Documente Academic
Documente Profesional
Documente Cultură
1
Copyright
Copyright Tyco International Ltd. ("Tyco") 1996 - 2002. All Rights Reserved. Copyright in this document is
owned by Tyco. Any person is hereby authorized to view, copy, print, and distribute this document subject
to the following conditions:
Note that any product, process or technology described in this document may be the subject of other
intellectual property rights reserved by Tyco and are not licensed hereunder.
TYCO FIRE PRODUCTS, TYCO FLOW CONTROL DIVISION, TYCO INTERNATIONAL LTD
ELECTRONIC END USER LICENSE AGREEMENT FOR SPRINKCALC SOFTWARE SUITE
NOTICE TO USER: THIS IS A CONTRACT. BY INSTALLING THIS SOFTWARE YOU ACCEPT ALL
THE TERMS AND CONDITIONS OF THIS AGREEMENT.
This Agreement TYCO FIRE PRODUCTS, TYCO FLOW CONTROL DIVISION, TYCO INTERNATIONAL
LTD (TFP) License Agreement accompanies the SPRINKCALC SOFTWARE SUITE and related
materials (Software). Please read this Agreement carefully. At the bottom of this dialog box you may
Accept this Agreement and agree to be bound by its terms and conditions and continue to install, or
Decline this Agreement, in which case you will not be able to use the Software.
Upon your acceptance of this Agreement, TFP grants to you a nonexclusive license to use the Software,
provided that you agree to the following:
1. NO WARRANTY. ANY USE BY YOU OF THE SOFTWARE IS AT YOUR OWN RISK. The software
is provided for use "as is" without warranty of any kind. To the maximum extent permitted by law,
central disclaims all warranties of any kind, either express or implied, including, without limitation,
implied warranties of merchantability and fitness for a particular purpose. TFP is not obligated to
provide any updates to the software.
2. NO LIABILITY FOR CONSEQUENTIAL DAMAGES. In no event shall TFP be liable for any damages
whatsoever (including, without limitation, incidental, direct, indirect special and consequential
damages, damages for loss of business profits, business interruption, loss of business information, or
other pecuniary loss) arising out of the use or inability to use this TFP Software, even if TFP has been
advised of the possibility of such damages. Because some states/countries do not allow the
exclusion or limitation of liability for consequential or incidental damages, the above limitation may not
apply to you.
3. U.S. GOVERNMENT RESTRICTED RIGHTS. The Software and documentation are provided with
RESTRICTED RIGHTS. Use, duplication, or disclosure by the Government is subject to restrictions
as set forth in subparagraph (c)(1)(ii) of The Rights in Technical Data and Computer Software clause
at DFARS 252.227-7013 or subparagraphs (c)(1) and (2) of the Commercial Computer Software -
Restricted Rights at 48 CFR 52.227-19, as applicable. Manufacturer is TYCO FIRE PRODUCTS
451 N Cannon Avenue/Lansdale, PA 19446.
If you acquired this product in the United States, this Agreement is governed by the laws of the
Commonwealth of Pennsylvania. This document was produced by
2
Table of Contents
3
SETTING THE DEFAULTS ......................................................................................................................... 58
Setting the Piping Materials Defaults................................................................................................. 58
Setting the Fittings, Nodes and Pumps Defaults................................................................................. 59
Setting the Fluid and the Model.......................................................................................................... 59
USING THE TREE/GRID GENERATOR....................................................................................................... 60
Spacing ............................................................................................................................................... 61
Layout ................................................................................................................................................. 62
Materials............................................................................................................................................. 64
Using the Auto RA Button.............................................................................................................. 65
Manually Adjusting the Remote Area ............................................................................................ 65
Insert ................................................................................................................................................... 67
VIEWING THE SYSTEM IN 3D .................................................................................................................. 68
ADJUSTING THE DRAWING FOR THE UNDERGROUND ............................................................................. 69
OVERRIDING PIPE LENGTHS ................................................................................................................... 73
ADJUSTING THE SYSTEM RISER .............................................................................................................. 76
SPLITTING THE BRANCH LINES TO ADD STARTER PIECES ..................................................................... 77
ADJUSTING THE OUTRIGGER SIZES......................................................................................................... 82
CALCULATING THE SYSTEM ................................................................................................................... 83
Running a Supply Calculation ............................................................................................................ 89
TUTORIAL #3: USING MANUAL ENTRY ......................................................................................... 92
ADDING A HOSE VALVE ......................................................................................................................... 93
CHECKING THE FLOW DIRECTION .......................................................................................................... 94
LAYING OUT THE SYSTEM ...................................................................................................................... 95
TUTORIAL #4: BUILDING A SYSTEM WITH NODE COMMANDS .......................................... 105
4
Tutorial #1: Calculating a Simple Tree with the Tree/Grid
Command
This tutorial will guide you through the more common functions of SprinkCalc. You will be
generating a tree system that will include all of the components that are required to perform
hydraulic calculations.
5
The figure below shows the plan view of the system.
This system is designed for an Extra Hazard Occupancy with a Design Area of 2500 ft2.
6
The figure below is a three dimensional view of the system.
Starting SprinkCalc
Start SprinkCalc by navigating to the Windows START menu located on the bottom taskbar.
7
If the shortcut has already been created, you can also double-click on the
Desktop icon.
When SprinkCalc opens, the main screen will appear as shown below.
The screen will be blank, as shown in the diagram above. You are now ready to begin entering
your data.
8
Saving the File
Before building your system, it is important to save your file to disk.
To save your file, select Save from the File pull down menu.
In addition to using the File pull down menu, you may also use the
Save button or the hot key combination Ctrl+S.
Navigate to a folder where you would like to save the file. The example above shows Projects
as the selected folder. Enter turorial1 in the File Name cell and press the Save button.
9
Setting the Defaults
To set the default values for your system, select Defaults from the
Tools pull down menu.
To view the values in the Schedule, pick the OrdinStl button to the right of the Apply Schedule
box.
10
This is one of the Schedules that ships with the software. You may modify this one or create
new schedules as you wish from within the program. For now, you will use the existing
Schedule for this tutorial. Close the Schedule dialog box and return to the Defaults dialog box.
The Hose value will be 0 GPM. This is the default flow for any inside hoses that are added to
the system. Since there are no inside hoses for this system, the entry here is not relevant. The
Pump Limit value restricts a calculation if the pump flow exceeds the entered factor multiplied
by the rated flow.
11
Setting the Piping Materials Defaults
You control the pipe roughness factors and internal diameters
through the Piping Materials dialog box. Open this box by selecting
Piping Materials from the Tools pull down menu.
Here you can specify the internal diameters and C-Factors for various pipe types. The Absolute
Roughness value is used for Darcy-Weisbach calculations. Check to ensure that your C-Factors
and internal diameters are correct. When finished, close the dialog box.
12
Using the Tree/Grid Generator
The Tree/Grid Generator is used to simplify the process of building
a system.
To access the Generator, select Tree/Grid from the Edit pull down
menu.
13
Spacing
The Spacing window is the first to appear.
The Spacing window is used to enter criteria about the Design Area, Spacing of the branch
lines and the Water supply.
