Sunteți pe pagina 1din 5

2016 IEEE PES Asia-Pacific Power and Energy Conference - Xi'an - China

An Improved Pilot Protection for Distribution Network


With Inverter-Interfaced Distributed Generations
1.BowenHan 2.0ang Wang,
School of Electric Power, 3. Haifeng Li, 4.Dehui Zeng
South China University ofTechnology School ofElectric Power,
Guangzhou, China, 510641 South China University ofTechnology
ephanbw@mail.scut.edu.cn Guangzhou, China, 510641

Abstract-Inverter-Interfaced Distributed Generation (IIDG) longer applicable for complex distribution system as a main
connected to distribution network with a teed liDe may eause protection [3], [4].
protective relay tripping failure even using eonventional eurrent
differential protection, whieh is regarded as one of the most Therefore, lots of research on the protection principle of
effective protection for distribution network with distributed distribution neiwork with DO has been carried out so far [5] ~
generations. Therefore, the impacts of IIDGs on traditional [9]. In general, the proposed protection principle can be
current differential pilot protection is analyzed firstly in this divided into two categories: one is the improvement base on
paper. Next, the fauIt characteristics ofIIDG are introduced and the existing three-step overcurrent protection; while one is to
the fauIt model of IIDG is established, in which IIDG is viewed implant some new protection principle applied in transmission
as a current source controlled by the positive-sequence voltage neiwork. The improved three-step protection is mainly aimed
at the point of common coupling. Then, based on the three-phase at the DG which is connected to the grid connected via bus. If
voItage and current on both sides of line, an improved pilot the DG is connected to the grid with teed lines, the proposed
protection is proposed, whieh consists of a negative-sequenee protection would not meet the requirements of selectivity and
current differential protection as an auxiliary eriterion for the reliability.
conventional pilot protection. Finally, the effectiveness of the
improved protection scheme is verified by a IOkV distribution Among those new protection principles, pilot protection is
network with multi-IIDGs established in PSCAD/EMPDC. The generally regarded as one of the most effective protection
simulation results indicate that the proposed protection can scheme for distribution network with distributed generations.
effeetively reduee or eliminate IIDG's impacts on eurrent However, due to the great increase in line density and the
differential proteetion, particularly for an asymmetrie fauIt, shortage in transmission corridor, T-connection mode has
under various conditions involving different IIDG's output and appeared to be a preferred choice for lIDO connecting to
fauIt resistance, thereby improve its reliability significantly. distribution network in practical engineering. Nevertheless,
neither the voltage at the point of common coupling (PCC) nor
Index Terms--inverter-interfaced distributed generations; teed the output currents of lIDOs in this grid-connection mode is
lines; negative-sequenee eurrent; pilot protection
unknown to the protective relays installed at both sides of line,
which would make a further adverse impact on the protective
I. INTRODUCTION relays in distribution network. What's worse, multi-lIDOs
The renewed interest in distributed generation, particularly connected to distribution network with teed lines may cause
Inverter-Interfaced Distributed Generation (IIDG) including protective relay tripping failure in severe cases even using
photovoltaic and wind power, has resulted in a high current differential protection.
penetration in distribution system [I], [2]. However, those For this reason, some wide area protections based on IED
grid-connected IIDGs have make distribution network become or Multi-Agent have been proposed in some papers [10], [11].
a multi-sources power network, in which the distribution Wide area information collected by intelligent electronic
characteristics of fault current will change significantly. In devices can provide comprehensive and synchronous data,
addition, the output power of lIDO, particularly for those which helps the protection adapted to various fault conditions.
mainly based on clean renewable energy, is volatile and But this protection scheme may ask for a stricter requirement
intermittent. on the automation level in distribution network, which is
These characteristics would lead to a significant reduction difficult to achieve in the current distribution neiwork in China.
in the selectivity and sensitivity ofthe land 11 segment ofthe Hence, to reduce the rebuilding cost of protection system
conventional over-current protection relying on current setting for the distribution network with DOs, an improved pilot
criteria, so the conventional three-step current protection is no protection scheme based on the existing protection device and

