Contents
Program Time (' ...................20
1. About the Alarm System ............................ 3 Program Date () ...................20
Introduction ...................................................................... 3 Program Banner Text (LCD only) (* ...................20
About this Manual............................................................ 3 Print 100 Events (! ...................20
Fire Detection................................................................... 3 Exit Program Mode (( ...................20
Monitoring ........................................................................ 3
Zones and Partitions........................................................ 3 5. Fire Safety & Maintenance .......................21
Access Codes .................................................................. 3 Fire Safety .......................................................................21
Remote Keypads .............................................................. 4 Fire Alarm Operation ......................................................21
Keypad Types .................................................................. 4 Household Fire Safety Audit ..........................................21
Keypad Layouts ............................................................... 4 Fire Escape Planning .....................................................21
Function Keys .................................................................. 5 Maintenance ...................................................................22
Emergency Keys.............................................................. 5 Glossary ..........................................................................22
!
3. User Functions Menu ............................... 11
Reset Alarms .................................................................. 11
Last Alarm Log ............................................................... 11
Service Faults................................................................. 11
Acknowledging a New Service Fault ............................ 11
View Service Faults........................................................ 11 MAINS VOLTAGES INSIDE
Anti-code Reset .............................................................. 12
Toggle Chime On and Off .............................................. 12 No user serviceable parts, servicing by qualified
Change User Code......................................................... 13 personnel only.
View Log (LCD Only)...................................................... 13
Abort Communications .................................................. 13
2 INS141-6
Premier 412/816/832 Master User Manual About the Alarm System
INS141-6 3
About the Alarm System Premier 412/816/832 Master User Manual
Keypad Layouts
Remote Keypads
5
One or more remote keypads will be installed throughout
the protected premises, usually one at each entry/exit door. 1 Zones
3
1 2 3 4 5 6 7 8
Service Ready
that it is going to control. A keypad can be assigned to more
2 4
9 10 11 12 13 14 15 16
3
location of the remote keypad. This keypad is normally used
on systems that monitor up to 32 zones.
12:55.22 28/04 Armed
4
# Bypass Service
Ready
reader.
Yes 0 No Area Menu
4 INS141-6
Premier 412/816/832 Master User Manual About the Alarm System
2-wire smoke sensors. If there is an accompanied zone Emergency Alarm Press Keys
indication, the fire alarm has occurred from the smoke
sensor on the indicated zone. #&%
*- Bypass: If the Bypass light is on, one or more zones have
been manually bypassed, (see Manually Bypassing &&)
Zones on page 9).
*&(
+- Stay: If the Stay light is on, the partition/system is in the
stay armed mode. The Armed light will also be flashing.
INS141-6 5
Operating the Alarm System Premier 412/816/832 Master User Manual
have familiarised yourself with all the arming and disarming Alarm
1 2 3 4 5 6 7 8
Armed
Arming & Disarming the Alarm System 3 Leave the premises, when the system has armed the
exit tone will stop. The system is now Away armed.
6 INS141-6
Premier 412/816/832 Master User Manual Operating the Alarm System
1 2 3
Zones
4 5 6 7 8
Premier 816 Zone 05 Active
Alarm
Service
Armed
3 Arming has been cancelled and the alarm system is 2 The system is disarmed and the keypads display the
source of the alarm.
now disarmed.
The system must now be reset before you can arm again,
" If the system only has one partition you will not have
to perform step 2.
see page 11 for details on resetting alarms.
1 Enter the premises via the designated entry point, " To auto Stay arm your alarm system proceed as follows:
the entry tone will sound. Proceed directly to the
1 Enter Access code ????
remote keypad.
Enter Your Code
Zones
YES to Arm?
1 2 3 4 5 6 7 8 Zones
1 2 3 4 5 6 7 8
Alarm Armed
08:30.59 28/04
Alarm Armed
Service Ready Service Ready MENU for Options
2 Enter Access code ???? 2 Press a Press y
Premier 816
Zones
Please Exit....