In the Design Area, enter a value of 2500 as the Proposed size and a Square Multiplier of
1.2. The Square Multiplier will control the shape of your design area rectangle.
In the Spacing Area, enter a 6 for the total Number of Branch Lines. Also, enter 6 for the total
Number of Sprinklers per branch line. The Total Number of Sprinklers is automatically
calculated as 36. The Distance Between Branch Lines will be 10 ft and the Distance
between Sprinklers on the branch lines will be 10 ft. The Coverage per Sprinkler is
automatically calculated as 100 ft2.
Enter the Water Supply information in the bottom area. The Static Pressure will be 90 psi and
the Residual Pressure will be 85 psi at a Flow of 2000 gpm.
14
Layout
The Layout window will appear after pressing Next.
The Layout window is used to enter information about the Mains and Elevations for your
system. The drawing below shows the mains in the plan view. First, you will specify the location
of the cross main. The Near Main is located 2 heads and 7 feet over from the left end of the
branch lines.
15
In the Near Main area, pick the Heads Left cell with your mouse and enter a value of 2. Move
to the Offset cell and enter a 7 as shown in the diagram below.
As you enter values, the diagram on the right side of the dialog box will change. This diagram
allows you to visualize what your system will look like when distances and elevations are
specified.
16
Enter the Elevations as shown.
You may have to use the Zoom All button in the Graphics View to see the whole system.
When you have finished entering the values, press the Show 3D button.
17
Materials
The Materials window has several areas for entering information including the K-factor, Piping
Material, and the default Fittings. You can also generate a 3D preview of the system. The
various cells should be filled by the Defaults that you set earlier. Ensure that the dialog box is
set up as shown below. Although you have selected a Pipe Schedule for your branch line sizes,
you are free to override the Schedule here or after the system is created.
When the Piping and Fittings areas have been completed, you can generate the remote area.
SprinkCalc will generate a remote area automatically when you pick the Auto RA button at the
bottom of the window. You can also generate a remote area manually by picking the nodes with
your mouse.
Pick the Auto RA button located
directly below the drawing
window.
18
Manually Adjusting the Remote Area
When a remote area has been drawn, you can adjust it by selecting or deselecting nodes.
Hover the hand over the node you wish to deselect and pick it as
shown to the right.
When a node is selected, the remote area box will change shape as
shown in the diagram to the left. The values for Heads and Actual
Remote Area size will also change as you select heads.
You can also draw a window around a series of nodes to deselect or select more than one.
When the outline of the remote area has been established, press the
Build RA button at the bottom of the dialog box.
19
The Tree/Grid dialog box should now appear the same as the diagram below.
If the remote area is not the same as shown, use the Select RA button to
return to the full system where the remote area may be established again.
When the remote area is set up, press the Next button.
20
Insert
The Insert window contains a Shift area, Rotate area, Flip area, Attach area and a graphic for
generating a 3D preview. When finished using the window you can add the system to the main
screen.
The Shift area is for entering X, Y and Z (elevation) values which will move the entire system in
the specified direction and distance.
The Rotate area is used to enter values that will re-orientate the new system.
The Flip area is used to mirror the system relative to one of the three axis or the origin point.
The Attach area is used to identify a node in an existing system where this new system will be
attached.
In this tutorial, you will not be adding a system to an existing system, so leave the Attach and
other areas blank.
When the system appears as shown in the diagram above, press the Insert button.
21
A graphic of the new system will be inserted into the Graphics View. The system information will
be placed in the Pipes and Nodes Views.
The Buttons allow you to rotate the image around the X, Y, and Z-axes. This gives you the
opportunity to view the system from a variety of perspectives.
22
Viewing your system in 3D
There are four Graphics View buttons which can be used to manipulate your system into
different 3D perspectives.
The 3D View button is used to move your system along the X, Y and Z
axis simultaneously. Pick this button and move your mouse to the
Graphics View. Press your left mouse button and move the mouse
around to get the desired perspective.
The Rotate X, Rotate Y and Rotate Z buttons behave in a similar manner except that the object
will be moved, around the respective axis only. Practice with these buttons to get various
perspectives of your system. You will find it helpful to observe the orientation of the XYZ icon
when using the 3D buttons.
You will find out later in the Tutorial how to show information such as node
numbering and pipe flow direction in the Graphic View.
23
Adjusting the Drawing for the Underground
Rotate your system until it has a perspective
similar to what is shown here.
Although SprinkCalc does an excellent job at generating systems automatically, in most cases
you will have to alter some aspect of it to match your job. For example, the system in this tutorial
must be edited to accommodate the underground pipe.
To add this information several changes will have to be made. The water supply must be moved
and several components added, including a node at the base of the riser, pipes, fittings and
valves.
To view the node numbers, you first have to make sure that the
node numbers are set to appear in the Graphics View. From the
View pull down menu, select Settings.
24
The Graphic Settings dialog box will appear.
From the drop down lists, select Numbering for the Pipe and Node Parameters. Press OK.
You can also hover over a node in the Graphic View and right pick to
open the dialog box shown below.
25
When selected, the number associated with each node will appear in the Graphic View as
shown below.
The water supply is indicated by a node number of src1 as shown above. To make the Node
Numbers disappear, select Node: Numbering from the View pull down menu again.
Another way to search for the water supply node is to use search cells at the top of Nodes View.
If the search cells are not visible, press the closed Eye button at the top left corner of
the View.
When the Eye button is set to the Open position, the search cells are visible.
26
There is only one node that matches the criteria entered in the search cell. Here you can view
the columns for information relating to the Supply node. When finished, pick the Type cell and
delete the criteria. All nodes in the View will return. You can also close the Eye button and all
items will return.
By default, when a system is generated using the Tree/Grid generator, SprinkCalc will assign a
Node # of src1 to the water supply. This Node number is set up by using Node Types from the
Tools pull down menu.
You may also press F2 or use the Properties button to open the box.
27
The Properties dialog box will appear with the data displayed for the selected node.
Moving the Water Supply from the Base of the Riser to the Hydrant
When SprinkCalc generated the system, it placed the water supply at the bottom of the system
riser. Since the water supply test was taken at a hydrant, the node must be moved to that
location. A 150 ft Ductile Iron pipe must be inserted from the water supply to the bottom of the
riser.
Select the src1 node, by hovering your mouse over it and picking it.
The color and size of the node will change when selected. The selected node
will also darken in the Nodes View.
28
Changing the Node Properties
To move the water supply an additional 150 feet, you will need to add 150 to the value
appearing in the Y, ft cell. You can do this by entering an absolute coordinate (i.e. 53 + 150 =
203). You may also enter a relative coordinate with the @ symbol. For example you could enter
@150 in the Y cell to arrive at an absolute coordinate of 203.
The src1 row in the Nodes View will change to match the coordinates specified in the Nodes
properties dialog box. The Graphics View will also change to show the new location of the
Supply node.
29
To refresh the Graphics View and see the changes, select the Zoom All
button. Your screen should appear similar to the diagram below.
30
Delete the pipe with the Delete Pipes command.
31
The information for this node will appear in the Properties dialog box.
To add a new node at the base of the riser, select Add nodes > Add Nodes (Multiple) from the
Edit pull down menu.
32
Recall that the selected node at the top of the riser has an X coordinate of -3, a Y coordinate of
53 and an elevation of 16 feet. This is displayed in the Properties dialog box. The new node at
the base of the riser will have the same X and Y coordinates with an elevation of 0.
