Sunteți pe pagina 1din 8

ULTRA QUICK

FUSE-LINKS
D0
D
HRC

UQ
FUSES FOR PROTECTION OF SEMICONDUCTORS

POWER NEEDS CONTROL


FUSE LINKS
Description:
Fuse-links are the oldest protective devices in the electrical industry. The Semiconductors in rectifiers require quick fuse-links of type aR and gR for
protection by fuses is based on the principle a piece of wire melting at the protection. ULTRA-QUICK fuse-links comply with the following regulations:
point of defect of an electric circuit. For this purpose a sufficient amount VDE 0636/23, VDE 0636/33, IEC 60269, DIN 57636, DIN 43620,
of energy is necessary, which is called the Joule integral I2t. In order to DIN43653, DIN 49522.
adapt the fuse-links to specific protection requirements, various time current
characteristics have been developed. A time current characteristic is a The requirements with which fuse-links for protection of semiconductors
graphical representation of the melting time as a function of the overload must comply are:
current. The type of fuse is chosen based on the operational range of the fuse -high breaking capacity and quick action
and the type of object under protection. -high current limitation
-low heat values
Marks -they should not be subject to ageing
Fuse marking consists of two letters where the first letter denotes the
ULTRA QUICK fuse-links provide optimum protection of semiconductors,
function class and the second the type of facility under protection.
being used for special purposes:
Example: gG; g: protects a facility across the entire current axis; G: the facility
under protection is electrical installation. A: Ipol INtv
UQ

The current passing through the semiconductor must be smaller or


Function class of fuses
the same as the rated current of the fuse-link. Here you have
It determines the range on the current axis for which a fuse-link
to consider special ways of load (periodical, non-periodical, uniform,
is capable of breaking a circuit.
non-uniform) and other influences (thermical influences, cooling).
Function class g
B: Upol UNtv
The entire range of operation of a fuse. Fuse-links continuously
conduct rated currents and in case of a defect in the circuit they The operating voltage on the semiconductor must be smaller or the same
break all currents from the lowest melting current up to the highest as the rated voltage of the fuse-link. In case of doubt the rated voltage of
breaking capacity (protection against overload and short circuits). the semiconductor element to be protected can be used as a guideline.

Function class a C: *i2 pol dt > *i2 Ntv dt


These fuses provide limited range of protection. Fuse-links conduct
The total Joule-integral of the chosen fuse-link I2dt must be lower than the
continuously the rated currents and in case of a defect in the circuit they
limit integral of the semiconductor. If this data is not directly stated, it can be
break all currents from a multiple of rated current up to the breaking
calculated from the data for the maximum permissible surge forward current
current (protection against short circuits).
for the duration of one-half period (10ms)-ITSM in the following way:
Facilities under protection *i2 POL dt =(lTSM
2 T
)2
L: cables and mains
B: mining equipment D: Ik < Iltv
M: switching devices
R: semiconductors The highest possible surge forward current of the short circuit which
T: transformers can appear in a circuit must be lower than the rated breaking
capacity of the fuse-link.
The types of fuse-links used for protection of the specified objects
gG: total range of protection - cable and mains E: URRM > UL UDRM > UL
aM: partial range of protection - switching devices The switching voltage (arc voltage) of the fuse-link must be lower than the
aR: partial range of protection semiconductors repetitive peak voltage of the semiconductor in the negative or positive
gR: total range of protection semiconductors direction.
gB: total range of protection - mining equipment
gTr: total range of protection - transformers

DO
Fuse-link D 01 ULTRA-QUICK for base E 14
10,7

lN (A) code No. colour weight packaging dimension


(g) (pcs) (D)
1

2 4311001 pink 6 10/500 7,3


36

4 4311002 brown 6 10/500 7,3


6 4311003 green 6 10/500 7,3
10 4311004 red 6 10/500 8,5
16 4311005 grey 6 10/500 9,7
D
Fuse-link D 02 ULTRA-QUICK for base E 18 14,9

lN (A) code No. colour weight packaging dimension


(g) (pcs) (D)
20 4312001 blue 11 10/500 10,9

1
25 4312002 brown 12 10/500 12,1

36
35 4312003 black 13 10/500 13,3
50 4312004 white 13 10/500 14,5
63 4312005 copper 15 10/500 15,9
D

