Sunteți pe pagina 1din 91

SUBMITTAL

Project

NORDES 2015
Date

jueves, 04 de junio de 2015


Table Of Contents
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

SPLIT 7.5 TON 3


Unit Report 4
Performance Summary 6
Acoustic Summary 10
Certified Drawing 12
Guide Specifications 15
Unit Feature Sheet 19
SPLIT 10 TON 22
Unit Report 23
Performance Summary 25
Acoustic Summary 28
Certified Drawing 30
Guide Specifications 33
Unit Feature Sheet 37
SPLIT 12.5 TON 40
Unit Report 41
Performance Summary 43
Acoustic Summary 46
Certified Drawing 48
Guide Specifications 51
Unit Feature Sheet 55
SPLIT 15 TON 58
Unit Report 59
Performance Summary 61
Acoustic Summary 64
Certified Drawing 66
Guide Specifications 68
Unit Feature Sheet 72
SPLIT 20 TON 75
Unit Report 76
Performance Summary 78
Acoustic Summary 81
Certified Drawing 83
Guide Specifications 85
Unit Feature Sheet 89

Commercial Split Systems Builder 1.33 Page 2 of 91


SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

SPLIT 7.5 TON

SPLIT 7.5 TON

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Feature Sheet

Commercial Split Systems Builder 1.33 Page 3 of 91


Unit Report For SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Unit Report

Outdoor Unit Parameters Indoor Unit Parameters


Unit Quantity: 1 Unit Model: 40RUA
Unit Model: 38AUZ Unit Size: 7.5 Tons
Unit Size: 7.5 Tons No. of Splits: 1
Voltage: 230-3-60 V-Ph-Hz Voltage: 230-3-60 V-Ph-Hz
Condenser Coil: Al/Cu
No. of DX Circuits: 1

System Parameter
System Quantity: 1
Refrigerant Type: PURON
Compressor Quantity: 1
Compressor Type: Scroll
Std. Capacity Steps: 100
Std. Min. Outdoor Temp(Cooling): 35.0 F
No. of Outdoor fans: 2

Outdoor Unit Dimensions and Weight Indoor Unit Dimensions and Weight
Unit Length: 4' 11.4'' Unit Length: 4' 1.0''
Unit Width: 3' 9.9'' Unit Width: 2' 4.2''
Unit Height: 3' 6.4'' Unit Height: 4' 8.1''
Unit Shipping Weight: 391 lb Unit Shipping Weight: 404 lb
Unit Operating Weight: 391 lb Unit Operating Weight: 404 lb

Warranty Information (Note: for US & Canada only)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Qua


ntity
Base Unit - Outdoor

38AUZA08A0A5-0A0A0 1
Base Unit
Al/Cu Condensing Coil 1
Standard Refrigerant Options 1
Service Options - None 1
Electrical Options - None 1
Packaging Options - Standard 1
Standard Electrical Mechanical Controls 1
Single Stage 1
Base Unit - Indoor
40RUAA08A2A6-0A0A0 1
Base Unit
Std Static, Std Eff Motor/ Medium Drive 1

Commercial Split Systems Builder 1.33 Page 4 of 91


Unit Report For SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Cabinet Paint - None 1


None- No Controller 1

Commercial Split Systems Builder 1.33 Page 5 of 91


Performance Summary For SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Performance Summary

System: 38AUZ008/40RUA008
System Quantity: 1
Altitude: 5200.0 ft
EER @ ARI Conditions: 11.2
IEER: 11.8
Linear Pipe Length: 30.0 ft
Suction Line Size: 1 1/8 in
Liquid Line Size: 1/2 in
Suction Line Loss: 1.4 F
System meets the Energy Star EER rating.

Outdoor Unit Parameters


Unit Quantity: 1
PartNumber: 38AUZA08A0A5-0A0A0
Unit Model: 38AUZ
Unit Size: 7.5 Tons
Condenser Coil: Al/Cu
No. of DX Circuits: 1
Voltage: 230-3-60 V-Ph-Hz
Clg Ent Air DB: 95.0 F

Outdoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit#1 MCA: 35.0 Amps
Unit#1 MOCP: 50.0 Amps
Total Compressor Power of Unit #1: NA
Voltage Range Min: 187 V
Voltage Range Max: 253 V
Compressor RLA: 25
Compressor LRA: 164
Compressor Quantity: 1
Fan Motors Qty: 2
Notice: Outdoor unit elect. data is based on 230-3-60
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage

Indoor Unit Parameters


PartNumber: 40RUAA08A2A6-0A0A0
Unit Model: 40RUA
Unit Size: 7.5 Tons
Coil Rows: 4
No. of Splits: 1
Voltage: 230-3-60 V-Ph-Hz
Actual Airflow: 3000.0 CFM
Standard Airflow: 2477.5 CFM
Total Clg Cap.(Gross): 91.3 MBH
Sensible Clg Cap.(Gross): 61.6 MBH
Ent Air DB: 80.0 F
Ent Air WB: 67.0 F
Ent Enthalpy: 34.79 BTU/lb
Lvg Air DB: 57.0 F
Lvg Air WB: 56.9 F
Lvg Enthalpy: 26.60 BTU/lb
Coil Bypass Factor: NA

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Commercial Split Systems Builder 1.33 Page 6 of 91
Performance Summary For SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Fan Speed: 796 RPM


Fan Power: 1.02 BHP
Fan Motor Max: 2.40 BHP
Fan Motor FLA: 6.9 Amps
Motor and Medium Static Drive Required.
Selected Medium Static Drive Range: 733 - 949

Indoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit MCA: 9.0 Amps
Unit MOCP: 15.0 Amps
Notice: Indoor unit elect. data is based on 230-3-60

Acoustics
Sound Power Levels, db re 10E-12 Watts

Outdoor Unit Indoor Unit


(dB) (dB,Ducted)
A-Weighted Total 84.6 88.4
Level
63Hz 89.3 95.3
125Hz 85.0 91.3
250Hz 82.0 87.3
500Hz 82.7 86.3
1000Hz 80.2 82.3
2000Hz 75.2 80.3
4000Hz 71.0 76.3
8000Hz 66.0 NA
Sound Message Sound for Sound for
AUZ008 RUA008

Acoustic Notes:
1. 38AUZ07-12 units are in accordance with ARI 270-2008 Sound Rating of Unitary Equipment.
2. The sound data for all 38AUZ14 units are based on upona limited amount of actual testing with the estimated sound power data
being generated from this data in accordance with ARI 370-2001 for Large Outdoor Refrigerating and Air-Conditioning Equipment.
3. The indoor duct sound power data is estimated based on the ASHRAE calculation approachfrom the ASHRAE handbook 1987
HVAC Systems and Applications, Chapter 52.
4. The acoustic center of the unit is located at the geometric center of the unit.
5. All estimated sound power levels, dB re 1 Pico watt should not be guaranteed or certified as being the actual sound power levels.

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal dist. from obstruction to receiver: 0.0 ft
6. Horizontal dist. from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 6 1 2 5 1 2 4 8 Ov


3 2 5 0 k k k k er
5 0 0 all

Commercial Split Systems Builder 1.33 Page 7 of 91


Performance Summary For SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Sound Power Levels at Unit's Acoustic Center (Lw), dB 8 8 8 8 8 7 7 6 92.


9 5 2 2 0 5 1 6 2
. . . . . . . .
3 0 0 7 2 2 0 0
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), 6 6 7 7 8 7 7 6 84.
dBA 3 8 3 9 0 6 2 4 6
. . . . . . . .
1 9 4 5 2 4 0 9
Sound Press. Levels at Dist. Specified above (Lp), dB 6 6 5 5 5 5 4 4 67.
5 0 7 8 5 0 6 1 9
. . . . . . . .
0 7 7 4 9 9 7 7
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 3 4 4 5 5 5 4 4 60.
8 4 9 5 5 2 7 0 3
. . . . . . . .
8 6 1 2 9 1 7 6

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

Commercial Split Systems Builder 1.33 Page 8 of 91


Performance Summary For SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

40RUA008withStandardCapacityCoil
3
1200RPM
1100RPM

1000RPM
Static Pressure (in. wg.)

2
900RPM

800RPM SC 5.00BHP

700RPM

1
600RPM
PP

500RPM RP
3.70BHP
400RPM

2.00BHP
1.00BHP
1.30BHP 3.00
2.402.90
BHP BHP
BHP
0
0 1 2 3 4 5
Airflow(CFM-thousands)
RPM=796 BHP=1.02 MaximumRPM=1200 MaximumHP=2.40
ShadedArea-RecommendedOperatingRange
SC-SystemCurve RP-RatedPoint MP-MinimumPoint PP-PsuedoPoint

Commercial Split Systems Builder 1.33 Page 9 of 91


Acoustic Summary For SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Acoustic Summary

Outdoor Unit Parameters:


Tag Name: SPLIT 7.5 TON
Unit Model: 38AUZ
Unit Size: 7.5 Tons
System Type: Dx Cooling Only
Refrigerant Type: PURON
Compressor Quantity: 1
Compressor Type: Scroll

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal distance from obstruction to receiver:0.0 ft
6. Horizontal distance from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 6 1 2 5 1 2 4 8 Ov


3 2 5 0 k k k k er
5 0 0 all
Sound Power Levels at Unit's Acoustic Center (Lw), dB 8 8 8 8 8 7 7 6 92.
9 5 2 2 0 5 1 6 2
. . . . . . . .
3 0 0 7 2 2 0 0
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), 6 6 7 7 8 7 7 6 84.
dBA 3 8 3 9 0 6 2 4 6
. . . . . . . .
1 9 4 5 2 4 0 9
Sound Press. Levels at Dist. Specified above (Lp), dB 6 6 5 5 5 5 4 4 67.
5 0 7 8 5 0 6 1 9
. . . . . . . .
0 7 7 4 9 9 7 7
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 3 4 4 5 5 5 4 4 60.
8 4 9 5 5 2 7 0 3
. . . . . . . .
8 6 1 2 9 1 7 6

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

Acoustic Notes:
1. 38AUZ07-12 units are in accordance with ARI 270-2008 Sound Rating of Unitary Equipment.
2. The sound data for all 38AUZ14 units are based on upon a limited amount of actual testing with the estimated sound power
data being generated from this data in accordance with ARI 370-2001 for Large Outdoor Refrigerating and Air-Conditioning
Equipment.
3. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook
1987 HVAC Systems and Applications, Chapter 52.
4. The acoustic center of the unit is located at the geometric center of the unit.
5. All estimated sound power levels, dB re 1 Pico watt should not be guaranteed or certified as being the actual sound power levels.
Commercial Split Systems Builder 1.33 Page 10 of 91
Acoustic Summary For SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Indoor Unit Parameters:


Tag Name: SPLIT 7.5 TON
Unit Model: 40RUA
Unit Size: 7.5 Tons
System Type: Dx Cooling Only
External Static Pressure: 0.60 in wg
Fan Speed: 796 RPM
Fan BHP: 1.02 BHP

Octave Band Center Frequency, Hz 3 6 1 2 5 1 2 4 8 T


1 3 2 5 0 k k k k o
5 0 0 t
a
l
Sound Power,dB N 9 9 8 8 8 8 7 N 9
A 5 1 7 6 2 0 6 A 7
. . . . . . . .
3 3 3 3 3 3 3 8
A-Weighted Sound Power, dBA N 6 7 7 8 8 8 7 N 8
A 9 5 8 3 2 1 7 A 8
. . . . . . . .
1 2 7 1 3 5 3 4

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Commercial Split Systems Builder 1.33 Page 11 of 91


Certified Drawing for SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Certified Drawing

Commercial Split Systems Builder 1.33 Page 12 of 91


Certified Drawing for SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Commercial Split Systems Builder 1.33 Page 13 of 91


Certified Drawing for SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Commercial Split Systems Builder 1.33 Page 14 of 91


Guide Specification for SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Guide Specifications