This work is supported in part by the National Natural Science Foundation


ofChina (No.51477057)

978-1-5090-5417-6/16/ $ 31.00 2016 IEEE

2555
longitudinal communication system is proposed for the protection will decreased, which may cause relay tripping
distribution network T-connected with IIDGs in this paper. failure particularly in the situation when an internal single-
The proposed scheme only needs to add a negative-sequence phase grounding fault with high resistance occurs. Obviously,
current differential protection as an auxiliary criterion to the conventional current differential protection is also not
achieve full line high speed protection, thereby improve the applicable for the complex distribution network with IIDGs T-
selectivity and reliability of protection. connected to feeder. Therefore, it is necessary to improve the
traditional protection principle.
The rest ofthis paper is organized as folIows: The impacts
of IIDG on distribution network are analyzed in Section 11. 111. FAULT CHARACTERISTICS OF IIDG
The fault characteristics of IIDG are introduced Section III,
followed by the establishment of IIDG's fault equivalent At present, most of the grid-connected IIDG is based on
model. Section IV proposes an improved pilot protection the interface of voltage source converter (VSC). Besides, the
scheme. The proposed scheme is verified in PSCADIEMPDC fauIt characteristic of the IIDG based on the interface of VSC
and the simulation results are presented in Section V. Section is mainly determined by its control strategy, so the impacts of
VI concludes the paper. control strategy on fault current must be considered. PQ
control strategy is widely adopted in the IIDGs connected to
11. ANALYSIS ON IIDG's IMPACTS ON CURRENT power grid to capture the maximum energy from wind and
DIFFERENTIAL PROTECTION solar energy, thereby realize the full use of clean energy [13].
PQ control is done by transforming three-phase to two-phase
The schematic diagram of a distribution network with an d-q rotating reference frame aligning the d-axis with the
IIDG T -connected to line MN is depicted in Fig. 1. voItage at PCC. According to the PQ control system, IIDG can
track the reference value of active current and reactive current
respectively in real time, so as to output the reference power:

DG 1 j ~ut = ~ef =
3
'2 U
3
pcc_d1d _re!
(2)
Figure.l Single-line diagram of distribution network with IIDGs QOUI -- Qrej
--U
- 2
1
pcc_d q_reJ

Because there is no CT installed at IIDG's branch in


generally, and unable to achieve communication with the where Pout and Qout are the output active power and reactive
protective relays at both sides of line MN, the output current power of IIDG respectively; Pref and Qref are the reference
of IIDG is unknown for the traditional current differential value of active power and reactive power respectively; IdJej
protection, so it is similar to the unbalanced current in essence and IqJet are the reference value of active current and reactive
from the perspective of current differential protection. Take current respectively; Upcc d is the d-axis component of the
the direction that current flows from the bus to the protected voltage at PCe.
line as the positive direction. Kirchhoffs Current Law shows Besides, many grid codes worldwide, including Denmark
the differential current between the currents at both sides of and Germany, have demanded that reactive current should has
line is IOG+lunb. According to the operation setting principle of a priority to be provided when voltage at PCC is lower than
the conventional current differential protection, the pickup the pre-determined setting value, namely active power is
current Ikset must be higher than IOG+Iunb. However, IIDG's encouraged to generate by the grid-connected IIDG (e.g. WTG,
output current is not only related to the natural environment PV, etc.) during voltage dip, which would affect the fault
conditions and the inverter capacity, but also directly affected current ofIIDG significantly [14]. Therefore, the low voltage
by its control strategy, so lOG is changing in real-time during ride through (L VRT) control strategy have to be considered.
normal operation. In order to avoid the mal operation of the Taking the requirements of reactive current supply in
protective relays, the pickup current must be higher than the Germany as an example, the reference values of active current
maximum value of IOG+Iunb. In practical engineering, IIDG and reactive current during the power grid faults can
maximum output current is usually restricted to 2 times the respectively be expressed as :
rated current of inverter [12], so the minimum pickup current
of differential protection must be set as: u -u

where I n. OGl is the rated current of1IDG 1


(1)
l
/

I
qJerr
.... = /

-
q(O)
+
... K..

