Cross Reference Table for Area Classification Details

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
Adjacent Areas
Area Focus Adequately ventilated Figure 2
nonenclosed area adjacent to a
classified area
Enclosed area with vaportight Figure 3
barriers adjacent to a classified
area
Enclosed area with non-vaportight Figure 4
barriers adjacent to a classified
area and in contact with its
Division 1 hazardous influence
boundary
Enclosed area with non-vaportight Figure 5
barriers adjacent to a classified
area and in contact with its
Division 2 hazardous influence
boundary
Bulk Loading or Unloading
Drum Filling Station Handling Flammable Liquid Figure 5.9.6
(Outdoors or Indoors
in an Adequately
Ventilated Building))
Marine Terminal Handling Flammable or Figure 19 Figure 5.9.14
Combustible Liquid
Tank Car or Tank Product Transfer through Bottom Figure 11 Tank Truck:
Truck Loading and Only for Flammable Liquid Figure
Unloading Via Closed 5.9.4(d)
System Tank Car:
Figure
5.9.4(c)
Product Transfer through Dome Figure 10 Tank Car
Only for Flammable Liquid Only: Figure
5.9.4(b)
Product Transfer through Bottom Figure 13
Only for Liquefied Gas,
Compressed Gas, or Cryogenic
Liquid
Product Transfer through Dome Figure 9 Figure 5.9.5
Only for Flammable Liquefied Gas,

Page 1 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
Compressed Gas, or Cryogenic
Liquid
Tank Car or Tank Product Transfer through Top or Figure 12 Figure
Truck Loading and Bottom for Flammable Liquid 5.9.4(e)
Unloading Via Open
System
Compressors
Compressor Below Handling Flammable or Figure 101
Grade Combustible Gas or Vapor or
(Inadequately Highly Volatile Liquids (HVL)
Ventilated Area)
Compressor at Grade Handling Flammable or Figure 51 Figure
(Outdoors) Combustible Gas or Vapor 5.9.2(a)
Handling Highly Volatile Liquid Figure 93
(HVL)
Compressor Handling Lighter-Than-Air Figure 23 Figure
(Inside Adequately Flammable or Combustible Gas or 5.9.9(a)
Ventilated Vapor
Compressor Shelter)
Compressor Handling Lighter-Than-Air Figure 25 Figure
(Inside Inadequately Flammable or Combustible Gas or 5.9.9(b)
Ventilated Vapor
Compressor Shelter)
Compressor Handling Flammable or Figure 52
(Outdoors but Under Combustible Gas or Vapor
Roofed Building Handling Highly Volatile Liquid Figure 52 with
without Sides) (HVL) Figure 93
Compressor Handling Lighter-Than-Air Figure 105
(Inside Adequately Flammable or Combustible Gas or
Ventilated Roofed Vapor
Building with One or Handling Flammable or Figure 53
More Sides) Combustible Gas or Vapor
Handling Flammable or Figure 94
Combustible Liquid or Highly
Volatile Liquid (HVL)
Compressor Handling Lighter-Than-Air Figure 106
(Inside Inadequately Flammable or Combustible Gas or
Ventilated Roofed Vapor
Building with One or Handling Flammable or Figure 54
More Sides) Combustible Gas or Vapor
Handling Flammable or Figure 95