33
Connecting Nodes for the System Riser
Next, you will connect the nodes at the top and bottom of the riser.
Press the Connect Nodes button and the Material dialog box will
appear.
Press OK.
34
SprinkCALC will then
prompt with: First
Node is: n12 Please
Select Second Node:
35
If you select this new
pipe in the Graphic
View, its information
will be displayed in
the Properties dialog
box.
36
Installing the Underground Pipe
You can add pipes to your system with the Connect Nodes command, as you just did with the
System Riser, or use the Add Pipes Multiple command. You will use the Add Pipes Multiple
command to insert your underground pipe.
Press the Add Pipes (Multiple) button at the top of the screen.
The Pipe# p2 is the next available pipe number. Select scr1 and n13 as the nodes to be
connected. The Material will be DI 350 and the Size will be 6. From the Fitting drop down list
select Mult.. to add more than one fitting.
The Add Fittings dialog box will appear as shown to the left.
37
Move your mouse to the Amount column and the nTee fitting
row.
Select 1 from the pull down list and it will be added to the cell.
You will return to the Add Pipe dialog box with the fittings
added. Press OK to insert the new pipe.
38
Setting up an Alarm Valve
You will need to create an Alarm Valve to add to the system riser.
To set up an Alarm Valve, select Fittings and Valves from the Tools
pull down menu.
The Fittings and Valves dialog box has two tabs at the top: NFPA13 and Custom.
The NFPA13 window contains several fittings that ship with SprinkCalc. You cannot edit any of
the fittings appearing in this window. Equivalent lengths are listed to the right of the fitting
names. This table is referenced for n type fittings and adjusted if necessary for the C-Factor
and non-schedule 40 pipe diameters.
If you wish to add, delete, rename or edit fittings you must select the Custom tab.
39
When selected, the Custom window will appear as shown here.
The Custom window contains various sizes along the top of the window and 3 buttons along the
bottom. To add a new fitting, select the Add button with your mouse.
Press OK.
40
Scroll through the columns until you find the 4 column header and pick it. Enter an equivalent
length of 28 as shown below.
The new valve Alarm will be added to the database and become available when choosing
fittings for 4" pipes.
41
Make sure that the Properties dialog box is open.
42
Next, you need to add a Gate valve. Navigate your mouse to the nGate valve and add a value
of 1.
43
First, you would like to see how SprinkCalc has sized the pipe. There are several ways in which
you can do this. You can check the pipe sizes in the Pipes View or select the pipes in the
Graphics View and then check the size in the Properties dialog box. You can also check the
sizes in the Graphics View when the pipe sizes are turned on.
44
The pipe diameters will now appear in the Graphics View.
The pipe diameters will be displayed as actual internal diameters. From this you can see that
the second pipe segment from the end of each branch line on both sides of the main must be
changed to 1 from 1. All other pipe sizes match the plan.
First, you have to make sure that no pipes are selected otherwise you may mistakenly adjust
the size of the wrong pipe. All pipes will become unselected when you pick any pipe in the Pipes
View.
Hold the Ctrl key down while picking the pipe you just selected and the pipe will become
unselected.
Now you can be sure that no pipes are selected in your system.
45
Next, you will select the branch line pipes that need to be changed.
You'll have to hold the Ctrl key down while picking to select multiple pipes.
46
Calculating the System
Now, you are ready to calculate your system. To start a Demand
calculation, select Demand from the Calcs pull down menu.
Enter a Minimum
Density of 0.30 and
a Sprinkler
Coverage of 100
GPM / ft2.
The Results dialog box will appear indicating that the calculation is complete. Press the Close
button to exit the box.
47
The Flow Diagram
To see a flow diagram of your system, select Flow Direction
from the View pull down menu.
The basic flow diagram will show the direction of flow in your
Graphics View.
48
The Summary Sheet
To view the Summary Sheet, select Summary from the View
pull down menu.
49
The Analysis
To view the water supply curve with your system calculation,
select Analysis from the View pull down menu.
The Analysis dialog box will show system demand and water
supply curves as well as other useful data on your calculation.
Enter a value of 500 GPM for the outside hose allowance in the Hose Flow cell. From the
Show curve area you can select the criteria that you would like to show on the graph. System
Demand, and Supply, Out Hose were selected in the example above. You can also press the
Heads button to view the discharge details for all of your sprinklers.
50
Setting Up Views
With SprinkCalc you can set up your Nodes and Pipes Views to show the criteria that you want.
The printed reports will show the same information that appears in the screen Views. You will
now set up your own custom Views and print your reports.
51
Press the Nodes tab at the top of the dialog box and then select the Default tab at the bottom.
You will create a custom Nodes View first and then a Pipes View. By selecting the Default
View, you will be using it as a template for your new View. Press the New button as shown
above.
The Node Layout dialog box will open. Enter Calcs as your
new style and press OK.
Your new Calcs View will appear in the row of tabs at the
bottom of the dialog box.
Make sure that Calcs is current and press the Edit button.
The Node Layout dialog box will appear. Set the Lines Per
Row value to 1. This will list all of your node criteria in one
row only.
The Options dialog box will return. Eliminate all headings except Node#, Type, Elev, K-Fact.,
Discharge, Hose and Ttl. Pres.
52
You should be left with what is shown below.
To add headers to your View, double click on the item from the list on the right side of the dialog
box. You may also drag the headers with your mouse to change the order. Your new Nodes
View is now complete.
Select the Pipes tab. You are now going to create a custom Pipes View.
Start with the Defaults tab for a template and create a new View with the name Calcs. Set the
Rows to 1 and setup the headers as shown above.
53
Select Calcs from both the Nodes and Pipes drop down lists. Your setup will now appear in the
Nodes and Pipes Views.
The information shown in your printed reports will correspond with the current View style. For
example, if you were to print a Node report with the new Calcs style, the Node Number, Type,
Elevation, K-Factor and Total Pressure would be shown. You would also sort the data in the
order that you want before printing. SprinkCalc has several sorting options. The easiest of these
is to pick the headers in the Pipe or Node views and the data will be sorted in ascending or
descending order.
This is also true for the Graphics View when printing a Flow Diagram. Set up the Graphics View
with the perspective that you want and turn on any node or pipe information that you would like
from the options set up though the View > Settings dialog box.
Now, you can go to the File pull down menu and select Print. A dialog box will appear where
you can specify which results you would like to send to the printer. For this example use Calcs
for the Nodes and Pipes Views and US as the units.
54
Tutorial #2: Calculating a Grid with the Tree/Grid Command
The Tutorial System
The system is a simple grid with grooved, Schedule 10, black steel mains. The main outlets are
welded pipe-o-lets. The riser nipples and outriggers are threaded Schedule 40 black steel pipe
with cast iron fittings. The grid branch lines are Schedule 10 black steel with welded outlets for
sprinklers and grooved ends for couplings. All Sprinklers are on 12" sprigs. The underground is
6" Ductile Iron. The figures, which follow, show details of the system. The figure below is the
system riser.
The figure on the next page shows a plan view of the system. The grid lines are all 1 1/4"
Schedule 10 between the mains. The starter pieces are 1 1/4" Schedule 40 and are 1' -0" long.
The outriggers are 1" Schedule 40. Spacing between sprinklers on the branch lines is 11' -6".
