SCHEDULE OF TECHNICAL DATA

(WAPDA/NTDC SPECIFICATION P-46:2008)

1) Manufacturers name and TBEA Hengyang Transformer Co., Ltd.


Type designation SFZ-50000/132
2) Type test certificates: KEMA SZ11-40000/110
a) Issuing Laboratory KEMA,SVET, CTQC
b) No. and Date 70450001-TDT 04-42590A
3) Vector group YNd11
4) Rated power of the transformer
(Temperature-rise measured by resistance)
a) With 55C temperature-rise of winding
i) ONAN cooling kVA 31500
ii) ONAF1/ONAF2 cooling kVA 40000/50000
b) With 60C temperature-rise of winding
i) ONAN cooling kVA 32500
ii) ONAF1/ONAF2 cooling kVA 41200/51500
c) With 65C temperature-rise of winding
i) ONAN cooling kVA 33400
ii) ONAF1/ONAF2 cooling kVA 42400/53000
5) Temperature-rise of oil corresponding to the
kVA and temperature-rise values given in:
a) i) Item 4a(1) degC _45_
ii) Item 4a(2) degC _45_
b) i) Item 4b(1) degC _50_
ii) Item 4b(2) degC _50_
c) i) Item 4c(1) degC _55_
ii) Item 4c(2) degC _55_
6) Hottest spot winding temperature-rise
corresponding to kVA and temperature-rise
ratings given in:
a) i) Item 4a(1) degC _68_
ii) Item 4a(2) degC _68_
b) i) Item 4b(1) degC _73_
ii) Item 4b(2) degC _73_
c) i) Item 4c(1) degC _78_
ii) Item 4c(2) degC _78_
7) Tertiary winding rating, corresponding to
55C temperature-rise of winding
(measured by resistance) where applicable
a) ONAN cooling kVA _N/A_
b) ONAF cooling kVA _N/A_
8) Rated voltage of windings
a) HV winding kV _132_
1 / 11
b) LV winding kV _33_
c) Tertiary winding (if applicable) kV _N/A_
9) Tapping voltages at all
plus and minus tappings Volts (Please attach table)
Tapping Voltage, V
1 145200 Highest voltage
2 143550
3 141900
4 140250
5 138600
6 136950
7 135300
8 133650
9 132000 Rated voltage
10 130350
11 128700
12 127050
13 125400
14 123750
15 122100
16 120450
17 118800

10) Highest operating voltage for which tappings


are designed for continuous overvoltage
operation, percent of tapping voltage. Percent 110%
11) Overvoltage Operation
Operating time Permissible
Max. Temp.
Applied for rated current for Temp. Rise
flux Rise of
HVTapping voltage tapping continuous of windings
density core
kV current, operation C
Tesla C
Hrs A
1 145.2 Continuous 198.8 1.87 78 65
12) Max. flux density and operating conditions
at which occurs: Tesla Approx. _1.87_
Frequency Hz 50
Voltage, HV V 145200
Voltage, LV V 33000
Load Current A 198.8

13) Design flux density at rated voltage,


rated current and frequency Tesla 1.7

14) Impedance voltage (principal tap) on 50 MVA base:


2 / 11
a) High voltage-low voltage Percent 10.5
b) Low voltage-tertiary Percent N/A
c) High voltage-tertiary Percent N/A

15) Resistance voltage (principal tap) on_50_ MVA base:


a) High voltage-low voltage Percent 0.37
b) Low voltage-tertiary Percent N/A
c) High voltage-tertiary Percent N/A

16) Reactance voltage (principal tap) on _50_ MVA base:


a) High voltage-low voltage Percent 10.4
b) Low voltage-tertiary Percent N/A
c) High voltage-tertiary Percent N/A