Technical data: l2* values D0 ULTRA-QUICK


Fuse-link D 01 / D 02 ULTRA QUICK Rated current (A) Melting integral (A2*s) Total integral (A2*s)
at 100 V at 200 V at 400 V
Rated voltage UN 400 V;/ 250 V 2 1 2,3 4 6,3
Rated current IN 2 - 63 A 4 2 4,7 8 13
Breaking capacity I1 50 kA;/ 8 kA 6 5 7 12 20
Fusing characteristic gR 10 12 25 40 65
16 35 70 100 200

UQ
20 55 120 180 275
25 85 160 280 480
35 180 250 450 1000
50 250 550 850 1800
63 550 800 1200 2500

D
Fuse-link D l ULTRA-QUICK for base E 16 13,2

lN (A) code No. colour weight packaging dimension


(g) (pcs) (B)
2 4321001 pink 12 20/500 6
50

4 4321002 brown 12 20/500 6


6 4321003 green 12 20/500 6
10 4321004 red 13 20/500 8
16 4321005 grey 14 20/500 10
20 4321006 blue 15 20/500 12 B
25 4321007 yellow 16 20/500 14

Fuse-link D ll ULTRA-QUICK for base E 27 21,5

lN (A) code No. colour weight packaging dimension


(g) (pcs) (B)
2 4322001 pink 27 5/500 6
50

4 4322002 brown 27 5/500 6


6 4322003 green 27 5/500 6
10 4322004 red 27 5/500 8
16 4322005 grey 28 5/500 10
20 4322006 blue 29 5/500 12 B
25 4322007 yellow 30 5/500 14
30 4322008 black 30 5/500 14

Fuse-link D lll ULTRA-QUICK for base E 33 27

lN (A) code No. colour weight packaging dimension


(g) (pcs) (B)
35 4323001 black 48 5/500 16
50

50 4323002 white 49 5/500 18


63 4323003 copper 52 5/500 20

B
Fuse-link D lV ULTRA-QUICK for base R1 1/4
33

lN (A) code No. colour weight packaging dimension


(g) (pcs) (B)
80 4324001 silver 105 10/100 5

56
100 4324002 red 110 10/100 7

Fuse-link D V ULTRA-QUICK for base R 2


46

lN (A) code No. colour weight packaging dimension


(g) (pcs) (B)
125 4325001 yellow 185 10/60 5
56
160 4325002 copper 210 10/60 7
200 4325003 blue 215 10/60 9
UQ

l2* values D ULTRA-QUICK Technical data:


Rated current (A) Melting integral (A2*s) Max. total integral (A2*s) Fuse-link Dl, Dll, Dlll, DlV, DV, ULTRA QUICK
at 125 V at 250 V at 500 V
Rated voltage UN 500 V;/ 315 V
2 0,7 1,8 3,5 5,8
4 1,8 4,1 6 11 Rated current IN 2 - 200 A
6 4 6 10 18 Breaking capacity I1 50 kA;/ 8 kA
10 8 12,5 23 40 Fusing characteristic gR
16 16,2 34 40 60
20 35,8 67 85 139
25 48,9 85 116 205
30 85 120 170 310
35 135 220 300 539
50 340 600 780 1250
63 530 850 1115 1890
80 980 1480 2110 4200
100 1950 3000 4200 8450
125 3100 4300 6000 16000
160 10000 12000 18000 24000
200 17000 22000 31000 40000

HRC
Fuse-links HRC ULTRA-QUICK can be delivered in two executions: U and U-N.
The execution U is suitable for direct screw mounting and the execution U-N
has a knife contacts to be used in standard HRC bases.

