Documente Academic
Documente Profesional
Documente Cultură
Prepared for:
Available f rora:
Prepared by:
Chas. T Main Inc.
Under Contract No. EC-77-C-01-2133
Prepared for:
1.1 Summary
' 1.2 Conclusions
CHAPTER 2: INTRODUCTION
APPENDIX A2: , Corona Performance of Single Conductor Ground Wires for UHV
Transmission Lines
REFERENCES
. . .~
DISCLAIMER
1
ACKNOWLEDGEMENT
The authors wish to express their appreciation to all of the people who have contributed
time and effort toward the completion of this report. The authors are indebted to all of
the members of the Project Team and the Review Board for their valuable suggestions
,
and comments, including especially the following:'
1.1 SUMMARY
This guide generally represents the results of the initial portion of a program
sponsored by the U.S. Department of Energy which has the overall objective of
developing new or improved transmission line support systems. This portion of the work
was devoted to the selection of electrical and mechanical design criteria and design
parameters fyr ac systems from 345 t o 1 I 0 0 kV and dc systems from + 600 t o + 1200 kV.
The working voltage is defined as the typical average voltage levels on lines as
compared to the maximum voltage which may occur at the generation end. Working
voltages are used in conjunction with radio and TV interference (RI and TVI), audible
noise (AN) and electric field levels. Maximum voltages are used in conjunction with
insulation requirements.
In order to select conductor and bundle sizes and minimum height of the line, it
is necessary t o establish limits for RI, AN and electric fields. The values selected are
: based on a review of pertinent literature [I-91 .and are listed in Table 1, lines 1-3.
The transmission corridor (TC) widths and phase spacings are based largely on
present practice and extrapolation for the higher voltages. They are listed in Iines 4 and 5.
TABLE I.
5 Phose Spacing m, 7.6 10.0 14.0 18.5 10.0 15.0 30.0 Bundle To Bundle Center.
6 Switching Surge PU
1.7- 2.0
, 1.6- 18
(1.70)
. 1.5-1.65
(1.55)
. -
1.5- 1.65
(1.55) (1.65) (1.65) (1.65)
Ronge
0Sele:ted For Base Case.
Conductor Bundle 46 3x53 4 x 71 6x102 4 x64 4x64 8 x 102 Assum, A l l Conductors Equally Spaced On A Circle.
Number x Diameter Cm
Mid-Spon Clearance 8.5 9.7 1 3.0 195 11.2 15.2 23.8 CeMw Of h n d l e To Earth, Flat Configuration.
To Ground
"v" StringAir Gaps To
1.6 ! 2.4 3.7 7.4 3.3 5.4 14.2
U w 1.1 Multiplier For Air Gap Above Phose
The Side-And Below Conductors.
Insulation Length
I' 1.8 1 2.63 3 -7 6.6 3.4 5.1 12.0 a w e d 4)n Switching Surge ( Clean-Wet 1
"v" String
12 Minimum 0-0 Air Gap
Spacing At Tower
, 2.3 i 3.4 4.9 9.2 - - - F i w d 3 y R l s To Leg Spacing For The DC Systems.
l3
Interphase
lnsulolion Length
. 2'3 3.4 4.9 '
!
9.2 - Not Recommended - -,
k e d On Switching Surge ( Cleon-Wet 1
16 Sag 8 Tensions Used Limit M : 70 % Of Ultimote Breaklng 'Strenp)h ~t 3.8cmOf Radial Ice. final Sags U 14-I8m At 50 C . Ruling Span Of 4 0 0 rn.
17 Bundle Height m 20.0 23.0 28.0 ' 33.0 25.0 27.0 38.0 Center Of Bundle To E a r t h , Flat Configumtion.
At Tower
18 Power Transfer 450 1130 2430 . 59X 2380 3820 13800 DC Pcwer Transfer Is Based On Thermal capacity
MW E Conducl~rs.
S I L =IpuFor AC
The switching surge p.u. levels are based on the use of resistor pre-insertion
breakers o r some other method t o limit the surges and are listed in line 6. .
Using these criteria, this guide shows the detailed development of electrical and
mechanical parameters, and provides a range of values from which a selection may be
made for a specific design situation. Base case values listed in Table 1 were chosen for
develop&ent .of structurr: concepts.
Conductor and bundle sizes t o meet the RI, TVI and audible noise criteria are
listed in lines 7 and 8. Midspan clearances t o ground to-meet the maximum electric field
f
or the National Electrical Safety Code are shown in line 9. The code governs up t o
500 kV; the electric field governs at 765 kV and above.
13, are considerably less, suggesting that a circuit can'be considerably compacted.
Shield angle requirements are listed in line 14. Minimum spacings from shield wire
t o conductor, given in line 15, are determined assuming the shield wire is loaded with ice
and ice has dropped from the phase conductor.
The sag of the conductors, line 16, is determined under loads resulting from 3.8
cm of radial ice and tensions of 70% of ultimate breaking strength. These sags are added
t o the midspan clearance to ground t o give the bundle height at the structure, line 17.
The power transfer values shown for the ac systems. are based on surge impedance
loading as 1 p.u. For selection of the conductors, ampacity values of 2 p.u. are used
based on an assutned outage of one of two lines. While today many lower voltage lines
operate in excess of this loading, it is felt that this SIL loading is realistic particularly at
the higher voltage levels. Line loadings are shown on line 18. For dc systems, it is based
on 5 0 ' ~ conductor temperature.
1.2 CONCLUSIONS
1.2.1 Audible noise and electric fields significantly impact the design of ac .
1.2.2 For the 5 600,,1+ 800 and 2 1200 kV dc transmission systems, the height
of the conductors above ground is not a major factor affecting conductor surface
gradient, but the corona-free electric field at ground level is a direct function of
conductor height. The required minimum height of' dc transmission line conductors
increases with increased pole spacing for a given level of electriqfield. For very large pole
spacings, a bipollr line performs as two monopolar lines.
1.2.3 Audible noise, radio noise and electric field levels determine the values of
electrical parameters such as subconductor diameter, number of subconductors, bundle
diameter and midspan clearance t o ground.
1.2.5 Air clearances and insulator lengths are selected for switching surges under
clean-wet conditions. Under light contamination, sixty hertz voltage determines the
requ~red insulator lengths. After concepts are developed, lightning perfbrmance must be
evaluated.
1.2.8 For the conductor.to shield wire spacing given in Table 1, the audible and
radio noise produced by shield wires at UHV levels is acceptable for diameters of 1.2 cm
or larger. Corona loss is substantial for wires less than 1.2 cm diameter.
f
cross-sectional attenuation curves are included in this guide $for these design
considerations.
1.2.10 The establishment of the "base case" electrical parameters for Table 1
revealed several areas where additional information would be desirable, including:
INTRODUCTION
This Guide presents the initial portion of work in progress for the Department of
Energy research project entitled "Optimization of Overhead Transmission Line Support
Systems for High Voltage Overhead Transmission." Basically, the guide concerns the
selection of criteria for meeting ultimate design objectives. The rationale developed, both
technical and philosophical, should be of benefit t o the transmission line design engineer.
It does not present any specific designs but provides criteria and parametkrs upon which
designs can be made.