Spacing between the branch lines is 10' -0". The near main and feeder main are 2 1/2"
Schedule 10. The far main is 2" Schedule 10. The riser nipples are 1 1/2" Schedule 40. The
branch line elevation is 19' -0". The mains elevation is 16' -0". The sprinklers are on 1' -0"
Schedule 40 sprigs.
55
56
The system is designed for an Ordinary Occupancy with a design area of 1500 ft2. The figure
below is a three dimensional view of the system.
57
Setting the Defaults
58
Setting the Fittings, Nodes and Pumps Defaults
Pick the Fittings, Nodes and Pumps tab
with your mouse.
You will not be using a pump so leave the Pump Limit at 1.5.
59
Using the Tree/Grid Generator
The Tree/Grid Generator is used to automatically generate
systems by entering design criteria.
60
Spacing
The Spacing window is the first to appear.
The Spacing window is used to enter criteria about the Design Area, Spacing of the branch
lines and the Water supply.
In the Design Area, enter a value of 1500 as the Proposed size and a Square Multiplier of
1.2.
In the Spacing Area, enter a 6 for the total Number of Branch Lines. Also, enter 8 for the total
Number of Sprinklers per branch line. The Total Number of Sprinklers is automatically
calculated as 48. The Distance Between Branch Lines will be 10 ft and the Distance
between Sprinklers on the branch lines will be 11.5 ft. The Coverage per Sprinkler is
automatically calculated as 115 ft2.
Enter the Water Supply information in the bottom area. The Static Pressure will be 50 psi and
the residual pressure will be 45 psi at a flow of 1000 gpm.
When completed, press the Next button to open the Layout window.
61
Layout
The drawing below shows the mains in the plan view. First, you will specify the location of the
cross main. The Near Main is located 1 head and 9.5 feet over from the left end of the branch
line.
In the Near Main area, pick the Heads Left cell with your mouse and enter a value of 1. Move
to the Offset cell and enter a 9.5 as shown in the diagram below.
As you enter values, the diagram on the right side of the dialog box will change. This diagram
allows you to visualize your system when distances and elevations are specified.
62
There will be a Far Main since this is a grid. Check the Heads Right box, enter a 1 in the cell
and enter an Offset of 9.5 feet.
Specify the Feed Main location as 6 branch lines out with an offset of 3 feet. This will locate the
start of the Feed Main at the top of the system as shown below. Enter a Feed Main Length of
-20 feet. This will place the other end of the feed main 20 feet to the left. If this value were
positive, the feed main would extend to the right.
Enter the Elevations as shown. Since the sprinklers are on 1' -0" springs, there will be a one
foot elevation difference between the sprinklers and the branch lines.
You may have to use the Zoom All button in the Graphics View to see the whole system.
When you have finished entering the values, you can press the Show 3D
button to view your system in three dimensions. For information on how to
do this, see Tutorial #1.
63
Materials
The Materials window has several areas for entering information; K-factor, Piping, and
Fittings. You can also generate a remote area for the system. The various cells can be
changed to the Defaults that you set earlier by pressing the Defaults button. Ensure that the
dialog box is set up as shown below.
Note, since you have specified a far main, the pipe schedules are not available. The pipe
schedules are only available for tree systems.
When these areas have been completed, you can generate the remote area.
64
Using the Auto RA Button
SprinkCalc will generate a remote area automatically when you pick the Auto RA button at the
bottom of the window. You can also generate a remote area manually by picking the nodes with
your mouse. Pick the Auto RA button located directly below the drawing window.
When a remote area has been drawn, you can adjust it by selecting or deselecting nodes. For
this tutorial you will be selecting more nodes than are necessary so that you can manually find
the most remote area by performing a series of calculations.
65
Using the Build RA Button
When the outline of the remote area has been established, press the
Build RA button at the bottom of the dialog box.
The Tree/Grid dialog box should appear the same as the diagram below.
If the remote area is not the same as shown, use the Select RA button to
return to the full system where the remote area may be established again.
When the remote area is set up, press the Next tab.
66
Insert
The Insert window contains Shift ,Rotate ,Flip and Attach areas and a window for generating
a 3D preview. When finished using the window you can add the system to the main screen. The
Attach area is used to enter information about attaching remote areas to existing systems. The
Shift ,Rotate , and Flip areas are used to enter values that will re-orientate the new system.
In this tutorial, you will not be adding a system to an existing system, so leave all areas blank.
When the system in the window appears as shown in the diagram above, press the Insert
button.
67
A Graphic of the new system will be inserted into the Graphics View. System information will be
placed in the Pipes and Nodes Views as shown below.
Use the buttons to view your system in 3 dimensions. For information on using these buttons,
see Tutorial #1.
68
Manipulate your system until it appears as shown below.
69
The Properties dialog box will show the
attributes of the scr1 node.
Start the Add Nodes (Multiple) command and enter the values as
shown.
Press OK to finish.
70
Use the Zoom All button in the Graphics View to expose the new Water Supply node.
Ensure that the Properties Dialog box is open and select the Water Supply node in the Graphics
View.
71
Set the Pipe Type to Undg.
The Starting Node will be src1 and the ending node will be BASE. The material will be DI350
with a size of 6 inches. From the Fitting drop down list select Multi.. and select two n90ells and
one nTee. The length will be 150 feet. Press OK to finish. With the Add Pipes (Multiple)
command you can add pipe and fittings in one step.
72
Overriding Pipe Lengths
With SprinkCalc you can override the calculated distance between nodes. You may want to use
this feature if you have a long pipe in your system which takes up too much of the Graphics
View. You may also use this feature for pipes that do not follow a direct line between two points
such as with plastic pipe that has been bent to avoid obstructions.
In your grid system the underground pipe takes up a large portion of the Graphics View. You will
now change this to a shorter appearing pipe which still has the 150 length attribute.
Open the Properties dialog box and use the Select Nodes button to select the Supply Node.
The attributes of the Water Supply node will appear in the Properties dialog box.
73
Change the Y Coordinate value to 73.
This will move the Water Supply node 130 feet closer to the riser. Now, pick the underground
pipe with the Select Pipes button and view the Properties dialog box.
74
The calculated length of this pipe between nodes is now 20 feet. SprinkCalc will use this
distance for calculations unless you override it.
75
Adjusting the System Riser
You must now adjust the system riser. Pick the riser in the Graphics View and note the
attributes in the Properties dialog box.
Change the Node Type to Pipe. The size will be 4 inches and the schedule will be 10. From the
Fittings drop down menu add a nGate valve and the Alarm valve that you created in Tutorial
#1.
76
Splitting the Branch Lines to Add Starter Pieces
Schedule 40 starter pieces are found on both ends of all 6 branch lines. In order to add the
starter pieces, the branch lines must be split. The starter pieces connect to the branch lines 12"
from the riser nipples. The diagram below shows how these pieces are arranged.
To enter the starter pieces, a new node must be inserted at the point where the Schedule 10
and Schedule 40 pipe meet. After a new node has been inserted, the branch line will be split
and new pipe sizes and schedules can be specified.
All grid branches will have to have a node inserted 12" towards the inside of the grid.
Start the Split Pipes command from the Edit pull down menu.
77
The Split Pipes dialog box will appear:
78
Be careful when splitting
the pipes on the far
main.
Also, make sure that you insert starter pieces in the lines which have no sprinklers as shown
below.
79
Here is an example of the Split Pipes dialog box settings for inserting the starter piece node on
the near main side.
