Sunteți pe pagina 1din 5

30th Power System Conference (PSC2015), 23-25 November 2015, Niroo Research Institute, Tehran, Iran

Application of a Parallel-Resonance-Type FCL for


Maintaining the Recloser-Fuse Coordination in a
Power Distribution System with a Dispersed
Generation
M. J. Damghani, D. Faramarzi, H. A. Abyaneh, B. Vahidi
Department of Electrical Engineering
Amirkabir University of Technology
Tehran, Iran
m.jorjani@aut.ac.ir

Abstract Dispersed generation (DG) sources are rapidly protective devices after the introduction of DGs into the grid.
opening their way to the power systems. Despite the many However, this solution may not solve the aforementioned
advantages that their introduction into the grid has, it may cause circuit breakers problem. Another way is interrupting the DGs
some problems. One of the problems is increasing the short- when a short circuit fault occurs [2]. One of the best proposed
circuit current and the loss of protective devices coordination. To solutions is using of a fault current limiter to limit DGs
deal with this problem, many different approaches have been contribution to the fault current during a short circuit fault [3].
proposed. One of the best promising approaches of resolving the
problem is using a fault current limiter (FCL) to limit DGs Fault current limiters have many different topologies
current during a short circuit fault. including superconducting FCLs, resonance-type FCLs and
solid-state FCLs. Superconducting FCLs limit the fault current
In this paper, a parallel-resonance-type fault current limiter by using a superconducting coil. In the normal system
is used in the interconnection point of the DG to the grid to keep operating condition, this coil has little resistance. When a short
its current at its pre-fault value during a short circuit fault. A circuit fault occurs, the resistance of this coil will increase
comparative study is carried out through the short-circuit tests to drastically. Thus the current will be limited [4]. Resonance-
demonstrate the superiority of using this kind of FCL over the type FCLs limit the current by the resonance between their
conventional resonance-type one. The novelty of this paper is that
capacitor and inductor during the fault. Solid-state FCLs use
by using the mentioned FCL, operating times of the recloser and
power electronic devices to limit the fault current by changing
fuse will be maintained at their values before the introduction of
DG. So, the recloser-fuse coordination can be restored with
the flowing path of the current during the fault [5].
higher coincidence with the pre-introduction of DG condition. In this paper, application of a parallel-resonance-type fault
Furthermore, using this kind of FCL has less effect on the normal current limiter in maintaining the recloser-fuse coordination is
system condition. analyzed [6]. Since the mentioned fault current limiter is
already presented in literature, the explanations relating its
Keywords Dispersed generation (DG); short-circuit current; topology and principle of working will be described short.
parallel-resonance-type fault current limiter; resonance-type fault
Performance of this FCL in maintaining the coordination after
current limiter; protection coordination
the introduction of DG into the system is studied on a typical
I. INTRODUCTION network. Then it is compared to a resonance-type fault current
limiter. Simulations are done using PSCAD/EMTDC and
Today, with the growing demand for electrical power and MATLAB software.
the need for clean sources of energy, the use of dispersed
generation (DG) into the grid is becoming widespread. II. THEORETICAL ANALYSIS
Although the introduction of these sources into the grid has
many advantages, it might also cause some difficulties [1]. In A. Resonance-type Fault Current Limiter
particular, with the use of high capacity DGs, fault current Fig. 1 shows a simple resonance-type fault current limiter.
levels of the system will be increased. It would arise the need The resistance R is used to model inductor losses. Values of
for replacing the existing circuit breakers with higher capacity capacitor and inductor are selected so as to resonance at the
ones. Moreover, increasing of short circuit currents may result grid frequency, that is:
in the loss of protective devices coordination.
1
Many works have been done to overcome these problems. = (1)
LC
One solution is changing the setting parameters of the

978-1-5090-2705-7/15/$31.00 2015 IEEE 190


Application of a Parallel-Resonance-Type FCL for Maintaining the Recloser-Fuse Coordination in a Power Distribution System with a
Dispersed Generation
30th Power System Conference - 2015 Tehran, Iran

