Documente Academic
Documente Profesional
Documente Cultură
Abstract Dispersed generation (DG) sources are rapidly protective devices after the introduction of DGs into the grid.
opening their way to the power systems. Despite the many However, this solution may not solve the aforementioned
advantages that their introduction into the grid has, it may cause circuit breakers problem. Another way is interrupting the DGs
some problems. One of the problems is increasing the short- when a short circuit fault occurs [2]. One of the best proposed
circuit current and the loss of protective devices coordination. To solutions is using of a fault current limiter to limit DGs
deal with this problem, many different approaches have been contribution to the fault current during a short circuit fault [3].
proposed. One of the best promising approaches of resolving the
problem is using a fault current limiter (FCL) to limit DGs Fault current limiters have many different topologies
current during a short circuit fault. including superconducting FCLs, resonance-type FCLs and
solid-state FCLs. Superconducting FCLs limit the fault current
In this paper, a parallel-resonance-type fault current limiter by using a superconducting coil. In the normal system
is used in the interconnection point of the DG to the grid to keep operating condition, this coil has little resistance. When a short
its current at its pre-fault value during a short circuit fault. A circuit fault occurs, the resistance of this coil will increase
comparative study is carried out through the short-circuit tests to drastically. Thus the current will be limited [4]. Resonance-
demonstrate the superiority of using this kind of FCL over the type FCLs limit the current by the resonance between their
conventional resonance-type one. The novelty of this paper is that
capacitor and inductor during the fault. Solid-state FCLs use
by using the mentioned FCL, operating times of the recloser and
power electronic devices to limit the fault current by changing
fuse will be maintained at their values before the introduction of
DG. So, the recloser-fuse coordination can be restored with
the flowing path of the current during the fault [5].
higher coincidence with the pre-introduction of DG condition. In this paper, application of a parallel-resonance-type fault
Furthermore, using this kind of FCL has less effect on the normal current limiter in maintaining the recloser-fuse coordination is
system condition. analyzed [6]. Since the mentioned fault current limiter is
already presented in literature, the explanations relating its
Keywords Dispersed generation (DG); short-circuit current; topology and principle of working will be described short.
parallel-resonance-type fault current limiter; resonance-type fault
Performance of this FCL in maintaining the coordination after
current limiter; protection coordination
the introduction of DG into the system is studied on a typical
I. INTRODUCTION network. Then it is compared to a resonance-type fault current
limiter. Simulations are done using PSCAD/EMTDC and
Today, with the growing demand for electrical power and MATLAB software.
the need for clean sources of energy, the use of dispersed
generation (DG) into the grid is becoming widespread. II. THEORETICAL ANALYSIS
Although the introduction of these sources into the grid has
many advantages, it might also cause some difficulties [1]. In A. Resonance-type Fault Current Limiter
particular, with the use of high capacity DGs, fault current Fig. 1 shows a simple resonance-type fault current limiter.
levels of the system will be increased. It would arise the need The resistance R is used to model inductor losses. Values of
for replacing the existing circuit breakers with higher capacity capacitor and inductor are selected so as to resonance at the
ones. Moreover, increasing of short circuit currents may result grid frequency, that is:
in the loss of protective devices coordination.
1
Many works have been done to overcome these problems. = (1)
LC
One solution is changing the setting parameters of the
j L
= Rsh - C || jLsh = shR C + jLsh (2)
sh sh sh
Load 1 8 + j1.885
Load 3 5 + j1.885
191
Application of a Parallel-Resonance-Type FCL for Maintaining the Recloser-Fuse Coordination in a Power Distribution System with a
Dispersed Generation
30th Power System Conference - 2015 Tehran, Iran
Before addressing the recloser to fuse coordination resistor values for different standard values of capacitor,
problem in presence of the DG source, the system condition which are adopted from [9], using MATLAB software.