Note, the total length of the grid line is 61.5 feet. The length to the new node is 1 foot and the
schedule for this piece is 40. This leaves 60.5 feet remaining to the far main riser nipple. Note
also that the pipe has two tees because it is picking up the far main riser nipple tee as well.
When splitting pipes with fittings you must option to place all of the associated fittings with one
of the split pipes. In this example there are two tees with the new starter piece. You will correct
this in a moment. Continue to split the near main lines for starter pieces until all three are split.
Next, split the far main branch lines which have no sprinklers. Here is an example for splitting
the pipe for the starter piece on the far main side.
The length of the existing pipe is 60.5. The new node will be inserted 59.5 feet from the starter
piece node on the near main side. This leaves 1 foot of pipe to the far main riser nipple. This
piece is schedule 40 and has no fittings allocated from the split.
80
Check your new pipes by selecting them in the Graphics View and checking the pipe criteria in
the Properties dialog box.
Correct each starter piece on both sides of the grid so that each has one has one nTee. This is
most easily accomplished by selecting all of the starter pieces at once in the Graphics View and
specifying the fitting in the Properties dialog box.
81
Adjusting the Outrigger Sizes
Now that the branch lines have the starter pieces added, adjustments must be made to the
outriggers. The threaded outriggers are 1" and require Schedule 40 pipe rather than Schedule
10.
82
Calculating the System
Recall that when you used the Tree/Grid Generator you selected more flowing nodes than are
required for the remote area. You did this so that you could determine the most remote area in
the system.
Any node in the system with Head as the Type is an operating sprinkler. When you run a
calculation, the flow from any Head Node will be included.
For the calculation procedure you will be changing the node types thus activating different
sprinklers within different remote areas. Calculations will be made on different remote areas to
determine which is the most remote.
First, change all of the Head type nodes to Node type nodes. A node with the type Node is non-
flowing.
In the Properties dialog box, select Head from the pull down list. All of the Head nodes in the
system will be selected.
83
Adjust your drawing so it appears similar to the diagram below. With the Node Select button
and the Ctrl key depressed, select the 14 nodes as shown:
You have to use an isometric view here because the nodes are at the top of sprigs. If you
attempt to pick the nodes from the plan view, you may pick the nodes that are on the branch
lines.
This is the remote area that SprinkCALC originally determined with the Tree/Grid Generator.
84
Run a Demand calculation and record the results for the system demand.
The coverage is
115 ft2 and the
density is 0.15. The
minimum pressure
(Water) will be
calculated as 9.489
PSI.
85
Select the three nodes to the left as shown and change the type to Node.
Select the three nodes to the right as shown and change the type to Head in the Properties
dialog box. Also set the K-Factor to 5.6.
86
Now, you can perform another calculation and compare it to the first.
Start a demand
calc again and
enter the density of
.15 and the
coverage of 115.
Press Run.
Return to the first remote area by changing your node types. Perform another Demand
calculation. Now, you can view your calculation results with the Analysis dialog box and produce
a printout as required.
87
From the View pull down menu select Analysis. The Analysis dialog box will appear:
Enter 250 GPM for the outside hose allowance in the Hose Flow cell. This will make any of the
hose dependant curves available for viewing. Select Supply, Out Hose and System Demand
from the Show curve area. The System Demand curve slopes up from about 9 PSI at zero
flow to the minimum demand point at 255 GPM @ 38 PSI. The Supply, Out Hose is the supply
curve modified for the outside hose allowance. This curve appears along the top of the graph.
You can select any curve that appears in the Show curve list and it will appear in the graph.
88
Running a Supply Calculation
The previous Demand calculation is based on the minimum pressure and flow required to
support your sprinkler system. You will also want to know how your system performs with the
specified water supply. This is a Supply calculation.
To run a Supply calculation based on your specified water supply, first run a
Demand or Supply calculation and then view the Analysis dialog box.
89
The Analysis dialog box will show you the results of your Demand calculation,
Now, to run a Supply calculation, press the Advanced button at the bottom of the dialog box.
The Advanced Options dialog box will show pressures and flows depending on whether you
specified a Safety Pressure in the Analysis dialog box. The example above shows a system
where a Safety Pressure has not been specified in the Analysis dialog box, hence, no values
are available in the lower area. The displayed pressure and flow are determined by SprinkCalc
by extending the demand curve to the point where it intersects with the supply curve. To run a
Supply calculation, press the Supply button.
90
The Supply dialog box will appear with the pressure entered from the Advanced Options dialog
box.
For this example the Safety Pressure should be close to zero. Press the Close button and the
Analysis dialog box will reappear showing the result. Your system requirement will be displayed
at the top left.
To view the supply point select Supply Flow@ Fixed Pressure from the available curves. You
can now view any pipe or node in the system to gather more specific information. For some jobs
it may be necessary to calculate a few Supply calculations through the Advanced button until a
safety pressure approaching zero is reached.
91
Tutorial #3: Using Manual Entry
If you prefer a more traditional input method and you dont want a graphical representation of
your system, use the Manual Entry dialog box. You wont lose any of the precision or
functionality of the SprinkCalc calculation engine by using this method. This tutorial will show
you how to calculate the standpipe system shown below with the Manual Entry dialog box.
92
Adding a Hose Valve
Before entering your system, you have to make sure that hose valves exist in your equivalent
lengths database.
From the Tools pull down menu, select Fittings and Valves.
The Fittings and Valves dialog box will open. Select the Custom tab.
93
The angle valve will now appear in the list.
From the Tools menu, select Defaults. The Defaults dialog box will
open.
94
Laying Out the System
Open the Manual Entry dialog box from the Edit pull down menu.
Begin by entering your water supply information in the cells at the top.
The supply node name will be TEST. The static pressure is 50 PSI. The residual pressure is 45
PSI at 1650 GPM. The elevation of the supply node is 0.
95
Start by entering information from the most remote standpipe.
Q 250
K= = = 25
First, calculate the K-Factor for the hose connection H1. p 100
Since this is a Class I system, you require 250 GPM @ 100 PSI at the most remote hose
connection. You may enter your information with the flow ( 1 to H1) or against the flow
( H1 to1) and SprinkCalc will reverse the order for you automatically. For this example you will
enter the nodes and pipes against the flow. Enter the hose connection H1, K-factor and the rest
of the row as shown below. Enter the data with the keyboard or select items from the drop down
lists. When you press the Enter key you will shift to the next column.
In the Fittings column select Mult.. and enter an angle valve and a tee. After entering 80 as the
elevation, press the down arrow key to start the next row or press the Enter key. There you will
define the standpipe from node 1 to node 2.
96
There will be no K-Factor in this row. Delete any unnecessary items with the delete key. The
elevation of node 1 will be 80 feet. Fill in the other information as shown.
Press the Enter key to start the next row. Here you will enter the standpipe information from
node 2 to node 3. There will be an additional 250 GPM hose at this node.
Notice that 250 was entered under the K-Factor column. This is for the 250 GPM hose flow on
the second floor. If you enter a number in this column it will be interpreted by the program as a
K-factor. If you enter a number preceded by a negative sign, it will be interpreted as a hose flow.
Enter the rest of the values as shown.
97
Continue adding values for the remaining nodes on the standpipe. These nodes are on each
floor and will be used to determine if and where pressure reducing valves are required.
