Documente Academic
Documente Profesional
Documente Cultură
an
Engineers
Newsletter Live
telecast
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 1
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
Copyrighted Materials
This presentation is protected by
U.S. and international copyright laws.
Reproduction, distribution, display, and
use of the presentation without written
permission of Trane or American
Standard is prohibited.
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 2
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
airside economizers
Todays Topics
What an airside economizer is
Types of control
Application considerations
Todays Presenters
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 3
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
What Is an Airside
Economizer?
definitions
Airside Economizer
1. Device that, on proper variable
sensing, initiates control signals or
actions to conserve energy
ASHRAE Terminology
of Heating, Ventilation,
Air Conditioning & Refrigeration
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 4
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
definitions
Airside Economizer
A duct-and-damper arrangement and
automatic control system that together
allow a cooling system to supply outdoor
air to reduce or eliminate the need for
mechanical cooling during mild or
cold weather
2006 American Standard All rights reserved
ASHRAE/IESNA
Standard 90.1-2004
RA
RL
OA SA
space
2006 American Standard All rights reserved
Supply-air temperature
varies to match cooling load
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 5
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
CAV system
Operating Modes
heating mechanical cooling
100
OA intake flow, %
heating
capacity
2006 American Standard All rights reserved
0
cold OA temperature hot
cooling
capacity
2006 American Standard All rights reserved
outdoor air
min
0
cold OA temperature hot
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 6
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
outdoor
air
2006 American Standard All rights reserved
outdoor
air
mech clg
2006 American Standard All rights reserved
capacity
min
0
cold OA temperature hot
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 7
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
outdoor
air
mech clg
2006 American Standard All rights reserved
capacity
min
0
cold OA temperature hot
integrated
economizer
100% OA
modulated
economizer
min to
100% OA
high-limit shutoff
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 8
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
Why Use an
Airside Economizer?
airside economizer
Why Use It?
Comply with ASHRAE 90.1-2004,
Section 6.5.1
or local energy code
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 9
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
1a
c b a
marine dry moist
1 very hot 3 warm 5 cool 7 very cold
2 hot 4 mixed 6 cold 8 subarctic
5 cool
Inuvik 8 6 cold
7 very cold
Whitehorse 8 subarctic
8
Ft. Nelson 8 8 Ft. Smith
7 Prince George
Goose Bay 7
Kamloops
5 St. Johns 6
2006 American Standard All rights reserved
5 7 7 Saskatoon Kapuskasing
Qubec
Vancouver Calgary 7 7 7
7 6 Halifax
Regina Montreal 6
Winnipeg
6 Toronto
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 10
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
Mexico
climate zone examples
1 very hot
2 hot
3 warm
4 mixed
3 Monterrey
1 Tampico
Guadalajara 1 1 Mrida
2006 American Standard All rights reserved
Mexico City 3
4 Veracruz
4b
Economizer
NOT required
System 65,000 Btu/h?
Economizer required
2006 American Standard All rights reserved
c b a
marine dry moist
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 11
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 12
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
airside economizer
Why Use It?
Comply with ASHRAE 90.1-2004,
Section 6.5.1
or local energy code
95
% of base
90
85
2006 American Standard All rights reserved
80
75
base VAV CAV
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 13
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
95
% of base
90
85
2006 American Standard All rights reserved
80
75
base VAV CAV
airside economizer
Why Use It?