GUIDE SPECIFICATIONS 38AUZA08A0A5-0A0A0

Commercial Air-Cooled Condensing Units


HVAC Guide Specifications

Size: 08
Part 1: General
SYSTEM DESCRIPTION
1.01. Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall consist of a hermetic
scroll air-conditioning compressor(s) assembly, an air-cooled coil, propeller-type condenser fans, and a control box. Unit shall
discharge supply air upward as shown on contract drawings. Unit shall be used in a refrigeration circuit matched with a
packaged air-handling unit.
QUALITY ASSURANCE
1.01. Unit shall be rated in accordance with AHRI Standard 360.
1.02. Unit construction shall comply with ANSI/ASHRAE 15 safety code latest revision and comply with NEC.
1.03. Unit shall be constructed in accordance with UL 1995 standard and shall carry the UL and UL, Canada label.
1.04. Unit cabinet shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).
1.05. Air-cooled condenser coils for hermetic scroll compressor units (38AUZ) and 38AUD shall be leak tested at 150 psig, and
pressure tested at 650 psig.
1.06. Unit shall be manufactured in a facility registered to ISO 9001:2000 manufacturing quality standard.
DELIVERY, STORAGE, AND HANDLING
1.01. Unit shall be shipped as single package only, and shall be stored and handled according to unit manufacturers
recommendations.
WARRANTY (FOR INCLUSION BYSPECIFYING ENGINEER.)
Part 2: Products
EQUIPMENT
2.01. General:
A. Factory-assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring,
piping, controls, compressor, holding charge, and special features required prior to field start-up.
2.02. Unit Cabinet:
A. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a prepainted baked enamel finish.
B. A heavy-gauge roll-formed perimeter base rail with forklift slots and lifting holes shall be provided to facilitate rigging.
2.03. CondenserFans:
A. Condenser fans shall be direct driven, propeller type, discharging air vertically upward.
B. Fan blades shall be balanced.
C. Condenser fan discharge openings shall be equipped with PVC-coated steel wire safety guards.
D. Condenser fan and motor shaft shall be corrosion resistant.
2.04. Compressor:
A. Compressor shall be of the hermetic scroll type .
Commercial Split Systems Builder 1.33 Page 15 of 91
Guide Specification for SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

B. Compressor shall be mounted on rubber grommets.


C. Compressors shall include overload protection.
D. Compressors shall be equipped with a crankcase heater.
E. Compressor shall be equipped with internal high pressure and high temperature protection.
F. 38AUZ*16 and 25 sizes shall use two scroll compressors manifold together.
2.05. Condenser Coils:
A. Standard Aluminum fin - Copper Tube Coils:
1. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seamless
internally grooved copper tubes with all joints brazed.
2. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at
1775 psig.
3. Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at
1980 psig.
2.06. Refrigeration Components:
A. Refrigeration circuit components shall include liquid line service valve, suction line service valve, a full charge of
compressor oil, and a partial holding charge of refrigerant.
2.07. Controls and Safeties:
A. Minimum control functions shall include:
1. Control wire terminal blocks.
2. Compressor lockout on auto-reset safety until reset from thermostat.
3. Each unit shall utilize the Comfort Alertt Diagnostic Board that provides:
a. System Pressure Trip fault code indication
b. Short Cycling fault code indication
c. Locked Rotor fault code indication
d. Open Circuit fault code indication
e. Reverse Phase 3 fault code indication
f. Welded Contactor fault code indication
g. Low Voltage fault code indication
h. Anti-short cycle protection
i. Phase reversal protection
B. Minimum safety devices which are equipped with automatic reset (after resetting first at thermostat), shall include:
1. High discharge pressure cutout.
2. Low pressure cutout.
2.08. Operating Characteristics:
A. The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of ______F. The power
consumption at full load shall not exceed _____ kW.
B. The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____
Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at ______F wet bulb and ______F
dry bulb, and air entering the condensing unit at ______F.
C. The system shall have an EER of _____ Btuh/Watt or greater at standard AHRI conditions.
D. Standard unit shall be capable to operate up to 125_F (52_C) and down to 40_F (4_C)
2.09. Electrical Requirements:
A. Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation
within voltage limits of ____ v to _____ v.
B. Unit electrical power shall be single-point connection.
C. Unit control circuit shall contain a 24-v transformer for unit control.
2.10. Special Features:
A. Thermostat Controls:
Commercial Split Systems Builder 1.33 Page 16 of 91
Guide Specification for SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

1. Programmable multi-stage thermostat shall have 7-day clock, holiday scheduling, large backlit display, remote sensor
capability, and Title 24 compliance.
2. Commercial Electronic Thermostat shall have 7-day time clock, auto-changeover, multi-stage capability, and large
LCD (liquid crystal display) temperature display.

GUIDE SPECIFICATIONS 40RUAA08A2A6-0A0A0

Commercial Packaged Air-Handling Unit


HVAC Guide Specifications

Size: 08
Part 1: GENERAL
SYSTEM DESCRIPTION
1.01. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be
capable of horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be
applied without ductwork.)
1.02. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with
chilled water coil shall be used in a chilled water circuit.
QUALITY ASSURANCE
1.01. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest
edition.
1.02. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL,
Canada, labels.
1.03. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation.
Insulation shall contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi
as proven by tests in accordance with ASTM standards G21 and 22 (U.S.A.).
1.04. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
1.05. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
DELIVERY AND STORAGE
1.01. Units shall be stored and handled per manufacturers recommendations.
Part 2: Products
EQUIPMENT
2.01. Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical
configuration. Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan
motor contactor, factory-installed refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm)
disposable air filters, and condensate drain pans for vertical or horizontal configurations.
2.02. Base Unit:
A. Cabinet shall be constructed of mill-galvanized steel.
B. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-
registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in

Commercial Split Systems Builder 1.33 Page 17 of 91


Guide Specification for SPLIT 7.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

accordance with ASTM standards G21 and 22 (U.S.A.).


C. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have
connections on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward
the right or left side of the unit to prevent standing water from accumulating in pans.
D. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access
shall be from either the right or left side of the unit.
2.03. Coils:
A. DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion.
Suction and liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The
TXVs shall be Puron R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall
have a factory-installed bypass line and check valve assembly around the TXVs to allow liquid flow from the coil to
the outdoor unit during the heating mode. Coil tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
2.04. Operating Characteristics:
A. Unit shall be capable of providing ____ cfm (L/s) airflow at an external static pressure of ____ in. wg (kPag).
2.05. Motor:
A. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and
installed.
B. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at
5 hp (3.73 kW) shall be protected by a circuit breaker.
C. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload
protection or manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not
have conventional horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the air-
over location downstream of the cooling coil and carry a maximum continuous bhp rating that is the maximum application
bhp rating for the motor; no safety factors above that rating may be applied.
D. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy
Policy Act of 1992 (EPACT), effective October 24, 1997.
2.06. Special Features:
A. Alternate Motor and Drive:
1. An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static
pressure requirements specified on the equipment schedule.
B. Thermostat Controls:
1. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, F/C
capability, and CCN (Carrier Comfort Network) compatibility.
2. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD
temperature display.

Commercial Split Systems Builder 1.33 Page 18 of 91


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


38AUZ 6 TO 20 TON
38AUD 10 and 20 Ton
AIR-COOLED CONDENSING UNITS with PURON REFRIGERANT
These commercial quality air-cooled condensing units are easily connected by refrigerant lines and low voltage
control wiring to matching Carrier packaged air-handling units or other suitable evaporator units. They are ideal for
new construction or renovation applications where quality and performance are required.

BASE UNIT STANDARD FEATURES:



Puron (R-410A) HFC refrigerant partial charge

Single-stage cooling capacity control on 07 to 14
models

All models utilize aluminum Novation Heat
Exchanger Technology Condenser Coils

Standard one-year unit warranty, 5-year
compressor plan and 3-year parts plan on
Novation coil

Cooling operating range up to 125 F (52 C) and
down to 35 F (2 C)

Brass suction and liquid line service valves

Fully Hermetic Scroll compressor with crankcase
heater

New terminal board facilitating simple safety circuit
troubleshooting and simplified control box
arrangement. 24-volt 75va control system

High and low pressure switches.

Comfort Alert Diagnostic Board:
LED Go-No-Go and fault code
Certified to ISO 9001:2000

Built in time guard anti-short cycle



Phase protection

Fault code retention logic

Low voltage compressor contactor protector

UL and UL, Canada apply to standard units; 575-
volt units UL, Canada only.

Full perimeter base rails with built-in rigging
adapters and fork truck slots

Pre-painted exterior panels and primer-coated
interior panels tested to 500 hours salt spray
protection

Direct drive permanently lubricated condenser fan
motors

All units factory run tested

Compressors mounted on independent vibration
isolators

Commercial Split Systems Builder 1.33 Page 19 of 91


COMMERCIAL SPLIT SYSTEMS
40RUA DIRECT EXPANSION
PACKAGED AIR-HANDLING UNITS with PURON REFRIGERANT

40RUA 6 TO 30 TON CHASSIS SHOWN

STANDARD FEATURES FOR PURON (R-410A) HFC Refrigerant


1. Cleanable insulation treated with an anti-microbial agent.
2. Two sloped condensate pans on each unit for horizontal or vertical applications.
3. 2 inch filters.
4. Powerful belt-driven forward curved fans.
5. Factory-installed fan motor and contactor.
6. Refrigerant metering devices (TXV's) -- factory installed.
7. Easy maintenance -- removal of a single panel allows access to virtually all components.
8. Single blower on 07 to 12 sizes; dual blower on 14 to 30 sizes.
9. 24-volt terminal block for control wiring connection.
10. Standard one year warranty.

40RUA DIRECT EXPANSION


PACKAGED AIR-HANDLING UNITS
The 40RUA units are completely packaged direct expansion air-handling units offering the ultimate in installation ease and flexibility.
Combined with Carrier 38AU Series condensing units these packaged air handling units offer system capacities from 6 up to 30 tons.
These units may be installed in either the vertical or horizontal configuration with no modifications. Powerful fan systems allow easy
adaptation to existing ductwork. Heating capability is provided by electric heaters, hot water coils or steam coils.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.33 Page 20 of 91


Commercial Split Systems Builder 1.33 Page 21 of 91
SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

SPLIT 10 TON

SPLIT 10 TON

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Feature Sheet

Commercial Split Systems Builder 1.33 Page 22 of 91


Unit Report For SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Unit Report

Outdoor Unit Parameters Indoor Unit Parameters


Unit Quantity: 1 Unit Model: 40RUA
Unit Model: 38AUD Unit Size: 10 Tons
Unit Size: 10 Tons No. of Splits: 2
Voltage: 230-3-60 V-Ph-Hz Voltage: 230-3-60 V-Ph-Hz
Condenser Coil: Al/Cu
No. of DX Circuits: 2

System Parameter
System Quantity: 1
Refrigerant Type: PURON
Compressor Quantity: 2
Compressor Type: Scroll
Std. Capacity Steps: 50, 100
Std. Min. Outdoor Temp(Cooling): 35.0 F
No. of Outdoor fans: 2

Outdoor Unit Dimensions and Weight Indoor Unit Dimensions and Weight
Unit Length: 4' 11.4'' Unit Length: 4' 1.0''
Unit Width: 3' 9.9'' Unit Width: 2' 4.2''
Unit Height: 4' 2.4'' Unit Height: 4' 8.1''
Unit Shipping Weight: 516 lb Unit Shipping Weight: 425 lb
Unit Operating Weight: 516 lb Unit Operating Weight: 425 lb

Warranty Information (Note: for US & Canada only)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quanti


ty
Base Unit - Outdoor

38AUDA12A0A5-0A0A0 1
Base Unit
Al/Cu Condensing Coil 1
Standard Refrigerant Options 1
Service Options - None 1
Electrical Options - None 1
Packaging Options - Standard 1
Standard Electrical Mechanical Controls 1
Single Stage 1
Base Unit - Indoor
40RUAA12A2A6-0A0A0 1
Base Unit
Std Static, Std Eff Motor/ Medium Drive 1
Commercial Split Systems Builder 1.33 Page 23 of 91
Unit Report For SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Cabinet Paint - None 1


None- No Controller 1

Commercial Split Systems Builder 1.33 Page 24 of 91


Performance Summary For SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Performance Summary

System: 38AUD012/40RUA012
System Quantity: 1
Altitude: 5200.0 ft
EER @ ARI Conditions: 11.2
IEER: 11.6
Linear Pipe Length: 30.0 ft
Suction Line Size: 7/8 in
Liquid Line Size: 3/8 in
Suction Line Loss: 1.4 F
System meets the Energy Star EER rating.