The next entry is for node 9 to node10. Dont forget the 90 elbow at node 9. Enter the values as
shown.
98
The next entry is for the pipe leading from node10 to the pump. Enter the values as shown
below. Enter an additional hose flow at node 10. This is for the other standpipe.
99
As you enter data in the Manual Entry dialog box, the default pipe type is a Pipe. Here, you
must change this pipe to a Pump.
Press OK to finish.
Press the Exit button at the top right corner of the screen to exit the dialog box and enter the
SprinkCalc screen.
100
Save your file and then perform a Demand calculation.
Enter a minimum
flow of 250 GPM in
the cell as shown,
press the Select
All button and then
the Apply button.
The minimum
pressure of 100
PSI will be
calculated
automatically.
101
Open the Analysis dialog box and select the Supply and System Demand curves.
Since the pipe type was entered as a pump, the pump has become part of the system and will
be reflected in the system demand curve. As a result 750 GPM @ 46.9 PSI is required from the
city supply.
You can view the Node and Pipe information on the screen for a further analysis of the system.
Use the Calcs Views that you created in Tutorial #1.
102
From the previous results it is apparent that a smaller pump may be used with a higher rated
pressure.
Select the
pump row in
the Pipes View
and open the
Properties
dialog box.
103
The previous method of calculating standpipe systems is acceptable, however, you may
achieve a more precise calculation by balancing the system. To do this you would provide K-
Factors for all hose connections.
Return to the Manual Entry screen. All of your previous data will still be there.
Modify the screen as it is shown above. You can use the Delete and Insert buttons at the top left
to remove or add rows as needed.
After doing a Demand calc your system will be balanced with node H1 flowing at the minimum
flow and pressure. The other hose connections, H2 and H3 will show the actual flows and
pressures when the system is operating with H1 at the minimum.
You can modify your pump criteria as you did before to get an acceptable safety margin.
104
Tutorial #4: Building a System With Node Commands
In addition to using the Tree/Grid Generator and the Manual Entry dialog box, you may also
build systems manually with SprinkCalcs node commands. To do this, you will use the Add
Nodes (Array), Add Nodes (Multiple), and Connect Nodes commands extensively.
For this tutorial you will be building a system with sloped branch lines.
Start a new project and SaveAs.. to your project folder. Open the Properties dialog box and
position it in a convenient location on your screen.
105
Press the Front View button to have a look at your new branch line.
Notice that your branch line slopes upward from left to right. Node 1 is to the left. Looking at the
Node and Pipe Views, you can see that the pipes and nodes have been created for you.
106
Press the Add Nodes (Array) button again to start the command.
The Add Nodes dialog box will appear again. Notice that your original
settings are retained from your earlier branch line.
107
Press the Add Nodes (Array) button again to start the command.
The Add Nodes dialog box will appear again. Once again, your
original settings are retained from your earlier branch line.
Now, your third branch line will be created. You may have to use the Zoom All button now to
see all of the branch lines.
108
You can continue to add as many branch lines as you would like using this technique with the
Add Nodes (multiple) command. You can keep your branch lines level by entering a value of 0
in the Step Elevation cell.
Next, you will specify a point on the last branch lines where the riser nipples will be connected.
Press the Split Pipes button. The following dialog box will appear:
109
Press OK and the pipe will be split and the new node inserted as shown.
Press the Delete Nodes button at the top of the screen to delete this last
node.
110
The Delete Nodes with pipes dialog box will appear:
111
With the 3D Zoom tools, manipulate your graphic so that it appears similar to the view shown
below. Open the Properties dialog box.
You are now going to insert your riser nipples. Select the node as shown below:
The values for this node will appear in the Properties dialog box. To insert a new node you will
need the X, Y and elevation of this existing node.
112
Pick the Add Nodes (Multiple) button to add new nodes. The
nodes which will be added are where the riser nipples will attach to
the cross main.
The riser nipples will be 3 feet long. Note the coordinates of the selected node on the branch
line in the Properties dialog box. The Elevation is 15.5 feet, the X value is 66 feet and the Y
value is 0. The new node will have the same X and Y values. The only difference will be the
elevation which will be 12.5. You get this by subtracting 3 feet from the existing node elevation.
113
You can add these nodes one at a time or add all three at the same time. For this exercise you
will add all three at once.
Press OK to finish.
114
The new nodes will appear as shown below in the Graphic View.
Now, you will add the riser nipple pipes. Press the Connect Nodes
button at the top of the screen.
Press OK.
First pick
the node
on the
branch
line.
Then pick
the new
node at the
cross main.
115
The new pipe will be added as shown below:
Continue with the Connect Nodes command to add the other riser nipple pipes.
116
Now, you will add your cross main pipes. Press the Connect Nodes button again and connect
the nodes at the bottom of the riser nipples.
Insert the second cross main piece as shown below. The command will continue until the Esc
key is pressed.
117
Now, you are going to add the required fittings to the branch lines and adjust a few pipe sizes.
Select the pipes as shown below. Hold down the Ctrl key and use the Select Pipes button.
In the Properties dialog box make sure that Selected is chosen from the drop down list. This will
ensure that any changes you make will occur on your three selected pipes.
118
From the Properties dialog box, select Rnppl to
select all of the riser nipples you just inserted.
119
Manipulate your Graphic View so that it is similar to the image shown below:
You are now going to insert your mains. Select the node at the bottom of the third riser nipple to
use as a reference. Its values will appear in the Properties Dialog box.
Pick the Add Nodes (Multiple) button to add new nodes for
your mains.
120
The first node will be at the same
elevation as the selected node.
121
Press the Connect Nodes button at the top of the screen to connect the nodes that you just
inserted.
122
Select the Node BASE at the bottom of the
riser.
123
Your system should now appear as shown below:
If you tried to perform a Calculation now, the program will not permit you to do so. You have not
yet identified which nodes are operating sprinklers.
124
Recall when you inserted the branch lines and nodes with the Add Nodes (Array) command. In
the dialog box you had the option of inserting the nodes as a type "Node" or a "Head". In this
exercise you inserted the nodes as a "Node" type. By using this method, you can later change
the "Nodes" to "Heads" within your remote area. You can also insert the nodes as a type
"Head" if the Heads are within your remote area. Either method is acceptable.
125
These nodes are now operating sprinklers. Use the View pull down menu to display the Node
numbers.
Press the Demand button at the top of the screen to start a calculation.
Select Hazen-
Williams as the
Hydraulic Model.
Enter a Minimum
Density of .15 and
a Sprinkler
Coverage of 120.
The Minimum Pressure(Water) and Minimum Flow cells will be automatically filled.
126
The Results dialog box will appear showing the system demand pressure and flow.
Enter 250 as the Outside Hose @ Source value. This will allow you to display Supply, Out
Hose which is the city supply with the hose allowance removed. Also select the System
Demand curve to determine where the system demand point occurs relative to the water
supply.
From here you can adjust pipe sizes to fine tune your system. You may also generate a Supply
calculation by pressing the Advanced button.
By pressing the Heads button, you can view the pressure and discharge information for the
sprinklers.
127
Tutorial #5: Adding a Pump to Your System
There are two types of pumps that you can use with SprinkCalc and you should clearly
understand their differences.