3.3 U?'cIJ
U
pcc(O)
pec(O)
peel
(3)
d_cer! -
pcc.{
As for the protection that is set in accordance with (1), it
can avoid the malfunction of the pilot protective relays in where I q reff and Id reff are respectively the reference values of
normal operation or in the situation when an extern al fault reactive current and active current; Upcc(O) and U pcc/ are the
occurs. Hence, the pickup current hset can be set as a small voItage amplitudes at PCC before and after a fault occurring;
value if the capacity of IIDG is small enough, and the pilot Preffis the reference active power oflIDG in a fault; Iq(o) is the

protection still have a high sensitivity for the internal fault. reference reactive current before a fault occurring, and is set as
However, the setting value will become higher with the zero in general; K is the voltage support coefficient, which is
increase of the penetration of IIDG, and the sensitivity of the set as 2 when the voltage amplitude is lower than 0.9 p.u.,
otherwise is often set as O.

2556
Equation (3) states that a serious voltage drop may lead to Fig.2 indicates when an asymmetric fault takes place at the
a large increase of 1100's fault current, which would damage distribution network with lIDO, its negative-sequence network
the inverter in some severe cases. Therefore, the capacity is similar to the positive-sequence network of the traditional
constraint of inverter has to be considered in the actual grid without lIDOs, and namely the negative-sequence current
engineering, which usually requires 1100's maximum short differential protection will not be affected by the lIDO.
circuit current should not be more than two times the rated Therefore, negative-sequence component of fault current can
current [12]. So the output current oflIDO can is presented as: be used as a differential quantity for the distribution network
connecting lIDO with teed line. For unsymmetrical faults, the
jTq = Jq nf f (Tq <; J,mu)
protection criterion of negative-sequence current differential
(4)
lJd=min{Jd nff,~Jm",'-Jq nfI } protection can be expressed as folIows:

where I" and Id are the output values of the reactive current (5)
and active current of lIDO, respectively; I max is the acceptable
where lunb_negalil'e is the maximum negative-sequence current
maximum output current of inverter.
during normal operation or an extern al fault occurring.
In addition, to improve the output performance of inverter,
Since lIDOs does not provide negative-sequence currents,
a control strategy based on positive-sequence voltage at PCC
usually can be set as a smaller value far less than
lunh_negalil'e
is widely adopted in engineering so that the negative-sequence
hset shown in (1). So negative-sequence current differential
currents can be eliminated [15]. Accordingly, only a sym-
protection can detect an internal asymmetric fault with a high
metrical current is output by 1100 in theory even an
sensitivity. At the same time, the pickup current of negative-
asymmetric fault occurs, which is significantly different from
sequence current differential criterion is lower than the
conventional generator [16]. Therefore, all the voltages in the
maximum unbalance negative-sequence current, which can
equations mentioned above are their positive-sequence
avoid protection mal operation during normal operation or
components.
external faults occurring.
Equation (2)~(4) show 1100 can be viewed as a current
However, when a symmetrical fault occurs, the negative-
source controlled by the positive-sequence voltage at PCC,
sequence component of fault current is so small that the
namely jDG = f(U;cJ [16], [17]. When lIDOs are connected to protection criterion in accordance with (5) cannot operate,
distribution network with teed lines, different fault position or which will cause relay tripping failure if only a negative-
different types of faults would result in various positive- sequence current differential protection criterion is adopted.
sequence voltage at PCC, and the magnitude and phase ofthe Hence, another proteetion criterion is required in this case.
fault current of lIDO would change constantly. Obviously,
these fault characteristics of lIDO will reduce the selectivity The equivalent circuit of distribution network during a
and sensitivity of pilot protection, thereby causing some three-phase grounding fault occurs atf can depicted in Fig.3.
unneglectable impacts on the current differential protection.