Outdoor Unit Parameters


Unit Quantity: 1
PartNumber: 38AUDA12A0A5-0A0A0
Unit Model: 38AUD
Unit Size: 10 Tons
Condenser Coil: Al/Cu
No. of DX Circuits: 2
Voltage: 230-3-60 V-Ph-Hz
Clg Ent Air DB: 95.0 F

Outdoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit#1 MCA: 39.0 Amps
Unit#1 MOCP: 50.0 Amps
Total Compressor Power of Unit #1: NA
Voltage Range Min: 187 V
Voltage Range Max: 253 V
Compressor RLA: 15.9
Compressor LRA: 110
Compressor Quantity: 2
Fan Motors Qty: 2
Notice: Outdoor unit elect. data is based on 230-3-60
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage

Indoor Unit Parameters


PartNumber: 40RUAA12A2A6-0A0A0
Unit Model: 40RUA
Unit Size: 10 Tons
Coil Rows: 4
No. of Splits: 2
Voltage: 230-3-60 V-Ph-Hz
Actual Airflow: 4000.0 CFM
Standard Airflow: 3303.4 CFM
Total Clg Cap.(Gross): 119.8 MBH
Sensible Clg Cap.(Gross): 82.6 MBH
Ent Air DB: 80.0 F
Ent Air WB: 67.0 F
Ent Enthalpy: 34.79 BTU/lb
Lvg Air DB: 56.9 F
Lvg Air WB: 56.9 F
Lvg Enthalpy: 26.73 BTU/lb
Coil Bypass Factor: NA

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Commercial Split Systems Builder 1.33 Page 25 of 91
Performance Summary For SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Fan Speed: 897 RPM


Fan Power: 1.77 BHP
Fan Motor Max: 2.40 BHP
Fan Motor FLA: 6.9 Amps
Motor and Medium Static Drive Required.
Selected Medium Static Drive Range: 733 - 949

Indoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit MCA: 9.0 Amps
Unit MOCP: 15.0 Amps
Notice: Indoor unit elect. data is based on 230-3-60

Acoustics
Sound Power Levels, db re 10E-12 Watts

Outdoor Unit (dB) Indoor Unit


(dB,Ducted)
A-Weighted Total Level 84.2 91.7
63Hz 86.3 98.6
125Hz 85.8 94.6
250Hz 81.4 90.6
500Hz 81.9 89.6
1000Hz 79.5 85.6
2000Hz 75.1 83.6
4000Hz 71.9 79.6
8000Hz 68.9 NA
Sound Message Sound for AUD012 Sound for RUA012

Acoustic Note:
1. 38AUZ and 38AUD sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment.
2. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
3. The acoustic center of the unit is located at the geometric center of the unit.
4. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal dist. from obstruction to receiver: 0.0 ft
6. Horizontal dist. from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 63 1 2 5 1 2 4 8 Over


2 5 0 k k k k all
5 0 0
Sound Power Levels at Unit's Acoustic Center (Lw), dB 86. 8 8 8 7 7 7 6 90.9
3 5. 1. 1. 9. 5. 1. 8.
8 4 9 5 1 9 9
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA 60. 6 7 7 7 7 7 6 84.2
1 9. 2. 8. 9. 6. 2. 7.
7 8 7 5 3 9 8

Commercial Split Systems Builder 1.33 Page 26 of 91


Performance Summary For SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Sound Press. Levels at Dist. Specified above (Lp), dB 62. 6 5 5 5 5 4 4 66.6


0 1. 7. 7. 5. 0. 7. 4.
5 1 6 2 8 6 6
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 35. 4 4 5 5 5 4 4 59.8
8 5. 8. 4. 5. 2. 8. 3.
4 5 4 2 0 6 5

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

40RUA012withStandardCapacityCoil
3 1200RPM
1100RPM

1000RPM
Static Pressure (in. wg.)

2
900RPM

800RPM SC

700RPM
7.50BHP
1
600RPM
5.00BHP
PP
RP 3.70BHP
500RPM 2.90BHP
2.00BHP 2.40
3.00BHP
BHP
400RPM

0
0 1 2 3 4 5 6 7
Airflow(CFM-thousands)
RPM=897 BHP=1.77 MaximumRPM=1200 MaximumHP=2.40
ShadedArea-RecommendedOperatingRange
SC-SystemCurve RP-RatedPoint MP-MinimumPoint PP-PsuedoPoint

Commercial Split Systems Builder 1.33 Page 27 of 91


Acoustic Summary For SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Acoustic Summary

Outdoor Unit Parameters:


Tag Name: SPLIT 10 TON
Unit Model: 38AUD
Unit Size: 10 Tons
System Type: Dx Cooling Only
Refrigerant Type: PURON
Compressor Quantity: 2
Compressor Type: Scroll

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal distance from obstruction to receiver:0.0 ft
6. Horizontal distance from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 63 1 2 5 1 2 4 8 Over


2 5 0 k k k k all
5 0 0
Sound Power Levels at Unit's Acoustic Center (Lw), dB 86. 8 8 8 7 7 7 6 90.9
3 5. 1. 1. 9. 5. 1. 8.
8 4 9 5 1 9 9
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA 60. 6 7 7 7 7 7 6 84.2
1 9. 2. 8. 9. 6. 2. 7.
7 8 7 5 3 9 8
Sound Press. Levels at Dist. Specified above (Lp), dB 62. 6 5 5 5 5 4 4 66.6
0 1. 7. 7. 5. 0. 7. 4.
5 1 6 2 8 6 6
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 35. 4 4 5 5 5 4 4 59.8
8 5. 8. 4. 5. 2. 8. 3.
4 5 4 2 0 6 5

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

Acoustic Note:
1. 38ARZ, 38ARS and 38ARD012 sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment.
2. 38ARD014-024 and 38AKS data is estimated sound power levels. It is based upon a limited amount of actual testing with the
estimated sound power data being generated from this data in accordance with ARI Standard 370 for large outdoor refrigerating and
air-conditioning equipment.
3. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
4. The acoustic center of the unit is located at the geometric center of the unit.
5. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Indoor Unit Parameters: Unit Size: 10 Tons


Tag Name: SPLIT 10 TON System Type: Dx Cooling Only
Unit Model: 40RUA External Static Pressure: 0.60 in wg
Commercial Split Systems Builder 1.33 Page 28 of 91
Acoustic Summary For SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Fan Speed: 897 RPM


Fan BHP: 1.77 BHP

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Tot


al
Sound Power,dB NA 98. 94. 90. 89. 85. 83. 79. NA 101
6 6 6 6 6 6 6 .1
A-Weighted Sound Power, dBA NA 72. 78. 82. 86. 85. 84. 80. NA 91.
4 5 0 4 6 8 6 7

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Commercial Split Systems Builder 1.33 Page 29 of 91


Certified Drawing for SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Certified Drawing

Commercial Split Systems Builder 1.33 Page 30 of 91


Certified Drawing for SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Commercial Split Systems Builder 1.33 Page 31 of 91


Certified Drawing for SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Commercial Split Systems Builder 1.33 Page 32 of 91


Guide Specification for SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Guide Specifications

GUIDE SPECIFICATIONS 38AUDA12A0A5-0A0A0

Commercial Air-Cooled Condensing Units


HVAC Guide Specifications

Size: 12
Part 1: General
SYSTEM DESCRIPTION
1.01. Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall consist of a hermetic
scroll air-conditioning compressor(s) assembly, an air-cooled coil, propeller-type condenser fans, and a control box. Unit shall
discharge supply air upward as shown on contract drawings. Unit shall be used in a refrigeration circuit matched with a
packaged air-handling unit.
QUALITY ASSURANCE
1.01. Unit shall be rated in accordance with AHRI Standard 360.
1.02. Unit construction shall comply with ANSI/ASHRAE 15 safety code latest revision and comply with NEC.
1.03. Unit shall be constructed in accordance with UL 1995 standard and shall carry the UL and UL, Canada label.
1.04. Unit cabinet shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).
1.05. Air-cooled condenser coils for hermetic scroll compressor units (38AUZ) and 38AUD shall be leak tested at 150 psig, and
pressure tested at 650 psig.
1.06. Unit shall be manufactured in a facility registered to ISO 9001:2000 manufacturing quality standard.
DELIVERY, STORAGE, AND HANDLING
1.01. Unit shall be shipped as single package only, and shall be stored and handled according to unit manufacturers
recommendations.
WARRANTY (FOR INCLUSION BYSPECIFYING ENGINEER.)
Part 2: Products
EQUIPMENT
2.01. General:
A. Factory-assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring,
piping, controls, compressor, holding charge, and special features required prior to field start-up.
2.02. Unit Cabinet:
A. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a prepainted baked enamel finish.
B. A heavy-gauge roll-formed perimeter base rail with forklift slots and lifting holes shall be provided to facilitate rigging.
2.03. CondenserFans:
A. Condenser fans shall be direct driven, propeller type, discharging air vertically upward.
B. Fan blades shall be balanced.
C. Condenser fan discharge openings shall be equipped with PVC-coated steel wire safety guards.
D. Condenser fan and motor shaft shall be corrosion resistant.
2.04. Compressor:
A. Compressor shall be of the hermetic scroll type .
Commercial Split Systems Builder 1.33 Page 33 of 91
Guide Specification for SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

B. Compressor shall be mounted on rubber grommets.


C. Compressors shall include overload protection.
D. Compressors shall be equipped with a crankcase heater.
E. Compressor shall be equipped with internal high pressure and high temperature protection.
F. 38AUZ*16 and 25 sizes shall use two scroll compressors manifold together.
2.05. Condenser Coils:
A. Standard Aluminum fin - Copper Tube Coils:
1. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seamless
internally grooved copper tubes with all joints brazed.
2. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at
1775 psig.
3. Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at
1980 psig.
2.06. Refrigeration Components:
A. Refrigeration circuit components shall include liquid line service valve, suction line service valve, a full charge of
compressor oil, and a partial holding charge of refrigerant.
2.07. Controls and Safeties:
A. Minimum control functions shall include:
1. Control wire terminal blocks.
2. Compressor lockout on auto-reset safety until reset from thermostat.
3. Each unit shall utilize the Comfort Alertt Diagnostic Board that provides:
a. System Pressure Trip fault code indication
b. Short Cycling fault code indication
c. Locked Rotor fault code indication
d. Open Circuit fault code indication
e. Reverse Phase 3 fault code indication
f. Welded Contactor fault code indication
g. Low Voltage fault code indication
h. Anti-short cycle protection
i. Phase reversal protection
B. Minimum safety devices which are equipped with automatic reset (after resetting first at thermostat), shall include:
1. High discharge pressure cutout.
2. Low pressure cutout.
2.08. Operating Characteristics:
A. The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of ______F. The power
consumption at full load shall not exceed _____ kW.
B. The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____
Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at ______F wet bulb and ______F dry
bulb, and air entering the condensing unit at ______F.
C. The system shall have an EER of _____ Btuh/Watt or greater at standard AHRI conditions.
D. Standard unit shall be capable to operate up to 125_F (52_C) and down to 40_F (4_C)
2.09. Electrical Requirements:
A. Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation
within voltage limits of ____ v to _____ v.
B. Unit electrical power shall be single-point connection.
C. Unit control circuit shall contain a 24-v transformer for unit control.
2.10. Special Features:
A. Thermostat Controls:
Commercial Split Systems Builder 1.33 Page 34 of 91
Guide Specification for SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

1. Programmable multi-stage thermostat shall have 7-day clock, holiday scheduling, large backlit display, remote sensor
capability, and Title 24 compliance.
2. Commercial Electronic Thermostat shall have 7-day time clock, auto-changeover, multi-stage capability, and large
LCD (liquid crystal display) temperature display.

GUIDE SPECIFICATIONS 40RUAA12A2A6-0A0A0

Commercial Packaged Air-Handling Unit


HVAC Guide Specifications

Size: 12
Part 1: GENERAL
SYSTEM DESCRIPTION
1.01. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be
capable of horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be
applied without ductwork.)
1.02. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with
chilled water coil shall be used in a chilled water circuit.
QUALITY ASSURANCE
1.01. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest
edition.
1.02. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL,
Canada, labels.
1.03. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation.
Insulation shall contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi
as proven by tests in accordance with ASTM standards G21 and 22 (U.S.A.).
1.04. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
1.05. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
DELIVERY AND STORAGE
1.01. Units shall be stored and handled per manufacturers recommendations.
Part 2: Products
EQUIPMENT
2.01. Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical
configuration. Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan
motor contactor, factory-installed refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm)
disposable air filters, and condensate drain pans for vertical or horizontal configurations.
2.02. Base Unit:
A. Cabinet shall be constructed of mill-galvanized steel.
B. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-
registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in

Commercial Split Systems Builder 1.33 Page 35 of 91


Guide Specification for SPLIT 10 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

accordance with ASTM standards G21 and 22 (U.S.A.).


C. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have
connections on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward
the right or left side of the unit to prevent standing water from accumulating in pans.
D. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access
shall be from either the right or left side of the unit.
2.03. Coils:
A. DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion.
Suction and liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The
TXVs shall be Puron R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall
have a factory-installed bypass line and check valve assembly around the TXVs to allow liquid flow from the coil to
the outdoor unit during the heating mode. Coil tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
2.04. Operating Characteristics:
A. Unit shall be capable of providing ____ cfm (L/s) airflow at an external static pressure of ____ in. wg (kPag).
2.05. Motor:
A. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and
installed.
B. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at
5 hp (3.73 kW) shall be protected by a circuit breaker.
C. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload
protection or manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not
have conventional horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the air-
over location downstream of the cooling coil and carry a maximum continuous bhp rating that is the maximum application
bhp rating for the motor; no safety factors above that rating may be applied.
D. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy
Policy Act of 1992 (EPACT), effective October 24, 1997.
2.06. Special Features:
A. Alternate Motor and Drive:
1. An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static
pressure requirements specified on the equipment schedule.
B. Thermostat Controls:
1. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, F/C
capability, and CCN (Carrier Comfort Network) compatibility.
2. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD
temperature display.

Commercial Split Systems Builder 1.33 Page 36 of 91


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


38AUZ 6 TO 20 TON
38AUD 10 and 20 Ton
AIR-COOLED CONDENSING UNITS with PURON REFRIGERANT
These commercial quality air-cooled condensing units are easily connected by refrigerant lines and low voltage
control wiring to matching Carrier packaged air-handling units or other suitable evaporator units. They are ideal for
new construction or renovation applications where quality and performance are required.

BASE UNIT STANDARD FEATURES:



Puron (R-410A) HFC refrigerant partial charge

Single-stage cooling capacity control on 07 to 14
models

All models utilize aluminum Novation Heat
Exchanger Technology Condenser Coils

Standard one-year unit warranty, 5-year
compressor plan and 3-year parts plan on Novation
coil

Cooling operating range up to 125 F (52 C) and
down to 35 F (2 C)

Brass suction and liquid line service valves

Fully Hermetic Scroll compressor with crankcase
heater

New terminal board facilitating simple safety circuit
troubleshooting and simplified control box
arrangement. 24-volt 75va control system

High and low pressure switches.

Comfort Alert Diagnostic Board:
LED Go-No-Go and fault code
Certified to ISO 9001:2000

Built in time guard anti-short cycle



Phase protection

Fault code retention logic

Low voltage compressor contactor protector

UL and UL, Canada apply to standard units; 575-
volt units UL, Canada only.

Full perimeter base rails with built-in rigging
adapters and fork truck slots

Pre-painted exterior panels and primer-coated
interior panels tested to 500 hours salt spray
protection

Direct drive permanently lubricated condenser fan
motors

All units factory run tested

Compressors mounted on independent vibration
isolators

Commercial Split Systems Builder 1.33 Page 37 of 91


COMMERCIAL SPLIT SYSTEMS
40RUA DIRECT EXPANSION
PACKAGED AIR-HANDLING UNITS with PURON REFRIGERANT

40RUA 6 TO 30 TON CHASSIS SHOWN

STANDARD FEATURES FOR PURON (R-410A) HFC Refrigerant


1. Cleanable insulation treated with an anti-microbial agent.
2. Two sloped condensate pans on each unit for horizontal or vertical applications.
3. 2 inch filters.
4. Powerful belt-driven forward curved fans.
5. Factory-installed fan motor and contactor.
6. Refrigerant metering devices (TXV's) -- factory installed.
7. Easy maintenance -- removal of a single panel allows access to virtually all components.
8. Single blower on 07 to 12 sizes; dual blower on 14 to 30 sizes.
9. 24-volt terminal block for control wiring connection.
10. Standard one year warranty.

40RUA DIRECT EXPANSION


PACKAGED AIR-HANDLING UNITS
The 40RUA units are completely packaged direct expansion air-handling units offering the ultimate in installation ease and flexibility.
Combined with Carrier 38AU Series condensing units these packaged air handling units offer system capacities from 6 up to 30 tons.
These units may be installed in either the vertical or horizontal configuration with no modifications. Powerful fan systems allow easy
adaptation to existing ductwork. Heating capability is provided by electric heaters, hot water coils or steam coils.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.33 Page 38 of 91


Commercial Split Systems Builder 1.33 Page 39 of 91
SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

SPLIT 12.5 TON

SPLIT 12.5 TON

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Feature Sheet

Commercial Split Systems Builder 1.33 Page 40 of 91


Unit Report For SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Unit Report

Outdoor Unit Parameters Indoor Unit Parameters


Unit Quantity: 1 Unit Model: 40RUA
Unit Model: 38AUD Unit Size: 12.5 Tons
Unit Size: 12.5 Tons No. of Splits: 2
Voltage: 230-3-60 V-Ph-Hz Voltage: 230-3-60 V-Ph-Hz
Condenser Coil: Al/Cu
No. of DX Circuits: 2

System Parameter
System Quantity: 1
Refrigerant Type: PURON
Compressor Quantity: 2
Compressor Type: Scroll
Std. Capacity Steps: 50, 100
Std. Min. Outdoor Temp(Cooling): 35.0 F
No. of Outdoor fans: 2

Outdoor Unit Dimensions and Weight Indoor Unit Dimensions and Weight
Unit Length: 4' 11.4'' Unit Length: 7' 5.0''
Unit Width: 3' 9.9'' Unit Width: 2' 4.2''
Unit Height: 4' 2.4'' Unit Height: 4' 8.1''
Unit Shipping Weight: 571 lb Unit Shipping Weight: 695 lb
Unit Operating Weight: 654 lb Unit Operating Weight: 695 lb

Warranty Information (Note: for US & Canada only)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity


Base Unit - Outdoor

38AUDA14A0A5-0A0A0 1
Base Unit
Al/Cu Condensing Coil 1
Standard Refrigerant Options 1
Service Options - None 1
Electrical Options - None 1
Packaging Options - Standard 1
Standard Electrical Mechanical Controls 1
Single Stage 1
Base Unit - Indoor
40RUAA14A2A6-0A0A0 1
Base Unit
Std Static, Std Eff Motor/ Medium Drive 1
Cabinet Paint - None 1
Commercial Split Systems Builder 1.33 Page 41 of 91
Unit Report For SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

None- No Controller 1

Commercial Split Systems Builder 1.33 Page 42 of 91


Performance Summary For SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Performance Summary

System: 38AUD014/40RUA014
System Quantity: 1
Altitude: 5200.0 ft
EER @ ARI Conditions: 11.0
IEER: 12.0
Linear Pipe Length: 30.0 ft
Suction Line Size: 7/8 in
Liquid Line Size: 3/8 in
Suction Line Loss: 1.4 F
System meets ASHRAE 90.1 min EER requirement.

Outdoor Unit Parameters


Unit Quantity: 1
PartNumber: 38AUDA14A0A5-0A0A0
Unit Model: 38AUD
Unit Size: 12.5 Tons
Condenser Coil: Al/Cu
No. of DX Circuits: 2
Voltage: 230-3-60 V-Ph-Hz
Clg Ent Air DB: 95.0 F

Outdoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit#1 MCA: 54.0 Amps
Unit#1 MOCP: 60.0 Amps
Total Compressor Power of Unit #1: NA
Voltage Range Min: 187 V
Voltage Range Max: 253 V
Compressor RLA: 22.4
Compressor LRA: 149
Compressor Quantity: 2
Fan Motors Qty: 2
Notice: Outdoor unit elect. data is based on 230-3-60
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage

Indoor Unit Parameters


PartNumber: 40RUAA14A2A6-0A0A0
Unit Model: 40RUA
Unit Size: 12.5 Tons
Coil Rows: 4
No. of Splits: 2
Voltage: 230-3-60 V-Ph-Hz
Actual Airflow: 5000.0 CFM
Standard Airflow: 4129.2 CFM
Total Clg Cap.(Gross): 148.6 MBH
Sensible Clg Cap.(Gross): 100.7 MBH
Ent Air DB: 80.0 F
Ent Air WB: 67.0 F
Ent Enthalpy: 34.79 BTU/lb
Lvg Air DB: 57.4 F
Lvg Air WB: 57.1 F
Lvg Enthalpy: 26.79 BTU/lb
Coil Bypass Factor: NA

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Commercial Split Systems Builder 1.33 Page 43 of 91
Performance Summary For SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Fan Speed: 761 RPM


Fan Power: 1.65 BHP
Fan Motor Max: 2.90 BHP
Fan Motor FLA: 11.0 Amps
Motor and Medium Static Drive Required.
Selected Medium Static Drive Range: 715 - 926

Indoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit MCA: 7.5 Amps
Unit MOCP: 15.0 Amps
Notice: Indoor unit elect. data is based on 230-3-60

Acoustics
Sound Power Levels, db re 10E-12 Watts

Outdoor Unit (dB) Indoor Unit


(dB,Ducted)
A-Weighted Total Level 82.8 91.1
63Hz 81.7 97.3
125Hz 80.9 93.3
250Hz 82.2 89.3
500Hz 80.4 90.3
1000Hz 78.2 84.3
2000Hz 73.6 82.3
4000Hz 69.7 78.3
8000Hz 65.4 NA
Sound Message Sound for AUD014 Sound for RUA014

Acoustic Note:
1. 38AUZ and 38AUD sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment.
2. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
3. The acoustic center of the unit is located at the geometric center of the unit.
4. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal dist. from obstruction to receiver: 0.0 ft
6. Horizontal dist. from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall


Sound Power Levels at Unit's Acoustic Center (Lw), dB 81.7 80. 82. 80. 78. 73. 69. 65. 88.1
9 2 4 2 6 7 4
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA 55.5 64. 73. 77. 78. 74. 70. 64. 82.8
8 6 2 2 8 7 3
Sound Press. Levels at Dist. Specified above (Lp), dB 57.4 56. 57. 56. 53. 49. 45. 41. 63.8
6 9 1 9 3 4 1
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 31.2 40. 49. 52. 53. 50. 46. 40. 58.5
5 3 9 9 5 4 0

Commercial Split Systems Builder 1.33 Page 44 of 91


Performance Summary For SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

40RUA014withStandardCapacityCoil
3
1100RPM 1200RPM

1000RPM
Static Pressure (in. wg.)