The ''Blue ~ o o k " piiblished by EEI [ l o ] and the "Red Book" published by
EPRI [ I 11 provided the engineer with much of the engineering data required for
transmission line design. However, this guide includes a fundamental and searching
re-examination of the art and science of transmission line design and brings together the
mechanical ahd the electrical design parameters. It shows the interrela.tion of these
parameters which can be useful in solving environmental, reliability and economic needs.
Anticipating future power transmission needs for EHV and' UHV lines, and the
increasing emphasis on operational and environmental requirements, this guide deals with
the development o f electrical. and mechanical criteria for the maximum system voltages
for 362, 550, 800 and 1200 kV ac, and .bipolar f 600, f 800 and + 1200 kV dc.
These electrical design criteria include air and insulator clearances based on
achievable switching surge levels, which are not the same for all voltage levels, as well as
provisions for shield wire protection against lightning.
Base case bundle design parameters are selected using conventional phase-to-phase
spacings, and conventional conductor arrays to satisfy corona and electric field criteria
for assumed transmission corridor widths.
Similar design parameters have been developed for the compaction o f circuits
which would have audible noise and electric field performance equal t o o r better than
existing lines. .I
Development of actual structure concepts and proof testing, both physical and
electrical, would be the subject of continued research.. , . .
CHAPTER 3
The nominal system voltages used in this guide are listed in Table 3.1.1. Also
listed is the working voltage, which is defined as the typical average voltage level on lines,
and the maximum voltage. Working voltages are used in conjunction with radio and
television interference, audible noise and electric field levels. Maximum voltages are used
in conjunction with insulation requirements.
TABLE 3.1.1
SYSTEM VOLTAGES - kV
3.2.1 Introduction
Of the variobs corona effects, audible noise is seen t o be the most lilniting
in the selection of conductors at the UHV level. 1201 Several states have enacted o r are
in the process o f developing noise control legislation. These generally fall into he
category of "land use" standards. That is, limits are put on man-made noise according t o
the classification of the land use, such as residential, commercial and industrial. The most
stringent limitation is occurring during nighttime hours in "residential" areas, where
"residential" is generally defined as anywhere people live. The strictest limitations may
not be confined entirely to residential areas. For example, Illinois puts wilderness areas
and wild life refuges, leisure and ornamental parks in the same land use class as
residential areas. Examples of limitatio~isare sunimarized below: #
Limit
--
of Sound Emitted to "Residential" Areas
----
* Limits are expressed ,in terms of allowable levels in each octave band of
frequencies; dB(A) levels presented here are computed from the octave band
levels.
-9-
There is much discussion as t o the applicability of these noise standards t o
transniission lines, since the standards have been based presumably on studies of reactions
t o more familiar types of noise sources. The generic hearings in the State of New
Yoi-k [ 1] on the application of three utilities to build 765 kV transniission lines may
establish a precedent in regard t o corona produced noise. The dominating effect is that of
interference t o sleep. Expert witnesses agree that noise levels of 35 dB(A) o r less are
desirable inside a bedroom. There is disagreement, however, as to what this means in
terms of noise level permitted outside the bedroom window, the differences being
attributable t o the assumed attenuation of sound through the structure of the house. This
is estimated at between 10 and 19 dB, resulting in outdoor levels considered acceptable
between 45 and 54 dB(A).
For the case of dc lines, the audible noise during rain is generally less than
in fair weather, and fair weather exists for perhaps 70 t o 90% of the time, depending on
the area of the country considered. Thus, fair weather noise, rather than foul weather
noise, is the limiting factor for dc lines. Results of some investigations indicated that
40 dB(A) is a level above which noise from dc lines may be considered objectionable. [2]
For this guide, a range froni 4 0 dB(A) t o 45 dB(A) under average fair weather conditions
is used.
For most lines above 500 kV, audible noise is the limiting corona effect.
For lower voltage lines, where little audible noise is produced, radio interference (R.1)
considerations may be limiting.
For dc lines, studies [2] show that SNR's of 911 o r 1 9 dB are required for
acceptable AM radio reception, indicating that higher noise levels are tolerable from a dc .
line than an ac line. 'l'heret'ore, K1 l ~ m i t sfor dc lines of 53 t o 58 dB above 1 pV/m al the
edge of the TC (80% all weather) are used in this guide.
The effects of dc fields are quite different from those of ac fields, and
consequently allowable levels o f dc fields cannot be related to allowable levels of ac
fields. The current induced in an object under an ac transmission line'is a result of the
capacitive coupling between the line and the object, and is directly proportioned t o the
power frequency; the current induced in an object under a dc line is dependent only on
the level .of ionization resulting from corona on the line, and is a small fraction of the
current induced b y . i n ac line.
In this guide certain widths of transmission corridor (TC) are utilized. The
widths of t'hkse corridors may or may ,not be equal to the widths of right-of-way that
should be selected since the latter are determined by local requirements o r by special
technical or economic constraints.
3.2.6 Summary
The ranges and base case study levels for audible noise, radio interference
and electric field levels are summarized as follows and as listed in Table 1 , lines 1, 2
and 3.
AC L i e s DC Lines Comments
-
Alldihle Noise 5 0 t o 60 dB(A) LS0 rain * 4 0 to 4 5 dB(A) LS0 fair ** At edge of TC
. , Duvc Cusc , ss c l n ( ~ ) 45 I:IU(A)
3.3.1 Introduction
surge of peak amplitude V is denoted by P(V). The probability P(V) is cumulative. piving
the probability that the insulation will flash over at a voltage level. The foml of
P(V) may be determined from a large number of laboratory- tests on the same gap. An
approximation for the distribution which yields sufficicnt accuracy for practical purposes
is the Gaussian
where CFO is the critical (50%) flashover voltage and of its standard deviation. Thesc
parameters are obtained'from laboratory tests. .
For N identical. insulations subjected to the same peak surge of amplitude
V, the fla.$ho,ver probability P(FO) is
where factor 112 has been used because negative polarity switching surges, may ' b e
neglected under normal conditions. This is dus t o tl?e fact that thc positive polarity
strength is ordinarily much lower than negative.
(V . p ) ?.
where p is the average stress and oo its standard deviation. These parameters must be
determined from network analysis studies o r field tests on actual lines. .
k = CF0/V2% (3.3.5)
whore V2% is the 2% surge crest value of the assumed Gaussian distribution, or
Vi% = p + 20,
..
and the estimated maximum surge (Vmax) is Vmaxq = p + 3.50,
The safety factor, k, may be used t o calculate the CFO required for a
specific gap configuration if V2% is .given. In this statistical approach, k is a function of
k=- CFO
vza
\ ,-N = 500
\3-cfl=N":,,,,
N=l
nflCFO = 0,05
oo/p = 0.08
1
\-*: /
/
\
Fig. 3.3.2 Safcty factor ( I ) as a fi~nrtinnof
flashover probab~lityper surge (Ptot)
&>\ '
I 1 1 1 I I I 1 1 1 1 1 I I I I
--
-
k = CFO
v.55
of/CFO = 0.05
oo/p =0.12
\
I
Fig. 3.3.4 Safety factor (k) as a function of the
number O f insulations(N),for different
values of the stress standard deviation
1.30 - and different flashover probabilities
-- - - - - -.
o0/p = . I 2
- 2 - -
o0/p = .08 , 'tot =
//----- 0.001
- o0la = .04
, 1.25
- _------
-
------- - - --y
---- C _ _ - - - - - -
k
1.20
1.15
-
---_---------. -
-\
- "tot =
,
0.01
oo/p = .04
- ____,_-------\
---- ----
_CC---
... . .. ..