without it is investigated. Considering a 3-phase short circuit Intersecting this plot with DG pre-fault currents value, values
fault from 0.4 s to 0.6 s at point P1 in Fig. 1, I1 is shown in of resistor and capacitor, and consequently inductor, can be
Fig. 4. It is seen that the recloser operates before F3 with its obtained [6]. In this case study, DG pre-fault currents value is
fast curve to clear the fault. After the predefined period of 0.2 6 A. Fig. 7 shows versus resistor values for different
s, recloser reconnects the feeder again and since the fault is values of capacitor. As it can be seen, there are three
disappeared from the system, no further action will take place. intersections. However the intersection point with C = 1.5 mF
Now, the DG source will be connected to load 3. In this diagram has less value for resistor and thus poses less losses
condition, the DG will contribute to the fault current seen by during the fault to the system. So the values R = 0.6 , C =
F3. Therefore, as it can be seen from Fig. 5, F3 operates 1.5 mF and L = 470 H are chosen for the simulation. The dc
before the recloser. Thus load 3 is interrupted permanently for inductor of the FCL is taken to be 100 H.
this transient fault, which will cause several problems
Fig. 8 shows I1 for this system configuration. According to
including the decrease in reliability. Fig. 6 shows DGs current
this figure, the recloser operated before F3 with its fast curve.
for this condition.
Thus the coordination between recloser and fuse is restored.
To overcome this problem, a parallel-resonance-type fault DGs current is shown in fig. 9. It can be seen that it remained
current limiter, which maintains the current contribution level constant during the fault.
of the DG during the fault to its pre-fault value, is used to
Simulations are redone with a conventional resonance-type
connect the DG to the grid. For designing the suitable R, L, C
fault current limiter to compare its performance with the
parameters of this FCL, the following procedure is used:
newer one. Since the dc inductor of the parallel-resonance
During fault condition, DGs current can be written as: type FCL is 100 H, the inductor value of the resonance-type
FCL is set at the same value to impose the same conditions on
=
V
(3) the system during normal operating mode. With this
assumption, considering (1), the value of capacitor should be
70 mF. Besides the economic issues concerning this design,
Considering (3), the parameters of the FCL can be derived by this FCL cannot restore the recloser to fuse coordination
equating DGs current during the fault with its pre-fault value. because of its slow speed to limit the DGs contribution to the
Since has two unknown parameters (capacitor and fault current. Fig. 10 shows I1 and fig. 11 shows DGs current
inductor values are related based on (1)), (3) is plotted versus for this condition.
192
Application of a Parallel-Resonance-Type FCL for Maintaining the Recloser-Fuse Coordination in a Power Distribution System with a
Dispersed Generation
30th Power System Conference - 2015 Tehran, Iran
Fig. 8. Feeder 1 current (I1 ) using the parallel-resonance-type FCL. Fig. 11. DG current using the resonance-type FCL with L = 100 H.
Fig. 9. DG current using the parallel-resonance-type FCL. Fig. 12. Feeder 1 current (I1 ) using the resonance-type FCL with L = 10 mH.
Fig. 10. Feeder 1 current (I1 ) using the resonance-type FCL with L = 100 H. Fig. 13. DG current using the resonance-type FCL with L = 10 mH.
For a good limiting function of this FCL, value of the Another weakness of this configuration can be understood
inductor is increased to 10 mH which would result in C = 0.7 by comparing fig. 8 and fig. 12 with fig. 4. As it can be seen
mF. Fig. 12 shows I1 and fig. 13 shows DGs current for these from fig. 4, when the DG is not present in the network, the
new values of L and C. It can be seen that the maximum DGs recloser performs its fast trip at t = 0.472 s. When the DG is
contribution to fault current is limited to 30 A and is decreased introduced to the network and the parallel-resonance-type FCL
to zero rapidly. Thus the FCL can properly limit the fault is used to limit its current during the fault, the recloser
current and restore the coordination between recloser and fuse performs its fast trip at t = 0.472 s again. But when using the
with these values for L and C. However, it still has some resonance-type FCL, the fast operation will take place at t =
major drawbacks. Because the 10 mF inductor is in the circuit 0.575 s, which means that the fault will remain on the system
during normal condition, DGs current will be reduced in this for a longer period. It is evident that the performance of
state, too. Note that in the parallel-resonance-type FCL the parallel-resonance-type FCL is better from this point of view,
100 H dc inductor is in the circuit during normal condition. too. Table II summarizes the comparisons made between the
Thus it will not reduce DGs current in this state. system without DG, with DG and without FCL, the system
with DG and parallel-resonance-type FCL and the system with
DG and resonance-type FCL.
193
Application of a Parallel-Resonance-Type FCL for Maintaining the Recloser-Fuse Coordination in a Power Distribution System with a
Dispersed Generation
30th Power System Conference - 2015 Tehran, Iran
194