2 900RPM

800RPM
SC

700RPM

1
600RPM
PP 7.50BHP
500RPM RP
5.00BHP
3.70BHP
400RPM 2.40BHP 2.90BHP
2.00BHP 3.00BHP

0
0 1 2 3 4 5 6 7 8 9 10 11 12
Airflow(CFM-thousands)
RPM=761 BHP=1.65 MaximumRPM=1200 MaximumHP=2.90
ShadedArea-RecommendedOperatingRange
SC-SystemCurve RP-RatedPoint MP-MinimumPoint PP-PsuedoPoint

Commercial Split Systems Builder 1.33 Page 45 of 91


Acoustic Summary For SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Acoustic Summary

Outdoor Unit Parameters:


Tag Name: SPLIT 12.5 TON
Unit Model: 38AUD
Unit Size: 12.5 Tons
System Type: Dx Cooling Only
Refrigerant Type: PURON
Compressor Quantity: 2
Compressor Type: Scroll

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal distance from obstruction to receiver: 0.0 ft
6. Horizontal distance from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall


Sound Power Levels at Unit's Acoustic Center (Lw), dB 81.7 80. 82. 80. 78. 73. 69. 65. 88.1
9 2 4 2 6 7 4
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA 55.5 64. 73. 77. 78. 74. 70. 64. 82.8
8 6 2 2 8 7 3
Sound Press. Levels at Dist. Specified above (Lp), dB 57.4 56. 57. 56. 53. 49. 45. 41. 63.8
6 9 1 9 3 4 1
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 31.2 40. 49. 52. 53. 50. 46. 40. 58.5
5 3 9 9 5 4 0

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

Acoustic Note:
1. 38ARZ, 38ARS and 38ARD012 sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment.
2. 38ARD014-024 and 38AKS data is estimated sound power levels. It is based upon a limited amount of actual testing with the
estimated sound power data being generated from this data in accordance with ARI Standard 370 for large outdoor refrigerating and
air-conditioning equipment.
3. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
4. The acoustic center of the unit is located at the geometric center of the unit.
5. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Indoor Unit Parameters:


Tag Name: SPLIT 12.5 TON
Unit Model: 40RUA
Unit Size: 12.5 Tons
System Type: Dx Cooling Only
External Static Pressure: 0.60 in wg
Fan Speed: 761 RPM
Fan BHP: 1.65 BHP

Commercial Split Systems Builder 1.33 Page 46 of 91


Acoustic Summary For SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total


Sound Power,dB NA 97.3 93.3 89.3 90.3 84.3 82.3 78.3 NA 100.0
A-Weighted Sound Power, dBA NA 71.1 77.2 80.7 87.1 84.3 83.5 79.3 NA 91.1

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Commercial Split Systems Builder 1.33 Page 47 of 91


Certified Drawing for SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Certified Drawing

Commercial Split Systems Builder 1.33 Page 48 of 91


Certified Drawing for SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Commercial Split Systems Builder 1.33 Page 49 of 91


Certified Drawing for SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Commercial Split Systems Builder 1.33 Page 50 of 91


Guide Specification for SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Guide Specifications

GUIDE SPECIFICATIONS 38AUDA14A0A5-0A0A0

Commercial Air-Cooled Condensing Units


HVAC Guide Specifications

Size: 14
Part 1: General
SYSTEM DESCRIPTION
1.01. Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall consist of a hermetic
scroll air-conditioning compressor(s) assembly, an air-cooled coil, propeller-type condenser fans, and a control box. Unit shall
discharge supply air upward as shown on contract drawings. Unit shall be used in a refrigeration circuit matched with a
packaged air-handling unit.
QUALITY ASSURANCE
1.01. Unit shall be rated in accordance with AHRI Standard 360.
1.02. Unit construction shall comply with ANSI/ASHRAE 15 safety code latest revision and comply with NEC.
1.03. Unit shall be constructed in accordance with UL 1995 standard and shall carry the UL and UL, Canada label.
1.04. Unit cabinet shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).
1.05. Air-cooled condenser coils for hermetic scroll compressor units (38AUZ) and 38AUD shall be leak tested at 150 psig, and
pressure tested at 650 psig.
1.06. Unit shall be manufactured in a facility registered to ISO 9001:2000 manufacturing quality standard.
DELIVERY, STORAGE, AND HANDLING
1.01. Unit shall be shipped as single package only, and shall be stored and handled according to unit manufacturers
recommendations.
WARRANTY (FOR INCLUSION BYSPECIFYING ENGINEER.)
Part 2: Products
EQUIPMENT
2.01. General:
A. Factory-assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring,
piping, controls, compressor, holding charge, and special features required prior to field start-up.
2.02. Unit Cabinet:
A. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a prepainted baked enamel finish.
B. A heavy-gauge roll-formed perimeter base rail with forklift slots and lifting holes shall be provided to facilitate rigging.
2.03. CondenserFans:
A. Condenser fans shall be direct driven, propeller type, discharging air vertically upward.
B. Fan blades shall be balanced.
C. Condenser fan discharge openings shall be equipped with PVC-coated steel wire safety guards.
D. Condenser fan and motor shaft shall be corrosion resistant.
2.04. Compressor:
A. Compressor shall be of the hermetic scroll type .
Commercial Split Systems Builder 1.33 Page 51 of 91
Guide Specification for SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

B. Compressor shall be mounted on rubber grommets.


C. Compressors shall include overload protection.
D. Compressors shall be equipped with a crankcase heater.
E. Compressor shall be equipped with internal high pressure and high temperature protection.
F. 38AUZ*16 and 25 sizes shall use two scroll compressors manifold together.
2.05. Condenser Coils:
A. Standard Aluminum fin - Copper Tube Coils:
1. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seamless
internally grooved copper tubes with all joints brazed.
2. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at
1775 psig.
3. Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at
1980 psig.
2.06. Refrigeration Components:
A. Refrigeration circuit components shall include liquid line service valve, suction line service valve, a full charge of
compressor oil, and a partial holding charge of refrigerant.
2.07. Controls and Safeties:
A. Minimum control functions shall include:
1. Control wire terminal blocks.
2. Compressor lockout on auto-reset safety until reset from thermostat.
3. Each unit shall utilize the Comfort Alertt Diagnostic Board that provides:
a. System Pressure Trip fault code indication
b. Short Cycling fault code indication
c. Locked Rotor fault code indication
d. Open Circuit fault code indication
e. Reverse Phase 3 fault code indication
f. Welded Contactor fault code indication
g. Low Voltage fault code indication
h. Anti-short cycle protection
i. Phase reversal protection
B. Minimum safety devices which are equipped with automatic reset (after resetting first at thermostat), shall include:
1. High discharge pressure cutout.
2. Low pressure cutout.
2.08. Operating Characteristics:
A. The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of ______F. The power
consumption at full load shall not exceed _____ kW.
B. The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____
Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at ______F wet bulb and ______F
dry bulb, and air entering the condensing unit at ______F.
C. The system shall have an EER of _____ Btuh/Watt or greater at standard AHRI conditions.
D. Standard unit shall be capable to operate up to 125_F (52_C) and down to 40_F (4_C)
2.09. Electrical Requirements:
A. Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation
within voltage limits of ____ v to _____ v.
B. Unit electrical power shall be single-point connection.
C. Unit control circuit shall contain a 24-v transformer for unit control.
2.10. Special Features:
A. Thermostat Controls:
Commercial Split Systems Builder 1.33 Page 52 of 91
Guide Specification for SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

1. Programmable multi-stage thermostat shall have 7-day clock, holiday scheduling, large backlit display, remote sensor
capability, and Title 24 compliance.
2. Commercial Electronic Thermostat shall have 7-day time clock, auto-changeover, multi-stage capability, and large
LCD (liquid crystal display) temperature display.

GUIDE SPECIFICATIONS 40RUAA14A2A6-0A0A0

Commercial Packaged Air-Handling Unit


HVAC Guide Specifications

Size: 14
Part 1: GENERAL
SYSTEM DESCRIPTION
1.01. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be
capable of horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be
applied without ductwork.)
1.02. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with
chilled water coil shall be used in a chilled water circuit.
QUALITY ASSURANCE
1.01. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest
edition.
1.02. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL,
Canada, labels.
1.03. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation.
Insulation shall contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi
as proven by tests in accordance with ASTM standards G21 and 22 (U.S.A.).
1.04. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
1.05. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
DELIVERY AND STORAGE
1.01. Units shall be stored and handled per manufacturers recommendations.
Part 2: Products
EQUIPMENT
2.01. Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical
configuration. Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan
motor contactor, factory-installed refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm)
disposable air filters, and condensate drain pans for vertical or horizontal configurations.
2.02. Base Unit:
A. Cabinet shall be constructed of mill-galvanized steel.
B. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-
registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in

Commercial Split Systems Builder 1.33 Page 53 of 91


Guide Specification for SPLIT 12.5 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

accordance with ASTM standards G21 and 22 (U.S.A.).


C. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have
connections on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward
the right or left side of the unit to prevent standing water from accumulating in pans.
D. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access
shall be from either the right or left side of the unit.
2.03. Coils:
A. DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion.
Suction and liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The
TXVs shall be Puron R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall
have a factory-installed bypass line and check valve assembly around the TXVs to allow liquid flow from the coil to
the outdoor unit during the heating mode. Coil tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
2.04. Operating Characteristics:
A. Unit shall be capable of providing ____ cfm (L/s) airflow at an external static pressure of ____ in. wg (kPag).
2.05. Motor:
A. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and
installed.
B. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at
5 hp (3.73 kW) shall be protected by a circuit breaker.
C. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload
protection or manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not
have conventional horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the air-
over location downstream of the cooling coil and carry a maximum continuous bhp rating that is the maximum application
bhp rating for the motor; no safety factors above that rating may be applied.
D. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy
Policy Act of 1992 (EPACT), effective October 24, 1997.
2.06. Special Features:
A. Alternate Motor and Drive:
1. An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static
pressure requirements specified on the equipment schedule.
B. Thermostat Controls:
1. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, F/C
capability, and CCN (Carrier Comfort Network) compatibility.
2. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD
temperature display.

Commercial Split Systems Builder 1.33 Page 54 of 91


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


38AUZ 6 TO 20 TON
38AUD 10 and 20 Ton
AIR-COOLED CONDENSING UNITS with PURON REFRIGERANT
These commercial quality air-cooled condensing units are easily connected by refrigerant lines and low voltage
control wiring to matching Carrier packaged air-handling units or other suitable evaporator units. They are ideal for
new construction or renovation applications where quality and performance are required.

BASE UNIT STANDARD FEATURES:



Puron (R-410A) HFC refrigerant partial charge

Single-stage cooling capacity control on 07 to 14
models

All models utilize aluminum Novation Heat
Exchanger Technology Condenser Coils

Standard one-year unit warranty, 5-year compressor
plan and 3-year parts plan on Novation coil

Cooling operating range up to 125 F (52 C) and
down to 35 F (2 C)

Brass suction and liquid line service valves

Fully Hermetic Scroll compressor with crankcase
heater

New terminal board facilitating simple safety circuit
troubleshooting and simplified control box
arrangement. 24-volt 75va control system

High and low pressure switches.

Comfort Alert Diagnostic Board:

LED Go-No-Go and fault code
Built in time guard anti-short cycle
Certified to ISO 9001:2000

Phase protection


Fault code retention logic

Low voltage compressor contactor protector

UL and UL, Canada apply to standard units; 575-volt
units UL, Canada only.

Full perimeter base rails with built-in rigging adapters
and fork truck slots

Pre-painted exterior panels and primer-coated
interior panels tested to 500 hours salt spray
protection

Direct drive permanently lubricated condenser fan
motors

All units factory run tested

Compressors mounted on independent vibration
isolators

Commercial Split Systems Builder 1.33 Page 55 of 91


COMMERCIAL SPLIT SYSTEMS
40RUA DIRECT EXPANSION
PACKAGED AIR-HANDLING UNITS with PURON REFRIGERANT

40RUA 6 TO 30 TON CHASSIS SHOWN

STANDARD FEATURES FOR PURON (R-410A) HFC Refrigerant


1. Cleanable insulation treated with an anti-microbial agent.
2. Two sloped condensate pans on each unit for horizontal or vertical applications.
3. 2 inch filters.
4. Powerful belt-driven forward curved fans.
5. Factory-installed fan motor and contactor.
6. Refrigerant metering devices (TXV's) -- factory installed.
7. Easy maintenance -- removal of a single panel allows access to virtually all components.
8. Single blower on 07 to 12 sizes; dual blower on 14 to 30 sizes.
9. 24-volt terminal block for control wiring connection.
10. Standard one year warranty.

40RUA DIRECT EXPANSION


PACKAGED AIR-HANDLING UNITS
The 40RUA units are completely packaged direct expansion air-handling units offering the ultimate in installation ease and
flexibility. Combined with Carrier 38AU Series condensing units these packaged air handling units offer system capacities from 6 up
to 30 tons. These units may be installed in either the vertical or horizontal configuration with no modifications. Powerful fan systems
allow easy adaptation to existing ductwork. Heating capability is provided by electric heaters, hot water coils or steam coils.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.33 Page 56 of 91


Commercial Split Systems Builder 1.33 Page 57 of 91
SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

SPLIT 15 TON

SPLIT 15 TON

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Feature Sheet

Commercial Split Systems Builder 1.33 Page 58 of 91


Unit Report For SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Unit Report

Outdoor Unit Parameters Indoor Unit Parameters


Unit Quantity: 1 Unit Model: 40RUA
Unit Model: 38AUD Unit Size: 15 Tons
Unit Size: 15 Tons No. of Splits: 2
Voltage: 230-3-60 V-Ph-Hz Voltage: 230-3-60 V-Ph-Hz
Condenser Coil: Al/Cu
No. of DX Circuits: 2

System Parameter
System Quantity: 1
Refrigerant Type: PURON
Compressor Quantity: 2
Compressor Type: Scroll
Std. Capacity Steps: 50, 100
Std. Min. Outdoor Temp(Cooling): 35.0 F
No. of Outdoor fans: 3

Outdoor Unit Dimensions and Weight Indoor Unit Dimensions and Weight
Unit Length: 7' 2.4'' Unit Length: 7' 5.0''
Unit Width: 3' 7.4'' Unit Width: 2' 4.2''
Unit Height: 4' 2.4'' Unit Height: 4' 8.1''
Unit Shipping Weight: 731 lb Unit Shipping Weight: 713 lb
Unit Operating Weight: 731 lb Unit Operating Weight: 713 lb

Warranty Information (Note: for US & Canada only)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity


Base Unit - Outdoor

38AUDA16A0A5-0A0A0 1
Base Unit
Al/Cu Condensing Coil 1
Standard Refrigerant Options 1
Service Options - None 1
Electrical Options - None 1
Packaging Options - Standard 1
Standard Electrical Mechanical Controls 1
Single Stage 1
Base Unit - Indoor
40RUAA16A2A6-0A0A0 1
Base Unit
Std Static, Std Eff Motor/ Medium Drive 1
Cabinet Paint - None 1
Commercial Split Systems Builder 1.33 Page 59 of 91
Unit Report For SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

None- No Controller 1

Commercial Split Systems Builder 1.33 Page 60 of 91


Performance Summary For SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Performance Summary

System: 38AUD016/40RUA016
System Quantity: 1
Altitude: 5200.0 ft
EER @ ARI Conditions: 11.2
IEER: 11.8
Linear Pipe Length: 30.0 ft
Suction Line Size: 1 1/8 in
Liquid Line Size: 1/2 in
Suction Line Loss: 1.4 F
System meets ASHRAE 90.1 min EER requirement.