I . I ~
. . ool# = .OR ' plot = 0.1'
1.05
-/--
----- - . - - - -
o,/p = . I 2 I
-
standard. deviation for different flsghove~p m
babiities. 'the number of lnsulaliuds is N UH).
TABLE 3.3.1
SWITCHING SURGE V A E m
pole t o ground faults than from actual switching operatiois. Such t o ground faults
induce overvoltages on the other pole which are similar to switching surges on ac lines
and hence are included here. [13] In the event of the sudden loss of one pole, it is
desirable to maintain the other one without flashover. Consequently, the acceptable risk
of failure is chosen with some knowledge of the expected frequency of occurrence of
these faults.
. .TABLE 3.3.2
Critical (50%) flashover voltage for each of N identical phase-to-ground
insulations as a function of ac system voltage level. Standard deviation
of applied stress = 8%.Standard deviation of strength = 5%.
NOTE: The.range of parameters in boxes are preferred values which should be used for a first attempt
at individual tower design.
TABLE 3.3.3
-..
3.3.3 Phase-to-Phase Insulation for switching Surges
Two types of phase-to-phase air gaps are considered for overhead line
design. The first involves the gap between adjacent phase conductors at midspan when
the otherwise large clearance may be reduced by wind swing. It is assumed that this will
occur in only one span at a time, and consequently the analysis is made according t o
reference [ 11] with N = 1, again for the two probabilities of flashover of .O1 and .001
per surge. The second tybe of gap involves unique tower designs in which insulators are
located between adjacent phase conductors in each tower. For this case, the analysis was
done according t o reference [ 1 11 with an effective number of towers N = 200 for
flashover probabilities of .O1 and .OO 1 per surge.
TABLE 3.3..4
Maximum
CFO (kV)
System Voltage Switching Surge
(kV)
TABLE 3.3.5
--
CFO (kV)
System Voltage Switching Surge
TABLE 3.3.6
AC p h a ~ ~ p l l a scritical
e flashover voltagcs for single (N = 1)
gaps (applied Lo t~lidspanclearances) and multiple (N - 200)
gaps (applied to clearances at towers). Maxiniuli~phase-phasc
switching surge assumed = 1.7 x phase-ground surge. Standard
deviation of stress (phase-phase) = 2.5'%. Standard deviation
of strength = 5%.
,(,.I
-- CFO (kV)
Maximum
Systern Voltage N = I Gap N = 200 Gaps
(kV) . -- P = 0.01 P = 0.001 P-= 0.01 P = 0.001
-- -
No pole-pole switching surge design criteria are given for dc. This is a
consequence of the fact that during pole-'to-ground faults, the pole-pole voltage is
essentially the same as that of the unfaulted pole-to-ground.
3.4 SHIELD ANGLE
3) The lightning current that is required to develop this critical flashover voltage '
when a phase 'conductor is struck is calculated. This is called the critical "threshold
current. "
5 ) A point P is located at distance S from the shield wire and PS above ground. :
The factor /3 is a catch-all to compensate roughly for different flashover strengths from
point P to conductors and shield wire, and from P t o ground, for the fact thatnsome
strokes' do not descend vertically and can have excessive branching, for the fact that the
ground plane may not be horizontal, and as a sort of safety factor.
1
This method is not rigorous but it does provide a practical approach to the
problem.
4.1.1 Introduction
The purpose of this section is 'to show how these two phenomena affect
the design of UHV lines, and also to review EHV lines to see if any aspect of their design
is influenced by audible noise and eleckc field considerations. From this information
bundle and line configurations and minimum heights are selected to meet the criteria
listed in 3.2.6.
4.1.2 AC Systems
* The method of AN calculation in the book has been modified t o take into accowlt the
effect of k = Gma, + Gavg, as shown by recent tests at Project UHV.
1100 kV Systems
Figures 4.1.3 and 4.1.4 show the effect of phase spacing and height above
ground on audible noise.
Figure 4.1.9 shows that the influence of average height on electric field at
the edge of a TC of 122 m is negligible. Also, again the delta configuration produces a
field at the edge of the TC which is one-half of that of a flat configuration for the same
average height.
. .
The influence of phase spacing on maximum field at ground is shown in,
Figure 4.1.10. Compacting the line by 3 m is equivalent to increasing line height by 0.6
m. The effect of phase spacing on field at edge of TC (61 m from line center) is
pronounced as shown in Figure 4.1.1 1. A 3 m phase spacing reduction reduces the field
by -- 15%. \
Figures 4.1.12 and 4.1.13 show the TC required for various configurations
and levels of audible noise and electric field. Figure 4.1.12 illustrates that a small
variation in subconductor diameter causes large variation in TC. Conversely, a small
change in TC does not substantially affect the selection of subconductor diameter. Figure
4.1.13 shows that equivalent bundle diameter has little effect on TC. The greatest effect
here is caused by the various line configurations. Therefore, audible noise and electric
field requirements can be considered separately. Line configuration (flat-delta, phase
spacing, extent of TC, necessity of shielding) should be determined by electric field
requirements at edge of TC. ' ~ i n eminimum height above ground should be dimensioned
according to maximum field levels allowable at ground under the line, and bundle
configuration should be set by audible noise considerations.
Choice of Bundles.
From Figures 4.1.1. and 4.1.2, the following bundles result for
AN = 55 dB(A) and TC = 122 m.
A field less than 2 kV/m at the edge of a 122 m TC can be obtained with
a flat configuration, phase spacing = 18.5 m from bundle center-to-bundle center (see
Figure 4.1.13). (The equivalent, bundle diameter for the conductor configurations shown
-
above is 94 cm).
Phase Spacing . 14 m 10 m
Average Height Above Ground
18.5 m 14 m
of the Lowest Phase,
Height of Midspan 14.3 m 9.9 m
The following considerations for 765 kV lines, are derived from the
analysis of the results shown in Figures 4.1.14 through 4.1.20.) \
Choice of Bundles
/
N = 3 Flat d - 5.7 cm A = 76 cm
Delta d - 6.1 cm A = '76 cm
N = 4 Fl3t d --
4.0 cm A = 71cm
Delta d - 4.3 cm A = 71cm
N = 5 Flat d -3.2cm A = 66 cm
Delta d - 3.3 cm A = 66 cm
N = 6 Flat d - 2.2 cm A = 64 cm
' Delta d - 2.5 cm A = 64 cm
The height at midspan, with the condition that the field be not more than
12 kV/m and for a phase spacing of 14 m, is: ,
The following considerations for 500 kV lines are derived from the
analysis of the results shown in Figures 4.1.2 1 through 4.1.28.
The bundle for audible noise of 55 dB(A) can be chosen among the
following:
The height at midspan lor the condition that the ficld be not more thm
12 kV/m and for a phase spacing of 10 m is:
Tl~est: values alt: lower than thc NESC which roquirec 9.4 m. Therefore,
the height is determined by the Code.
