Documente Academic
Documente Profesional
Documente Cultură
Derive the equation for terminal voltage of synchronous generator for load current I
Let consider the load is connected and the load current is I. Hence per phase equivalent circuit can be
drawn as,
E = V + I ( ra+ j Xs )
= V + j I Xs ; Neglecting ra
= V + ( I Cos + j Sin ) j Xs
E = ( V I XsSin ) + j ( I XsCos )
E2 = ( V I XsSin ) 2 + ( I XsCos ) 2
E2 = V 2 + I 2 Xs2 2 V I XsSin
V 2 - 2 V I XsSin + I 2 Xs2 - E 2 = 0
Prove that (), =
SCR = =
But, Xs( SAT ), pu = / =
Xs( SAT ), pu =
Open Circuit Characteristic And Short Circuit Characteristic
280
Open Circuit Characteristic
260
240
220
200
Open Circuit Voltage ( V) / Short Circuit Current ( A )
180
160
140
120
100
80
60
y = 39.72x + 0.3898
20
0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8
Field Current ( A )
Using thevenins equivalent circuit,
/
= ( 2 + 2 ) =
/
sincera is small we can write
/
=
/
Where VO/C - Open circuit phase voltage
IS/C - Short circuit current
Therefore synchronous reactance (XS) can be determined by using the plotted characteristics
curves for a given field current.
Short Circuit characteristics equation can be defined form the graph as;
/ = y = 39.72x + 0.389 ;WhereIf Field Current
VO/C = ;Where 110V is the L-L Voltage obtained from the graph
= .
/ = . . + .
= .
.
=
.
= .
Similarly, we can calculate synchronous reactance (XS) for given field currents and results are
listed below.
14
13
12
Synchronous Reactance ( )
11
10
6
0.1 0.2 0.3 0.4 0.5 0.6
Field Current ( A )
Short Circuit Ratio is defined as,
() =
.
() = = .
.
Saturated synchronous reactance (XS(sat))in per unit,
1 1
XS(sat) = = = .
3.0769
/
() = = . = .
.
Load Voltage Vs Load Current
240
239
238
237
236
235
234
Load Voltage (V)
233
232
231
230
229
228
227
226
225
0 1 2 3 4 5 6 7
Load Current (A)
e.) Calculate the terminal Voltage theoretically for load currents of 1, 2, 4, 6, 8, 10,12A for purely
inductive ( = ),capacitive ( = )and resistive ( = )loads.Also calculate the
terminal voltages for load of 0.9 power factor ( = . )
V 2 - 2 V I XsSin + I 2 Xs2 - E 2 = 0
= 900 = 900
V 2 (2 XS I Sin ) V + (XS 2 I 2 - E 2) = 0 V 2 (2 XS I Sin ) V + (XS 2 I 2 - E 2) = 0
V = 165V V = 111.476V
When Cos = 1
=0
V 2 (2 XS I Sin ) V + (XS 2 I 2 - E 2) = 0
V = 135.89V
= 25.840 = - 25.840
V 2 (2 XS I Sin ) V + (XS 2 I 2 - E 2) = 0 V 2 (2 XS I Sin ) V + (XS 2 I 2 - E 2) = 0
V = 148.21V V = 124.6V
Terminal Voltage
Load (V)
Current
(A) =0
= 900 = -900 = 25.840 = - 25.840
220
210
200
190
180
170
160
150
Terminal Voltage ( V)
140
130
120
110
100
90
80
70
60
50
0 2 4 6 8 10 12 14
LOad Current (A)
DISCUSSION
01.) Discuss the importance of SCR with respect to the generator performance.
The ratio of the field current for rated open circuit Voltage and field current for rated short
circuit current give SCR. In addition, An SCR is given by the reciprocal of per unit synchronous
reactance.The synchronous reactance is higher when the SCR is low. So it becomes comparatively
very high value than armature resistance. This results in a significant phase angle (lagging) between
the induced Voltage and the armature current.
Also the short circuit ratio of a synchronous generator is a measure of the transient stability
of the generator unit. Synchronous generators with higher SCR values operate more stable under
transient conditions while the generators with lesser SCR values have less stability under transient
conditions. Because when the SCR value is lower, to maintain a constant terminal voltage for a
given change in load, a larger change in field current is required when compared with a higher SCR
value.
When SCR is low, the synchronous reactance is higher. Therefore it becomes
comparatively a very high value than the armature resistance. This results in a significant phase
difference (lagging) between the induced voltage and the armature current. When SCR is higher, the
Synchronous reactance reduces considerably causing a good voltage regulation at the output
terminals.
In the cases of parallel operation of generators, Synchronous reactance is essential in
determining the circulating current within the two generators. As Xsis a function of SCR we can have
an idea about the circulating current by knowing the SCR.The physical dimensions and properties
are relatively smaller on low SCR machines, so their cost is also lower
/
=
/
The graph of Open circuit characteristics and Short circuit characteristics can be divided in
to two parts as a linear region and a nonlinear region. When observe the characteristic curves we can
see that ratio between Voc and Iscvalues are constant for lower values of the field current. Because both
curves are straight lines for lower values. But after machine begins to saturation situation will be
change and synchronous reactance start to drop down.This is because of the fact that the rate of
increase of open circuit characteristic is reducing faster and at the saturated region the slow growth of
flux affects to the armature reaction and the self-inductance of the armature coils.
03.) Synchronous Generator has characteristics of a Current Transformer .Briefly account for
this.
If we take the rotor winding of a synchronous generator to be the primary winding of a
transformer, the field winding to be the secondary, the field current to be the primary current, and the
armature current to be the secondary current, then a synchronous generator can be taken to resemble a
step-up current transformer since the armature current is much higher than the field current. In a
current transformer, when the secondary winding is short circuited, that short circuit current is
proportional to the primary current. Similarly, when the armature is short circuited in a synchronous
generator, we can observe that the armature current is proportional to the field current by the short
circuit characteristic curve. Hence, the synchronous generator shows characteristics of a current
transformer. A synchronous generators field current depends on the connected load. Similarly in a
current transformer, the primary current depends on the load connected to the secondary winding.
04.) Comment on the variation of the terminal voltage with load current for various power factor
loads.
Terminal voltage tends to reduce with increasing field current when power factor is lagging
in the Inductive Load, and it tends to increase with increasing field current when power factor is
leading in the Capacitive Load. That reduction or rise becomes rapid and linear when power factor
tends to zero while it becomes non-linear when power factor tends to unity.Value of Xs is essential in
finding the terminal Voltage and each curve is nearly straight at the beginning but tends to bow with
the load current increases
05.) Discuss the importance of synchronization, conditions for synchronization and Dark lamp
method of synchronization
Synchronization is important in that it ensures quality, reliability as well as optimizing
efficiency within the system. By synchronizing generators within a grid, it ensures no destructive
interference occurs. This then in causes a more consistent energy supply to the consumers since all
generators are working in unison. Finally, not only will the grid not have destructive interference,
constructive interference will occur which increases the total power the grid can produce which
optimizes the grid.