Fuse-link HRC 00 C ULTRA-QUICK


lN (A) characteristic code No. packaging weight
U U-N (pcs) (g)
6 aR 4331003 4331018 3/90 0,18
10 aR 4331004 4331019 3/90 0,18
16 aR 4331005 4331020 3/90 0,18
20 aR 4331006 4331021 3/90 0,18
25 aR 4331007 4331022 3/90 0,18
35 aR 4331008 4331023 3/90 0,18
40 aR 4331009 4331024 3/90 0,18
50 aR 4331010 4331025 3/90 0,18
63 aR 4331011 4331026 3/90 0,18
80 aR 4331012 4331027 3/90 0,18
100 aR 4331013 4331028 3/90 0,18
125 aR 4331014 4331029 3/90 0,18
U UN
Fuse-link HRC 00 ULTRA-QUICK
lN (A) characteristic code No. packaging weight
U U-N (pcs) (kg)
6 gR 4331102 4331201 3/90 0,18
10 gR 4331103 4331202 3/90 0,18
16 gR 4331104 4331203 3/90 0,18
20 gR 4331105 4331204 3/90 0,18
25 gR 4331106 4331205 3/90 0,18
35 gR 4331116 4331214 3/90 0,18
40 gR 4331110 4331208 3/90 0,18
50 gR 4331111 4331209 3/90 0,18
63 gR 4331112 4331210 3/90 0,18
80 gR 4331113 4331211 3/90 0,18
100 gR 4331114 4331212 3/90 0,18
125 gR 4331115 4331213 3/90 0,18
160 aR 4331117 4331215 3/90 0,18 U UN

Fuse-linkHRC 0 ULTRA-QUICK

UQ
lN (A) characteristic code No. packaging weight
U U-N (pcs) (kg)
6 gR 4332101 4332201 3/45 0,32
10 gR 4332102 4332202 3/45 0,32
16 gR 4332103 4332203 3/45 0,32
20 gR 4332104 4332204 3/45 0,32
25 gR 4332105 4332205 3/45 0,32
35 gR 4332116 4332216 3/45 0,32
40 gR 4332108 4332208 3/45 0,32
50 gR 4332109 4332209 3/45 0,32
63 gR 4332110 4332210 3/45 0,32
80 gR 4332111 4332211 3/45 0,32
100 gR 4332112 4332212 3/45 0,32
125 gR 4332113 4332213 3/45 0,32
160 aR 4332114 4332214 3/45 0,32 U UN

Fuse-link HRC 1 ULTRA-QUICK


lN (A) characteristic code No. packaging weight
U U-N (pcs) (kg)
35 gR 4333117 4333217 3/24 0,45
50 gR 4333108 4333208 3/24 0,45
63 gR 4333109 4333209 3/24 0,45
80 gR 4333110 4333210 3/24 0,45
100 gR 4333111 4333211 3/24 0,45
125 gR 4333112 4333212 3/24 0,45
160 aR 4333113 4333213 3/24 0,45
200 aR 4333114 4333214 3/24 0,45
250 aR 4333116 4333216 3/24 0,45

U UN

Fuse-link HRC 2 ULTRA-QUICK


lN (A) characteristic code No. packaging weight
U U-N (pcs) (kg)
80 gR 4334109 4334209 3/15 0,68
100 gR 4334110 4334210 3/15 0,68
125 gR 4334111 4334211 3/15 0,68
160 aR 4334112 4334213 3/15 0,68
200 aR 4334113 4334214 3/15 0,68
250 aR 4334115 4334216 3/15 0,68
280 aR 4334116 4334218 3/15 0,68
315 aR 4334117 4334220 3/15 0,68
355 aR 4334118 4334221 3/15 0,68
400 aR 4334119 4334222 3/15 0,68

U UN
Fuse-link HRC 3 ULTRA-QUICK
lN (A) characteristic code No. packaging weight
U U-N (pcs) (kg)
250 aR 4335117 4335207 3/12 0,88
280 aR 4335108 4335208 3/12 0,88
315 aR 4335109 4335209 3/12 0,88
355 aR 4335110 4335210 3/12 0,88
400 aR 4335111 4335211 3/12 0,88
450 aR 4335113 4335213 3/12 0,88
500 aR 4335114 4335214 3/12 0,88
560 aR 4335115 4335215 3/12 0,88
630 aR 4335116 4335216 3/12 0,88

U UN

Fuse-link HRC 1-1000V ULTRA-QUICK


lN (A) characteristic code No. packaging weight
U U-N (pcs) (kg)
UQ

25 gR 4333315 4333415 3/12 0,49


35 gR 4333317 4333417 3/12 0,49
50 gR 4333320 4333420 3/12 0,49
63 gR 4333321 4333421 3/12 0,49
80 gR 4333322 4333422 3/12 0,49
100 gR 4333323 4333423 3/12 0,49
125 gR 4333324 4333424 3/12 0,49
160 aR 4333325 4333425 3/12 0,49
200 aR 4333326 4333426 3/12 0,49
224 aR 4333328 4333428 3/12 0,49
250 aR 4333327 4333427 3/12 0,49