17) Short-circuit impedance referred to the


1st winding in the following pairs:
a. At principal tap
i) High voltage-low voltage Ohm per 36
phase
ii) Low voltage-tertiary Ohm per N/A
phase
iii) High voltage-tertiary Ohm per N/A
phase
b. At extreme plus tap
i) High voltage-low voltage Ohm per 45
phase
ii) Low voltage-tertiary Ohm per N/A
phase
iii) High voltage-tertiary Ohm per N/A
phase
c. At extreme minus tap
i) High voltage-low voltage Ohm per 29
phase
ii) Low voltage-tertiary Ohm per N/A
phase
iii) High voltage-tertiary Ohm per N/A
phase
18) Zero sequence impedance (principal tap) on _50_ MVA base:
a) High voltage-low voltage Percent 8.9
b) Low voltage-tertiary Percent N/A
c) High voltage-tertiary Percent N/A
19) Regulation (principal tap) on _50_ MVA base:
a) 100% power factor Percent 0.92
b) 80% power factor Percent N/A
c) 70% power factor Percent N/A
3 / 11
20) Exciting current on _50_ MVA base:
a) 90% voltage Percent 0.23
b) 100% voltage Percent 0.4
c) 105% voltage Percent 0.77
d) 110% voltage Percent 2.76
e) 120% voltage Percent 15
21) Impulse test voltage
a) HV winding kV Peak 650
b) LV winding kV Peak 220
c) Tertiary winding kV Peak N/A
22) Separate source power frequency test voltage
a) HV winding kV rms 275
b) LV winding kV rms 85
c) Tertiary winding kV rms N/A
23) Induced overvoltage withstand test kV rms 275
24) Short-circuit characteristics at rated voltage
a) Max. asymmetrical short-circuit current for which the
mechanical bracings are designed and constructed to
withstand without damage frequent short-circuit faults
i) HV winding kA Peak 5.2
ii) LV winding kA Peak 20.8
iii) Tertiary winding kA Peak N/A
b) Max. symmetrical short-circuit current for
which transformer windings are designed and
constructed to thermally withstand without injury
i) HV winding
1 Sec kA 2.94
2 Sec kA 2.08
3 Sec kA 2.18
4 Sec kA 1.47
5 Sec kA 1.31
ii) LV winding
1 Sec kA 11.7
2 Sec kA 8.33
3 Sec kA 8.74
4 Sec kA 5.89
5 Sec kA 5.26
iii) Tertiary winding
1 Sec A N/A
2 Sec A N/A
3 Sec A N/A
4 Sec A N/A
5 Sec A N/A
c) Short circuit duration (Sec) 3
25) Guaranteed no-load losses at rated frequency
4 / 11
i) 100% voltage kW 32
ii) 105% voltage kW 39
iii) 110% voltage kW 49
iv) 120% voltage kW 88
26) Guaranteed load losses for reference
temperature of 75C including corresponding
consumption of fan motors
a) At principal tap
i) 100% ONAN rating kW 74
ii) 75% ONAN rating kW 42
iii) 50% ONAN rating kW 19
iv) 100% ONAF rating kW 185
v) 75% ONAF rating kW 104
vi) 50% ONAF rating kW 46
b) At extreme plus tap
i) 100% ONAN rating kW 72
ii) 75% ONAN rating kW 40
iii) 50% ONAN rating kW 18
iv) 100% ONAF rating kW 180
v) 75% ONAF rating kW 101
vi) 50% ONAF rating kW 45
c) At extreme minus tap
i) 100% ONAN rating kW 88
ii) 75% ONAN rating kW 49
iii) 50% ONAN rating kW 22
iv) 100% ONAF rating kW 220
v) 75% ONAF rating kW 124
vi) 50% ONAF rating kW 55

