Sunteți pe pagina 1din 6

SWITCHING PROGRAMME Area Transmission

"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION" Zone 33 KV

Description of work for which switching is done:- To maintain the T11 33/6.6kV Transformer at Salford Quays Pry S/S Serial No. 02892 N2017
100641 - Training Programme 5
No. of sheets attached

Programme to commence on (date) Tuesday 20 June 2017 @ 09.00

Planned restoration on (date) Friday 23 June 2017 This switching programme shall be updated immediately after each instruction has been given,
operation carried out, or document issued. The Control Engineer shall record the time at which
Operator(s) names(s) G. Andreakos 50016 A. Bamford operations are instructed and to whom they are issued. When an instruction has been carried
out he shall record the time the last operation was performed. The operator shall record the
time an instruction is received and the time each operation is carried out, together with his
initials. When safety documents are issued details should be entered below. The date should
only be recorded against the first operation after a change of date.

Copies to:- DSMC & Operators

RECORD OF SAFETY DOCUMENTS


Document Issued Cancelled
Op. No Description Serial No. Issued by Received by Op. No. Returned by Cancelled by
24 Permit to Work 25

17/05/2017 15:19

Programme endorsed by (S.A.P.) Date Approved:- (S.A.P.) Date

COMPLETION The programme has now been completed/suspended/cancelled and associated safety documents are attached. (Delete as appropriate) A further
programme has been/will be prepared for future work as follows:

SIGNED (AUTHORISED PERSON) DATE Audited by Date


9/657-6/01
SWITCHING PROGRAMME Zone Serial No.
33 KV 02892 N2017
"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION"
Sheet No. 1
9/658-4/01 Number of sheets 5
Each item in the programme to consist of one operation only. Include the issue and cancellation of relevent documents as separate operations.

Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time

1 Introduction of Operators A. Bamford 33kV SAP G. Andreakos 33kV SAP under PS 1

2 DSMC System Confirm Suitable for Outage 2

3 Frederick Rd Grid S/S B222 Salford Quays T12/ Check Protection 3


100504 Robert Hall St T12 33kV CB

4 Salford Quays S/S 100641 T12 33/6.6kV Transformer Check Protection and Cooling 4

5 Salford Quays S/S 100641 Broadway Backup Supply Switch out by TC 5


Auto Trip Scheme

6 Broadway Back Up Supply HV customer Inform BBC Broadway Backup Supply unavailable (expected 6
S/S 168526 RTS 23/06/17)

7 Broadway Back Up Supply BBC MA1 Board 6.6kV CB Open by TC 7


S/S 168526

8 Broadway Back Up Supply BBC MB1 Board 6.6kV CB Open by TC 8


S/S 168526

9 Salford Quays S/S 100641 T11 & T12 Tap Change Make non auto and adjust for T11 outage by TC 9
Control

10 Salford Quays S/S 100641 T11 6.6kV CB Open by TC 10

11 Frederick Rd Grid S/S B29 Salford Quays T11 Open by TC 11


100504 33kV CB

12 Salford Quays S/S 100641 T12 Tap Change Control Make independant auto by TC 12
SWITCHING PROGRAMME Zone Serial No.
33 KV 02892 N2017
"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION"
Sheet No. 2
9/658-4/01 Number of sheets 5
Each item in the programme to consist of one operation only. Include the issue and cancellation of relevent documents as separate operations.

Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time

13 Salford Quays S/S 100641 T11 6.6kV CB Confirm Open 13

14 Salford Quays S/S 100641 T11 6.6kV CB Isolate SL & CN on BB & FDR Shutters 14

15 Salford Quays S/S 100641 T11 6.6kV VT Isolate SL & CN on Shutters 15

16 Frederick Rd Grid S/S B29 Salford Quays T11 Confirm Open 16


100504 33kV CB

17 Frederick Rd Grid S/S B29 Salford Quays T11 Move to the OFF position SL & CN 17
100504 33kV BB Isolator

18 Frederick Rd Grid S/S B29 Salford Quays T11 Move to the EARTH position SL & CN 18
100504 33kV Earth Selector

19 Frederick Rd Grid S/S B29 Salford Quays T11 Isolate Trip Links Post CN 19
100504 33kV CB

20 Frederick Rd Grid S/S B29 Salford Quays T11 Close to Earth SL & CN 20
100504 33kV CB

21 Salford Quays S/S 100641 T11 6.6kV ES Close to Earth SL & CN 21

22 Salford Quays S/S 100641 T11 Transformer Isolate Tap Change & Cooling Supplies Post CN 22

23 Salford Quays S/S 100641 T11 Transformer Isolate Buchholz and Winding Temp trip and alarm links 23
Post CN
SWITCHING PROGRAMME Zone Serial No.
33 KV 02892 N2017
"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION"
Sheet No. 3
9/658-4/01 Number of sheets 5
Each item in the programme to consist of one operation only. Include the issue and cancellation of relevent documents as separate operations.

Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time

24 Salford Quays S/S 100641 T11 Transformer Issue PTW ____________ to maintain transformer and 24
auxiliary equipment

25 Salford Quays S/S 100641 T11 Transformer Cancel PTW from operation 24 25

26 Salford Quays S/S 100641 T11 Transformer Restore Tap Change and Cooling Supplies 26

27 Salford Quays S/S 100641 T11 Transformer Restore Buchholz and Winding Temp trip and alarm links 27

28 Salford Quays S/S 100641 T11 6.6kV ES Open from Earth 28

29 Frederick Rd Grid S/S B29 Salford Quays T11 Restore tripping 29


100504 33kV CB

30 Frederick Rd Grid S/S B29 Salford Quays T11 Open from Earth 30
100504 33kV CB

31 Frederick Rd Grid S/S B29 Salford Quays T11 Move to the OFF Position 31
100504 33kV Earth Selector

32 Frederick Rd Grid S/S B29 Salford Quays T11 Move to Service Position 32
100504 33kV Busbar Isolator

33 Salford Quays S/S 100641 T11 6.6kV CB Rack into Service Position 33
SWITCHING PROGRAMME Zone Serial No.
33 KV 02892 N2017
"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION"
Sheet No. 4
9/658-4/01 Number of sheets 5
Each item in the programme to consist of one operation only. Include the issue and cancellation of relevent documents as separate operations.

Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time

34 Salford Quays S/S 100641 T11 6.6kV VT Return to Service Position 34

35 Salford Quays S/S 100641 T11 & T12 Tap Change Make non auto and adjust for T11 return by TC 35
Control

36 Frederick Rd Grid S/S B29 Salford Quays T11 Close by TC 36


100504 33kV CB

37 Salford Quays S/S 100641 T11 6.6kV CB Close by TC 37

38 Salford Quays S/S 100641 T11 & T12 Tap Change Equate taps and restore auto by TC 38
Control

39 Broadway Back Up Supply HV customer Inform BBC of intention to close BBC MA1/MB1 6.6kV circuit 39
S/S 168526 breakers

40 Broadway Back Up Supply BBC MA1 Board 6.6kV CB Close by TC 40


S/S 168526

41 Broadway Back Up Supply BBC MB1 Board 6.6kV CB Close by TC 41


S/S 168526

42 Salford Quays S/S 100641 Broadway Backup Supply Switch in by TC 42


Auto Trip Scheme

43 Broadway Back Up Supply HV customer Inform BBC Broadway Back Up Supply available 43
S/S 168526

44 Salford Quays S/S 100641 T11 Transformer Confirm EPM 17, 18, 19, 21 Complete 44

Programme complete
SWITCHING PROGRAMME Zone Serial No.
33 KV 02892 N2017
"RIGHT SUBSTATION, RIGHT SWITCH, RIGHT OPERATION"
Sheet No. 5
9/658-4/01 Number of sheets 5
Each item in the programme to consist of one operation only. Include the issue and cancellation of relevent documents as separate operations.

Op Date/Time Op Performed
Location Circuit/Unit Operation
no. instructed no. By Date/Time