U UN

l2* values HRC ULTRA-QUICK


IN(A) Melting integral (A2*s) Max. total integral max. gesamtes Integral (A2*s)
at 180 V at 330 V at 660 V
NV 00 C
6 4 7 10 19
10 13 22 31 62
16 32 54 77 154
20 60 103 145 290
25 123 209 296 590
35 242 410 580 1160
50 490 840 1180 2370
63 960 1650 2300 4650
80 1100 1890 2660 5350
100 2180 3690 5200 10500
125 4450 7550 10600 21300
NV 00
6 4 7 10 18
10 13 20 35 60
16 32 56 90 170
20 52 94 140 250
25 85 160 240 460
35 190 310 500 1000
50 290 520 760 1500
63 500 750 1050 3000
80 1000 1550 2200 5300
100 2000 2800 3900 9000
125 3100 4300 6000 16000
160 10000 12000 18000 24000
NV 0
6 4 7 10 18
10 13 20 35 60
16 32 56 90 170
20 52 94 140 250
25 85 160 240 460
35 190 310 500 1000
50 290 520 760 1500
63 500 750 1050 3000
80 1000 1550 2200 5300
100 2000 2800 3900 9000
125 3100 4300 6000 16000
160 10000 21000 18000 24000
l2* values HRC ULTRA-QUICK
IN(A) Melting integral (A2*s) Max. total integral max. gesamtes Integral (A2*s)
at 180 V at 330 V at 660 V
NV 1
35 190 300 500 1000
50 290 520 750 1500
63 500 750 1050 3000
80 1000 1500 2200 5300
100 2000 2800 3900 9000
125 3100 4300 6000 16000
160 10000 12000 18000 24000
200 17000 22000 31000 40000
250 29000 37000 44500 65000
NV 2
80 1000 1500 2200 5300
100 2000 2800 3900 9000
125 3100 4300 6000 16000
160 10000 12000 18000 24000
200 17000 22000 31000 40000
250 31000 35500 47600 60000
315 48000 55000 75000 175000
400 85000 101000 140000 270000
NV 3
250 31000 35000 47000 60000
315 48000 55000 75000 175000

UQ
400 90000 115000 160000 441700
500 160000 200000 300000 620000
630 270000 348000 460000 850000

Technical data:
Rated voltage UN 690 V;/ 440 V , UN = 1000 V;/ 600 V
Breaking capacity I1 50 kA;/ 25 kA
Fusing characteristic IN gR , aR

Dimension figures
A B C D E F G H I J
NV 00 C U 105 54 21 49 2 - 58 28 - 80
NV 00 U 105 54 27 49 2 - 58 28 - 80
NV 0 U 121 69 27 68 2 - 58 28 - 97
NV 1 U 140 75 26 68 2 40 57,5 46 6 110
NV 2 U 140 75 26 68 2 48 71,5 57 6 110
NV 3 U 140 75 36 68 2 60 69 6 110
NV 1 - 1000V U 160 95 26 88 2 40 57,5 46 6 130

B G
6
11,5

10
C

E
7,5 2,5
D

D 10
E 6
7,5
2,5

G
F
11,5
C

I
B

H
J

A
A B C D E F G H I
NV 00 C U 80 54 15 49 2 35 50,5 21 6
NV 00 U-N 80 54 15 49 2 35 50,5 28 6
NV 0 U-N 125 66 15 68 2 35 56,5 28 6
NV 1 U-N 135 75 20 68 2 40 61,5 46 6
NV 2 U-N 150 75 26 68 2 48 71,5 57 6
NV 3 U-N 150 75 36 68 2 60 81,5 69 6
NV 1 - 1000V U 155 95 20 88 2 40 57,5 46 6

10
D
6

7,5
E

2,5

G
F
C

I
B
H
A
UQ

ETI Elektroelement d. d.
Obrezija 5, 1411 Izlake,
Slovenia

tel. +386 (0)3 56 57 570


fax: +386 (0)3 56 74 077

e-mail: eti@eti.si
www.eti.si

S-ar putea să vă placă și