Comply with ASHRAE 90.1-2004,
Section 6.5.1
or local energy code
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 14
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
Economizer
Control Types
Dew point & dry bulb Warmer or wetter Cooler and drier
(fixed DB with than fixed DB,DP than fixed DB,DP
DP lockout) settings settings
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 15
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
wet-bulb temperature, F
minimum
OA intake
2006 American Standard All rights reserved
dry-bulb temperature, F
econ economizer econ
OFF ON OFF
c b a
marine dry moist
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 16
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
missed opportunities:
Fixed Dry Bulb
wet-bulb temperature, F
minimum
OA intake
2006 American Standard All rights reserved
dry-bulb temperature, F
econ economizer econ
OFF ON OFF
wet-bulb temperature, F
humidity ratio, grains/lb of dry air
high-limit shutoff
28 Btu/lb
minimum
OA intake
2006 American Standard All rights reserved
dry-bulb temperature, F
econ economizer
OFF ON
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 17
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
missed opportunities:
Fixed Enthalpy
wet-bulb temperature, F
possible increased
2006 American Standard All rights reserved
cooling tons
dry-bulb temperature, F
econ economizer
OFF ON
wet-bulb temperature, F
humidity ratio, grains/lb of dry air
high-limit shutoff
curve A
minimum
OA intake
2006 American Standard All rights reserved
dry-bulb temperature, F
econ economizer
OFF ON
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 18
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
missed opportunities:
Electronic Enthalpy
wet-bulb temperature, F
minimum
55F
OA intake
possible increased
2006 American Standard All rights reserved
cooling tons
dry-bulb temperature, F
econ economizer
OFF ON
wet-bulb temperature, F
humidity ratio, grains/lb of dry air
high-limit
shutoff range
minimum
OA intake
2006 American Standard All rights reserved
dry-bulb temperature, F
econ economizer
OFF ON
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 19
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
missed opportunities:
Differential Enthalpy
wet-bulb temperature, F
minimum 55F
OA intake
2006 American Standard All rights reserved
dry-bulb temperature, F
econ economizer
OFF ON
wet-bulb temperature, F
humidity ratio, grains/lb of dry air
high-limit
shutoff
55F DP OA
minimum
OA intake
high-limit
2006 American Standard All rights reserved
shutoff
75F DB OA
dry-bulb temperature, F
econ economizer
OFF ON
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 20
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
missed opportunities:
Dew-Point and Dry-Bulb Temperatures
wet-bulb temperature, F
minimum 55F
OA intake
high-limit
2006 American Standard All rights reserved
shutoff
75F DB OA
dry-bulb temperature, F
econ economizer
OFF ON
No differential
dry bulb
2006 American Standard All rights reserved
c b a
marine dry moist
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 21
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
economizer control
High-Limit Shutoff
Its an enable/disable point,
prescribed by control type and climate
(see Table 6.5.1.1.3B)
economizer control
Integrated Economizer
Extends economizer hours to save
more cooling energy
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 22
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
integrated
economizer
required DX systems that reduce
OA to prevent frosting
Small DX systems with
capacities < 65,000 Btu/h
Any system in most
climates
2006 American Standard All rights reserved
c b a
marine dry moist
economizer control
Integrated Economizer
Use in chilled water systems whenever
possibleeven if not required
cycling, and possible premature failure
Out-of-control space relative humidity
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 23
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
high-limit
shutoff
2006 American Standard All rights reserved
outdoor air
min
0
cold OA temperature hot
enable
outdoor
air
mech clg
2006 American Standard All rights reserved
capacity
min
0
cold OA temperature hot
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 24
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
Performance in a
Constant-Volume System
Economizer Performance
Compare:
Economizer control types
High-limit shutoff settings
Space humidity
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 25
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
TRACE 700
Space Humidity Profile
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 26
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
Columbus, Ohio
5a
warm,
humid