C. Recloser and Fuse and their Coordination Problem


Recloser and fuse are two of the main protective devices
which are used in the distribution networks. Reclosers are
used to prevent long interruptions of the system for an
instantaneous fault. A recloser has two kind of interrupting
curves: fast curve and slow curve. Whenever a fault is
detected on the system, the recloser operates with its fast curve
and clears the fault. After a predefined period of time, the
Fig. 1. Resonance-type fault current limiter.
recloser connects the feeder again. If the fault is present on the
system, the recloser will do the same actions to clear the fault.
In the normal operating condition, the current flows The number of recloser fast operations is adjustable. After
through the inductor L. When a short circuit fault occurs, the several fast operations of the recloser, if the fault is persistent
control circuit will send firing signal to the gate of the on the system, the fuse should operate and clear the fault. If
thyristors T1 and T2. Therefore, the capacitor will be the fuse fails to operate correctly, the recloser will operate
connected in parallel with the inductor. Because of the with its slow curve to clear the fault. In fact, the slow curve of
resonance between the inductor and the capacitor, the the recloser is considered as a backup for the fuse [8].
impedance will become nearly infinite. So the current, which In this study, the recloser is set to have one reclosing event
is now flowing through this impedance, will become zero with the reclosing interval time of 0.25 s. The pickup current
during the short circuit fault. of all the protective devices is 10 A. As there is no model for
B. Parallel-resonance-type Fault Current Limiter recloser and fuse in PSCAD/EMTDC software, these devices
are modeled so as to fulfill their tasks properly. The fuse is
Fig. 2 shows the proposed parallel-resonance-type fault modeled using comparator and integrator blocks and the
current limiter. It consists of two main parts: a bridge part recloser is consisted of overcurrent and some other logical
which is composed of four diodes, a dc limiting reactor, and a blocks, too [2].
semiconductor switch, and a resonance part. The aim of this
FCL is to limit the current during a short circuit fault to its III. SIMULATION RESULTS AND DISCUSSIONS
pre-fault value. The operating principles of this FCL are
The recloser-fuse coordination problem is tested using the
briefly explained below [6].
power distribution system shown in fig. 3. Load 3 is linked to
During normal condition, the semiconductor switch is ON. a DG source through a fault current limiter. The effect of the
So the current flows through D1, LDC , Switch and D4 in the DG on recloser-fuse coordination is investigated for two
positive half cycle and D2, LDC , Switch and D3 in the different kinds of fault current limiters, i.e. resonance-type and
negative half cycle. Thus  will be charged to the peak of parallel-resonance-type FCLs. Necessary data of the system
the line current and will act as a short circuit. Therefore there are represented in table I [7].
is no impedance in the currents path in this condition.
When a short circuit fault is detected, the semiconductor
switch will become OFF. As a result, the current will flow
through the resonance part of the FCL. The equivalent
impedance of the resonance part is as follows:

j L
 = Rsh - C || jLsh = shR C + jLsh (2)
sh sh sh

Considering (2), values of capacitor and resistor can be


Fig. 3. Configuration of power distribution system.
selected so as to the fault currents magnitude becomes equal
to the pre-fault currents one. This procedure is described in TABLE I. SIMULATION SYSTEM PARAMETERS
section III.
T1 5 kVA, 200 V/ 60 V
Transformer
T2 1 kVA, 200 V/60 V

R1 +X1 , R2 +X2 0.097 + j0.686


Distribution line
R3 +X3 0.14 + j1.033

Load 1 8 + j1.885

Load Load 2 10 + j1.885

Load 3 5 + j1.885

Fig. 2. Parallel-resonance-type fault current limiter.

191
Application of a Parallel-Resonance-Type FCL for Maintaining the Recloser-Fuse Coordination in a Power Distribution System with a
Dispersed Generation
30th Power System Conference - 2015 Tehran, Iran

Fig. 4. Feeder 1 current (I1 ) in the absence of DG source. Fig. 6. DG current.

Fig. 5. Feeder 1 current (I1 ) in the presence of DG source.


Fig. 7. Fault current magnitude versus R.

