Documente Academic
Documente Profesional
Documente Cultură
Engineering Practice
D
etermining the proper prelimi- Figure 1. Refer to this pump-system sketch for the pump-design calculations
nary size for centrifugal pumps discussed here. Note, a distance of 2 ft between the pump-inlet piping and grade and
3-ft distance between pump-discharge piping and grade is assumed during initial siz-
during the initial stages of any ing. These values should be confirmed once pump selection is done
pump-specification exercise
requires numerous calculations and clude calculation of suction pressure Horsepower and efficiency. In the
assumptions. This article reviews the and rated differential pressure. early stages of the project, you will
steps needed to size centrifugal pumps Net pressure suction head (NPSH) have to provide preliminary horse-
during the early stages of a project, to calculations. During the early stages power to the electrical engineer for
support initial cost-estimation efforts. of the project, the plant layout is not load calculations. From the rated dif-
Such early pump-sizing efforts are im- yet firm. Hence, NPSH available for ferential pressure, calculate the rated
portant steps toward final pump selec- the pump(s) cannot yet be calculated horsepower. Since the pump has not
tion and detailed engineering. with confidence. However, it is okay yet been selected, you can assume a
to carry out preliminary NPSH cal- pump efficiency between 50 and 60%.
Sizing centrifugal pumps culations using information from the Make a judgment call 50% is typi-
Normal flowrate and rated flow- preliminary layout. Note that NPSH cally a sufficient value for calculating
rate. To define the normal and rated values can be increased by later modi- horsepower during the initial stages
flowrates, refer to the heat and mass fications to the layout. NPSH plays a of a project.
balance of your project. Normal flow- very important role during pump se- Shutoff pressure. Shutoff pressure is
rate is the flow at 100% capacity. lection, and could significantly impact required in early stages of the project
Rated flowrate is the design margin the cost of the pump if a lower-NPSH to determine the flange rating for the
that is added to the normal flowrate (required) pump is specified, since discharge piping of the pump. There
(typically on the order of 1030%), to pumps with a lower NPSH require- are several ways to calculate shutoff
accommodate potential short-term ex- ment tends to be more expensive. pressure. A more conservative method
cursions in flowrate during operation. The goal is to calculate a preliminary uses the following formula:
Rated flowrate is usually defined by NPSH value and provide it to the
Differential pressure 1.25 +
the user. If it is not defined, consider pump vendors to get initial feedback.
maximum suction pressure
10% for normal-service pumps, and This allows both parties to determine
2030% for critical-service pumps, whether a pump with the specified Maximum suction pressure is
such as distillation column reflux NPSH can be achieved or not, can be calculated by:
pumps, reactor feed and furnace-feed achieved with some modification to Pressure safety valve (PSV) set pres-
pumps and other feed pumps that play the plant layout, or can be achieved sure 10 21% accumulation + static
a critical role in the overall process. by selecting a pump with lower NPSH head based on high liquid level
Pressure-drop calculations. The requirements. Based on the vendors If a user does not have information
intent of these calculations is to de- feedback, modify your layout to have a such as the PSV set pressure in the
termine suction pressure and rated design margin between the available early stages of the project, a simple
differential pressure. Please refer and required NPSH. A design margin approach for calculating shutoff head
to sample calculation #1 (discussed of 34 ft is widely accepted, per indus- is to use this formula:
below) and Figure 1 for performing try standards. See sample calculation
pump-sizing calculations, which in- #2 for calculating NPSH (available). Rated differential head 1.5
Impeller 1 ing ded Static head = 10.5 ft (ft x specific gravity/2.31), 3.2 3.2
ran
ge* psi
Impeller 2
Suction line loss, psi 0.3 0.3
Impeller 3 Pump suction pressure, psig (30+3.2) (30+3.2)
0.3 = 32.9 0.3 = 32.9
Best efficiency
Discharge pressure
point (BEP)** Delivery pressure, psig 100 100
Static head = 19 ft (ft x specific gravity/2.31), psi 5.8 5.8
Flowrate produced
Line loss, psig 33 23
