Sunteți pe pagina 1din 6

Reprinted with permission from CEP (Chemical Engineering Progress), April 2007.

Copyright 2007 American Institute of Chemical Engineers (AIChE).

Heat Transfer

Improving
Heat Exchanger
Designs
Christopher A. Bennett
This article defines and explains the
R. Stanley Kistler factors that affect heat exchanger
Thomas G. Lestina
Heat Transfer Research, Inc.
design margins. With the proper
David C. King application of design margins,
BP p.l.c. capital costs can be lowered and
plant operation improved.

R
ecognizing the need for a more effective procedure In order of magnitude: Uclean Uactual Urequired.
for designing heat exchangers, Heat Transfer Modern heat exchanger design software calculates the
Research, Inc. (HTRI), a global research and clean overall heat-transfer coefficient incrementally by:
development consortium, organized the Exchanger Design 1 n
Margins Task Force (EDMTF) in 2005. Twenty-five com- U clean = Uclean, j Ao, j (4)
Ao, total j =1
panies engineering contractors, heat exchanger fabrica-
tors and processors (box, p. TK) are currently repre- where the subscript j denotes the variable value at a spe-
sented on the EDMTF. Its goal is to establish a consensus cific increment, and Uclean,j, based on the clean outside
for the definition and application of design margins. This area, excluding fouling resistances, is given by:
consensus is needed because design margins have tradi- 1 1 Ao, j xw, j Ao, j 1
tionally been concealed in fouling factors instead of being = + + (5)
U clean, j ho, j Alm, j km, j Ai, j hi, j
explicitly designated, thereby resulting in inconsistent
margin application and ambiguous design comparisons. The logarithmic mean area for increment j is:

Defining design margin Ao, j Ai, j


Alm, j = (6)
Heat exchanger design margin is defined as any heat Ao, j
transfer area exceeding what is required by a clean heat ln
Ai, j
exchanger to satisfy a specified duty, as defined by Eqs. 13:
The actual overall heat-transfer coefficient is calculated
U incrementally from:
% Excess Area from Fouling = 100 clean 1 (1)
U actuaal n
1
U U actual = Uactual, j Ao, j ( 7)
% Overdesign = 100 actual 1 (2) Ao, total j =1
U required
U For increment j, Uactual,j, the actual overall heat-transfer
% Total Excess Area = 100 clean 1 ( 3) coefficient based on the clean outside area, including foul-
U required ing resistances, is therefore:

40 www.aiche.org/cep April 2007 CEP


1 1 Ao, j xw, j Ao, j Ao, j 1
= + R fo, j + + R fi, j + (8) handled by adding fouling resistances, common-
U actual , j ho, j Alm, j km, j Ai, j Ai, j hi, j ly known as fouling factors, to the overall heat-
The overall heat-transfer coefficient required by a spe- transfer resistance, as shown in Eq. 8. These fouling resist-
cific heat exchanger to satisfy the process conditions is: ances can be obtained from multiple sources, including
Qspecified company experience and the Tubular Exchanger
U required = (9) Manufacturers Association (TEMA) standards (1).
Ao, total EMTD
Fouling factors have become quite controversial in
The effective mean temperature difference (EMTD) is: recent years for many reasons. Published fouling resistanc-
1 1 n Qj es often do not reflect true performance; for some servic-
= (10 ) es, they are too high, while for others, they are too low.
EMTD Qtotal j =1 LMTD j
Fouling factors are static values, but some fouling mecha-
The logarithmic mean temperature difference over nisms are dynamic. Temperature and velocity can greatly
increment j (LMTDj) is computed by applying the standard influence fouling, but published fouling factors account
LMTD formula to the inlet and outlet temperatures of an for these effects in a limited manner, at best. Fouling fac-
increment. The average total fouling resistance, based on tors often implicitly account for uncertainty in the heat
the clean outside area, is: transfer methods, which can result in the duplication of
uncertainty effects.
1 n Ao, j
Rf = R fo, j + R fi, j (11)
n j =1 Ai, j
Nomenclature
Reasons for adding a design margin Ai,j = inside area of increment j, m2
Margins are added to heat exchangers during the design Alm,j = logarithmic mean area of increment j, m2
stage to account for fouling, uncertainties in heat transfer Ao,j = outside area of increment j, m2
methods and fluid properties, variable process or ambient Ao,total = total outside heat-transfer area, m2
conditions, lessons learned from previous experience, and EMTD = effective mean temperature difference, K
hi,j = inside heat-transfer coefficient of increment j,
risks associated with an exchanger that does not meet the
W/m2-K
process requirements. ho,j = outside heat-transfer coefficient of increment j,
Fouling. Fouling is defined as a conductive resistance W/m2-K
that accumulates on the heat-transfer surface. It can lead to j = counting variable, dimensionless
an unacceptable pressure drop. km,j = metal thermal conductivity of increment j, W/m-K
A common misconception is that heat exchangers LMTD = logarithmic mean temperature difference, K
always foul. A few streams that usually do not foul are LMTDj = logarithmic mean temperature difference of
increment j, K
listed in Table 1a. Other streams, such as boiler feedwater
n = number of increments, dimensionless
and cooling water, can be maintained relatively clean with Qj = calculated duty of increment j, W
proper attention. However, some process streams, such as Qspecified = specified duty, W
those listed in Table 1b, can foul heavily. Qtotal = total calculated duty, W
During heat exchanger design, fouling is traditionally Rf = total fouling resistance, m2-K/W
Rfi,j = inside fouling resistance of increment j, m2-K/W
Rfo,j = outside fouling resistance of increment j, m2-K/W
Table 1. Fouling tendencies of common streams. Uactual = overall heat-transfer coefficient, based on outside
area, including fouling resistance, W/m2-K
a. Streams that Typically Do Not Foul
Uactual,j = overall heat-transfer coefficient, based on outside
Refrigerants
area, including fouling resistance, of increment j,
Demineralized Water
W/m2-K
Non-Polymerizing (Olefin-Free) Condensing Gases
Liquid Natural Gas (LNG)
Uclean = overall heat-transfer coefficient, based on outside
area, excluding fouling resistance, W/m2-K
b. Streams that Typically Foul Heavily Uclean,j = overall heat-transfer coefficient, based on outside
Crude Oil area, excluding fouling resistance, of increment j,
Crude Oil Distillation Overhead W/m2-K
Amines Urequired = overall heat-transfer coefficient, based on outside
Hydrogen Fluoride (HF) area, needed by a specific design to satisfy
Coal Gasification process specifications, W/m2-K
Improperly Maintained Cooling Water xw,j = wall thickness of increment j, m