Before addressing the recloser to fuse coordination resistor values for different standard values of capacitor,
problem in presence of the DG source, the system condition which are adopted from [9], using MATLAB software.
without it is investigated. Considering a 3-phase short circuit Intersecting this plot with DG pre-fault currents value, values
fault from 0.4 s to 0.6 s at point P1 in Fig. 1, I1 is shown in of resistor and capacitor, and consequently inductor, can be
Fig. 4. It is seen that the recloser operates before F3 with its obtained [6]. In this case study, DG pre-fault currents value is
fast curve to clear the fault. After the predefined period of 0.2 6 A. Fig. 7 shows versus resistor values for different
s, recloser reconnects the feeder again and since the fault is values of capacitor. As it can be seen, there are three
disappeared from the system, no further action will take place. intersections. However the intersection point with C = 1.5 mF
Now, the DG source will be connected to load 3. In this diagram has less value for resistor and thus poses less losses
condition, the DG will contribute to the fault current seen by during the fault to the system. So the values R = 0.6 , C =
F3. Therefore, as it can be seen from Fig. 5, F3 operates 1.5 mF and L = 470 H are chosen for the simulation. The dc
before the recloser. Thus load 3 is interrupted permanently for inductor of the FCL is taken to be 100 H.
this transient fault, which will cause several problems
Fig. 8 shows I1 for this system configuration. According to
including the decrease in reliability. Fig. 6 shows DGs current
this figure, the recloser operated before F3 with its fast curve.
for this condition.
Thus the coordination between recloser and fuse is restored.
To overcome this problem, a parallel-resonance-type fault DGs current is shown in fig. 9. It can be seen that it remained
current limiter, which maintains the current contribution level constant during the fault.
of the DG during the fault to its pre-fault value, is used to
Simulations are redone with a conventional resonance-type
connect the DG to the grid. For designing the suitable R, L, C
fault current limiter to compare its performance with the
parameters of this FCL, the following procedure is used:
newer one. Since the dc inductor of the parallel-resonance
During fault condition, DGs current can be written as: type FCL is 100 H, the inductor value of the resonance-type
FCL is set at the same value to impose the same conditions on
=
V
(3) the system during normal operating mode. With this
assumption, considering (1), the value of capacitor should be
70 mF. Besides the economic issues concerning this design,
Considering (3), the parameters of the FCL can be derived by this FCL cannot restore the recloser to fuse coordination
equating DGs current during the fault with its pre-fault value. because of its slow speed to limit the DGs contribution to the
Since  has two unknown parameters (capacitor and fault current. Fig. 10 shows I1 and fig. 11 shows DGs current
inductor values are related based on (1)), (3) is plotted versus for this condition.

192
Application of a Parallel-Resonance-Type FCL for Maintaining the Recloser-Fuse Coordination in a Power Distribution System with a
Dispersed Generation
30th Power System Conference - 2015 Tehran, Iran

Fig. 8. Feeder 1 current (I1 ) using the parallel-resonance-type FCL. Fig. 11. DG current using the resonance-type FCL with L = 100 H.

Fig. 9. DG current using the parallel-resonance-type FCL. Fig. 12. Feeder 1 current (I1 ) using the resonance-type FCL with L = 10 mH.

Fig. 10. Feeder 1 current (I1 ) using the resonance-type FCL with L = 100 H. Fig. 13. DG current using the resonance-type FCL with L = 10 mH.

For a good limiting function of this FCL, value of the Another weakness of this configuration can be understood
inductor is increased to 10 mH which would result in C = 0.7 by comparing fig. 8 and fig. 12 with fig. 4. As it can be seen
mF. Fig. 12 shows I1 and fig. 13 shows DGs current for these from fig. 4, when the DG is not present in the network, the
new values of L and C. It can be seen that the maximum DGs recloser performs its fast trip at t = 0.472 s. When the DG is
contribution to fault current is limited to 30 A and is decreased introduced to the network and the parallel-resonance-type FCL
to zero rapidly. Thus the FCL can properly limit the fault is used to limit its current during the fault, the recloser
current and restore the coordination between recloser and fuse performs its fast trip at t = 0.472 s again. But when using the
with these values for L and C. However, it still has some resonance-type FCL, the fast operation will take place at t =
major drawbacks. Because the 10 mF inductor is in the circuit 0.575 s, which means that the fault will remain on the system
during normal condition, DGs current will be reduced in this for a longer period. It is evident that the performance of
state, too. Note that in the parallel-resonance-type FCL the parallel-resonance-type FCL is better from this point of view,
100 H dc inductor is in the circuit during normal condition. too. Table II summarizes the comparisons made between the
Thus it will not reduce DGs current in this state. system without DG, with DG and without FCL, the system
with DG and parallel-resonance-type FCL and the system with
DG and resonance-type FCL.