1 2 3 4 5 6 7 8 Zones
1 2 3 4 5 6 7 8
Alarm Armed
08:31.12 28/04
Alarm Armed
Service Ready Service Ready 17:30.21 28/04
3 The entry tone will stop and the Armed light will turn off. The Armed light will flash and the exit tone will sound.
The alarm system is now disarmed.
3 Do NOT leave the premises during the exit delay. At
the end of the exit delay the alarm system will Stay arm.
" If a valid Access code is not entered before the end of
the entry delay, an alarm will occur.
Changing between Delayed and Instant Stay
When Stay arming the system the delayed zones (front door
Disarming when not in Entry etc) are normally delayed, i.e., when a delayed zone is
" To disarm the alarm system when not in entry, proceed violated it will start the entry delay timer. However, it is
as follows: possible to change the delayed zones to instant when the
system is in a Stay armed mode. If a delayed zone is
1 Enter Access code ???? violated when the system is in the Instant Stay mode the
system will generate an alarm immediately.
MENU for Options
Zones
1 2 3 4 5 6 7 8
Alarm Armed
"
1 2 3 4 5 6 7 8
Alarm Armed
If the system only has one partition you will not have Service Ready 17:30.21 28/04
to perform step 2. 3 The Armed light will flash quickly.
The system is Instant Stay armed.
If the Quick Disarm feature is enabled and the system
is Stay armed you can omit step 1 from the above
procedure.
" If the system is fitted with a Premier RKP8/16 Plus the
Instant light will also illuminate.
INS141-6 7
Operating the Alarm System Premier 412/816/832 Master User Manual
" To change from Instant Stay to Delayed Stay, proceed Stay Arming Partitions
as follows: This option allows you to Stay arm one or more partitions.
1 Ensure that the system is Instant Stay armed. " To Stay Arm selected partitions, proceed as follows:
Press and hold the s key until you hear the Enter Access code ????
2 confirmation tone.
1
YES to Arm?
Zones
DELAYED STAY
Zones 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 Armed
Alarm
YES to Arm?
Zones 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 Alarm Armed
Alarm
Service
Armed
Ready MENU for Options Service Ready Area > **.. <
Alarm
Service
1 2 3 4 5 6 7 8
Armed
" If the Quick Arm feature is enabled, you can omit step
1 from the above procedure.
8 INS141-6
Premier 412/816/832 Master User Manual Operating the Alarm System
However, you can temporarily switch the remote keypad to a Service Ready MENU for Options
different partition so that the zone and status lights indicate Press B
2
the information relevant to the partition that you have
Bypass Zone> 00
Zones
1 2 3 4 5 6 7 8
selected. Whilst in this mode you can also use your Access Alarm
Service
Armed
The user should be set for Local Partition Access Only, 5 Once the selected zones have been bypassed press:
see page 18. y/a to Away arm
s to Stay arm
The remote keypads should only be assigned to a N to return to the normal disarmed state
single partition.
" To change to another partition, proceed as follows: " If the Quick Bypass feature is enabled, you can omit
step 1 from the above procedure.
1 Press A
1 2 3
Zones
4 5 6 7 8
Armed AREA ARMED >.... When one or more zones are bypassed the Ready
Alarm
Service Ready 17:35.34 28/04 light will flash and if the system is fitted with a Premier
RKP8/16 Plus or LCD remote keypad then the Bypass
2 Enter partition 1 - 4,
e.g. Press 2 to select Partition 2. light will also illuminate.
Premier 816
Zones
Alarm
Service
1 2 3 4 5 6 7 8
Armed
Bypassing Zones
INS141-6 9
Operating the Alarm System Premier 412/816/832 Master User Manual
Group Bypass " To Quick Bypass a group of zones and Away arm,
The Group Bypass feature allows you to bypass a proceed as follows:
predefined group of zones. The alarm system has up to four
1 Enter bypass group 1 - 4
groups.