* The recommended operating range is between
70120% of the BEP flowrate Control-valve pressure drop, psid 38 83.5
* * BEP is a point on the curve, is specific to each
pump, and is provided by the pump manufacturer Filter pressure drop, psid 14.4 10
Heat exchanger 1 pressure drop, psid 14.4 10
Figure 2. This pump-performance
curve shows the best efficiency point Heat exchanger 2 pressure drop, psid 14.4 10
(BEP) and the recommended operating Furnace pressure drop, psid 72 50
range, which are helpful during pump
selection. Note the shaded region rep- Orifice flowmeter pressure drop, psid 2.88 2
resents the operating range for different Contingency, psig 10 10
impeller sizes
Differential pressure, psig
Specifying centrifugal pumps Discharge pressure, psig =100+5.8+3 =100+5.8+2
The following steps must be carried 3+14.4+14. 3+10+10+10
4+14.4+72+ +50+2+83.5
out during the specification of centrif- 2.88+38+10 +10=305
ugal pumps: =305
Gather basic process data. Fill out
Minus suction pressure, psig 32.9 32.9
the pump data sheet with the follow-
ing basic information: Suction pres- Total pump differential pressure, psig 272 272
sure, normal and rated discharge Pump head (psi x 2.31/specific gravity) 900 900
pressures, normal flowrate and rated Hydraulic power = gal/min x pump head (ft) x 382 318
flowrate, fluid properties, such as den- specific gravity/3,960, hP
sity, viscosity and vapor pressure at Efficiency at 3,600 rpm, % 60 60
operating temperature.
Rated power = Hydraulic power/efficiency, hp 637 530
Determine a preliminary value
for NPSH. Please refer to the NPSH
calculations presented below (sample regarding whether to use a sealed or must be based on the end users re-
calculation #2). sealless design pump. Consider seal- quirements, process conditions, and
Specify desired materials of con- less pumps for liquids that are flam- the cost of the equipment. In general,
struction. This should come from the mable, toxic and corrosive. For in- the cost increases in this order: Non-
end user or from a metallurgist who is stance, many facilities use traditional ANSI, sub-ANSI, ANSI and API, while
involved in the project and is respon- sealed pumps for pumping water, and non-ANSI pumps have the lowest cost.
sible for specifying the appropriate sealless pumps for pumping acids and A non-ANSI pump usually finds its ap-
metallurgy of the equipment. alkalis and other corrosive liquids. plication in small sizes handling less
Specify sealless versus mechanical Work closely with your vendor and critical service, such as water that is
seals. Magnetic-drive sealless pumps seek guidance based on previous being pumped at relatively low pres-
are desirable for many applications experience in applications with sure and low temperature. An ANSI
since they eliminate the need for me- similar service. If a sealless pump is pump is usually used in applications
chanical seals, and thus eliminate the not available, consider using a double requiring relatively larger sizes (for
inherent risk of leakage and mainte- mechanical seal to minimize the risk instance, more than 10 hP) in chemi-
nance associated with such seals. But of leakage. Rely on the vendors expe- cal or hydrocarbon service.
sealless pumps also have drawbacks, rience, as well, in selecting the most However, some ANSI pumps may be
such as an inability to handle larger appropriate mechanical seal for your limited to a maximum casing pressure.
particles in the process fluids. And service. Provide vendors with as much For higher-casing pressures, the user
in some applications, relatively high process data as you have, to ensure may have no choice but to consider a
differential pressure requires high proper seal selection for your service. custom-made pump or an API pump.
torque, which may be beyond the ca- Classify non-ANSI, sub-ANSI and API pumps tend to be considerably
pabilities of the sealless pump. ANSIAPI pumps. Ultimately, the more expensive than ANSI pumps, as
Rely on the end-users experience selection of specific centrifugal pumps they are typically used in hydrocarbon
44 Chemical Engineering www.che.com FEBRuary 2013
40
NPSH required, ft
NPSH-required
20
380
0
Rated flow Efficiency
90 360
80 340 Head
BEP The pump-sizing calculations also
70 320
Head, ft
Power, BHP
20 100
of the dynamic head loss at rated flow.
Power In this case, dynamic head loss at the
10 50
rated flow is 151 psig (the sum of pres-
0 0 sure drop across filters, heat exchang-
0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 1,300
ers, furnaces, orifices and line losses.