345 kV System
There is a great deal of experience at this voltage level which can be used
to establish the parameters. The following are used:
In the preceding sections it was shown that audible noise influences the
choice of the conductors and electric field influences the width of the TC and the height
at rnidspan. However, usual design practices are based on radio noisc (and other
considerations) for conductor design and the National Electric Safety Code for clearances.
It is interesting to compare the two practices and determine the cases in which one
consideration will prevail over the other.
Choice of Conductors - Comparison Between Audible Noise and Radio
Noise Requirements
A base case radio noise level of 55 dB above 1 pV/m for 80% all weather
noise is selected in 3.2.6. The curves on page 168 of reference. [ I l l can be used t o
determine'the bundle. However, these curves are for rain and at 15 m from the outside
phase, and are given for maximum rather than for the working voltage.
The diameters of the conductors required for radio noise and those
required for audible noise are reported in Figure 4.1.33, which shows that audible noise ,
is the determining parameter at 1100'kV and 765 kV, while radio noise is' limiting at
345 kV. Radio noise and audible noise requirements have about the same result for
500 kV.
(feet)
12
where V is the line voltage in kV. Minimum clearances .are.shown below together with
the height at the center of the bundle.
The heights selected for "base case" studies are listed below and in
Table 1, line 9.
The 7th edition of the 1977 National Electric Safety Code recommends that
the current induced in the largest vehicle which could be stationed under the transmission
line should be, in the worst case less than 5 mA. There is a linear relation between
induced current in a vehicle and unperturbed electric field at ground; therefore, the 5 mA
criterion can be translated into maximum design value for the electric field for ally given
vehicle. This is shown in the following examples:
Field Required To
Vehicle Induce 5 m/A Reference Source
Summary
Bundle and subconductor sizes, minimum heights, and phase spacings for
ac systems are summarized in the following table.
Lie Phase Bundle
Configuration Hmin' Spacing Subconductors , Diameter
Flat
Normal Delta
(Equilateral)
Flat
**Present
Practice
2 3 4 5 6
SUBCONDUCTOR DIAMETER - cm
FIG. 4.1.1
PHASE SMCING- m
AVG. HEIGHT ABOVE GROUND- m
FIG. 4.1.3
FIG. 4.1.4
I
1 I I V = I l 5 0 kV
.' Vz 1150kV MIN. HT.(AT BUMLE CENTER) HMIN =20m P= 18.5 m
- P=l8.5m OF LOWEST PHASE - AVG.HEIGHT OF LOWEST PHASE = 24m
- x---+, I/
I* e---
- .e=== I
- I N
"o,,.-' I
I.
/
0 0-300. I. /
-
/
-09 ' ,06:a . I
- I0 ' /
, 'at-300
I
-
- 'I
I
t -
- 0
1'
BX40a-n x102cml2X2.3cmx 127cm
615.3cm x 102cm
-
.
-
-
N.8 d-4.06cm
A- I 0 2 crn
P=18.5m
\ \
\
n B 1 s m 2 1 a m w
EIGHT AT MWAN OF HIMST PHL\S- m
FIG. 4.1.8
2 s n
AVG. HEIGHT ABOVE GRWND- m
FIG. 4.1.9 PHASE SPACING -m
FIG. 4 . 1 . 1 0
BUNDLE DIAMETER
FIG. 4.1. I5
- cm I I1
I
12
1
13 14 15 16 17 .
PHASE SPACING - m
F I G . 4.1.16
v = 780kV
-
MIN. HT.(AT BUNDLE CENTER)= 14m
- AVO. HT.. 18.5n1
PHASE SPAC!NG = I 4 m
-
-+ , FLAT
V * 780 kV
/
MAX. FIELO I N 'I'C
FIELD AT EDGE OF TC
4 4 m FROM CENTER L I N E
FLAT
-- - - - - - a (NORMAL)
w- -
* --
4
. - S
- lbl
- B
W
- 2
m
- n
a
N =2
-
audible noise at 33.5 m
WCONDUCTOR DIA. - cm
' FIG. 4.1. 21 SUBCONWCTOR DIAMETER- cm
FIG. 4.1.22 .
I 1
30 40 50 60
CONDUCTOR SPACING - c m .
FIG. 4.1.23
'PHASE SPACING- m
FIG.. 4 . 1 . 2 4
Ol, A i 5 'BUNDLE
; EQUIVALENT ,'A DIAMETER
io i t . , , ; :
- cm
FIG. 4.1.25
RIlNlMUN HEIGHT ABOVE CROW- m
FIG. 4.1.'26
- IkVlm
A/--
/ @ - -
FLAT
A--
/---
0
0
DELTA -
3 1 FIELD AT EDGE OF %
33.5m FROM CENTER LINE.
-2kVfm
AINORYALI
15 20 25 30 35 40 45 50 55 60
25 30 35 40 45 50 55 60 65 70 75
-41-
I I I I 1
LlNE VOLTAGE- kV
FIG. 4.1.33
6 - -
BPA suggestions. -
Japane e N'=4
: r' -
I - -
(N =number of subconductors,)
0 1 1 I 1 . 1 1
Conductor Configuration
..: The conductor . configurations Listed below have been chosen mainly
following suggestions made at the UHV DC Symposium' between the U.S.A. and U.S.S.R.
(1 975) and extrapolating to 1200 kV (see Figure 4.1.35).
' . d (cm)
where
i
'U is the 'pbsitive pole-to-ground voltage
and
in which
and
Fig. 4.1.36 Variation of Minimum Ground Clearance with Pole Spacing (see
Table 4.1.2 for Conductor Geometries)
Summary
Bundle and subconductor sizes, minimum heights, and pole spacings for dc
systems are summarized in the following table.
4.2.1 Introduction
The base case air clearances from phase to tower listed in Table 1, line 10,
are determined for a probability of flashover of 0.01 and tower widths of:
The clearances listed in Table 4.2.2 for switching surges. are calculated
using CFO values from Table 3.3.6. For midspan calculations, it is assumed that only one
span (N = 1) is involved and for tower calculations N = 200 as explained in subsection
3.3.3. . Clearances for sixty hertz are also calculated. These are the minimum
phase-to-phase clearances to be permitted under phase displacement' or galloping
conditions. Under normal conditions switching surge considerations determine the
minimum phase-to-phase air clearance. These are listed in Table 1, line , l 2 for the
clearance at tower with a probability of flashover of 0.01.
- .. . . ..
TABLE 4.2.1
PHASE (P0LE)TOGROUND AIR CLEARANCES
(1) Clearances determined from Figures 1 1.5.1 and 1 1.1 2.3 of reference [ l 11 .
(2) Sixty hertz clearances determined from Figure 10.2.1 of reference [ l l ] using CFO ='1.25 x Max.
System k~/*. . .
(3) .DCclearances determined using 4.8' kV/cm as calculated from Figure 10.4 of reference [9] and
CFO = 1.25 x System kV.
TABLE 4.2.2
PHASE-TO-PHASE AIR CLEARANCES
(1) Clearances determined from Figure 1 1.9.6 nf reference [I I] plus modificatioi~ usil~g Last data
generated in this program.