Premier 816
Zones
1 2 3 4 5 6 7 8
Alarm Armed
" To bypass a group of zones, proceed as follows: Service Ready 19:30.56 28/04
2 Press a Press y
1 Enter Access code ????
Please Exit....
Zones
1 2 3 4 5 6 7 8
Alarm Armed
Alarm
1 2 3
Zones
4 5 6 7 8
Armed YES to Arm? Service Ready 19:30.56 28/04
Service Ready MENU for Options
The Armed and Ready lights will flash and the exit tone
2 Enter bypass group 1 - 4 followed by B will sound.
Bypass Zone> 00
Zones
1 2 3 4 5 6 7 8
3
Alarm Armed
Service Ready Zone 03 Bypassed When the exit tone stops, the system is Away armed
with the selected group of zones bypassed.
Bypass Zone> 00
Zone 04 Bypassed
4 The selected zone is now bypassed. Repeat step 3 to Service Ready 19:30.56 28/04
bypass additional zones. The alarm system will arm immediately and the Armed
and Ready lights will flash.
5 Once the selected zones have been bypassed press:
y/a to Away arm
s to Stay arm
3 The system is Stay armed with the selected group of
zones bypassed.
N to return to the normal disarmed state
" If the Quick Bypass feature is enabled, you can omit " The Quick Arm feature must be enabled to use this
feature.
step 1 from the above procedure.
When one or more zones are bypassed the Ready
light will flash and if the system is fitted with a Premier
RKP8/16 Plus or LCD remote keypad then the Bypass
light will also illuminate.
10 INS141-6
Premier 412/816/832 Master User Manual User Functions Menu
Alarm
1 2 3 4 5 6 7 8
Armed programmed. The Service light will turn steady yellow
Service Ready MENU for Options
immediately on either of these faults but no Service Fault
2 Press N0 Press R Alarm (transmission or audible alarm) will occur unless the
Alarm
1 2 3
Zones
4 5 6 7 8
Armed Premier 816 delay expires.
Service Ready 17:30.21 28/04
3 The keypad will bleep and the alarm system will reset
all latching detectors and attempt to clear any standing
" If your installer has disabled AC fail acknowledgement
the Service light will flash rapidly during an AC fail
Alarms or Service Faults. condition. The system can be armed without requiring
acknowledgement of this fault.
Service Ready Zone 03 The keypad will display all Service Faults.
Last Alarm From: Press N or R to acknowledge the fault and return to
Zone 04 3
the normal disarmed state.
The keypad will display the zones that caused an alarm
when the system was last armed.
INS141-6 11
User Functions Menu Premier 412/816/832 Master User Manual
7
Service Ready
The keypad will display a
Press * to view keypad number 1 2 3
Zones
4 5 6 7 8 randomly generated
Alarm Armed
Equipment Faults
Service Ready 4-digit Code.
Zones
1 2 3 4 5 6 7 8
Ready
1 = Output 1 Fault
2 = Output 2 Fault 3 Contact your ARC/Installer to obtain a Anti-code Reset
number.
3 = Siren/Bell Fault
8
4 = 2-Wire Smoke Sensor Fault Tel No.__________________________________________
5 = Auxiliary Fuse Failed
6 = Battery Fault
7 = Service Timer/Zone Soak Test Failed 4 Enter the Anti-code Reset number given to you by your
ARC/Installer ????.
8 = Communication Fault
If the code is accepted, the keypad will sound an
Service Faults Displayed on LCD Keypads
acceptance tone and the system will reset and return to
LCD Fault Condition the normal disarmed state.
!"#$%&'# AC Fail
(&)*#$%+',# Telephone Line Fault
-./0*#!'%1.#2345# 2-Wire Smoke Alarm Toggle Chime On and Off
6/78!+7#9%.:*1# Box Tamper
When a zone is enabled for Chime the keypad will generate
!+7#9%.:*1# Auxiliary Tamper (Aux Input) a Chime tone every time the zone is violated. This function
!+7&'&1;#9%.:*1 Auxiliary Tamper (UK Bell Module) allows you to turn the Chime feature on and off.