IV. IMPROVED PILOT PROTECTION SCHEME N


In order to facilitate the analysis, the line MN in the Es jlX~l ZT! Z"~d
distribution network system shown in Fig.l is taken as an
i/x"
example, and both two sides of !ine MN are equivalent to two
system based on the Thevenin's theorem. As shown in Fig.l, Figure.3 Equivalent circuit for distribution network during a fault occurs att
Es is the system voltage; z~ and Z'oad are the system impe-
dance and load impedance respectively; ZM1; Z11, and ZjN are As shown in Fig.3, the fault current seen by the relay
the line impedance. installed at bus M and bus N can be obtained:

When an asymmetric fault occurs at f, the negative-


sequence network can be depicted in Fig.2, where jM and _0

jN _" respectively are the negative-sequence currents seen by


(6)
the relays installed at both sides of line MN, and U; is the
negative-sequence voltage atf As the aforementioned analysis
in section III, 1100 can be viewed as a current source So the differential current between bus M and bus N is
controlled by the positive-sequence voltage at Pcc. So the . . . E- Zlf iDGI i
Zioad DG2 (7)
negative-sequence network does not contain lIDO. M = I'f + I v = + ---'!:!!!!...~'--
Zy + ZM) + Zlf ZjV + Z/oad
Equation (7) shows if there is no 00 connected at the
downstream of the line MN, the differential current M will be
[fr equal to jM , obviously which would reduce relay's sensitivity
compared to the situation when one or more lIDOs are
Figure.2 Negative-sequence network of distribution network with
embedded at the downstream of the line MN. Thus, it is
unbalanced fault occurring necessary to discuss this worst case firstly.

2557
The grid code in China requires the penetration of DG The transmission grid is represented by GRID, and its
should not exceed 25% ofthe total load capacity [9], and the short powers is set as 500 MV A. And there are four IIDGs
maximum output current ofllDG can be described as: embedded within the distribution network. The rated capacity
. 1 E of DG] ~DG4 are set as 2MW, 1.5MW, 3MW, and 3MW. Ji
/ - (8) and .12 are the faulty points at line MN and line ND
DG_m,,, - 4 Z, + Z,IV + Z/oad
respectively. The line data and load data ofthe test system are
From (1) we know if the current differential protection given in table I.
can detect the symmetrical fault, it must meet the requirement
as follow: TABLEL LINEAND LOAD DATA
E-Zlf.. j DG > 2jnc Parameter Value
max (9)
Z, + Z,rr + Zr; , Impedance 01 18+jO 356 Q/km
Combining with (7)~(9), we can obtain Length of Line Section AB 1.5 km
Length of Line Section BC 1.5 km
2Z, + ZMl + 3ZjN + Z '"N + 4Z/oad > 0 (10) Length of Line Section AM 1.5 km
Length of Line Section MN 2.5 km
Clearly, it is easy to meet the requirement shown in (10)
Length ofLine Seetion ND 1.0 km
when a symmetrical fault occurs in line MN. From another Total Load Capacity 20MVA
perspective, due to the constraint of DG's penetration and Power Factor 0.9
inverter capacity , the fault current provided by system is far
greater than DG's fault current when a three-phase grounding The improved protection scheme is verified based on the
fault occurs. So the current flowing through the bus M is protective relays installed at both sides of the line MN. The
much greater than the current of bus N, and the differential operating current of the negative-sequence current differential
current can be greater than the pickup current even if the protection is set as 0.05kA, while the operating current of
operating criteria is set in accordance with (1). Consequently, conventional current differential protection is set as 0.693 kA
as for an internal symmetrical fault, which is viewed as the by the operating criteria shown in (1) according to the rated
most serious fault type, the conventional current differential capacity ofDG4. Three possible cases are considered:
protection can detect it effectively in vast majority of cases. Case 1 is a single-phase (phase-A) grounding fault occurs
atJi with different resistance and power output of DG4.
Therefore, the diagram of the tripping logic for the
improved proteetion can be shown in FigA. Case 2 is a two-phase (phase-B&C) grounding fauIt occurs
atJi andJ2 respectively with different resistance.
Case 3 is a three-phase grounding fauIt is simulated at./i
andJ2 respectively with different power output ofDG 4 .
The EMTDC/PSCAD is employed for power system fauIt
2:1 simulation, and the proposed protection is implemented in
Trip
MATLAB. The simulation results of the protective relays
operation are listed in Table 11, Table III, and Table IV,
respectively. "T" and "NT" in the tables below represent
tripping and Non-tripping, respectively.