Page 2 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
Combustible Liquid or Highly
Volatile Liquid (HVL)
Compressor Groups F or G Dust with no visible Figure 5.8(c)
(Indoor with Enclosed dust cloud, dust layer less than 1/8
Operating Equipment) inch and surface color not
discernable
Groups F or G Dust with no visible Figure 5.8(d)
dust cloud or dust layer and
surface color discernable
Compressor Group E Dust with moderate or Figure 5.8(b)
(Indoor with Open or dense dust cloud, dust layer
Semi-Enclosed greater than 1/8 inch to less than
Operating Equipment) 1/8 inch and surface color not
discernable
Groups F or G Dust with moderate Figure 5.8(a)
or dense dust cloud to no visible
dust cloud, dust layer greater than
1/8 inch to less than 1/8 inch and
surface color not discernable
Compressor Group E Dust Figure 5.8(f)
(Indoor, Walled Off
Area, Enclosed
Operating Equipment)
Effluent Handling and Treatment
Drain System Type 1 Open Drain System Figure 58
(Enclosed Area)
Drain System Type 2 Open Drain System Figure 59
(Enclosed Area) Adequately ventilated Type 3 Figure 61
(cont.) Open Drain System
Type 4 Open Drain System Figure 63
Inside Adequately Ventilated Figure 5.9.13,
Building handling Cryogenic Top Detail
Flammable Liquids including
Natural Gas
Drain System Type 1 Open Drain System Figure 58
(Nonenclosed Area) Type 2 Open Drain System Figure 59
Adequately ventilated Type 3 Figure 60
Open Drain System
Adequately ventilated Type 4 Figure 62
Open Drain System
Handling Cryogenic Flammable Figure 5.9.13,

Page 3 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
Liquids including Natural Gas Bottom
Detail
Emergency Impounding Basin Figure 5.9.7,
(Above Grade) Oil-Water Separator Top Detail
handling Flammable Liquid
Emergency or Drainage Ditch Figure 5.9.7,
Temporary Oil-Water Separator Bottom
(Below Grade) handling Flammable Liquid Detail
Sump Below grade Open Sump handling Figure 57 with
(Adequately Flammable or Combustible Liquid Division 2 for the
Ventilated Enclosed remainder of the
Area) enclosed area
Sump Above Grade Sump inside an Figure 34
(Inadequately enclosure handling Flammable or
Ventilated Enclosed Combustible Liquid
Area)
Below Grade Open Sump Inside Figure 63
Open Vault or Containment Area
Sump Below grade Open Sump handling Figure 58
(Nonenclosed Clean Water
Adequately Ventilated Below grade Open Sump handling Figure 57
Area) Flammable or Combustible Liquid
Below grade Closed Sump or Oily Figure 27
Water Separator with Detail 4
Atmospheric Vent and No Access
Hatch(es)
Below grade Closed Sump or Oily 1. Figure 27
Water Separator with Vent to - Detail 4 but
Carbon Cannisters and No Access without Vent
Hatch(es) classification
2. Add Vent
note To
Carbon
Cannisters
Sump Below grade Closed Sump or Oily 1. Figure 27
(Nonenclosed Water Separator with Detail 4
Adequately Ventilated Atmospheric Vent and Access 2. Figure 100
Area) Hatch(es) Detail B
(cont.) Below grade Closed Sump or Oily 1. Figure 27
Water Separator with Vent to Detail 4 but
Carbon Cannisters and Access without Vent

Page 4 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
Hatch(es) classification
2. Add Vent note
To Carbon
Cannisters
3. Figure 100
Detail B
Waste Water Open Top Below Grade Separator Figure 27
Treatment or Preseparator Detail 1
(Nonenclosed
Adequately Ventilated Open Top Above Grade Separator Figure 7
Area) or Preseparator
Fixed Roof Above Grade Figure 6
Separator or Preseparator
Open Top Below Grade Dissolved Figure 27
Air Flotation (DAF) Unit Detail 2
Open Top Above Grade Dissolved Figure 7
Air Flotation (DAF) Unit
Fixed Roof Above Grade Dissolved Figure 6
Air Flotation (DAF) Unit
Open Top Below Grade Biological Figure 27
Oxidation (BIOX) Unit Detail 3
Open Top Above Grade Biological Figure 7
Oxidation (BIOX) Unit
Fixed Roof Above Grade Biological Figure 6
Oxidation (BIOX) Unit
Injecton Well without Cellar or Figure 39
Below Grade Sump
Injecton Well with Inadequately Figure 40
Ventilated Cellar or Below Grade
Sump
General Process Equipment
Above Grade Source Diverter Line Outlet handling Figure 89
with Closure Flammable or Combustible Liquid
(Nonenclosed Pig Launching or Receiving Figure 49
Adequately Ventilated Installation handling Flammable or
Area) Combustible Liquid
Process Filter or Strainer handling Figure 102
Flammable or Combustible Liquid
or Highly Volatile Liquid (HVL)
Cooling Tower Mechanical Draft handling Process Figure 28
Cooling Water

