Description of work for which switching is done:- To maintain the T11 33/6.6kV Transformer at Salford Quays Pry S/S Serial No. 02892 N2017
100641 - Training Programme 5
No. of sheets attached
Planned restoration on (date) Friday 23 June 2017 This switching programme shall be updated immediately after each instruction has been given,
operation carried out, or document issued. The Control Engineer shall record the time at which
Operator(s) names(s) G. Andreakos 50016 A. Bamford operations are instructed and to whom they are issued. When an instruction has been carried
out he shall record the time the last operation was performed. The operator shall record the
time an instruction is received and the time each operation is carried out, together with his
initials. When safety documents are issued details should be entered below. The date should
only be recorded against the first operation after a change of date.
17/05/2017 15:19
COMPLETION The programme has now been completed/suspended/cancelled and associated safety documents are attached. (Delete as appropriate) A further
programme has been/will be prepared for future work as follows:
Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time
4 Salford Quays S/S 100641 T12 33/6.6kV Transformer Check Protection and Cooling 4
6 Broadway Back Up Supply HV customer Inform BBC Broadway Backup Supply unavailable (expected 6
S/S 168526 RTS 23/06/17)
9 Salford Quays S/S 100641 T11 & T12 Tap Change Make non auto and adjust for T11 outage by TC 9
Control
12 Salford Quays S/S 100641 T12 Tap Change Control Make independant auto by TC 12
SWITCHING PROGRAMME Zone Serial No.
33 KV 02892 N2017
"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION"
Sheet No. 2
9/658-4/01 Number of sheets 5
Each item in the programme to consist of one operation only. Include the issue and cancellation of relevent documents as separate operations.
Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time
14 Salford Quays S/S 100641 T11 6.6kV CB Isolate SL & CN on BB & FDR Shutters 14
17 Frederick Rd Grid S/S B29 Salford Quays T11 Move to the OFF position SL & CN 17
100504 33kV BB Isolator
18 Frederick Rd Grid S/S B29 Salford Quays T11 Move to the EARTH position SL & CN 18
100504 33kV Earth Selector
19 Frederick Rd Grid S/S B29 Salford Quays T11 Isolate Trip Links Post CN 19
100504 33kV CB
20 Frederick Rd Grid S/S B29 Salford Quays T11 Close to Earth SL & CN 20
100504 33kV CB
22 Salford Quays S/S 100641 T11 Transformer Isolate Tap Change & Cooling Supplies Post CN 22
23 Salford Quays S/S 100641 T11 Transformer Isolate Buchholz and Winding Temp trip and alarm links 23
Post CN
SWITCHING PROGRAMME Zone Serial No.
33 KV 02892 N2017
"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION"
Sheet No. 3
9/658-4/01 Number of sheets 5
Each item in the programme to consist of one operation only. Include the issue and cancellation of relevent documents as separate operations.
Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time
24 Salford Quays S/S 100641 T11 Transformer Issue PTW ____________ to maintain transformer and 24
auxiliary equipment
25 Salford Quays S/S 100641 T11 Transformer Cancel PTW from operation 24 25
26 Salford Quays S/S 100641 T11 Transformer Restore Tap Change and Cooling Supplies 26
27 Salford Quays S/S 100641 T11 Transformer Restore Buchholz and Winding Temp trip and alarm links 27
30 Frederick Rd Grid S/S B29 Salford Quays T11 Open from Earth 30
100504 33kV CB
31 Frederick Rd Grid S/S B29 Salford Quays T11 Move to the OFF Position 31
100504 33kV Earth Selector
32 Frederick Rd Grid S/S B29 Salford Quays T11 Move to Service Position 32
100504 33kV Busbar Isolator
33 Salford Quays S/S 100641 T11 6.6kV CB Rack into Service Position 33
SWITCHING PROGRAMME Zone Serial No.
33 KV 02892 N2017
"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION"
Sheet No. 4
9/658-4/01 Number of sheets 5
Each item in the programme to consist of one operation only. Include the issue and cancellation of relevent documents as separate operations.
Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time
35 Salford Quays S/S 100641 T11 & T12 Tap Change Make non auto and adjust for T11 return by TC 35
Control
38 Salford Quays S/S 100641 T11 & T12 Tap Change Equate taps and restore auto by TC 38
Control
39 Broadway Back Up Supply HV customer Inform BBC of intention to close BBC MA1/MB1 6.6kV circuit 39
S/S 168526 breakers
43 Broadway Back Up Supply HV customer Inform BBC Broadway Back Up Supply available 43
S/S 168526
44 Salford Quays S/S 100641 T11 Transformer Confirm EPM 17, 18, 19, 21 Complete 44
Programme complete
SWITCHING PROGRAMME Zone Serial No.
33 KV 02892 N2017
"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION"
Sheet No. 5
9/658-4/01 Number of sheets 5
Each item in the programme to consist of one operation only. Include the issue and cancellation of relevent documents as separate operations.
Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time