27) Tolerance applicable for


a) Guaranteed no-load losses
at 100% voltage Percent +0
b) Guaranteed load losses at 100%
ONAF rating at principal tap Percent +0
28) High voltage bushings
a) Rating
i) Voltage kV 145
ii) Current A 1250
iii) Impulse withstand voltage kV peak 650
iv) Power frequency withstand voltage kV rms 275
b) Type GOB.650-1250
c) Manufacturer ABB
d) Catalogue number (catalogue
to be attached with bid) N/A
e) Creepage distance mm 4495
5 / 11
29) Low voltage bushings
a) Rating
i) Voltage kV 40.5
ii) Current A 2000
iii) Impulse withstand voltage kV peak 220
iv) Power frequencywithstand voltage kV rms 95
b) Type B-40.5/2000
c) Manufacturer Nanjing Zhida
d) Catalogue number (catalogue
to be attached with bid) N/A
e) Creepage distance mm 1256
30) HV neutral bushing
a) Rating
i) Voltage kV 40.5
ii) Current A 800
iii) Impulse withstand voltage kV peak 220
iv) Power frequencywithstand voltage kV rms 95
b) Type GOB-325-800
c) Manufacturer ABB
d) Catalogue number (catalogue N/A
to be attached with bid)
e) Creepage distance mm 1256
31) LV neutral bushing N/A
a) Rating
i) Voltage kV N/A
ii) Current A N/A
iii) Impulse withstand voltage kV peak N/A
iv) Power frequency
withstand voltage kV rms N/A
b) Type N/A
c) Manufacturer N/A
d) Catalogue number (catalogue
to be attached with bid) N/A
e) Creepage distance mm N/A
32) Tertiary bushings
a) Number N/A
b) Rating
i) Voltage kV N/A
ii) Current A N/A
iii) Impulse withstand voltage kV peak N/A
iv) Power frequency
withstand voltage kV rms N/A
b) Type N/A
c) Manufacturer N/A
d) Catalogue number (catalogue
6 / 11
to be attached with bid) N/A
e) Creepage distance mm N/A

33) High voltage bushing current transformers


(catalogue to be attached with the bid)
a) Manufacturer TBEA or equivalent
b) Type LR
c) Number 1
d) Ratio 300/2300/1
e) Accuracy class 0.5
f) Accuracy limit factor 5
g) Rated burden VA 15
h) Short-time thermal current kA 10
i) Continuous thermal current kA 5
j) Dynamic current kA 25
k) Resistance of the secondary winding Ohms 0.5
l) No. of cores in each bushing CT Y2
Two for Phase Y only, one for winding thermometer and the
other one for starting the fan on the basis of load

34) HV neutral point bushing current transformer


(catalogue to be attached with the bid)
a) Manufacturer TBEA or equivalent
b) Type LRB
c) Number 2
d) Ratio 200:400/1
e) Accuracy class 5p20
f) Accuracy limit factor 5
g) Rated burden VA 30
h) Short-time thermal current ka 10
i) Continuous thermal current kA 5
j) Dynamic current kA 25
k) Resistance of the secondary winding Ohms 0.5
l) No. of cores in each bushing CT 2