(2) Sixty hertz conductor-to-conductor data of Figure 10.2.1; reference [ I l l , is for one conductor
grounded. An ignorance factor of 1.15 was applied for the case of both conductors energized. Thus,
CFO = 1.25 x 1.1 5 x Max. System k ~ / f l .
4.2.4. Phase-To-Ground Insulator Lengths
TABLE 4.2.3
2.1 Standard
3.2 Standard
4.6 Standard
7.7 Standard
5.4 Anti-Fog
7.9 Anti-Fog
12.0 Anti-Fog
(1) For sixty hertz: Wet CFO = Dry (301.78, see reference [ l l ] , Figure 10.2.5 for precipitation rate
of 2 mmlminute. Dry CFO = 1.25 x Max. System k V a m , Figure 10.2.1.
(2) For steady state dc: From reference [9], Table 8.5, the dc CFO is given for various types of
suspension insulators. The average CFO for typical ball and socket insulators is 3.7 for rain and
3.1 kV/m for fog adjusted to a water resistivity of 10 k c c m . Reference [9] also states that the
dc strength is linear with length. The lengths are calculated using the fog condition value of
3.1 kV/m and CFO = 1.25 x System kV.
(3) From Appendix A l .
Insulation lengths listed in Table 4.2.3 to meet steady state ac and dc
voltage requirements under clean, wet conditions are also calculated. The methods of
calculation are explained in the footnotes. Lengths required for light contamination are
also listed as a matter of interest. These are derived as described in Appendix A l .
The phase-to-phase insulator lengths for switching surge and ac voltages are
listed in Table 4.2.4 and are calculated as explained in the footnotes. The switching surge
requirements dominate and are listed in Table 1, line 13.
TABLE 4.2.4
AC
Maximum Switching Surge
System .Clean-Wet Clean-Wet (2) Light Contamination (3)
Voltage (kv) Length (4 Length (d Length (4
3 62 2.3
550 3.4
800 4.9
1200 9.2
f 600
800 >NO? Recommended.
+ 1200
(1) Test data generated in this program indicate that phase-to-phase insulators have essentially the
same switching suige stl.eng&has phase-to-phase air gaps. Lengths are obtained from Table 4.2.2
using the clearance-at-tower data.
(2) It is assumed that under dry condilions the length required will be the same as the air gap
requirement. For wet conditions the length is increased by 11.78 = 1.28 (see reference [ l l ] ,
Figure 10.2.5) for precipitation rate of 2 mm/minute:
(3) . From Appendix A1 . t.
4.3 SELECTION OF SHIELD ANGLE AND OVERHEAD GROUND WIRE SIZE
40
01
w
a
W w
H
W
i N
4
w
Z
2 10 8HlELDlNG ANGLES AS
W
I
0
- 10 1 I
For 500 kV and above, i d for the dc systems the analysis on pages .
374-377 .of reference [ l l ] is used. Table 4.3.1 shows the parameter assumed for these
calculations. The notation used in the table is as follows:
D = Bundle diameter
. ..<.,
reff = Effective radius of bundle (Dl2 x 1.5) to account for
corona envelope . -
2xh
zo = Conductor characteristic impedance (60 In x -1 .
'eff
Clear. = Switching ,surge air clearance from Table 4.2.1 for 1.2 m .
tower leg.
kVc = Impulse flashover strength (Figure 12.3.9, reference [ 11I )
2 (kVd)
IC = "Threshold Current" '( 1
zo
S = Strike distance (Figure 12.3.10, reference [ 11] ) ,
..
Where two entries are given in Table 4.3.1, they correspond to minimum
and maximum bundle diameters as suggested in subsections 4.1.2. and 4.1.3.
TABLE 4.3.1
h
System p
- Sag
- h
- D
- 'eff
- - clear.
- - kVc IC
- s
-
(m) (m) ' (m) ( 4 ( 4 (JZ) (m) -(kV) , @a) ( 4 '
The shield angles are given as a function of shield wire height at the tower
in Figures 4.3.2 through 4.3.7. For those cases in which the choice of phase conductors
makes a significant diffcrcnce in sl~ield angle, two curves are given. In addition, for
765 kV ac data are presented for two values of the coefficient (see reference [ I l l ) .
Finally, it should be noted that the curves in Figures 4.3.2 through 4.3.7 apply also to
the delta phase conductor configurations.
hg - Meters
Height of Shield ~k(st To-)
hg - Meters
Height of Shidd Wi (at Tower)
hg - Meters ..
Height of Shield Wire (at Tower)
Fi.4.3.4
The shield angles selected are listed in Table 1, line 14. It is important to
note that these angles apply to the outer phase only. Experience has shown that lightning
rarely strikes the center phase when at least two, shield wires are used. Based on the
"final step S" theory, a conservative value of 80' has been specified as the angle guarding
the center phase (see Section 3.4).
The shield wire gradients have been calculated for different shield wire
diameters and for configurations listed in Table 4.3.2. The results are shown in Figure
4.3.8.
TABLE 4.3.2
Height At Tower
Equiv. Diam.
Working Phase Shield Shield Phase
Voltage Conductors Wires Angle Conductors
(kV)
It must be noted that the shield wire gradient was calculated using the
wire height at the tower. This is somewhat conservative since at midspan the shield wire.
gradient will be lower. A check was made for 1150 kV at midspan where the ground wire
gradient was found to bt: abuut 7% lower.
3) Audible noise produced should be less than 44 dB(A). This level will
not affect line performance. If the line produces 50 dB(A) and the ground wires produce
44 dB(A), the combined result will be 51 dB(A).
4) The radio noise current in the ground wires from corona should not 0
increase the field produced by the phase wires. In the calculation of shield wire
contribution to radio noise, it must be considered that. the shield wires are grounded at
every tower and the corona current does not propagate along the line. This results in
about 16 dB attenuation relative to the phase wires.
5) Yearly average corona loss of ground wires should not exceed 10% of
the line corona loss.
The questions of visual corona, audible noise, radio noise, and corona loss
were considered in earlier work at Project UHV (see Appendix A2) which concluded that
radio and audible noise of shield wires were of no concern. Therefore, only the corona
loss is calculated for the ac configurations in question using reference [ 141.
Shield wires for 765 kV and 1100 kV have about the same gradient.
Therefore, the calculation of the loss is done for both voltages in the following table. The
wires are assumed to be moderately aged and wetted by a light rain.
Shield
Wire Peak Cradient p~ Loss*
Diameter Ec (Ref. [14] ) . Coefficient K Gradient E (Ref. [ 141 ) (K PN)
-- (cm) (kV/m_)_-." (Ref. [14] ) (kV/m) -
Ec (wlm) (W/m)
By. comparison, the yearly average. corona loss produced by the phase
conductors is (from reference [ l 11 - Table 7.4.1, Climate 1, Figures 7.5.3 and 7.5.4)
0.025 x 320 = 8 kW/km for 1100 kV system, and 0.025 x 300 = 7,5 kW/km for 765 kV
system.