CEP April 2007 www.aiche.org/cep 41


Heat Transfer

Table 2. Uncertainties in single-phase heat-transfer


coefficient as a function of geometry (4). Basic Design Algorithm
Detailed design algorithms for fouling mitigation and excess
Exchanger Uncertainty in
Geometry Heat-Transfer Coefficient margin reduction have been published elsewhere (5) and will
not be reiterated here. Instead, the following is the most
Shell-and-Tube basic of design algorithms.
Tubeside 10% 1. Check company experience with the heat exchanger to
Shellside 20%50% be designed.
Plate-and-Frame 10%30% 2. Decide on fouling factors.
a. If a stream is determined to be non-fouling, do not
Plate-Fin 20%
use a fouling factor for that stream in Eq. 8.
b. If a stream is known to foul, use a fouling factor in
The main reason fouling factors are so controversial, Eq. 8 according to the companys best practices.
however, is that they can result in significant overdesign, 3. Place the most heavily fouling stream on the tubeside
resulting in the specification of an expensive heat to facilitate cleaning, if necessary, and to avoid the areas of
low velocity that occur on the shellside.
exchanger with unnecessary area. For many applications,
4. Design for high velocities within erosion and vibration
fouling factors should not contribute more than 20% limits. If possible,
excess area to the heat exchanger design. a. Tubeside velocity should be 2 m/s.
Uncertainty. There are uncertainties associated with both b. Shellside B-stream (the main crossflow stream
the fluid properties (2) and the methods used to determine through the bundle) (6) velocity should be 0.6 m/s.
heat-transfer coefficients (3). These uncertainties propagate Exceptions to this general high-velocity rule for fouling
through the computations (4) and result in a calculated mitigation include corrosion, geothermal brines, and slurries
that present an erosion limit. Note the importance of metal
overdesign that can deviate from the true value. This devia-
selection on corrosion and erosion.
tion will result in a heat exchanger that performs more or 5. Keep overdesign (Eq. 2) between 0 and 20% where
less efficiently than the computations say it should. industry experience permits. Consider larger overdesigns for
Literature values for heat-transfer coefficient uncertain- tubeside laminar flow, mist flow boiling, and shellside mixture
ties are given in Table 2 (4). Fluid property uncertainties condensation in deep gravity flow.
vary dramatically depending upon the predictive method
used, and the reader is encouraged to peruse the literature
for values (2). Uncertainty propagation is highly depend- tor considered. The heat exchanger designer should initial-
ent on the heat transfer methods utilized, as well as the ly consult the companys design recommendations.
relative thermal resistances. Fouling factors and overdesign should then be assigned as
Variable process conditions. Process conditions can the field experience and anticipated turn-up dictate.
vary due to day-to-day changes in process operations and Risk. Heat exchangers are often intentionally oversized
turn-up and turn-down conditions. Turn-up is particularly because of perceived risk. Because certain heat exchangers
critical at present, as existing plants are pushed harder to are particularly essential to operations, the designer will
generate additional revenue. Turn-up can result in exceed- intentionally overdesign a unit to ensure that it will satisfy
ing the erosion velocity for the fluid/metal combination the duty no matter what occurs during operation. What the
and presents the potential for vibration damage to tubular designer needs to realize, however, is that excessive
designs. Because turn-down often results in lower veloci- overdesign can actually cause fouling and other problems
ties, it can cause the exchanger to foul. with the exchanger and plant operations.
Variable ambient conditions. When one of the heat
exchanger streams is influenced by ambient conditions, it Problems with excessive design margin
results in a variable EMTD, which affects the units per- The excessive use of design margin has several draw-
formance, particularly in such devices as air coolers and backs. Clearly, superfluous heat-transfer area translates direct-
once-through cooling water exchangers. Process reduc- ly to unnecessary capital cost. Needless heat-transfer area
tions occur when design temperature limits are exceeded. also results in a larger, heavier exchanger; weight and foot-
Previous experience. One of the most frequently cited print are very important considerations for offshore applica-
reasons for adding margin to a heat exchanger design is that tions. Worst of all, excessive design margin can also result in
is how it has always been done. As the example covered accelerated fouling becoming a self-fulfilling prophesy.
later will demonstrate, this is not always the best practice. Designers often incorporate excess margin by increasing
While accounting for the performance of previously the shell diameter. This increases the cross-sectional area
designed units is important, it should not be the only fac- available for flow, resulting in lower shellside velocities for

42 www.aiche.org/cep April 2007 CEP


a given flowrate. Furthermore,
Triethylene Glycol
the number of tubes increases, Contactor Heat
Exchanger
which reduces tubeside veloci- Heat Gas/Liquid Compressor
Gas
Heat Export
ty. Lower velocities often Exchanger Separator Exchanger
increase the rate of fouling. Production Metering
Package
Over-performance caused by Gas CW
excess heat-transfer area can Compressor
also accelerate fouling because Cooling CW Gas/Liquid Gas/Liquid
Water Separator Separator
the process stream temperature (CW)
change will be greater than
desired, requiring the flowrate  Figure 1. Gas compression process at an offshore facility analyzed in the example.
of the utility stream to be
reduced or other measures to be
taken. Turn-down results in lower
velocities, which can initiate or
accelerate fouling.

Example
To illustrate the significant
impact that excess margin can have
on heat exchanger design, consider a
gas compression process of an off-
shore facility as depicted schemati-  Figure 2. One-shell-pass, four-tube-pass (1-4) CEU heat exchanger in service at the example
cally in Figure 1. Production gas first offshore facility.
enters a partial condenser, where the
heavy ends are condensed and the light Table 3. Salient details of the heat exchanger designs.
ends cooled. The condensate is subsequent-
ly removed in a separator. Then the gas is BFU with
compressed and enters another partial con- In-service Fouling
Parameter CEU Factors BFU
denser, where the remaining heavy ends are
condensed. Effluent from the second partial Heat-Transfer Area, m2 187 154 93.5
condenser enters another separator and then Tube Material Titanium Titanium Titanium
proceeds through a triethylene glycol (TEG)
Relative Cost 1.5 1.3 1
contactor to strip water from the process
stream. The process stream proceeds Estimated Weight, kg 5,700 5,350 5,000
through the final separator, is compressed Estimated Footprint, m m 0.81 7.0 0.78 5.9 0.78 4.6
again, and is cooled in a final heat exchang- 2
Total Fouling Resistance, m -K/W 0.000429 0.000429 0
er before being metered and exported. 2
Uclean, W/m -K 1,540 1,510 1,510
The final heat exchanger in the train is
Uactual, W/m2-K 928 917 1,510
the focus of this discussion because experi-
ence has revealed that neither stream fouls Urequired, W/m2-K 748 757 1,250
under normal operating conditions. The Overdesign, % 24.1 21.1 21.0
shellside fluid is chlorine-treated once- Excess Area From Fouling, % 65.9 64.9 0
through seawater and the tubeside fluid was
Total Excess Area, % 106 99.8 21.0
modeled as supercritical methane.
Qspecified, MW 4.29 4.29 4.29
Three configurations for this final heat
exchanger were analyzed, and the salient EMTD, C 30.7 36.8 36.8
details are presented in Table 3. The base B-Stream (6) Fraction 0.382 0.685 0.691
case is the one-shell-pass, four-tube-pass Tube-Side Velocity, m/s 2.95 2.88 2.89
(1-4) CEU TEMA type that is currently in
B-Stream (6) Velocity, m/s 0.86 1.10 1.05
service (illustrated in Figure 2). The cen-