This pump will have no effect on your system demand. The purpose of this pump is to adjust the
supply curve. In this way you can plot a supply curve which includes a city supply, outside hose
and pump combined which can be referenced with the demand curve. If the upper right point of
the demand curve falls below the supply curve, then you can conclude that the supply can
satisfy the system requirement.
In this tutorial you will use both types of pumps. First, you will use the Additional Pump @
Source.
Open the Tutorial #1 project that you completed before. For this tutorial you will add a pump to
the system. Save the file as Tutorial5.clc. Manipulate your system in the Graphics View until it
appears as shown below.
128
Open the Properties dialog box and select the water supply node.
129
Change the Geometric Length setting to NO at the bottom of the dialog box. Set the Length to
150 feet.
Now, you have to adjust the system so that a pump is required. Select the Supply node and
view the attributes in the Properties dialog box.
130
Change the Static Pressure to 45 PSI and the Residual Pressure to 30 PSI. Change the
Residual Flow to 1000 GPM. Clearly this water supply will not support the requirements of the
system.
Enter 500 GPM for the Outside Hose and select Supply, Out Hose and System Demand from
the Show curve area. The Demand point is well above the available supply. You need a pump!
131
Using the Additional Pump @ Source
By adding pump specifications in the Additional Pump @ Source cells, additional curves
become available in the Show Curve area of the dialog box. The example below shows your
previous system. Data has been entered for the pump and Supply, Out Hose, Add Pump has
been selected as a curve to display.
This curve combines the effects of the city supply, outside hose and pump. Other options are
available in the list as well. You may enter new values in the Additional Pump @ Source cells
and see the effect it has on the selected curve. After you enter the new values press the TAB
key and the curve will adjust to suit the new data. By using this method you can determine the
correct pump for any given system.
Using the Additional Pump @ Source will have no effect on your system demand calculation or
the Demand curve. You may only have one of these in your system.
132
Installing Pumps as Pipe Types
Another method for installing pumps in your system is to change a pipe type to Pump. You may
install as many of these pumps as you would like and they may be inserted anywhere in your
system.
As an example, you will install one of these pumps in your Tutorial #5 system. Begin by zeroing
the values for Additional Pump @ Source in the Analysis dialog box.
Press OK.
133
The new node will
appear 1 foot away from
the Source Node.
Press OK.
134
Change the Type to a Pump.
This is the same pump criteria that you entered for the
Additional Pump @ Source.
135
Open the Analysis dialog box to view the results.
Here, the Supply + Outside Hose and the Demand curve have been selected. Now, the pump
has become a part of the system and its effects are reflected in the Demand curve. Note how
the System Required Pressure is down to 0.7 PSI. This is because the pump is supplying most
of the pressure required for the system. In the example above, the Demand curve actually
slopes downward as the flow is increased to an end point which is the system demand. The
Demand curve is generated by connecting the pressure point at zero flow with the pressure
point at system demand. The pressure at zero flow is the static pressure generated by elevation
in the system.
In the example above, the system demand pressure at the Supply Node is less than the static
elevation pressure in the system hence the Demand curve slopes down.
136
You can modify the pump parameters through the Properties dialog box. Close the Analysis
dialog box and select the pump pipe again. Open the Properties dialog box.
137
Tutorial #6: Adding In-Rack Sprinklers to Your System
Open your Tutorial #1 project and save it as Tutorial #6. Manipulate the Graphics View to what
is shown below:
138
Press the Select/Unselect Nodes button in the Graphics View.
139
Select the pipe as shown below:
Start the Split Pipes command. The Split Pipes dialog box will appear:
140
Start the Tree/Grid command.
Fill in the Spacing window as shown above. There will be 2 branch lines with 8 sprinklers on
each. The branch lines will be 10 feet apart and the sprinklers will be 10 feet apart on the
branch lines.
Enter the Design area values as shown. These really don't matter at this point since you will be
setting the active sprinklers later.
There will be no Water Supply values. There is already a water supply in the system.
Press Next.
141
The Layout window will appear:
In the Near Main area, set the Heads Left to 4 and the Offset to 5. This will place the drop pipe
in the middle of the branch lines.
In the Feed Main area, set the #Br Lines Out to 2 and the Offset to 10. This will place the end of
the drop pipe up 10 feet from the first branch line. The Feed Main Length will be 10.
Press Next.
142
The Materials window will appear:
The Sprinkler K-factor will be 5.6. Set the branch lines to Sch40 and 1 1/4" diameter. The Near
Cross Main and Feeder Main will be 2" Sch40. This will be the size of your drop pipe.
Use the Select/ Unselect Nodes & Pipes button to select all of the sprinklers on the
branch lines. When all of the sprinklers are selected, press the Build Remote Area
button.
Press Next.
143
The Insert window will appear:
In the Graphics View the new in-rack sprinklers will appear below the ceiling sprinkler system.
This is because you gave them an elevation of zero. From the pull down list, select RACK1 as
the attachment node. You set up this node previously. The coordinates of this node will be
automatically entered. Press the Move button to move the end of your rack system to this node.
144
The in-rack system will appear in the Graphic View.
145
Use the Demand dialog box to set the fixed pressure or flow for your in-rack sprinklers. Recall
from Tutorial #1 that you set your ceiling sprinklers to be K-Factor 8.0.
Delete the values in the Density and Coverage cells and enter 15 in the Required Pressure (W)
cell.
Other useful applications include multi-story systems and multiple systems fed from a common
underground loop.
146
Tutorial #7: Using Darcy-Weisbach to Calculate
The Hazen Williams formula is currently the approved formula for predicting pressure drops due
to friction in water based fire protection systems. One of the limitations of the Hazen Williams
formula is that it CANNOT be used for any fluid other than water @ 60 F.
The Darcy-Weisbach method has been used by other engineering disciplines for many years
and often demonstrates a higher degree of precision than Hazen Williams. It may be used for
water as well as any other liquid which exhibits a constant viscosity at a given temperature.
These fluids, which include water, are referred to as Newtonian Fluids and make up the vast
majority of available liquids.
K-Factor
Manufacturers of Sprinklers provide K-Factors for their heads in their specification sheets.
These K-Factors apply to Water Only in a narrow temperature range. These K-Factors are not
to be used for liquids which may have different viscosities and densities than water. If you use
the Darcy-Weisbach model to perform calculations with devices that have K-Factors, you will
have to use a K-Factor multiplier to get valid calculation results.
There is no easy method for mathematically determining a K-Factor multiplier. The only true
method for determining a multiplier is by testing the device with the liquid that you are going to
use. For this you should make arrangements with your supplier.
Pumps
Any pump specifications that you have for water will not be valid for other liquids. Consult your
pump supplier before attempting to use this program with pumps and liquids other than water.
This also applies to water based solutions.
147
Example
Lets assume that you have a system to calculate with a liquid which we will call Fluid X. Fluid X
has a specific gravity of 1.1 and a dynamic viscosity of 3.38 x 10-4 lb-s/ft2. This liquid is heavier
and more viscous than water.
You have contacted your sprinkler supplier who has performed tests on the sprinkler you wish to
use with Fluid X. They have found out that the sprinkler delivers 90% of the flow at prescribed
pressures than it does with water. From this you can calculate a new sprinkler K-Factor and set
the K-Factor multiplier to 1.0, or use the original K-Factor and set the K-Factor multiplier to
0.90.