Page 5 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
Dust Handling Groups F or G Dust with no visible Figure 5.8(c)
Equipment dust cloud, dust layer less than 1/8
(Indoor with Enclosed inch and surface color not
discernable
Operating Equipment) Groups F or G Dust with no visible Figure 5.8(d)
dust cloud or dust layer and
surface color discernable
Dust Handling Group E Dust with moderate or Figure 5.8(b)
Equipment dense dust cloud, dust layer
(Indoor with Open or greater than 1/8 inch to less than
Semi-Enclosed 1/8 inch and surface color not
discernable
Operating Equipment) Groups F or G Dust with moderate Figure 5.8(a)
or dense dust cloud to no visible
dust cloud, dust layer greater than
1/8 inch to less than 1/8 inch and
surface color not discernable
Dust Handling Group E Dust Figure 5.8(f)
Equipment
(Indoor, Walled Off
Area, Enclosed
Operating Equipment)
Fired Equipment Fired Heater with air-aspirated Unclassified
burners entending out 10
feet from
perimeter of
burner bank
Fired Heater with FD fan or FD/ID Unclassified
fans and safety shutdown system
Fired Heater with FD fan or FD/ID Figure 48
fans and no safety shutdown
system
Flare Unclassified
entending out 10
feet from tip
Flammable Gas- Located Outdoors at Grade in a Figure 50
Blanketed and Nonenclosed Adequately
Produced Water- Ventilated Area
Handling Equipment
Located at Grade in Adequately Figure 50 with
Ventilated Enclosed Area and all Division 2 for the
Vents extend outside enclosed remainder of the

Page 6 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
area extent of
enclosed area
Located at Grade in Adequately Figure 50 with
Ventilated Enclosed Area and all the remainder of
Vents do not extend outside the extent of
enclosed area enclosed area
Division 1
Located at Grade in an Figure 50 with
Inadequately Ventilated Enclosed Division 1 for the
Area extent of
enclosed area
More than One Piping Located Outdoors at Grade Figure 96 Figure
System With Multiple handling Flammable or 5.9.1(g)
Valves, Screwed Combustible Liquid or Highly
Volatile Liquid (HVL)
Fittings, Flanges, Located Outdoors at Grade Figure 5.9.11
Hoses, etc. in Close handling Cold Liquefied
Proximity: Flammable Gas including Liquefied
Metering Skid Natural Gas
Manifolds Located in Inadequately Ventilated Figure 22
Prover Skid Process Location handling Heavier-
Sampler System Than-Air Flammable or
Chemical Injection Combustible Gas or Vapor or
Skid Highly Volatile Liquid (HVL)
Located in Inadequately Figure 26
Ventilated Process Location
handling Lighter-Than-Air
Flammable or Combustible Gas or
Vapor
Located Inside Adequately Figure 97 Figure 5.9.13
Ventilated Roofed Building with
One or More Sides handling
Flammable or Combustible Liquid
or Highly Volatile Liquid (HVL)
Located Inside Adequately Figure 5.9.12
Ventilated Roofed Building with
One or More Sides handling Cold
Liquefied Flammable Gas including
Liquefied Natural Gas
Located Inside Inadequately Figure 98
Ventilated Roofed Building with