c b a Retail store
marine dry moist Constant-volume system
Office building
VAV system
RA
EA
SA
T space
OA MA
2006 American Standard All rights reserved
High-limit shutoff:
55F 70F single-zone CAV system
65F 75F
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 27
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
95 8%
% of base
90
13% 13%
15%
85
2006 American Standard All rights reserved
80
75
none 55F 65F 70F 75F
high-limit shutoff setting (fixed DB)
140
75
OA 120
100
MA
60 80
55
RA 60
50 SA
45
40 40
35
2006 American Standard All rights reserved
30
70F high-limit 75F high-limit 20
shutoff setting shutoff setting
0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 28
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
200
150
100
2006 American Standard All rights reserved
50
0
none 55F 65F 70F 75F
high-limit shutoff setting (fixed DB)
140
75
70
OA 120
100
65 MA
SA
60 RA 80
55 RA
60
50 SA
45
40 40
35
2006 American Standard All rights reserved
30
70F high-limit 75F high-limit 20
shutoff setting shutoff setting
0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 29
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
95 8%
% of base
90
13% 13% 14%
15%
85
2006 American Standard All rights reserved
80
200
150
100
2006 American Standard All rights reserved
50
0
none 55F 65F 70F 75F 75F DB,
high-limit shutoff setting (fixed DB) 55F DP
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 30
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
RA
EA
SA
h space
OA MA
2006 American Standard All rights reserved
High-limit shutoff:
23 Btu/lb 32 Btu/lb single-zone CAV system
28 Btu/lb
95
11%
% of base
90
14%
15% 14%
16%
85
2006 American Standard All rights reserved
80
75
none 70F 75F DB, 23 28 32
fixed DB 55F DP Btu/lb Btu/lb Btu/lb
lockout fixed h fixed h fixed h
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 31
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
fixed enthalpy:
Example at Part Load*
85
180
wet-bulb temperature, F
80 160
60 80
55
60
50 SA RA
45
40
40 MA
2006 American Standard All rights reserved
35
30
SA OA 20
0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
200
150
100
2006 American Standard All rights reserved
50
0
none 70F 75F DB, 23 28 32
fixed DB 55F DP Btu/lb Btu/lb Btu/lb
lockout fixed h fixed h fixed h
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 32
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
60 80
55
60
50 shutoff setting
45
40 40
35
2006 American Standard All rights reserved
30
20
0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
95
% of base
90
15% 14% 15%
16%
85
2006 American Standard All rights reserved
80
75
none 70F 75F DB, 28 electronic
fixed DB 55F DP Btu/lb enthalpy
lockout fixed h
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 33
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
200
150
100
2006 American Standard All rights reserved
50
0
none 70F 75F DB, 28 electronic
fixed DB 55F DP Btu/lb enthalpy
lockout fixed h
RA
EA RA
h
SA
h space
OA MA
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 34
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
95
% of base
90
15% 14% 16% 15% 16%
85
2006 American Standard All rights reserved
80
75
none 70F 75F DB, 28 electronic differential
fixed DB 55F DP Btu/lb enthalpy enthalpy
lockout fixed h
200
150
100
2006 American Standard All rights reserved
50
0
none 70F 75F DB, 28 electronic differential
fixed DB 55F DP Btu/lb enthalpy enthalpy
lockout fixed h
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 35
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
differential enthalpy:
Example at part load*
85
180
wet-bulb temperature, F
80 160
0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
Performance in a
Variable-Volume System
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 36
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
95 8%
9%
10% 11% 11%
% of base
90
85
2006 American Standard All rights reserved
80
200
150
100
2006 American Standard All rights reserved
50 29 26
19 19
3 8
0
none 55F 65F 70F 75F 75F DB,
high-limit shutoff setting (fixed DB) 55F DP
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 37
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
60
MA 80
SA RA
55
50 RA 60
45 SA
40 40
35
2006 American Standard All rights reserved
30
55F SA 75F high-limit 20
temperature shutoff setting 0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
VAV system:
Economizer Effect on Space Humidity*
85
180
wet-bulb temperature, F
80 160
humidity ratio, grains/lb of dry air
140
75
120
70
100
65
60 80
RA
55 SA MA
60
50
45 RA
35
40
OA MA/SA 40
2006 American Standard All rights reserved
30
55F 70F economizer 20
SA setpoint shutoff setting 0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 38
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