148
Setting up the Fluid
You will have to set up Fluid X in the database.
From the Tools pull down menu, select Fluid. The Fluid dialog box
will open. Select any fluid in the drop down list until the cells for the
properties appear.
In the Dynamic Viscosity cell enter 3.38E-4 and press the Tab key. The Kinematic viscosity
will be calculated automatically. Entering 3.38E-4 is equivalent to 3.38 x 10-4 or .000338.
149
For a K-Factor multiplier enter a value of .90. This is
because the tests showed that this sprinkler will
deliver 90% of flow with Fluid X when compared to
water.
Enter the values as shown above. There are 2 branch lines with 4 sprinklers per branch line.
The sprinklers are 10 feet apart on the branch lines and the branch lines are 10 feet apart.
The Static Fluid Supply pressure is 45 PSI. The Residual Pressure is 40 PSI @ 200 GPM.
Press Next.
150
Set up the Layout screen as shown here.
The cross main is 5 feet to the left of the first sprinklers. The cross main extends 25 feet from
the first branch line. Sprinklers and branch lines are at 20 feet of elevation. The mains are at 17
feet and the Source node is at 3 feet Press Next. Set up the Materials screen as shown below.
151
The sprinkler K-Factor is 5.6 for water. The branch lines and riser nipples are 2 Schedule 40.
The mains are 3 Schedule 10. Build the remote area and press Next.
Start a Demand
calculation.
Select Darcy-Weisbach
as the model and select
Fluid X from the drop
down list.
152
The Density and Viscosity of the fluid will be displayed.
Enter a Minimum
Density of .2 and a
Coverage of 100
ft2. Press the
Select All button
and then the Apply
button.
You can now view the Analysis dialog box and perform a Supply calculation if you wish. You
have all of the resources for editing and viewing that you had when running Hazen Williams
calculations.
153
Tutorial #8: Peaking Grids
Here is a quick and easy method for moving your design area for peaking. This method only
works when your design area resides between your mains.
The figure below shows a grid system that has been built with the Tree/Grid generator. The
calculated design area is shown.
Perform a Demand calculation with the calculated area and record the results. Now, you can
easily move the Remote area. Open the Properties dialog box.
154
Tutorial #9: Using Connect Nodes
Connect Nodes is a versatile command which may be used in a number of different ways. This
brief tutorial will show you how the command may be used. Open a new SprinkCalc file and
save it as Tutorial9.clc.
155
Pick node 1 and then node 2.
The pipe will be inserted as shown above. You can press the Esc key now to exit the command
or you can continue to pick nodes. Try picking node 3, then node 4, and then node 5.
The 1 schedule 40 pipes will be inserted between all of the nodes picked. This is a quick way to
insert pipes that are the same size and schedule. Now, select all of these pipes with the
Select/Unselect Pipes button and delete them. You are now going to try a new method of
entry. Start the Connect Nodes command again and, with the same pipe material, pick nodes 3
and then 4.
If you now pick node 3, it will be the starting point for the next pipe. Pick node 3 and then node
2.
156
You can start at another node by clicking on the last node picked. Pick on node 2 and then pick
node 4 and then node 5.
You can figure out what position of the command you are in by observing the command at the
bottom of the Graphic View. Select First Node indicates that the program requires a start node
for a pipe. Select Second Node indicates that the program requires an end node for a pipe.
157
Tutorial #10: Installing Armovers and Return Bends
Open Tutorial #1 and save it as Tutorial #10.
With the Select Nodes button, select all of the Heads on the left side of the cross main.
158
Select Add Armovers from the Edit pull down
menu or use the Add Armovers button.
159
Next, select the eight sprinklers on the right side of the main.
Enter the Sprinkler Horizontal Offset value as 1. This will give you a 1-0 armover in the other
direction. Enter the Sprinkler Vertical Offset value as 1.5 This will place your sprinkler 1-6
below the selected node. If this value is positive, the sprinkler will be placed above the selected
node. Enter an Armover RN/DN value of .33. This will give you a 0-4 riser pipe from the
selected node. Select your pipe specifications from the drop down lists. Press OK.
160
Tutorial #11: Using Pathing
SprinkCalc has a useful pathing routine for sorting your Nodes and Pipes Views in preparation
for printing reports. This tutorial will introduce you to the Pathing command.
Open the project from Tutorial #1 and save it as Tutorial #11. Perform a Demand calculation
with a density of 0.3 and a coverage of 100 ft2 for all sprinklers. You should get a demand flow
of 931GPM at a pressure of 76 PSI.
When you print your results, the nodes and pipes will appear in the order that they are displayed
in the Nodes and Pipes Views. Tutorial #1 demonstrated simple drag and drop techniques for
changing this order. The Pathing command can also be used to organize your Views so that a
path from your operating sprinklers to your supply can be established easily.
Set up your Graphics View so that Node numbers and Pipe numbers are displayed. Also, make
sure that no pipes are selected in the Graphics or Pipes Views.
161
Position the Pathing dialog box so that you can also see the Graphics View.
162
The 1 is the start of your path and you are being prompted to select the first pipe in your path.
In this example, H1 is the most remote head and pipe b1 will be the first pipe selected.
163
Observing the Graphics View note that the Path has stopped at the top of the riser nipple.
The path will continue down the riser nipple and along the cross main until the second branch
line is met. Here the path stops again because there is a split in the pipes and a decision has to
be made.
164
Continue to select the cross main pipes when branch lines are encountered.
By pressing the Close button, the Pathing dialog box will close and leave the Pipes and Nodes
Views unchanged. By pressing the Close and Sort button, the Pipes and Nodes Views will be
sorted based on the order that you just established in the Pathing dialog box. For this example,
press the Close and Sort button.
Note that the Nodes and Pipes Views are now sorted according to the specified path.
165
It is quite probable that the heads and pipes in your path do not follow an incremental order
such as b1, b2, b3, etc. You can change to this now that your path and sorting has been
established.
From the Edit pull down menu select Node Numbers and then
Pipe Numbers. The node and pipe numbers will now be changed
to increment in a logical order as they are sorted in the Pipes and
Nodes Views.
Now, when you print your reports, you will get the pathing that you
just set up.
The Pathing dialog box has additional buttons for Adding, Renaming and Deleting Paths. You
can create several paths if you like.
Use the End Path button to stop a Path before reaching the supply node. Use the Continue
button to continue a stopped path. The Pathing command can be used to easily sort large and
complex systems.
166
Tutorial #12: Using Simplify
You can use the Simplify command to quickly calculate systems that have multiple remote
areas. Start a new SprinkCalc file and name it simplify.clc.
167
Set up the Materials window as shown here.
168
You are now going to define the first remote area. Save As.. your file to the filename
simplify1.clc. Select the 12 Heads in the upper left as shown.
Select Simplify from the Edit pull down menu. The Warning
Dialog box will appear.
Note that the flowing heads must be selected as you have just
done. Press OK .
169
Any extra Nodes, Heads and pipes are removed from the system. The only Heads that remain
are the ones you selected before starting the Simplify command.
Now, you can calculate for this remote area. The node and pipe numbering will remain
unchanged after running the Simplify command. If you want, you can re-number them with the
Node Numbers and Pipe Numbers commands.
To calculate the second remote area, open the simply.clc file again, save it to another file name
such as simply2.clc. Select your flowing heads and run the Simplify command again.
170