Using the criterion that the shield wire loss should be less than 10% of the
&e loss, the shield wire diameter should be (Figure 4.3.10 - correspo~~dirlg tu'e loss of
0.775 + 0.2 = 3.9 kW/km) larger than 1.25 cm. This diameter will also satisfy the noise
requirements. Visual 'corona will be present only during rain and its observation will
require dark nights and field glasses.
I
The gradient of the shield wires of the 800 kV and 1200 kV ac lines is
. .
about 19 kVrms/cm which corresponds to 26.8 kVpeak/cm. This value was used to.
calculate the shield wire sizes for the dc lines.
Using a gradient of 26.8 kV/cm and Figure 4.3.8, the shield wire sizes are:
I
600 kV d 2 0.6 cm
800 kV d 2 0.6 cm for 12' shield angle, and = 0.5 for 16'
* 1200 kV d > 1.27 cm for 12' shield angle, and = 1.U8 for 18"
need only be larger than 0.6 cm and probably should'be determiried on the basis of
mechanical requirements.
Fi.4.3.8 Shield Wire Gradient
4.3.6 Shield Wire Selection and Spacing
In setting .up design criteria for innovative line concepts, lightning performance
cannot be ignored. This is particularly true for voltages up to 500 k ~ of, even 765 kV in
terrain with poor earth conductivity. However, the specific choice of base lightning
performance criteria in generalized line design work creates uncertainties of its own,
because lightning performance is greatly influences by geography, the isokeraunic level,
the earth conductivity, type of terrain and varying reliability requirements. A tripout rate
of 1.0 per 100 miles per year may be perfectly acceptable for one line while for another
even O..l is marginal. In this guide, it was concluded that it was not realistic to hold to a
rigid standard of lightning tripouts because of the strong dependence on local conditions.
Conversely, switching *surges and sixly-hertz pesful-~~~a~ct: call be morc rigorously
delineated since they are primarily electrical and are not so influenced by geography.
Therefore, the strategy adopted in this guide was to flrst selecl crileria f o ~ ,
switching surge and power frequency performance. If the designer then examines one of
the concepts and finds it insufficient from the viewpoint of lightning performance, it is
the designer's option to select the lightning remedial measures to be employed either by
'reducing the footing resistance, increasing the lengths 01insulators and air gaps, or adding
counterpoise or extra shield wires.
Transmission line outages due to back flashovers across insulator strings caused by
lightning flashes to the towers or to the shield wires near the towers, can be estimated
using Figures 12.6.2 (A through F) of reference 1111 . Each figure has curves for various
lengths of insulator strings, is drawn for an isokeraunic level of 100 thunderstorm days
pcr year, and assumes a certain line voltage, tower design and span length. The tower
design used for each set of curves is shown in Figures 12.6.1 (A through F) of
reference [ 11I .
Base case line design parameters are selected from Table. 1 and are applied to the
above mentioned curves for horizontal configurations and conventional structures.. Table
4.4.1 shows air strike distances and conductor heights for 345 kV, 500 kV and 765 kV
base case design parameters. (1 100 kV is not considered because footing resistances of
100 ohms or more are necessary to-lead to back flashover on UHV lines) [ I l l .
TABLE 4.4.1
The equivalent number of standard 5-314 in. insulator units shown in Table 4.4.1
' are selected on the basis that the insulator string has' a critical flashover of about 90% of
the critical flashover of the air strike distance of a phase conductor to the nearest tower
ground plane. Therefore, the number of equivalent insulator units shown in Table 4.4.1
has been selected on the basis that the insulator string length is 10% longer than the air
strike distances shown.
Using a typical tower footing resistance of 20 ohms and the equivalent number of
insulator' units, tripout rates are obtained from Figure 12.6.2BYE and F for 345 kV,
500 kV and 765 kV, respectively. These tripout rates must now be corrected for different
tower heights, isokerau,nic levels, and span lengths.
a Since conductor heights of the base case parameters are about the same as
those used to make the curves of Figure 12.6.2, reference [ I l l , no
correction for tower height is necessary.
i It is estimated that 60% of the lightning flashes to the line hit a tower or hit
the shield wires in the near vicinity of a tower. Lightning flashes hitting the
shield wires at or near midspan do not cause back flashovers. Corrections for
span lengths are made using equation 12.6.2 for reference [ 11I , assuming
span lengths of 400 meters.
a A typical value of 30 thunder days is selected and the tripout rates obtained
above .were multiplied by 301100.
The resulting tripout rates are shown in Table. 4.4.1 for a tower footing resistance
of 20 ohms, an isokerauAc level of 30, and span lengths of 400 meters. For comparison,
Table 4.4.1 also lists the required footing resistance to obtain tripout rates of 1.0 outage
per 100 miles/year and the air strike distance to obtain 1.0 outage per 100 mileslyear
with 20 ohm footing resistance.
In line with the strategy proposed at the beginning of this section, a review of
Table 4..1.1, which certainly is not universal and represe.nts only one spe.c.ific
,
configuration, points out that given a certain tripout rate, the footing resistance must be
reduced .as the insulation strength of the line is reduced (because insulators and gaps grow
smaller) but that even for 12 standard insulator units at 345 kV, tripout rates less than
1.0 per 100 miles per yew ire realizable. It also shows that if the footing resistance is
maintained at 20 ohm and the isokeraunic level is 30, the air strike distance determined
for switching surges must be increased approxhately 15% for 345 kV and SO0 kV
systems and decrease approximately 15% for 765 k V systems to produce a tripout rate of
1;O outage per ,100 miles per year.
CHAPTER 5
5.1.1 Introduction
The loading criteria chosen for the structure designs are based on the
"Ultimate Loading Concept." That is, the transmission line conductor support system is
designed in terms of a condition Q kithstand at failure threshold without safety factors,
instead of the traditional n o r m i or design load plus various safety factors.
Due to the dispersion in rupture strength of the many materials used for
transmission line components, it is necessary to determine the strength factors for each of
these materials. For example, when a steel transmission line structure is subjected t o an
ultimate load, the stressed members should be limited to a stress level which is just below
the level fplastic behavior, better known as the yield point of the material. In cases
where the materials specified are reinforced concrete, wood, laminated wood, epoxiglass
or other material, the ultimate strength information must be established and margins
selected for each material in order to determine if the structure can withstand the
selected ultimate loading.
system aftcr a structure collapse. The structure colla~st:lllay have rea11te.d from primary
loads being exceeded due to weather, accidents, acts of sabotage or vandalism.
Maximum Winds
where
= Gust factor
Fg
G = Maximum gust speed (instantaneous)
Gust factors decrease with increasing wind speeds and height above .
ground. The wind gusts cover a large enough area to envelop structures; thereforc, thc
wind pressure on a tower surface should be determined using a gust velocity and not the
~r~aximum sustained wind.
Height Factor
where
\
This is a reduction factor which accounts for the non-uniform wind force
integrated over the total wind span in order to obtain the effective loading on the
structure. ' . .
where
V = Wind velocity (mph)
rating, which is the approximate yield point of the metal pin and the strength is then
compatible with other hardware in the assembly.
5.1.1 1 Foundations
Since ultimate structure loads are used to determine foundation loads, the
ultimate soil values should be used for the design. A safety factor of 1.0 is sometimes
used when adequate soil data is available; however, this is not always the case. Borings
and complete soil information is.not usually provided at every structure location.