95
8%
10% 11% 9%
11% 11%
% of base
90
85
2006 American Standard All rights reserved
80
75
none 70F 75F DB, 23 28 32 electronic
fixed 55F DP Btu/lb Btu/lb Btu/lb enthalpy
DB lockout fixed h fixed h fixed h
200
150
100
2006 American Standard All rights reserved
50 29
19 19 19 19
8 2
0
none 70F 75F DB, 23 28 32 electronic
fixed 55F DP Btu/lb Btu/lb Btu/lb enthalpy
DB lockout fixed h fixed h fixed h
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 39
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
95
90
85
2006 American Standard All rights reserved
80
75
none 70F 75F DB, 28 electronic differential
fixed DB 55F DP Btu/lb enthalpy enthalpy
lockout fixed h
200
150
100
2006 American Standard All rights reserved
50 29
19 19 19 18
8
0
none 70F 75F DB, 28 electronic differential
fixed DB 55F DP Btu/lb enthalpy enthalpy
lockout fixed h
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 40
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
VAV system:
SA Temperature Reset*
85
180
wet-bulb temperature, F
80 160
60 RA 80
55 OA
60
50
RA
40
45 SA 40
35
2006 American Standard All rights reserved
30
55F 60F 20
SA setpoint SA setpoint
0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
140
75
120
70
100
65
60 80
55
60
50 55F
45
40 SA setpoint 40
35
2006 American Standard All rights reserved
30
modulated integrated 20
economizer economizer
0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 41
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
60 80
55
60
50
45
40 48F 40
35 SA setpoint
2006 American Standard All rights reserved
30
modulated integrated 20
economizer reset economizer
0
30 40 50 60 70 80 90 100 110
dry-bulb temperature, F
Energy/Humidity Effects
Control strategy and high-limit shutoff
setting impact energy use AND indoor
humidity levels
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 42
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
Implementing
Airside Economizers
Implementing
Airside Economizers
Single-zone systems
Multiple-zone systems
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 43
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
single-zone systems
Packaged DX Rooftop
Size OA intake hood for
design airflow of system
OA
2006 American Standard All rights reserved
RRA SA
single-zone systems
Indoor Air Handler
Size OA duct for the air handlers design airflow
OA
SA RRA
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 44
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
single-zone systems
Unit Ventilators
SA
OA
2006 American Standard All rights reserved
minimum = 1 ft RRA
multiple-zone systems
Outdoor Air Handler
Measure and control
OA outdoor airflow to maintain
proper airflow rates
SA
RRA
2006 American Standard All rights reserved
VAV terminals
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 45
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
multiple-zone systems
Indoor Air Handler
RRA
alt
OA
SA
2006 American Standard All rights reserved
multiple-zone systems
Commercial Self-Contained
minimum
OA
SA
RRA
RRA
SA
2006 American Standard All rights reserved
RRA
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 46
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
cooling tower
DX coil
condensers
2006 American Standard All rights reserved
RRA
SA
RRA
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 47
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
conditioned
OA minimum
OA
SA SA
RRA RRA
2006 American Standard All rights reserved
3-way valve
economizer coil
refrigerant-to-water
heat exchanger
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 48
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
conditioned
OA minimum
OA
SA SA SA
2006 American Standard All rights reserved
RRA
closed in
economizer
mode
heat
exchanger
typical
cooling
coil
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 49
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
SA
RRA
2006 American Standard All rights reserved
Application
Considerations
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 50
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
application considerations
Building Pressure Control
Standard 90.1 requires:
Low-leak dampers
Some method for controlling
building pressure
exfiltration
RRA
recirculated infiltration space
return air
EA
local
2006 American Standard All rights reserved
exhaust
OA SA air
outdoor mixed-air supply air
(intake) air plenum
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 51
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
system configurations
Only works for
Natural Relief small buildings
return-air
plenum return air
RA
exfiltration
RRA
recirculated infiltration space
return air
EA
local
2006 American Standard All rights reserved
exhaust