Outdoor Unit Parameters


Unit Quantity: 1
PartNumber: 38AUDA16A0A5-0A0A0
Unit Model: 38AUD
Unit Size: 15 Tons
Condenser Coil: Al/Cu
No. of DX Circuits: 2
Voltage: 230-3-60 V-Ph-Hz
Clg Ent Air DB: 95.0 F

Outdoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit#1 MCA: 60.8 Amps
Unit#1 MOCP: 80.0 Amps
Total Compressor Power of Unit #1: NA
Voltage Range Min: 187 V
Voltage Range Max: 253 V
Compressor RLA: 25
Compressor LRA: 164
Compressor Quantity: 2
Fan Motors Qty: 3
Notice: Outdoor unit elect. data is based on 230-3-60
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage

Indoor Unit Parameters


PartNumber: 40RUAA16A2A6-0A0A0
Unit Model: 40RUA
Unit Size: 15 Tons
Coil Rows: 4
No. of Splits: 2
Voltage: 230-3-60 V-Ph-Hz
Actual Airflow: 6000.0 CFM
Standard Airflow: 4955.0 CFM
Total Clg Cap.(Gross): 185.8 MBH
Sensible Clg Cap.(Gross): 122.4 MBH
Ent Air DB: 80.0 F
Ent Air WB: 67.0 F
Ent Enthalpy: 34.79 BTU/lb
Lvg Air DB: 57.1 F
Lvg Air WB: 56.7 F
Lvg Enthalpy: 26.45 BTU/lb
Coil Bypass Factor: NA

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Commercial Split Systems Builder 1.33 Page 61 of 91
Performance Summary For SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Fan Speed: 773 RPM


Fan Power: 2.01 BHP
Fan Motor Max: 3.70 BHP
Fan Motor FLA: 10.7 Amps
Motor and Medium Static Drive Required.
Selected Medium Static Drive Range: 742 - 943

Indoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit MCA: 14.0 Amps
Unit MOCP: 20.0 Amps
Notice: Indoor unit elect. data is based on 230-3-60

Acoustics
Sound Power Levels, db re 10E-12 Watts

Outdoor Unit (dB) Indoor Unit


(dB,Ducted)
A-Weighted Total Level 82.6 92.7
63Hz 86.7 98.9
125Hz 81.2 94.9
250Hz 78.9 90.9
500Hz 80.4 91.9
1000Hz 78.0 85.9
2000Hz 74.2 83.9
4000Hz 70.2 79.9
8000Hz 65.0 NA
Sound Message Sound for AUD016 Sound for RUA016

Acoustic Note:
1. 38AUZ and 38AUD sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment.
2. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
3. The acoustic center of the unit is located at the geometric center of the unit.
4. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal dist. from obstruction to receiver: 0.0 ft
6. Horizontal dist. from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall


Sound Power Levels at Unit's Acoustic Center (Lw), dB 86.7 81.2 78.9 80.4 78.0 74.2 70.2 65.0 89.5
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA 60.5 65.1 70.3 77.2 78.0 75.4 71.2 63.9 82.6
Sound Press. Levels at Dist. Specified above (Lp), dB 62.4 56.9 54.6 56.1 53.7 49.9 45.9 40.7 65.2
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 36.2 40.8 46.0 52.9 53.7 51.1 46.9 39.6 58.3

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
Commercial Split Systems Builder 1.33 Page 62 of 91
Performance Summary For SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

40RUA016withStandardCapacityCoil
3
1200RPM
1100RPM

1000RPM
Static Pressure (in. wg.)

2
900RPM

800RPM SC

700RPM

1
600RPM
PP
500RPM RP

400RPM
7.50BHP
3.70BHP 5.00BHP
2.40BHP
2.90BHP
3.00BHP
0
0 2 4 6 8 10 12 14
Airflow(CFM-thousands)
RPM=773 BHP=2.01 MaximumRPM=1200 MaximumHP=3.70
ShadedArea-RecommendedOperatingRange
SC-SystemCurve RP-RatedPoint MP-MinimumPoint PP-PsuedoPoint

Commercial Split Systems Builder 1.33 Page 63 of 91


Acoustic Summary For SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Acoustic Summary

Outdoor Unit Parameters:


Tag Name: SPLIT 15 TON
Unit Model: 38AUD
Unit Size: 15 Tons
System Type: Dx Cooling Only
Refrigerant Type: PURON
Compressor Quantity: 2
Compressor Type: Scroll

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal distance from obstruction to receiver: 0.0 ft
6. Horizontal distance from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall


Sound Power Levels at Unit's Acoustic Center (Lw), dB 86.7 81.2 78.9 80.4 78.0 74.2 70.2 65.0 89.5
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA 60.5 65.1 70.3 77.2 78.0 75.4 71.2 63.9 82.6
Sound Press. Levels at Dist. Specified above (Lp), dB 62.4 56.9 54.6 56.1 53.7 49.9 45.9 40.7 65.2
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 36.2 40.8 46.0 52.9 53.7 51.1 46.9 39.6 58.3

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

Acoustic Note:
1. 38ARZ, 38ARS and 38ARD012 sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment.
2. 38ARD014-024 and 38AKS data is estimated sound power levels. It is based upon a limited amount of actual testing with the
estimated sound power data being generated from this data in accordance with ARI Standard 370 for large outdoor refrigerating and
air-conditioning equipment.
3. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
4. The acoustic center of the unit is located at the geometric center of the unit.
5. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Indoor Unit Parameters:


Tag Name: SPLIT 15 TON
Unit Model: 40RUA
Unit Size: 15 Tons
System Type: Dx Cooling Only
External Static Pressure: 0.60 in wg
Fan Speed: 773 RPM
Fan BHP: 2.01 BHP

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total


Sound Power,dB NA 98.9 94.9 90.9 91.9 85.9 83.9 79.9 NA 101.6
Commercial Split Systems Builder 1.33 Page 64 of 91
Acoustic Summary For SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

A-Weighted Sound Power, dBA NA 72.7 78.8 82.3 88.7 85.9 85.1 80.9 NA 92.7

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Commercial Split Systems Builder 1.33 Page 65 of 91


Certified Drawing for SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Certified Drawing

Commercial Split Systems Builder 1.33 Page 66 of 91


Certified Drawing for SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Commercial Split Systems Builder 1.33 Page 67 of 91


Guide Specification for SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Guide Specifications

GUIDE SPECIFICATIONS 38AUDA16A0A5-0A0A0

Commercial Air-Cooled Condensing Units


HVAC Guide Specifications

Size: 16
Part 1: General
SYSTEM DESCRIPTION
1.01. Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall consist of a hermetic
scroll air-conditioning compressor(s) assembly, an air-cooled coil, propeller-type condenser fans, and a control box. Unit shall
discharge supply air upward as shown on contract drawings. Unit shall be used in a refrigeration circuit matched with a
packaged air-handling unit.
QUALITY ASSURANCE
1.01. Unit shall be rated in accordance with AHRI Standard 360.
1.02. Unit construction shall comply with ANSI/ASHRAE 15 safety code latest revision and comply with NEC.
1.03. Unit shall be constructed in accordance with UL 1995 standard and shall carry the UL and UL, Canada label.
1.04. Unit cabinet shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).
1.05. Air-cooled condenser coils for hermetic scroll compressor units (38AUZ) and 38AUD shall be leak tested at 150 psig, and
pressure tested at 650 psig.
1.06. Unit shall be manufactured in a facility registered to ISO 9001:2000 manufacturing quality standard.
DELIVERY, STORAGE, AND HANDLING
1.01. Unit shall be shipped as single package only, and shall be stored and handled according to unit manufacturers
recommendations.
WARRANTY (FOR INCLUSION BYSPECIFYING ENGINEER.)
Part 2: Products
EQUIPMENT
2.01. General:
A. Factory-assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring,
piping, controls, compressor, holding charge, and special features required prior to field start-up.
2.02. Unit Cabinet:
A. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a prepainted baked enamel finish.
B. A heavy-gauge roll-formed perimeter base rail with forklift slots and lifting holes shall be provided to facilitate rigging.
2.03. CondenserFans:
A. Condenser fans shall be direct driven, propeller type, discharging air vertically upward.
B. Fan blades shall be balanced.
C. Condenser fan discharge openings shall be equipped with PVC-coated steel wire safety guards.
D. Condenser fan and motor shaft shall be corrosion resistant.
2.04. Compressor:
A. Compressor shall be of the hermetic scroll type .
Commercial Split Systems Builder 1.33 Page 68 of 91
Guide Specification for SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

B. Compressor shall be mounted on rubber grommets.


C. Compressors shall include overload protection.
D. Compressors shall be equipped with a crankcase heater.
E. Compressor shall be equipped with internal high pressure and high temperature protection.
F. 38AUZ*16 and 25 sizes shall use two scroll compressors manifold together.
2.05. Condenser Coils:
A. Standard Aluminum fin - Copper Tube Coils:
1. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seamless
internally grooved copper tubes with all joints brazed.
2. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at
1775 psig.
3. Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at
1980 psig.
2.06. Refrigeration Components:
A. Refrigeration circuit components shall include liquid line service valve, suction line service valve, a full charge of
compressor oil, and a partial holding charge of refrigerant.
2.07. Controls and Safeties:
A. Minimum control functions shall include:
1. Control wire terminal blocks.
2. Compressor lockout on auto-reset safety until reset from thermostat.
3. Each unit shall utilize the Comfort Alertt Diagnostic Board that provides:
a. System Pressure Trip fault code indication
b. Short Cycling fault code indication
c. Locked Rotor fault code indication
d. Open Circuit fault code indication
e. Reverse Phase 3 fault code indication
f. Welded Contactor fault code indication
g. Low Voltage fault code indication
h. Anti-short cycle protection
i. Phase reversal protection
B. Minimum safety devices which are equipped with automatic reset (after resetting first at thermostat), shall include:
1. High discharge pressure cutout.
2. Low pressure cutout.
2.08. Operating Characteristics:
A. The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of ______F. The power
consumption at full load shall not exceed _____ kW.
B. The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____
Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at ______F wet bulb and ______F dry
bulb, and air entering the condensing unit at ______F.
C. The system shall have an EER of _____ Btuh/Watt or greater at standard AHRI conditions.
D. Standard unit shall be capable to operate up to 125_F (52_C) and down to 40_F (4_C)
2.09. Electrical Requirements:
A. Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation
within voltage limits of ____ v to _____ v.
B. Unit electrical power shall be single-point connection.
C. Unit control circuit shall contain a 24-v transformer for unit control.
2.10. Special Features:
A. Thermostat Controls:
Commercial Split Systems Builder 1.33 Page 69 of 91
Guide Specification for SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

1. Programmable multi-stage thermostat shall have 7-day clock, holiday scheduling, large backlit display, remote sensor
capability, and Title 24 compliance.
2. Commercial Electronic Thermostat shall have 7-day time clock, auto-changeover, multi-stage capability, and large
LCD (liquid crystal display) temperature display.

