 11 11/8/17, 4:13 PM