In setting the design parameters for foundations a 1.1 safety factor on all
ultimate leg reactions is chosen to allow for variations in soil data..
The mechanical conductor loads are selected and used to develop sag and tension
data. The maximum conductor load is based on 7m of its fated breaking strength under
.3.8 cm (1.5 in.) ice at OOC (32'~). Also 33% under - 1 8 ' ~ (0'~) bare unloaded initial,
and 25% a t -1 8 ' ~( 0 ' ~ ) bare unloaded final conditions. The creep check temperature is
assumed to be 1 6 ' ~ (60'~). Figures. 5.2.1 through 5.2.4 show sag-tension variation for
'
the 3 control tension limits with spans of 250 through 550 meters for the ac voltage
systems. 'The ruling span selected for all line voltages is 400 meters.
For these conductors, the 70% of breaking strength limits the tensions for 400
meter spans and longer. Tensions for spans less than 400 meters are, in general,
controlled by the 33% limitation. In summary, it can be said that the conductors are
utilized to their optimum mechanical strength point starting with spans of 400 meters
and above. Similarly, Figures 5.2.1 through 5.2.4 show sag vs. span values plotted for a
250 to 550 meter range at 50C conductor temperature and 3.8 cm (1.5 in.) ice
conditions. All.conductors using the selected ruling span of 400 meters have 12 t o 15 m
final sag vnlus.
For the dc conductors, Figures 5.2.5 through 5.2.7 show sag-tension variationsifor
the 3 control tension limits where sags for the selected ruling span of 400 meters have an
approximate 14.0 meter (45 ft.) final sag value at 5 0 ' ~ ( 1 2 ~ ~ ~ ) .
Often it is found that excessive tower heights will be necessary to provide for the
increased sag under ice loading. Less than normal clearance is considered acceptable for
rare ice s t o k s , and tower heights are based on conductor temperature of SOC, final sag.
Increasing conductor tensions will result in flatter sags and shorter suspension
structure but greater loads on angle and dead-end structures. This will cause decreased
suspension tower weights but increased angle tower weights. Therefore, the optimum
balance must be maintained between conductor sags and tensions.
I 1 I
<
I 1 1
500 k V 3.3 m (1.293 in.) FWCH CONDUCTOR
345 kV 275 cm (1.081 in.) IlEDWDIC CONDUCTOR
I 1
I l a ) kV 5.46 m (LI5 in.) AE CONDUCTOR '
765 kV 3.82 cm (1.504 in.) UPWlNC CONDUCTDR
FIG. 5.2.4
nc. 5.2.1
I I t 800 kV 4.57 m (1.8 in.)AE CONDUCTOR
I I
SPAN M M m R S SPAN IN M m S
SPAN lN MhlRS
CHAPTER 6
The .selection of structure loadings are made on the basis of ultimate load
concept. The following loading conditions are assumed for each tangent stmcture concept
design.
6.1.1 h a r y Loads
Assume 161 kmlh (100 milh) wind, 122 kg/m2 (25 psf) on the projkcted
area of all phase conductors and shield wires, with no ice, at 16OC (60F). 'The wind on
structure shall include a 1.2 gust factor, but the shape factor will depend on the structure
concept.
The structure should withstand impact loading due to ice dropping, at any
one conductor or shield wire support. This load will consist of 25 mm (1 inch) radial ice
with a 20 kg/m2 (4 psf) wind, at OC (32OF), on the projected area of all phase
conductors and shield wires including ice, except at the longitudinal load point. The
unbalanced longitudinal load is due t o ice dropping in one span before 'the next, with an
equivalent of 25 mm (1 inch) radial ice in one span and 13 mm (.5 inch) radial ice in the
other. Vertical and transverse loads are reduced at this support point due to the ice
dropping. The appropriate wind on structure should include a 1.2 gust factor. The shape
factor will depend on structure .concept.
collapsed tower may collapse or suffer some damage but that the next tower on either
side will withstand the resulting load. It is further assumed that the adjacent structures t o '
the collapsed tower will absorb energy as they buckle or collapse and thus reduce the
longitudinal loading on the next tower. The balanced longitudinal loading on the
structure is treated as a static load rather than an impact or dynamic load and this
loading condition takes place with an assumed wind of 44 kg/m2 (9 psf) at 1 6 ' ~ (60'~).
The loads on suspension type towers for each voltage and each load case
are shown in ~ ~ ~ e n d iA3. x . ' This information is intended for use as a guide in
development of conceptual designs. They may change slightly when selected concepts are
being designed for fabrication and testing.
6.2 MECHANICAL SELECTION OF CONDUCTOR SIZES
. From the range of subconductor and bundle sizes developed in Section 4.1,
conductors that can be economically manufactured, still satisfying the electrical
requirements, were analyzed for mechanical integrity. In this analysis, an ultimate vertical
load is assumed due to 38 mm radial ice on each subconductor, and an ultimate wind
pressure of 122 kg/m2. The conductor cost in $/meter/phase and sag-tension
characteristics are compared, and the following conductor sizes were selected.
No. of
Conductors Buildle
Voltage in Bundle Diameter (m) Cnnductnr Type
Air Expanded
ACSR LAPWING
ACSR FINCH
ACSR REDWING
Air Expanded
Air Expanded
ACSR PHEASANT
Damper requirements for both ac and dc lines are listed in Table 6.2.1. It can be
seen that, using a 400 meter span range and with the 70%, 33% and 25% tension control
limitations on conductors, only one damper per span .is needed for aeolian vibration
protection,
TABLE 6.2.1
AEOLIAN VIBRATION PROTECTION
.
UI 70%, 33% i ~ l d
(Bdb:t!d 25% Tewiurr L.h~ds)
Several special conductors have been developed to overcome this problem. They
have not, for the most part, been usable conductors. The most promising was the
air-expanded conductor but it still contained too much metal. The others either lacked
strength, could not be reeled, had poor thermal characteristics, had low internal damping
/
A conductor design which, at least on paper, overcomes most of the problems has
recently been developed. The conductor consists of a steel core whose diameter is
selected for proper sag characteristics, with a narrow metallized plastic expansion spider
placed at about one foot intervals along the core and a single layer of shaped aluminum
strands stranded over the spiders. The shaped strands are to prevent collapse of the
conductor between supports.
The following examples help clarify the procedure. The conductor diameter and
number of conductors in the bundle was fixed by the corona induced noise limits. The
design clearance for these lines is based on a maximum conductor temperature of 50C
and several conductors were designed with the aluminum area selected to give a
conductor temperature of 50C with a 3 0 ' ~ anlbient .6 mlsec. wind velocity, no sun,
and a conductor surface emissivity of .5, with the line loaded to twice its surge
impedance load. Three of these conductors - namely, 6.35 cm diameter, 4.57 cm
diameter, and 2.79 cm diameter - are described and the principal differences between
themand conventional conductors are shown in the follow&g table.
This new conductor concept seems to have many advantages over conventional
conductors. The next step is to determine whether the conductor can actually be
manufactured and handled. The actual stress-strain and creep characteristics of the
conductor could be measuyd as well as the temperature characteristics and the ac
resistance and reactance.