Flowrate, U.S. gal/m
Hence the differential pressure across
Figure 3. This figure shows a relationship between flowrate and head, power, effi- the control valve in this scenario at
ciency and NPSH. Note the NPSH curve is bowl-shaped. NPSH requirements increase rated flow is 38 psig).
with flow. Make sure you analyze this value carefully and select a NPSH (required)
Note: If the calculated pressure drop
value that corresponds to the rated flowrate
across the control valve is less than 10
service involving high temperatures Sample calculations psig, use a minimum value of 10 psig
and very high pressures. Such pumps Consider the pump system sketch for the control valve at rated flowrate.
are widely used in refinery service. shown in Figure 1. A fluid with a vapor Now adjust the pressure drop across
Specify design pressure and tem- pressure of 45.9 psia at operating tem- the control valve at normal flow and
perature. Specifying design pressure perature of 430F with a viscosity of try to match the discharge pressure
and temperature based on the design 0.5 cP is pumped at normal flow of until it is equal at normal and rated
conditions of the pump suction vessel 2,000 gal/min. The specific gravity is flow. Pressure drop is directly propor-
may seem to be the easiest approach. 0.7 and the delivery pressure is 100 tional to the square of the flow, hence
But check for any possible upset condi- psig. The operating pressure of col- pressure drop across rated flow is cal-
tions that might warrant an increase umn C-100 is 30 psig. The atmospheric culated using the following formula
in design pressure and temperature, pressure at site is 14.5 psia. Assume (Note that the rated flow is 1.2 times
such as a new process stream entering a rated flowrate of 2,400 gal/min (1.2 the normal flow):
the pump suction in a different pro- times the normal flowrate).
cess operating mode. Note that two sets of calculations Filter pressure drop at normal flow =
Specify the motor requirements. are done for calculating horsepower 10 psig
The required power supply, whether one for normal flowrate and other Filter pressure drop at rated flow =
it is 460 V at 60 Hz, or 230 V at 50 for rated flowrate. Refer to Figure 1 10 (1.2 1.2) = 14.4 psig
Hz, must be supplied by the end user. for calculating static head. Pressure
Lastly you have to specify the hazard- drop across filters, heat exchangers, In reality, the discharge pressure at
ous area classifications and tempera- orifice meters and furnaces are taken normal flow and rated flow may not be
ture rating of the motor. Check with from actual equipment vendor quotes. the same, but the two values will be
your electrical engineers to identify These quotes may be available from very close. A pump is designed to oper-
the required hazardous area classi- different disciplines, such as mechani- ate at rated flow conditions. However,
fication. Motor temperature rating cal and instrumentation departments. a pump operates at normal flow most
should also come from the end user. If vendor quotes are not available of the time during normal operation.
This is based on the lowest autoigni- during preliminary pump sizing, then
tion temperature of the components assumptions must be made based on Normal operation
involved in the process. Keep in mind, interactions with other disciplines. During normal operation, because the
most of the time, a motor rating up to For instance, it is okay to assume a flow is lower than the rated flow, the
T3A is available at no added cost, but pressure drop of 10 psid across heat pump will try to develop more head.
the cost increases substantially if a exchangers or a pressure drop of 510 During this scenario, the control valve
motor with a rating of T4 or higher is psid across a filter. Pressure drop will start closing and will consume
specified. across a vessel filled with catalyst more pressure drop. This will have the
Next, you need to specify whether should be calculated using the Ergun effect of moving the pump back onto
you want a fixed-speed motor or a equation. These pressure-drop values the pump curve.
variable-speed drive motor. If you are are finalized when equipment design Here, you will notice that pressure
controlling the pump flow with a speed is finalized and are used for final pump difference in rated flow is 38 psig
controller, then you must select an sizing, during the detailed engineering (specified by the designer) and is 83.5
inverted-duty, variable-speed motor. phase, to check the rated differential psig in normal flow. The difference be-
However, note that if there is a control pressure and rated brake horsepower. tween these two values is the excess
valve on the pump discharge, then you It is helpful to perform these calcula- dynamic head between normal flow-
must use a fixed-drive motor. tions using an Excel spreadsheet. rate and rated flowrate. The relation-
Chemical Engineering www.che.com FEBRuary 2013 45
Head capacity curve
Operating points Control valve
A
pressure drop
Engineering Practice
B