2x300 MW, CTPP CT/PT Application Check

Data Symbol Unit Value Remarks Reference


CT Core dimensioning for protection Relay 7SJ80

CT / Core Number 407CTA CORE - 4,


407CTB CORE -1 &
4,
408CTA CORE -1 &
4,
409CTA CORE -4
AND
CT location GT # 3 BAY, Reactor
Bay
& Tie Bay
Purpose TEED/ 67 & 67N
Protection Class IEC class PS C
Fault current Iscc(extn. Fault) A = 50000
CT primary current Ipn A = 2000 Adopted ratio
CT secondary Isn A 1
current
CT secondary Rct ohm 5 CTP-21-ED-E-DS-
resistance BAT-001
Cable used sq.mm 4
Specific resistivity of Cu mm2/ 0.0217
Cu at 75 Deg C m
Length of lead Mtrs 250 Assumed
Lead resistance AC (2 RL = 2.71 (Kwire.Cu.Iwire )/(Awire
way) ) where as kwire=2

Connected resistive R'b = 2.76 Relay Burden = 0.05 SIEMENS


burden= RL+Rrelay SIPROTEC Book
Knee point voltage Vk V = 149.30 Vk > (Iscc(extn fault) x SIEMENS
required C (Rct + R'b) x SIPROTEC Book
Isn/(1.3*Ipn)
CT Knee Point Vk V 800 CTP-21-ED-E-DS-
Voltage selected BAT-001
Magnetizing current Imag 30mA CTP-21-ED-E-DS-
@Vk/2 BAT-001

Knee point voltage V = 80.98 Rct Values taken from


required@1000/1A manufacturer
ratio of CT datasheet. Knee point
voltage, Imag values
given in data sheet.

1 of 1