193
Application of a Parallel-Resonance-Type FCL for Maintaining the Recloser-Fuse Coordination in a Power Distribution System with a
Dispersed Generation
30th Power System Conference - 2015 Tehran, Iran

TABLE II. COMPARISON BETWEEN DIFFERENT CONFIGURATIONS REFERENCES


Parameter under study [1] G. N. Hadjsaid, J. F. Canard, and F. Dumas, Dispersed generation
System
DG current in I1 in normal Recloser impact on distribution networks, IEEE Computer Applications in
configuration Power, vol. 12, pp. 2228, April 1999.
normal condition condition operating time
Without DG - 8.32 A 0.472 s [2] J. K. Tailor and A. H. Osman, Restoration of fuse-recloser coordination
in distribution system with high DG penetration, in Proc. IEEE Power
With DG and Energy Soc. Gen. Meeting, 2008, pp. 18.
5.93 A 3.43 A -
without FCL
[3] W. EL-Khattam and T. S. Sidhu, Restoration of directional overcurrent
With DG and
relay coordination in distributed generation systems utilizing fault
parallel- current limiter, IEEE Trans. Power Del., vol. 23, no.2, pp. 576-585,
5.84 A 3.48 A 0.472 s
resonance- Apr. 2008.
type FCL
With DG and [4] L. Ye, L. Lin, and K. P. Juengst, Application studies of
resonance- 2.23 A 7.19 A 0.575 s superconducting fault current limiters in electric power system, IEEE
type FCL Trans. Appl. Supercond., vol. 18, no. 2, pp. 624627, Jun. 2008.
[5] C. Meyer and R. W. De Doncker, LCC analysis of different resonant
IV. CONCLUSION circuits and solid-state circuit breakers for medium-voltage grids, IEEE
Trans. Power Del., vol. 21, no. 3, pp. 14141420, Jul. 2006.
In this paper, application of a recently proposed parallel- [6] S. B. Naderi, M. Jafari, and M. Tarafdar Hagh, Parallel-resonance-type
resonance-type fault current limiter for restoring the recloser fault current limiter, IEEE Trans. Ind. Electron., vol. 60, no. 7, pp.
to fuse coordination after the introduction of the DG sources 2538 2546, Jul. 2013.
into the grid is analyzed through the short circuit tests and its [7] Sung-Hun Lim, Jin-Seok Kim, Myong-Hyon Kim, and Jae-Chul Kim,
performance is compared to a conventional resonance-type Improvement of Protection Coordination of Protective Devices
Through Application of a SFCL in a Power Distribution System With a
FCL. Maintaining DGs current level to its pre-fault one Dispersed Generation, IEEE Trans. Appl. Superconduct., vol. 22, no. 3,
during a short circuit condition, the parallel-resonance-type pp. 5601004, June 2012.
FCL can restore the recloser to fuse coordination, which was [8] M. H. Kim, S. H. Lim, J. F. Moon, and J. C. Ki, Method of recloser-
lost because of the introduction of DGs. While the resonance- fuse coordination in a power distribution system with superconducting
type FCL can be designed so as to restore the coordination, fault current limite, IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp.
but it will reduce DGs current during normal condition and 11641167, Jun. 2010.
thus its application might be undesirable. [9] General Atomics, Electronics Systems, High Voltage Capacitors and
Power Supplies. [Online]. Available: http://www.ga-esi.com/EP.

194

S-ar putea să vă placă și