GUIDE SPECIFICATIONS 40RUAA16A2A6-0A0A0

Commercial Packaged Air-Handling Unit


HVAC Guide Specifications

Size: 16
Part 1: GENERAL
SYSTEM DESCRIPTION
1.01. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be
capable of horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be
applied without ductwork.)
1.02. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with
chilled water coil shall be used in a chilled water circuit.
QUALITY ASSURANCE
1.01. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest
edition.
1.02. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL,
Canada, labels.
1.03. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation.
Insulation shall contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi
as proven by tests in accordance with ASTM standards G21 and 22 (U.S.A.).
1.04. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
1.05. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
DELIVERY AND STORAGE
1.01. Units shall be stored and handled per manufacturers recommendations.
Part 2: Products
EQUIPMENT
2.01. Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical
configuration. Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan
motor contactor, factory-installed refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm)
disposable air filters, and condensate drain pans for vertical or horizontal configurations.
2.02. Base Unit:
A. Cabinet shall be constructed of mill-galvanized steel.
B. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-
registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in

Commercial Split Systems Builder 1.33 Page 70 of 91


Guide Specification for SPLIT 15 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

accordance with ASTM standards G21 and 22 (U.S.A.).


C. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have
connections on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward
the right or left side of the unit to prevent standing water from accumulating in pans.
D. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access
shall be from either the right or left side of the unit.
2.03. Coils:
A. DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion.
Suction and liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The
TXVs shall be Puron R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall
have a factory-installed bypass line and check valve assembly around the TXVs to allow liquid flow from the coil to
the outdoor unit during the heating mode. Coil tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
2.04. Operating Characteristics:
A. Unit shall be capable of providing ____ cfm (L/s) airflow at an external static pressure of ____ in. wg (kPag).
2.05. Motor:
A. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and
installed.
B. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at
5 hp (3.73 kW) shall be protected by a circuit breaker.
C. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload
protection or manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not
have conventional horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the air-
over location downstream of the cooling coil and carry a maximum continuous bhp rating that is the maximum application
bhp rating for the motor; no safety factors above that rating may be applied.
D. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy
Policy Act of 1992 (EPACT), effective October 24, 1997.
2.06. Special Features:
A. Alternate Motor and Drive:
1. An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static
pressure requirements specified on the equipment schedule.
B. Thermostat Controls:
1. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, F/C
capability, and CCN (Carrier Comfort Network) compatibility.
2. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD
temperature display.

Commercial Split Systems Builder 1.33 Page 71 of 91


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


38AUZ 6 TO 20 TON
38AUD 10 and 20 Ton
AIR-COOLED CONDENSING UNITS with PURON REFRIGERANT
These commercial quality air-cooled condensing units are easily connected by refrigerant lines and low voltage
control wiring to matching Carrier packaged air-handling units or other suitable evaporator units. They are ideal for
new construction or renovation applications where quality and performance are required.

BASE UNIT STANDARD FEATURES:



Puron (R-410A) HFC refrigerant partial charge

Single-stage cooling capacity control on 07 to 14
models

All models utilize aluminum Novation Heat
Exchanger Technology Condenser Coils

Standard one-year unit warranty, 5-year compressor
plan and 3-year parts plan on Novation coil

Cooling operating range up to 125 F (52 C) and
down to 35 F (2 C)

Brass suction and liquid line service valves

Fully Hermetic Scroll compressor with crankcase
heater

New terminal board facilitating simple safety circuit
troubleshooting and simplified control box
arrangement. 24-volt 75va control system

High and low pressure switches.

Comfort Alert Diagnostic Board:

LED Go-No-Go and fault code
Built in time guard anti-short cycle
Certified to ISO 9001:2000

Phase protection


Fault code retention logic

Low voltage compressor contactor protector

UL and UL, Canada apply to standard units; 575-volt
units UL, Canada only.

Full perimeter base rails with built-in rigging adapters
and fork truck slots

Pre-painted exterior panels and primer-coated
interior panels tested to 500 hours salt spray
protection

Direct drive permanently lubricated condenser fan
motors

All units factory run tested

Compressors mounted on independent vibration
isolators

Commercial Split Systems Builder 1.33 Page 72 of 91


COMMERCIAL SPLIT SYSTEMS
40RUA DIRECT EXPANSION
PACKAGED AIR-HANDLING UNITS with PURON REFRIGERANT

40RUA 6 TO 30 TON CHASSIS SHOWN

STANDARD FEATURES FOR PURON (R-410A) HFC Refrigerant


1. Cleanable insulation treated with an anti-microbial agent.
2. Two sloped condensate pans on each unit for horizontal or vertical applications.
3. 2 inch filters.
4. Powerful belt-driven forward curved fans.
5. Factory-installed fan motor and contactor.
6. Refrigerant metering devices (TXV's) -- factory installed.
7. Easy maintenance -- removal of a single panel allows access to virtually all components.
8. Single blower on 07 to 12 sizes; dual blower on 14 to 30 sizes.
9. 24-volt terminal block for control wiring connection.
10. Standard one year warranty.

40RUA DIRECT EXPANSION


PACKAGED AIR-HANDLING UNITS
The 40RUA units are completely packaged direct expansion air-handling units offering the ultimate in installation ease and
flexibility. Combined with Carrier 38AU Series condensing units these packaged air handling units offer system capacities from 6 up
to 30 tons. These units may be installed in either the vertical or horizontal configuration with no modifications. Powerful fan systems
allow easy adaptation to existing ductwork. Heating capability is provided by electric heaters, hot water coils or steam coils.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.33 Page 73 of 91


Commercial Split Systems Builder 1.33 Page 74 of 91
SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

SPLIT 20 TON

SPLIT 20 TON

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Feature Sheet

Commercial Split Systems Builder 1.33 Page 75 of 91


Unit Report For SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Unit Report

Outdoor Unit Parameters Indoor Unit Parameters


Unit Quantity: 1 Unit Model: 40RUA
Unit Model: 38AUD Unit Size: 20 Tons
Unit Size: 20 Tons No. of Splits: 2
Voltage: 230-3-60 V-Ph-Hz Voltage: 230-3-60 V-Ph-Hz
Condenser Coil: Al/Cu
No. of DX Circuits: 2

System Parameter
System Quantity: 1
Refrigerant Type: PURON
Compressor Quantity: 2
Compressor Type: Scroll
Std. Capacity Steps: 50, 100
Std. Min. Outdoor Temp(Cooling): 35.0 F
No. of Outdoor fans: 3

Outdoor Unit Dimensions and Weight Indoor Unit Dimensions and Weight
Unit Length: 7' 2.1'' Unit Length: 7' 5.0''
Unit Width: 5' 7.1'' Unit Width: 2' 4.2''
Unit Height: 4' 2.4'' Unit Height: 4' 8.1''
Unit Shipping Weight: 978 lb Unit Shipping Weight: 730 lb
Unit Operating Weight: 978 lb Unit Operating Weight: 730 lb

Warranty Information (Note: for US & Canada only)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity


Base Unit - Outdoor

38AUDA25A0A5-0A0A0 1
Base Unit
Al/Cu Condensing Coil 1
Standard Refrigerant Options 1
Service Options - None 1
Electrical Options - None 1
Packaging Options - Standard 1
Standard Electrical Mechanical Controls 1
Single Stage 1
Base Unit - Indoor
40RUAA25A5A5-0A0A0 1
Base Unit
Std Static, High Eff Motor/ Medium Drive 1
Cabinet Paint - None 1
Commercial Split Systems Builder 1.33 Page 76 of 91
Unit Report For SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

None- No Controller 1

Commercial Split Systems Builder 1.33 Page 77 of 91


Performance Summary For SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Performance Summary

System: 38AUD025/40RUA025
System Quantity: 1
Altitude: 5200.0 ft
EER @ ARI Conditions: 11.0
IEER: 11.2
Linear Pipe Length: 30.0 ft
Suction Line Size: 1 1/8 in
Liquid Line Size: 1/2 in
Suction Line Loss: 1.4 F
Condensing unit is rated in accordance with ARI 365.

Outdoor Unit Parameters


Unit Quantity: 1
PartNumber: 38AUDA25A0A5-0A0A0
Unit Model: 38AUD
Unit Size: 20 Tons
Condenser Coil: Al/Cu
No. of DX Circuits: 2
Voltage: 230-3-60 V-Ph-Hz
Clg Ent Air DB: 95.0 F

Outdoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit#1 MCA: 73.7 Amps
Unit#1 MOCP: 100.0 Amps
Total Compressor Power of Unit #1: NA
Voltage Range Min: 187 V
Voltage Range Max: 253 V
Compressor RLA: 30.1
Compressor LRA: 225
Compressor Quantity: 2
Fan Motors Qty: 3
Notice: Outdoor unit elect. data is based on 230-3-60
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage

Indoor Unit Parameters


PartNumber: 40RUAA25A5A5-0A0A0
Unit Model: 40RUA
Unit Size: 20 Tons
Coil Rows: 4
No. of Splits: 2
Voltage: 230-3-60 V-Ph-Hz
Actual Airflow: 8000.0 CFM
Standard Airflow: 6606.7 CFM
Total Clg Cap.(Gross): 240.1 MBH
Sensible Clg Cap.(Gross): 162.3 MBH
Ent Air DB: 80.0 F
Ent Air WB: 67.0 F
Ent Enthalpy: 34.79 BTU/lb
Lvg Air DB: 57.3 F
Lvg Air WB: 57.0 F
Lvg Enthalpy: 26.71 BTU/lb
Coil Bypass Factor: NA

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Commercial Split Systems Builder 1.33 Page 78 of 91
Performance Summary For SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Fan Speed: 866 RPM


Fan Power: 3.41 BHP
Fan Motor Max: 5.00 BHP
Fan Motor FLA: 18.0 Amps
Motor and Medium Static Drive Required.
Selected Medium Static Drive Range: 798 - 984

Indoor Electrical Data


Unit Voltage: 230-3-60 V-Ph-Hz
Unit MCA: 23.0 Amps
Unit MOCP: 40.0 Amps
Notice: Indoor unit elect. data is based on 230-3-60

Acoustics
Sound Power Levels, db re 10E-12 Watts

Outdoor Unit (dB) Indoor Unit


(dB,Ducted)
A-Weighted Total Level 85.2 96.4
63Hz 91.0 102.6
125Hz 85.0 98.6
250Hz 80.0 94.6
500Hz 86.0 95.6
1000Hz 79.0 89.6
2000Hz 73.0 87.6
4000Hz 68.0 83.6
8000Hz 63.0 NA
Sound Message Sound for AUD025 Sound for RUA025

Acoustic Note:
1. 38AUZ and 38AUD sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment.
2. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
3. The acoustic center of the unit is located at the geometric center of the unit.
4. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal dist. from obstruction to receiver: 0.0 ft
6. Horizontal dist. from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall


Sound Power Levels at Unit's Acoustic Center (Lw), dB 91.0 85.0 80.0 86.0 79.0 73.0 68.0 63.0 93.4
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA 64.8 68.9 71.4 82.8 79.0 74.2 69.0 61.9 85.2
Sound Press. Levels at Dist. Specified above (Lp), dB 66.3 60.3 55.3 61.3 54.3 48.3 43.3 38.3 68.7
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 40.1 44.2 46.7 58.1 54.3 49.5 44.3 37.2 60.5

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
Commercial Split Systems Builder 1.33 Page 79 of 91
Performance Summary For SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

40RUA025withStandardCapacityCoil
4

1200RPM

3
1100RPM
Static Pressure (in. wg.)

1000RPM

SC
2 900RPM

800RPM

700RPM

1
600RPM
PP
500RPM RP 10.00BHP
7.50BHP
400RPM 5.00BHP
3.70BHP

0
0 2 4 6 8 10 12 14
Airflow(CFM-thousands)
RPM=866 BHP=3.41 MaximumRPM=1200 MaximumHP=5.00
ShadedArea-RecommendedOperatingRange
SC-SystemCurve RP-RatedPoint MP-MinimumPoint PP-PsuedoPoint

Commercial Split Systems Builder 1.33 Page 80 of 91


Acoustic Summary For SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Acoustic Summary

Outdoor Unit Parameters:


Tag Name: SPLIT 20 TON
Unit Model: 38AUD
Unit Size: 20 Tons
System Type: Dx Cooling Only
Refrigerant Type: PURON
Compressor Quantity: 2
Compressor Type: Scroll

Advanced Accoustics Parameters


1. Unit height above ground: 1.0 ft
2. Horizontal distance from unit to receiver: 20.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal distance from obstruction to receiver: 0.0 ft
6. Horizontal distance from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall


Sound Power Levels at Unit's Acoustic Center (Lw), dB 91.0 85.0 80.0 86.0 79.0 73.0 68.0 63.0 93.4
A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA 64.8 68.9 71.4 82.8 79.0 74.2 69.0 61.9 85.2
Sound Press. Levels at Dist. Specified above (Lp), dB 66.3 60.3 55.3 61.3 54.3 48.3 43.3 38.3 68.7
A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA 40.1 44.2 46.7 58.1 54.3 49.5 44.3 37.2 60.5

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.