Page 7 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
One or More Sides handling
Flammable or Combustible Liquid
or Highly Volatile Liquid (HVL)
Plate and Frame Filter Handling a Solid wet with a Figure
Press Flammable Liquid 5.9.3(b)
(Adequate
Ventilation)
Product Dryer Handling a Solid wet with a Figure
(Inside Adequately Flammable Liquid 5.9.3(a)
Ventilated Butilding)
Hydrocarbon Pressure Vessels
(e.g. Heat Exchanger (Hazardous Material Shell-side),
Fin-Fan Heat Exchanger, Reactor, Accumulator, Oil-gas Separator, Tower)
Multiple Sources of In Adequately Ventilated Building Figure
Leakage from Process Handling a Flammable Liquid 5.9.1(n)
Equipment Located on In Outdoor Process Area Handling Figure
More than One Floor a Flammable Liquid 5.9.1(k)
or
Figure
5.9.1(l)
or
Figure
5.9.1(m)
Vessel Handling Heavier-Than-Air Figure 22
(Inside Inadequately Flammable or Combustible Gas or
Ventilated Process Vapor or Highly Volatile Liquid
Enclosure) (HVL)
Handling Lighter-Than-Air Figure 26
Flammable or Combustible Gas or
Vapor
Vessel Handling Lighter-Than-Air Figure 105
(Inside Adequately Flammable or Combustible Gas or
Ventilated Roofed Vapor
Building with One or Handling Flammable or Figure 97 Figure
More Sides) Combustible Liquid or Highly 5.9.1(j)
Volatile Liquid (HVL)
Source above Floor Level handling Figure
Flammable or Combustible Liquid 5.9.1(d)
or Highly Volatile Liquid (HVL)
Handling Cold Liquefied Gas Figure 5.9.12
including Liquefied Natural Gas

Page 8 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
Vessel Handling Lighter-Than-Air Figure 106
(Inside Inadequately Flammable or Combustible Gas or
Ventilated Roofed Vapor
Building with One or Handling Flammable or Figure 98 Figure
More Sides) Combustible Liquid or Highly 5.9.1(i)
Volatile Liquid (HVL)
Vessel Groups F or G Dust with no visible Figure 5.8(c)
(Indoor with Enclosed dust cloud, dust layer less than 1/8
Operating Equipment) inch and surface color not
discernable
Groups F or G Dust with no visible Figure 5.8(d)
dust cloud or dust layer and
surface color discernable
Vessel Group E Dust with moderate or Figure 5.8(b)
(Indoor with Open or dense dust cloud, dust layer
Semi-Enclosed greater than 1/8 inch to less than
Operating Equipment) 1/8 inch and surface color not
discernable
Groups F or G Dust with moderate Figure 5.8(a)
or dense dust cloud to no visible
dust cloud, dust layer greater than
1/8 inch to less than 1/8 inch and
surface color not discernable
Vessel Group E Dust Figure 5.8(f)
(Indoor, Walled Off
Area, Enclosed
Operating Equipment)
Vessel Below Grade Handling Flammable or Figure 101
(Inadequately Combustible Liquid or Highly
Ventilated Area) Volatile Liquid (HVL)
Vessel at Grade Handling Flammable or Figure 48 Figure
(Nonenclosed Combustible Liquid 5.9.1(g)
Adequately Ventilated Handling Cold Liquefied Figure 5.9.11
Area) Flammable Gas including Liquefied
Natural Gas
Vessel Above Grade Handling Flammable or Figure 99 Figure
(Nonenclosed Combustible Liquid 5.9.1(b)
Adequately Ventilated or
Area) Figure
5.9.1(h)
or
Figure

Page 9 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
5.9.2(b)
Handling Highly Volatile Liquid Figure 21 with Figure
(HVL) Figure 99 5.9.1(b)
or
Figure
5.9.1(h)
Handling Cold Liquefied Figure 5.9.11
Flammable Gas including Liquefied
Natural Gas
Handling Liquified or Compressed Figure
Flammable Gas or Cryogenic 5.9.2(b)
Flammable Liquid
Instrumentation
Control Panel When Flammable Gas is vented to Figure 64
(Enclosure) for the inside of enclosure (control
Instruments having panel)
Connections to
Flammable or
Combustible Fluids Adequately ventilated control Figure 66
(Instruments located panel (enclosure) with
instruments inside
Inside or Attached to Inadequately ventilated control Figure 65
Panel) panel (enclosure) with
instruments inside
Process Control Valve Located in nonenclosed Division 2
adequately ventilated area extends 18
inches from stem
seal (not shown
on plot plan or
support drawing)
Located in enclosed adequately Division 2 to the
ventilated area extent of the
enclosed area
Located in enclosed inadequately Division 1 to the
ventilated area extent of the
enclosed area
Sample Valve Adequately ventilated area Figure 61
(Discharge located in
Enclosed Area) Inadequately ventilated area Figure 63
Pumps
Pump Below Grade Pump associated with Oil-gas Figure 101