6*''#9%.:*1# Bell Tamper (UK Bell Module)
" To toggle Chime on and off, proceed as follows:
!+7#<!#!'%1.# Auxiliary PA (Aux Input)
=%,*89&.*#(/>># Date or Time Lost 1 Enter Access code ????
YES to Arm?
Zones
9%.:*1#?/)*#@#AB# Zone Tamper/Trouble Alarm
1 2 3 4 5 6 7 8
Armed
12 INS141-6
Premier 412/816/832 Master User Manual User Functions Menu
" To change your Access code, proceed as follows: " To Abort Communications, proceed as follows:
1 Enter Access code ???? Enter Access code ????
1
YES to Arm?
Zones
1 2 3 4 5 6 7 8
YES to Arm?
Zones
Alarm Armed 1 2 3 4 5 6 7 8
Premier 816
Zones
Alarm Armed 1 2 3 4 5 6 7 8
YES to Arm?
MENU for Options
2 Enter N6
Event Type Event Type
(showing Zone Text) (Alarm Type & Zone No)
Press A to toggle
information displayed
INS141-6 13
System Program Menus Premier 412/816/832 Master User Manual
Programming Menu
Enter Code > ??
Zones
Alarm
1 2 3 4 5 6 7 8
Armed
All Zone lights lit and
Service Ready Ready light flashes
14 INS141-6
Premier 412/816/832 Master User Manual System Program Menus
Programming Users
Program User
Program User 00 Program User 03
Enter User No.?? Code : ******
80 1 2 3
Zones
4 5 6 7 8
Enter User Number
??. 1 2 3
Zones
4 5 6 7 8
Alarm Armed Alarm Armed
N Press y or a if code is
less than 6 digits.
A
Program User 03
Code : ****
Zones
1 2 3 4 5 6 7 8
Alarm Armed
Service Ready
User Options 1
User 00 Options1 User 03 Options1 User Options 1
Enter User No.?? > 1***5678 < 1 Enable for Partition 1
81 1 2 3
Zones
4 5 6 7 8
Enter User Number
??. 1 2 3
Zones
4 5 6 7 8
2 Enable for Partition 2
3 Enable for Partition 3 (Premier 816/832)
Alarm Armed Alarm Armed
User Options 2
User 00 Options2 User 03 Options2 User Options 2
Enter User No.?? > **34**** < 1 Enable One Time Use Access Code
82 1 2 3
Zones
4 5 6 7 8
Enter User Number
??. 1 2 3
Zones
4 5 6 7 8
2 Time Lock Code with Control Timer 1
3 Enable Open Reporting
Alarm Armed Alarm Armed
User Options 3
User 00 Options3 User 03 Options3 User Options 3
Enter User No.?? > ****5*** < 1 Allow Engineer Code Programming
83 1 2 3
Zones
4 5 6 7 8
Enter User Number
??. 1 2 3
Zones
4 5 6 7 8
2 Allow NVM Locking
3 Allow Engineer Programming
Alarm Armed Alarm Armed
Return to point A
Continues on
Next Page
INS141-6 15
System Program Menus Premier 412/816/832 Master User Manual
From
Previous Page User Text
Engineer Use U to select User. Engineer
84
Text Editing Keys
User 00 Text Press n to edit text. ^ser 00 Text 1.,?!1@-&
2abc2ABC
3def3DEF
Use keys to enter/edit text. 4ghI4GHI
N Then press y to accept. 5jkl5JKL
6mno7MNO
7pqrs7PQRS
8tuv8TUV
9wxyz9WXYZ
0 Space 0 , # *
U Move Left/Right
R Backspace (delete)
Press y or a if code is
less than 6 digits.