OA SA air
outdoor mixed-air supply air
(intake) air plenum
system configurations
Works okay, but
Local Barometric Relief isnt accurate
return-air
plenum return air local
RA relief air
exfiltration
RRA
recirculated infiltration space
return air
EA
local
2006 American Standard All rights reserved
exhaust
OA SA air
outdoor mixed-air supply air
(intake) air plenum
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 52
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
system configurations
Doesnt work
Central Barometric Relief very well
return-air
central plenum return air
relief air RA
exfiltration
RRA
recirculated infiltration space
return air
EA
local
2006 American Standard All rights reserved
exhaust
OA SA air
outdoor mixed-air supply air
(intake) air plenum
system configurations
Works well for
Relief Fan most buildings
return-air
relief air plenum return air P
RL RA
exfiltration
recirculated P
return air
RRA infiltration space
EA
local
2006 American Standard All rights reserved
exhaust
OA SA air
outdoor mixed-air supply air
(intake) air plenum
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 53
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
system configurations
Works well with
Return Fan ducted return
return-air
relief air plenum return air
RL RA
exfiltration
RRA
recirculated infiltration space
return air
EA
local
2006 American Standard All rights reserved
exhaust
OA SA air
outdoor mixed-air supply air
(intake) air plenum
application considerations
Dynamic Reset
The system may be designed to reset the
design outdoor air intake flow (Vot) and/or
space or zone airflow as operating conditions
change. These conditions include but are not
limited to:
Variations in occupancy
Variations in the efficiency
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 54
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
application considerations
Dynamic Reset Control
These conditions include Variations in occupancy
or ventilation airflow in one or more individual zones
for which ventilation airflow requirements will be
reset.
application considerations
Dynamic Reset
modulated integrated mech
heating econ econ cooling chilled
100 water
return
80 air
flow, %
60
40
outdoor
20 air
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 55
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
design
relief allowable reset
intake = exfiltrn exfiltrn
infiltrn
design
relief allowable reset
intake =
infiltrn
exhaust reset
intake
= exhaust
limit
2006 American Standard All rights reserved
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 56
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
a Trane Engineers Newsletter Live satellite broadcast
HVAC Systems and Airside Economizers 3 May 2006
application considerations
Dynamic Reset
These conditions include :
Variations in occupancy
Variations in efficiency with which outdoor
air is distributed to the occupants under
different ventilation system airflows and
temperatures
A higher fraction of outdoor air in the
2006 American Standard All rights reserved
airside economizers
What We Covered
ASHRAE 90.1 requirements, exceptions
(location/size, controls, integration)
Application considerations
(building pressurization)
Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any 57
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
Trane Engineers Newsletter Live satellite broadcast
Bibliography
Articles
Brambley, M., Pratt, R., Katipamula, S. et al. 1998. Diagnostics for
Outdoor Air Ventilation and Economizers. ASHRAE Journal 40-10
(October), 49-55.
Taylor, S. 2000. Comparing Economizer Relief Systems. ASHRAE
Journal 42-9 (September), 33-40, 42.
Trane Publications
Stanke, D. Keeping Cool with Outdoor Air: Airside Economizers.
Engineers Newsletter 35-2 (2006). Available at
<http://www.trane.com/commercial/
navigation/files/pdf/6/admapn020en_0406.pdf>
Trane. 2002. HVAC System Control (Trane Air Conditioning Clinic TRG-
TRC017-EN). La Crosse, WI: Inland Label and Marketing Services,
LLC.
Page 1 of 1
engineers newsletter live
Presenter Biographies
John is the author of numerous Trane application manuals and Engineers Newsletters, and
is a frequent presenter on Tranes Engineers Newsletter Live series of satellite broadcasts.
He also is a member of ASHRAE, has authored articles for the ASHRAE Journal, and is a
member of ASHRAEs Moisture Management in Buildings and Mechanical Dehumidifiers
technical committees.
In addition to his Trane responsibilities as staff applications engineer, Dennis also serves
on research advisory boards at UCBerkeley (Centers for the Built Environment) and Penn
State University (Indoor Environment Center), and is an active member of the USGBC
LEED Technical Advisory Group for Indoor Environmental Quality (EQ TAG).