FigureA Schematic diagram ofthe improved protection tripping logic TABLE H. PROTECTNE RELA YS OPERATION F OR SINGLE-PHASE
GROUNDING FAULT

V. SIMULATION VERIFICATION
Fault conditions Current differential value (A) Relayoperation
To verifY the proposed estimation method, a test case of a Output Fault M. . M M. Improved Traditional
lOkV distribution network connected with two IIDGs shown of DG4 resistance ..\JAJJegatJve A ( relay relay
in Fig.5 is established in PSCADI EMTDC for simulation. 00 1.674 4.909 0.119 0.118 T T
IMW
100 0.184 0.505 0.058 0.049 T NT
70 0.266 0.628 0.173 0.166 T NT
3MW
100 0.187 OAOI 0.171 0161 T NT

TABLEIIL PROTECTNE RELAYS OPERATION FOR TwO-PHASE


GROUNDING FAULT

Fault conditions Current differential value (A) Relay operation


Fault Fault M M M. Improved Traditional
position resistance .MN negative .1 C relay relay
Internal 70 1.726 0.171 0.626 0.634 T NT
fault ji 100 0.187 0.168 OA04 0.394 T NT
Figure.5 Diagram ofa 10kV distribution network with IIDGs
External 10 0.0001 0.289 0.286 0.288 NT NT
fault j2 100 0.0065 0.167 0.168 0.170 NT NT