CEP April 2007 www.aiche.org/cep 43


Heat Transfer

Literature Cited
1. Tubular Exchanger Manufacturers Association,
Standards of the Tubular Exchanger Manufacturers
Association, 8th ed., TEMA, New York (1999).
2. Reid, R. C., J. M. Prausnitz and B. E. Poling, The
Properties of Gases and Liquids, 4th ed., McGraw-Hill,
New York (1987).
3. Lestina, T., and K. Bell, Thermal Performance Testing of
Industrial Heat Exchangers, Advances in Heat Transfer, 35,
pp. 155 (2001).
4. American Society of Mechanical Engineers, Single-Phase
Heat Exchangers, ASME Performance Test Code 12.5,
ASME, New York (2001).
5. Nesta, J., and C. A. Bennett, Reduce Fouling in Shell-and-
 Figure 3. Two-shell-pass, four-tube-pass (2-4) BFU heat Tube Heat Exchangers, Hydrocarbon Processing, 83 (7),
exchanger studied in the example. pp. 7782 (2004).
6. Palen, J. W., and J. Taborek, Solution of Shellside Flow
Pressure Drop and Heat Transfer by Stream Analysis
tral baffle spacing was 22.6% of the shell inside diameter,
Method, Chem. Eng. Progress Symposium Series, 65 (92),
resulting in a low B-stream (6) fraction and inefficient pp. 5363 (1969).
heat transfer. Individual fouling factors of 0.000176 m2-
K/W were used for both streams (which combined via Eq.
11 to yield a total fouling resistance of 0.000429 m2- adjusting heat transfer area. Uclean, duty, EMTD, and the
K/W). These specifications resulted in a heat-transfer area velocities were effectively the same between the two BFU
requirement of 187 m2 and a total excess area of 106%. designs, confirming the comparability of this approach.
The second heat exchanger design investigated was a Comparing the BFU design with no fouling factors
two-shell-pass, four-tube-pass (2-4) BFU TEMA type with the other two designs reveals striking differences. For
(Figure 3), with the same fouling factors (0.000176 m2- example, the heat transfer area is reduced to only 93.5 m2,
K/W) for both streams as in the CEU exchanger. A lower- resulting in an exchanger that is 23% less expensive than
cost front head (TEMA Type B) was used because fouling the BFU with fouling factors and 33% less expensive than
will not be a problem, thereby negating the need for easy the in-service CEU. Because no fouling factors were used,
access to the tubesheet. An F-shell was selected to reduce the overdesign and total excess area are identical at 21%, a
the exchanger footprint and weight via increased EMTD reasonable value that gives flexibility to the process. The
across the exchanger. U-tubes were chosen to prevent ther- weight and footprint of this exchanger are also less than
mal expansion problems resulting from the large terminal the other designs, which is an important consideration for
temperature difference of this exchanger. Titanium was this offshore application. Because the in-service exchanger
utilized to avoid corrosion problems. does not foul and this design has similar temperatures,
This BFU configuration reduced the heat-transfer area velocities, and metallurgy, we are confident in the
requirement by 18%, with the exchanger cost dropping con- viability of this low-cost design. CEP