Page 10 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
but External to Separator, Receiver, Sump, etc.
Associated Equipment handling Flammable or
(Inadequately Combustible Liquid or Highly
Ventilated Area) Volatile Liquid (HVL)
Pump at Grade Handling Flammable or Figure 51 Figure
(Outdoors) Combustible Liquid 5.9.2(a)
Handling Highly Volatile Liquid Figure 93 Figure
(HVL) 5.9.1(a)
Handling Liquefied or Compressed Figure
Flammable Gas or Flammable 5.9.2(a)
Cryogenic Liquid
Pump Handling Flammable or Figure 52
(Outdoors but Under Combustible Liquid
Roofed Building Handling Highly Volatile Liquid Figure 52 with
without Sides) (HVL) Figure 93
Pump Handling Flammable or Figure 53
(Inside Adequately Combustible Liquid
Ventilated Roofed Handling Flammable or Figure 94 Figure
Building with One or Combustible Liquid or Highly 5.9.1(c)
More Sides) Volatile Liquid (HVL) or
Figure
5.9.1(e)
Pump Handling Flammable or Figure 54
(Inside Inadequately Combustible Liquid
Ventilated Roofed Handling Flammable or Figure 95 Figure
Building with One or Combustible Liquid or Highly 5.9.1(f)
More Sides) Volatile Liquid (HVL)
Storage
Storage Area Bags Figure 5.8(e)
Drums
Closed Hoppers
handling Groups E, F, or G Dusts
Storage Tank Fixed Roof Flammable Liquid Figure 6 Figure
(Nonenclosed Storage Tank 5.9.4(a)
Adequately Ventilated Fixed Roof Flammable Liquid Figure 6
Area) Storage Tank with Internal
Floating Roof
Open Top Floating Roof Figure 7
Flammable Liquid Storage Tank
Fixed Roof Combustible Liquid Figure 8
Storage Tank

Page 11 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
Storage Tank for Dike height less than distance Figure
Cryogenic and other from container to dike 5.9.10(a)
Cold Liquefied Dike height greater than distance Figure
Flammable Gases from container to dike 5.9.10(b)
(Outdoors) Conainer with liquid level below Figure
grade or top of dike 5.9.10(c)

Page 12 of 13
5656 So. Staples, Corpus Christi, TX 78411
(512) 992-2284 www.bathgroup.com

Cross Reference Table for Area Classification Details (cont.)

Cross Reference for Area Classification


Equipment Specific Details Per Recommended Practices
Equipment/Scenario API RP 500 NFPA 497 NFPA 499
Storage (cont.)
Storage for Hydrogen Gaseous Hydrogen only Figure
(Indoors in an 5.9.8(b)
Adequately Ventilated Liquid Hydrogen only Figure
Building) 5.9.8(a)
Storage for Hydrogen Gaseous Hydrogen only Figure
5.9.8(b)
(Outdoors) Liquid Hydrogen only Figure
5.9.8(a)
Vents
Vent To Atmosphere From a Division 1 Area Figure 16 or
(Nonenclosed Figure 87
Adequately From a Division 2 Area Figure 17 or
Ventilated) Figure 88
From Instrument or Control Figure 15
Device (Low Pressure)
From Process Equipment Figure 14
From Relief Valve Figure 18
From Rupture Disk Figure 18
From source handling Cryogenic Figure 5.9.13,
Flammable Liquids including Bottom
Natural Gas Detail
Vent To Atmosphere From source handling Cryogenic Figure 5.9.13,
(Indoors Adequately Flammable Liquids including Top Detail
Ventilated Building) Natural Gas

Notes:
1. NFPA Figures above use Division nomenclature. The use of NFPA Figures with Zone nomenclature is
discouraged.
2. See Section 5.10 for Highly Volatile Liquid (HVL), Flammable Liquid, and Combustible Liquid definitions.
3. Specific radius dimensions for use with the Figures above should be obtained from Gas/Vapor Dispersion
modeling results.
4. If modeling results cannot be obtained (e.g. composition of material is unknown), use the recommended
radius per the specific figure.