2558
TABLE IV. PROTECTIVE RELAYS OPERATION FOR THREE-PHASE to be implemented because it does not need the electrical
GROUNDING FAULT
parameters at PCC but only use the three-phase currents and
Fault conditions Current differential value (A) Relay operation voltages at both sides line. The proposed method is simple and
Fault Output of Me Improved Traditional effective, and has a good practicability in engineering.
position DG4 lHA'_lIegative /'Y.,.[4. relay relay
Internal IMW 0.0008 4.949 4.949 4.950 T T REFERENCES
fault ji 3MW 0.0001 4.950 4.950 4.950 T T
[I] C. S Wang, and PLi, "Development and Challenges of Distributed
External IMW 0.0015 0.226 0.224 0.225 NT NT Generation, the Micro-grid and Smart Distribution System,"
fault fi 3MW 0.0011 0.330 0.328 0.329 NT NT Automation 01 Electric Power Systems, 2010,34 (2): 10-14.
[2] L 1. Dulau, M. Abrudean, and D. Bica, "Etlects of distributed
generation on electric power systems," Procedia Technology, 2014, 12:
The simulation results shown in Table 11 and Table III 681-686.
indicate that with the occurrence of an asymmetrie fault, the [3] l H. WANG, N. L. TAl, K. SONG, L. F. GU, and l Q SHENG,
improved protection can operate correctly and cut off the "Penetration Level Permission of tr DG in Distributed Network
faulty lines reliably with a high sensitivity under different fault Considering Relay Protection," Proceedings olthe CSEE, 2010, 30(22):
conditions including fault resistance, fault types, and DG's 37-43.
[4] S. L. ZHAO, Z. l WU, M. Q. HU, and Y FAN, "Thought about
output power. However, the conventional current differential Protection of Distributed Generation and Microgrid," Automation 01
relay may run into a problem particularly in some fault cases Electric Power Systems, 2010, 34 (I): 73-77.
with high grounding resistance or large power output ofOG. [5] X. L. CHEN, Y. L. LI, H. Z. TAN, M. Y. ZHAO, A. WEN, et al, "An
Adaptive Instantaneous Trip Protection Based on Positive-sequence
The simulation results shown in Table IV indicates the Current tr Distribution Network with IBDG," Automation 01 Electric
negative-sequence current differential protection cannot detect Power Systems, 2015, 39(9): I 07-112.
a symmetrie fault, but the traditional relay is sensitive enough [6] P Mahat, Z Chen, B. Bak-Jensen, and C. L Bak, "A simple adaptive
to operate because of the high differential current in three- overcurrent protection of distribution systems with distributed
generation," IEEE Transactions on Smart Grid, 2011, 2(3): 428-437.
phase grounding fault current that is mainly provided by the [7] F. Coffele, C. Booth, and A. Dysko, "An Adaptive Overcurrent
Grid. In addition, the improved protection is also able to Protection Scheme tr Distribution Networks," IEEE Transactions on
ensure no maloperation ofrelays when an external fault occurs. Power Delivery, 2015,30(2): 561-568.
[8] D. Sampath Kumar, D. Srinivasan, and T. Reindl, "A Fast and Scalable
VI. CONCLUSION Protection Scheme for Distribution Networks with Distributed
Generation," IEEE Transactions on Power Delivery, 2015: 1-1.
The three-step current protection based on the traditional [9] S X. XU and Y P. LU, "A Pilot Protection Method tr Distribution
fault characteristics is no longer applicable for the distribution Network with Distributed Generators," Automation 01 Electric Power
network connected with DGs. In addition, the sensitivity and Systems, 2015, 39 (9)113-118.
reliability of conventional current differential protection are [10] W. D. XIAO, M. C. XIA, and N. TANG, "A new regional protection
scheme tr distribution network considering the introduction of multi-
still significantly affected by IIOG's output power and fault
DGs," Power System Protection and Control, 2014, 42(9): 103-109.
resistance. Therefore, the fault characteristics of IIDG [li] B. LI, H. Y ZHANG,l P. WANG, and Z. Q BO, "Integrated protect
considering its control strategy was analyzed and the fault tion of distribution system with multi distributed generators integrated,"
equivalent model eliminating negative-sequence current Automation 01 Electric Power Systems, 2015(15): 90-95.
component was established. On this basis, this paper proposed [12] H. Nikkhajoei and R. H. Lasseter, "Microgrid protection," Power
Engineering Society General Meeting, Tampa, USA: IEEE, 2007: 1-6.
an improved pilot protection scheme for the distribution
[13] C. S. Wang, Y Li, and K. Peng, "Overview of Typical Control
networks connected with IIDGs by teed lines. The proposed Methods for Grid-Connected Inverters of Distributed Generation,"
protection scheme only needs to add a negative-sequence Proceedings olthe CSU-EPSA, 2012, 24(2): 12-20.
current differential protection as an auxiliary criterion for the [14] X. G. Liu, Z. Xu, and K. P. Wong, "Recent advancement on technical
conventional current differential protection. When an asym- requirements tr grid integration of wind power," Journal 01 Modern
metrie fault takes place in the internal protected zone, the Power Systems & Clean Energy, 2013,1(3):216-222.
[15] A. V. Timbus, P. Rodriguez, R. Teodorescu, M. Liserre, F. BI aabjerget,
improved protection can operate depending on the auxiliary "Control strategies tr distributed power generation systems operating
criterion that uses negative-sequence current as a differential on faulty grid," IEEE International Symposium on Industrial
quantity. For the internal symmetrie fault, the conventional Electronics. Montreal, Canada: IEEE, 2006, 2: 1601-1607.
current differential relays can also operate reliably. [16] X. P. Kong, Z. Zhang, X. G. Yin, F. Wang, and M. H He, "Study on
Fault Current Characteristics and Fault Analysis Method of Power Grid
Simulation results indicate the proposed proteetion scheme With Inverter Interfaced Distributed Generation," Proceedings 01 the
can achieve the fuH line high speed protection under various CSEE, 2013, 33(34) 65-74.
types of short-circuit faults, and ensure relays no maloperation [17] G. Q. Pan, D. H Zeng, G. Wang, G. L Zhu, and H F. Li, "Fault
Analysis on Distribution Network With Inverter Interfaced Distributed
with the occurrence of extern fault, which helps to improve Generations Based on PQ Control Strategy," Proceedings olthe CSEE,
the selectivity and sensitivity of the conventional proteetion 2014, 34(4) 555-561.
significantly. Moreover, the improved pilot protection is easy

2559

S-ar putea să vă placă și