35) Type of on-load tap changer (catalogue and data to be supplied with bid)
a) Manufacturer MR
b) Type oil immersed
c) Rated current A 500
d) Step voltage V 3.300
e) No. of steps 17
f) Motor drive
i) Type ED100S
ii) Supply voltage V 380
iii) H.P 0.75kW
7 / 11
iv) Insulation level
(voltage to earth) kV rms325
g) Tap changer protective relay
(catalogue to be attached with the bid)
i) Type RS2001
ii) Make MR
iii) Contact rating 400VA
h) Insulation levels
i) Voltage to earth kV rms 72.5
ii) Impulse test voltage kV peak 325
iii) One minute power frequency kV rms 140
test voltage (50 Hz)
i) Internal insulation levels Impulse/one minute power frequency test voltage
i) Between selected and kV peak 90
pre-selected tap kV rms 20
ii) Across fine tap winding kV peak 150
kV rms 30
iii) Between phases of fine kV peak 350
tap winding kV rms 82
iv) Across coarse and fine kV peak 350
tap winding, if applicable kV rms 82
v) Across coarse tap winding, kV peak 545
if applicable kV rms 178
vi) Between phases of kV peak 550
coarse tap winding kV rms 182
j) Remote tap position indicator
i) Type designation SC001
ii) Manufacturer MR
iii) Method of remote indication BCD
k) Temperature-rise of contacts at 1.2
times maximum rated through current. 20,000 times
l) Permissible number of operations at rated
step voltage. 200,000 times
m)Permissible number of operations at reduced
step voltage. 120,000 times
n) Permissible number of operations for
selector switch. 800,000 times
o) Temperature-rise of transition resistors
at 1.5 times max. rated through current. 30,000 times
p) Mechanical endurance.
i. No. of operations without requiringoverhauling. 100,000 times
ii. Total No. of permissible operationsin life time. 800,000 times
36) Liquid type oil thermometer (catalogue to be
attached with bid)
a) Type designation BWY-804
8 / 11
b) Manufacturer Dalian Shiyou/ Hangzhou Huali
c) Catalogue No. N/A
d) Contact rating between
110V & 250V DC and A 3
250V AC A 10
37) Resistance type oil thermometer
(catalogue to be attached with bid)
a) Type designation Pt100
b) Manufacturer Dalian Shiyou/ Hangzhou Huali
c) Catalogue No. N/A
d) Contact rating between
110V & 250V DC and A 3
250V AC A 10
38) Oil level indicator (catalogue to be
attached with bid)
a) Type designation YZF
b) Manufacturer Shenyang Changqin
c) Catalogue No. N/A
d) Contact rating between
110V & 250V DC and A N/A
250V AC A N/A
39) Winding temperature indicator
(catalogue to be attached with bid)
a) Local
i) Type BWR-04
ii) Manufacturer Dalian Shiyou/ Hangzhou Huali
iii) Contact rating between
110V & 250V DC and A 3
250V AC A 10
b) Remote
i) Type BWR-04
ii) Manufacturer Dalian Shiyou/ Hangzhou Huali
iii) Contact rating between
110V & 250V DC and Amps 1
250V AC Amps 3
40) Buchholz relay (catalogue
to be attached with bid)
a) Type BC-80
b) Manufacturer EMB
c) Catalogue No. N/A
d) Contact rating between
110V & 250V DC and A 0.5
250V AC A 3
41) Pressure relief device (catalogue to be attached with the bid)
a) Type YSF-55/130
9 / 11
b) Manufacturer Shenyang Mingyuan
c) Catalogue No. N/A
d) Pressure range for operation kg/cm 0.055Mpa
e) Contact rating if applicable 66VA
f) Number 2
42) Automatic voltage regulator, if required
(catalogue to be attached with bid)
a) Type designation N/A
b) Manufacturer N/A
c) Catalogue No. N/A
d) Input PT supply voltage V N/A
e) Input CT supply current A N/A
f) Voltage adjustment range percent of
the voltage to be regulated. Percent N/A
g) Sensitivity range percent of
the voltage to be regulated Percent N/A
h) Under voltage blocking percent
of the voltage to be regulated Percent N/A
i) Overcurrent blocking
percent of normal current Percent N/A
43) Forced air cooling equipment
a) Type (whether plate or tube) of radiators plate
b) No. of radiators 10
c) No. of tubes /plates in one radiator 28
d)Radiator dimensions
Length (L) mm 520
Width (W) mm 1360
Height (H) mm 2000
e) Total No. of fans 5
d) No. of fans required for full upper rating
output under specified conditions 4
e) No. of spare fans 1
f) Motor rating
i) H.P 0.85kW
ii) Supply voltage V 380
g) Total fan consumption at full load kW 4.25

44) Breather (catalogue to be attached with bid)


a) Type 3kg+0.5kg
b) Make TBEA or equivalent
c) Number 1+1

45) Valves (catalogue to be attached with bid)


a) Type Ball valve/Butterfly
b) Make TBEA or equivalent
10 / 11
c) Size
i) Drain valve DN50
ii) Filter valve DN50
iii) Sampling valve 15

46) Guarantee noise level


a) At lower rating (ONAN) db 65
b) At upper rating (ONAF) db 65
47) Type of construction, core or shell core
48) Weight of core and coils kg approx. 37700
49) Weight of case and fittings (accessories) kg approx. 18800
50) Weight of core kg approx. 26600
51) Weight of coil kg approx. 6800
52) Weight of copper kg approx. 6200
53) Weight of oil kg approx. 16500
54) Total weight kg approx. 73000
55) Shipping weight of heaviest piece kg approx. 59800(with oil)
56) Weight of heaviest piece for untanking kg approx. 59800(with oil)
57) Total volume of oil
a) Main tank Litres approx. 4500
b) Conservator Litres approx. 650
c) Radiators Litres approx. 2400
58) Tank dimensions
Length (L) mm approx. 5800
Width (W) mm approx. 2500
Height (H) mm approx. 3300
59) Overall dimensions
Length (L) mm approx. 6600
Width (W) mm approx. 5200
Height (H) mm approx. 5800
60) Thickness of plates
a) Tank cover mm approx. 20
b) Tank sides mm approx. 8
c) Tank bottom mm approx. 12
d) Radiator mm approx. 1
e) Conservator mm approx. 8
61 Insulation level A

62 Fire prevention system SERGI,France