Program User 03
Code : ****
Zones
1 2 3 4 5 6 7 8
Alarm Armed
Service Ready
Delete User
Program User 00 Program User 03
Enter User No.?? Code : ******
80 1 2 3
Zones
4 5 6 7 8
Enter User Number
??. 1 2 3
Zones
4 5 6 7 8
Alarm Armed Alarm Armed
N Press B
INS141-6 17
System Program Menus Premier 412/816/832 Master User Manual
18 INS141-6
Premier 412/816/832 Master User Manual System Program Menus
Walk Test
Walk Test Zone 01 Active Top line scrolls active zones
No Zones Tested Zone 01 Tested Bottom line scrolls tested zones
90 1 2 3
Zones
4 5 6 7 8
Activate Zones
1 2 3
Zones
4 5 6 7 8 Zone light flashing = zone active
Alarm Armed Alarm Armed
Program Time
Program Time
> 13:15 Enter the Time in 24hr format
95 1 2 3
Zones
4 5 6 7 8
e.g. 6.30pm = 1830
HHMM
Alarm Armed
Service Ready
Program Date
Program Date
> 28/04/01 Enter the Date in a
96 Zones
DDMMYY format
Alarm
1 2 3 4 5 6 7 8
Armed e.g. 28 April 2001 = 280401
Service Ready
Continues on
Next Page
INS141-6 19
System Program Menus Premier 412/816/832 Master User Manual
From
Previous Page
Banner Text (LCD Only)
Premier 8SP Premier 8SP
97
Text Editing Keys
Press n to edit text.
Banner Text ^anner Text 1.,?!1@-&
2abc2ABC
3def3DEF
Use keys to enter/edit text. 4ghI4GHI
N Then press y to accept. 5jkl5JKL
6mno7MNO
7pqrs7PQRS
8tuv8TUV
98 Print 100 Events 9wxyz9WXYZ
0 Space 0 , # *
U Move Left/Right
R Backspace (delete)
99 Exit Program Mode
20 INS141-6
Premier 412/816/832 Master User Manual Fire Safety & Maintenance
INS141-6 21
Fire Safety & Maintenance Premier 412/816/832 Master User Manual
22 INS141-6
Premier 412/816/832 Master User Manual Installation Records
6. Installation Records
Control Panel
Model: Premier 412: ! Premier 816: ! Premier 832: !
Location:
Keypads
Fire Police Medical PA Quick Quick Quick
Keypad Location Partitions
(1 & 3) (4 & 6) (7 & 9) Silent Arm Disarm Bypass
1
2
3
4
5
6
Timers
Timer Partition 1 Partition 2 Partition 3 Partition 4
Exit Time Sec. Sec. Sec. Sec.
Entry Delay 1 Time Sec. Sec. Sec. Sec.
Entry Delay 2 Time Sec. Sec. Sec. Sec.
Alarm Delay Time Min. Min. Min. Min.
Bell Delay Time Min. Min. Min. Min.
Bell Duration Time Min. Min. Min. Min.
Users
No. Name No. Name No. Name No. Name
00 Engineer 16 32 48
01 Master 17 33 49
02 18 34 50
03 19 35 51
04 20 36 52
05 21 37 53
06 22 38 54
07 23 39 55
08 24 40 56
09 25 41 57
10 26 42 58
11 27 43 59
12 28 44 60
13 29 45 61
14 30 46 62
15 31 47 63
INS141-6 23
Zones
No. Location Partitions B C No. Location Partitions B C
1 17
2 18
3 19
4 20
5 21
6 22
7 23
8 24
9 25
10 26
11 27
12 28
13 29
14 30
15 31
16 32
B = Bypass; C = Chime
Address: _________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
Telephone: _________________________________________________________________________________
Fax: _________________________________________________________________________________
Email: _________________________________________________________________________________
Telephone: _________________________________________________________________________________
Email: _________________________________________________________________________________