Acoustic Note:
1. 38ARZ, 38ARS and 38ARD012 sound power data is tested in accordance with ARI270-95 Sound Rating of Unitary Equipment.
2. 38ARD014-024 and 38AKS data is estimated sound power levels. It is based upon a limited amount of actual testing with the
estimated sound power data being generated from this data in accordance with ARI Standard 370 for large outdoor refrigerating and
air-conditioning equipment.
3. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
4. The acoustic center of the unit is located at the geometric center of the unit.
5. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Indoor Unit Parameters:


Tag Name: SPLIT 20 TON
Unit Model: 40RUA
Unit Size: 20 Tons
System Type: Dx Cooling Only
External Static Pressure: 0.60 in wg
Fan Speed: 866 RPM
Fan BHP: 3.41 BHP

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total


Sound Power,dB NA 102.6 98.6 94.6 95.6 89.6 87.6 83.6 NA 105.3
Commercial Split Systems Builder 1.33 Page 81 of 91
Acoustic Summary For SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

A-Weighted Sound Power, dBA NA 76.4 82.5 86.0 92.4 89.6 88.8 84.6 NA 96.4

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Commercial Split Systems Builder 1.33 Page 82 of 91


Certified Drawing for SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Certified Drawing

Commercial Split Systems Builder 1.33 Page 83 of 91


Certified Drawing for SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Commercial Split Systems Builder 1.33 Page 84 of 91


Guide Specification for SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

Guide Specifications

GUIDE SPECIFICATIONS 38AUDA25A0A5-0A0A0

Commercial Air-Cooled Condensing Units


HVAC Guide Specifications

Size: 25
Part 1: General
SYSTEM DESCRIPTION
1.01. Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall consist of a hermetic
scroll air-conditioning compressor(s) assembly, an air-cooled coil, propeller-type condenser fans, and a control box. Unit shall
discharge supply air upward as shown on contract drawings. Unit shall be used in a refrigeration circuit matched with a
packaged air-handling unit.
QUALITY ASSURANCE
1.01. Unit shall be rated in accordance with AHRI Standard 360.
1.02. Unit construction shall comply with ANSI/ASHRAE 15 safety code latest revision and comply with NEC.
1.03. Unit shall be constructed in accordance with UL 1995 standard and shall carry the UL and UL, Canada label.
1.04. Unit cabinet shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).
1.05. Air-cooled condenser coils for hermetic scroll compressor units (38AUZ) and 38AUD shall be leak tested at 150 psig, and
pressure tested at 650 psig.
1.06. Unit shall be manufactured in a facility registered to ISO 9001:2000 manufacturing quality standard.
DELIVERY, STORAGE, AND HANDLING
1.01. Unit shall be shipped as single package only, and shall be stored and handled according to unit manufacturers
recommendations.
WARRANTY (FOR INCLUSION BYSPECIFYING ENGINEER.)
Part 2: Products
EQUIPMENT
2.01. General:
A. Factory-assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring,
piping, controls, compressor, holding charge, and special features required prior to field start-up.
2.02. Unit Cabinet:
A. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a prepainted baked enamel finish.
B. A heavy-gauge roll-formed perimeter base rail with forklift slots and lifting holes shall be provided to facilitate rigging.
2.03. CondenserFans:
A. Condenser fans shall be direct driven, propeller type, discharging air vertically upward.
B. Fan blades shall be balanced.
C. Condenser fan discharge openings shall be equipped with PVC-coated steel wire safety guards.
D. Condenser fan and motor shaft shall be corrosion resistant.
2.04. Compressor:
A. Compressor shall be of the hermetic scroll type .
Commercial Split Systems Builder 1.33 Page 85 of 91
Guide Specification for SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

B. Compressor shall be mounted on rubber grommets.


C. Compressors shall include overload protection.
D. Compressors shall be equipped with a crankcase heater.
E. Compressor shall be equipped with internal high pressure and high temperature protection.
F. 38AUZ*16 and 25 sizes shall use two scroll compressors manifold together.
2.05. Condenser Coils:
A. Standard Aluminum fin - Copper Tube Coils:
1. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seamless
internally grooved copper tubes with all joints brazed.
2. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at
1775 psig.
3. Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at
1980 psig.
2.06. Refrigeration Components:
A. Refrigeration circuit components shall include liquid line service valve, suction line service valve, a full charge of
compressor oil, and a partial holding charge of refrigerant.
2.07. Controls and Safeties:
A. Minimum control functions shall include:
1. Control wire terminal blocks.
2. Compressor lockout on auto-reset safety until reset from thermostat.
3. Each unit shall utilize the Comfort Alertt Diagnostic Board that provides:
a. System Pressure Trip fault code indication
b. Short Cycling fault code indication
c. Locked Rotor fault code indication
d. Open Circuit fault code indication
e. Reverse Phase 3 fault code indication
f. Welded Contactor fault code indication
g. Low Voltage fault code indication
h. Anti-short cycle protection
i. Phase reversal protection
B. Minimum safety devices which are equipped with automatic reset (after resetting first at thermostat), shall include:
1. High discharge pressure cutout.
2. Low pressure cutout.
2.08. Operating Characteristics:
A. The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of ______F. The power
consumption at full load shall not exceed _____ kW.
B. The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____
Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at ______F wet bulb and ______F dry
bulb, and air entering the condensing unit at ______F.
C. The system shall have an EER of _____ Btuh/Watt or greater at standard AHRI conditions.
D. Standard unit shall be capable to operate up to 125_F (52_C) and down to 40_F (4_C)
2.09. Electrical Requirements:
A. Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation
within voltage limits of ____ v to _____ v.
B. Unit electrical power shall be single-point connection.
C. Unit control circuit shall contain a 24-v transformer for unit control.
2.10. Special Features:
A. Thermostat Controls:
Commercial Split Systems Builder 1.33 Page 86 of 91
Guide Specification for SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

1. Programmable multi-stage thermostat shall have 7-day clock, holiday scheduling, large backlit display, remote sensor
capability, and Title 24 compliance.
2. Commercial Electronic Thermostat shall have 7-day time clock, auto-changeover, multi-stage capability, and large
LCD (liquid crystal display) temperature display.

GUIDE SPECIFICATIONS 40RUAA25A5A5-0A0A0

Commercial Packaged Air-Handling Unit


HVAC Guide Specifications

Size: 25
Part 1: GENERAL
SYSTEM DESCRIPTION
1.01. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be
capable of horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be
applied without ductwork.)
1.02. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with
chilled water coil shall be used in a chilled water circuit.
QUALITY ASSURANCE
1.01. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest
edition.
1.02. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL,
Canada, labels.
1.03. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation.
Insulation shall contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi
as proven by tests in accordance with ASTM standards G21 and 22 (U.S.A.).
1.04. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
1.05. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
DELIVERY AND STORAGE
1.01. Units shall be stored and handled per manufacturers recommendations.
Part 2: Products
EQUIPMENT
2.01. Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical
configuration. Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan
motor contactor, factory-installed refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm)
disposable air filters, and condensate drain pans for vertical or horizontal configurations.
2.02. Base Unit:
A. Cabinet shall be constructed of mill-galvanized steel.
B. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-
registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in

Commercial Split Systems Builder 1.33 Page 87 of 91


Guide Specification for SPLIT 20 TON
Project: NORDES 2015 06/04/2015
Prepared By: 12:11p.m.

accordance with ASTM standards G21 and 22 (U.S.A.).


C. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have
connections on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward
the right or left side of the unit to prevent standing water from accumulating in pans.
D. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access
shall be from either the right or left side of the unit.
2.03. Coils:
A. DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion.
Suction and liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The
TXVs shall be Puron R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall
have a factory-installed bypass line and check valve assembly around the TXVs to allow liquid flow from the coil to
the outdoor unit during the heating mode. Coil tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
2.04. Operating Characteristics:
A. Unit shall be capable of providing ____ cfm (L/s) airflow at an external static pressure of ____ in. wg (kPag).
2.05. Motor:
A. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and
installed.
B. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at
5 hp (3.73 kW) shall be protected by a circuit breaker.
C. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload
protection or manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not
have conventional horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the air-
over location downstream of the cooling coil and carry a maximum continuous bhp rating that is the maximum application
bhp rating for the motor; no safety factors above that rating may be applied.
D. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy
Policy Act of 1992 (EPACT), effective October 24, 1997.
2.06. Special Features:
A. Alternate Motor and Drive:
1. An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static
pressure requirements specified on the equipment schedule.
B. Thermostat Controls:
1. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, F/C
capability, and CCN (Carrier Comfort Network) compatibility.
2. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD
temperature display.

Commercial Split Systems Builder 1.33 Page 88 of 91


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


38AUZ 6 TO 20 TON
38AUD 10 and 20 Ton
AIR-COOLED CONDENSING UNITS with PURON REFRIGERANT
These commercial quality air-cooled condensing units are easily connected by refrigerant lines and low voltage
control wiring to matching Carrier packaged air-handling units or other suitable evaporator units. They are ideal for
new construction or renovation applications where quality and performance are required.

BASE UNIT STANDARD FEATURES:



Puron (R-410A) HFC refrigerant partial charge

Single-stage cooling capacity control on 07 to 14
models

All models utilize aluminum Novation Heat
Exchanger Technology Condenser Coils

Standard one-year unit warranty, 5-year compressor
plan and 3-year parts plan on Novation coil

Cooling operating range up to 125 F (52 C) and
down to 35 F (2 C)

Brass suction and liquid line service valves

Fully Hermetic Scroll compressor with crankcase
heater

New terminal board facilitating simple safety circuit
troubleshooting and simplified control box
arrangement. 24-volt 75va control system

High and low pressure switches.

Comfort Alert Diagnostic Board:

LED Go-No-Go and fault code
Built in time guard anti-short cycle
Certified to ISO 9001:2000

Phase protection


Fault code retention logic

Low voltage compressor contactor protector

UL and UL, Canada apply to standard units; 575-volt
units UL, Canada only.

Full perimeter base rails with built-in rigging adapters
and fork truck slots

Pre-painted exterior panels and primer-coated
interior panels tested to 500 hours salt spray
protection

Direct drive permanently lubricated condenser fan
motors

All units factory run tested

Compressors mounted on independent vibration
isolators

Commercial Split Systems Builder 1.33 Page 89 of 91


COMMERCIAL SPLIT SYSTEMS
40RUA DIRECT EXPANSION
PACKAGED AIR-HANDLING UNITS with PURON REFRIGERANT

40RUA 6 TO 30 TON CHASSIS SHOWN

STANDARD FEATURES FOR PURON (R-410A) HFC Refrigerant


1. Cleanable insulation treated with an anti-microbial agent.
2. Two sloped condensate pans on each unit for horizontal or vertical applications.
3. 2 inch filters.
4. Powerful belt-driven forward curved fans.
5. Factory-installed fan motor and contactor.
6. Refrigerant metering devices (TXV's) -- factory installed.
7. Easy maintenance -- removal of a single panel allows access to virtually all components.
8. Single blower on 07 to 12 sizes; dual blower on 14 to 30 sizes.
9. 24-volt terminal block for control wiring connection.
10. Standard one year warranty.

40RUA DIRECT EXPANSION


PACKAGED AIR-HANDLING UNITS
The 40RUA units are completely packaged direct expansion air-handling units offering the ultimate in installation ease and
flexibility. Combined with Carrier 38AU Series condensing units these packaged air handling units offer system capacities from 6 up
to 30 tons. These units may be installed in either the vertical or horizontal configuration with no modifications. Powerful fan systems
allow easy adaptation to existing ductwork. Heating capability is provided by electric heaters, hot water coils or steam coils.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.33 Page 90 of 91