comitantly. The total excess area is


still quite high at 99.8%, and the
total excess area is not simply the Companies Represented on the Exchanger Design Margins Task Force
sum of the overdesign and the
excess area from fouling factors; Alfa Laval Lund AB Joseph Oat Corp.
this demonstrates the compounding APV North America, Inc. Kellogg Brown & Root, Inc.
BASF Aktiengesellschaft Koch Heat Transfer Company, L.P.
of fouling factors in the overdesign.
Bechtel Ltd. Mitsubishi Chemical Engineering Corp.
The third exchanger design con- BP p.l.c. Nooter/Eriksen, Inc.
sidered was an identical BFU Celanese Ltd. Reliance Engineering Associates (P) Ltd.
except that no fouling resistance Chevron Energy Technology Co. Shell Canada Ltd.
was used in Eq. 8. An equivalent ConocoPhillips Co. Shell Global Solutions International B.V.
Eastman Chemical Co. Shell Global Solutions (U.S.), Inc.
overdesign of 21% was achieved
Ecodyne MRM, Inc. Statoil ASA
by shortening the tubes. Changing E.I. du Pont de Nemours & Company, Inc. Technip
the tube length is normally the ExxonMobil Research and Engineering Co. Toyo Engineering Corp.
most economical approach for High Performance Tube, Inc.

44 www.aiche.org/cep April 2007 CEP


CHRISTOPHER A. BENNETT is a researcher specializing in fouling at Heat THOMAS G. LESTINA, P.E., vice president, engineering services at HTRI
Transfer Research, Inc. (HTRI; 150 Venture Dr., College Station, TX, (Phone: (979) 690-5063; Fax: (979) 690-3250; E-mail: tgl@htri.net),
77845; Phone: (979) 690-5069; Fax: (979) 690-3250; E-mail: has 20 years of engineering project management experience. As the
cab@htri.net). He holds a BS in chemical engineering from the Univ. of person responsible for HTRI training, he develops, customizes and
Toledo and an MS and PhD in chemical engineering from the Univ. of teaches at HTRI events and member companies. In addition, he has
Michigan. His diverse research experience in wet chemistry, surface developed and taught the course, Heat Exchanger Design and
chemistry, materials science, mathematical modeling and aquatic Operation for ASME/AIChE. He also manages HTRIs growing contract
biology has proven very useful to understanding heat exchanger services and technical support. Prior to joining HTRI, he worked as a
fouling. Bennett co-chairs the HTRI Exchanger Design Margins Task lead engineer for MPR Associates, Inc. A licensed Professional
Force and chairs the HTRI Crude Oil Fouling Task Force. Engineer in Texas, Lestina earned a BS in mechanical engineering from
Union College (Schenectady, NY) and an MS in mechanical engineering
R. STANLEY KISTLER is vice president, research and software from Rensselaer Polytechnic Institute (Troy, NY). He is a member of
development at HTRI (Phone: (979) 690-5070; Fax: (979) 690-3250; E- ASME and serves as chair of the technical committee for the ASME
mail: rsk@htri.net). He obtained his undergraduate and masters Performance Test Code 12.5, Single Phase Heat Exchangers.
degrees, as well as his PhD in chemical engineering with an emphasis
on boiling, from the Univ. of Missouri-Rolla. Since joining HTRI in 1973, DAVID C. KING is a senior heat transfer consultant for BP p.l.c (Chertsey
he has primarily focused on software development. He has also Rd., Sunbury-on-Thames, Middlesex, TW16 7LN, UK; Phone: +44-1932-
conducted experimental research on shellside single-phase flow. 775621; Fax: +44-1932-738414; E-mail: dave.king@uk.bp.com). With 32
Kistler has helped develop many HTRI workshops and has taught years of experience working in the refining, petrochemical, and
dozens of courses and workshops around the world. He also serves as exploration and production sectors, he is currently responsible for
a guest lecturer for academic courses and has been involved in various developing and leading a global heat exchange community and for
engineering events in academia. An AIChE Fellow, Kistler is past chair providing leadership in heat transfer to the exploration and production
of AIChEs Heat Transfer and Energy Conversion division, and has sector. He developed the case for establishing HTRIs Exchanger
chaired numerous sessions at National Heat Transfer Conferences. He Design Margin Task Force and has actively participated in task force
co-chairs the HTRI Exchanger Design Margins Task Force. activities. He holds a BSc Honors in fuel and combustion engineering
from Leeds Univ.

CEP April 2007 www.aiche.org/cep 45

S-ar putea să vă placă și