If an examination of the weather records for the area traversed by the line show
that during the time of the maximum ambient temperature, there was a bright sun and
wind velocities of less than .6 m/sec., the maximum conductor temperature will be
greater than 50c and possibly as high as 60'~. Under these climatic conditions,
clearance should be based on the actual conductor temperature under load.
Using the assumption of no sun, the current which produces the 6OC temperature
rise is computed for the various conductors. The power loss associated with this current
is also calculated. The maximum power transferred when the line is thermally loaded is
calculated by multiplying the load current by twice the pole voltage. These values along :
with the conductor resistance in ohms/lOOO m at 2 0 ' ~ are shown in the following table.
The same values are calculated assuming a bright sun and a 60c conductor
temperature. For the *
1200 kV case, the bundle current is 5880 amps compared to
5750 amps with no sun and a conductor temperature of 50C.
If it is assumed that the loading for a dc: line sllould be the same as the one SIL
loading for an ac voltage equal to the dc voltage, then all of the conductors have too
much aluminum. New air-expanded conductors can be designed for these lines to meet
the above loading criterion.
After a tentative selection of the phase bundle configuration, which includes the
number and diameter of subconductors for each voltage, then a more detailed study is
required to satisfy the requirements of the assumed wind and ice loads. Thc fnst
selection of the conductor bundles is based on electrical considerations. This selection is
then refined by a study of strength considerations and sag and tension, data.
Subconductors are chosen within the electrical limits, for all voltaces, but which have
sufficient strength to limit sags t o approximately 14 to 18 meters for n 4nfl meter span.
\
Span clearances for conductor to earth or objects under the line are determined as
part of thc eltctfical palxrneters. The Ccintrnlllng 'sag, normally hot conductor
temperature with no wind, is added to the minimum clearance to obtain stmcture
heights. Although sags are greater for 3.8 cm of ice as compared to 50C (120~),we
select structure heights based on required clearances and 50c (120F) sags. To provide
minimum clearances for a very remote possibility of a 3.8 cm radial ice condition which,
if it does occur, is only of short duration, is very costly and not practical. At road or
railroad crossings 'or any area of high density traffic or population, the minimum
clearance for 3.8 cm ice should be provided. In all line design work, a range of stmcture
heights is needed for optimum costs. However, an average structure height for each
voltage using a 400 meter span is selected. Shown on Table 1, line 17 are thc heights of
conductors used for designs for all voltages listed in Table 6.5.1. The height is from enrth
to the center of the bundle.
TABLE 6.5.1
A1 .1 PHASE-TO-GROUND
Th.e length of insulator strings required for 345 and 500 kV systems was
determined using Figure 10.7.3 of reference [ I l l . For 765 and 1100 kV the 'length of
the strings were determined by linear extrapolation of the lower voltage data. It should
be noted that reference [ 1 1] indicates a nonlinearity effect with increasing voltage. Other
investigations have found a more linear dependence, 5, 6, 7. Since one of the objectives is
to optimize insulation distances it was decided t o use a linear relationship.
The required insulator string lengths for very light contamination on 'vertical and
vee-string are shown in Table Al.l for ac system. Also shown for comparison are the
ranges of lengths presently used by utilities as listed in Chapter 2 of reference [ I l l .
The string lengths for dc are also listed in Table Al. 1. ~ h e s ewere calculated using
the experience of the Pacific Intertie (+ 400 kV), reference [15] and reference [91. The
BPA section of the intertie i s located in an essentially clean area, and thus the insulator
lengths used there are not applicable for light contamination. However, on the Los
Angeles Department of Water and Power's section of the line, contamination ranges from
heavy in the vicinity of the Sylmar Terminal t o a presumed light level over most of the
line. For the insulator stiings on that portion of the line, far removed from the terminal,
the design specifies 1097.3 cm of leakage, or 2.74 cm leakage distance per kV. .
Fog type insulators are used, and performance is satisfactory. Consequently, these
*
same parameters are utilized for the + 800 and 1200 kV systems.
. .
*
For the 600 kV line, using a single string of standard insulators with a ratio of
.leakage distance to spacing of 2.1, a total string length of (2.74 cm/kV x 600 kV)
2.1 = 783 cm will be required using the above leakage criteria. For fog-type 'insulat6rs
such as EPRI Type IX of reference [ 9 ] , the string need only be 536 cm in length. The
actual acceptable length of standard units is probably between these values. Reference
[IS] claims a 2w reduction in string length can be affected by using anti-fog compared
with standard units. This implies that a standard insulator stiing should have a length of
536 cm x 1.25 = 670 cm.
TABLE A1 -1
. .
Insulator String Lengths for Very Light Contamination Conditions.
Standards (146 x 254 mm) Insulators.
* Some laboratory tests indicate that the length of double strings shall be increased 10% to
account for reduced strength of double strings. For the triple string 12%increase is used.
The other entries in 'l'able Al. 1 for dc are obtained by using fmdings reported in
reference [9]. For example, a linear extrapolation was made for required lengths from f
600 kV t o the higher voltage, since reference [9] claims dc contaminated insulator
strength is a linear function of insulation length. Recommendations for'vee-string lengths
are the same as for vertical.
Finally, it should be emphasized again that fog-type insulators may substantially
reduce insulator lengths for dc transmission lines. Table A1.2 shows a comparison of
string lengths for standard and anti-fog units at each voltage level in contaminated
conditions. The third column shows the insulator string lengths which may be used if the
lines are located in clean areas. These latter data are obtained by linearly extrapolating
the BPA k 400 kV intertie string lengths (913 cm leakage) to the other voltage levels,
assuming the EPRI Type IX fog insulator (14.9 cm spacing, 45.7 cm leakage).
TABLE A1.2
'7
A1.2 PHASE-TO-PHASE
Certain tower design concepts for ac systems may involve the use of insulators
between phases, as discussed in Section 3.3.3. For power frequency design, no
. experimental data are available for contaminated interphase insulators. The best estimates
of interphase insulator lengths for power frequency contamination design can bc obtained
by assuming the strengths for phase-ground power frequency contamination design of
Table Al. 1 also apply on the same kV/m hasis to ~hase~phase design. Using this criterion
and a 10% safety factor, the interphase insulator lengths are as shown in Table A1.3.
Since bipolar dc systems can generally be operated monopolar when one pole is
inoperative, it is probably inadvisable to use pole-to-pole insulators because failure of the
insulators could cause the entire system to shut down. Consequently, pole-to-pole lengths
" .are not given for dc systems.
TABLE A1.3
Introduction
At the May .21, Steering Committee Meeting, the question was raised whether
ground wires for UHV transmission lines should be bundled, since single wires could have
an unsatisfactory corona performance. This memorandum examines single conductor
ground wires for 1000-1 100 kV transmission from the point of view of visual corona,
audible and radio noise, and corona loss.
a. Flat Configuration
b. Delta configuration
Visual Corona
Figure A2.1 re,ports, also Peek's corona gradients. for fine spray and' dry
conditions. It is shown that the ground wire will always be in visible corona d u .rain.
~ ~
In dry conditions,. the ground wire with more than 318 in. (.95 cm) in diameter will not
be in visible corona.
Audible Noise
The contribution of the ground wire to the total noise generation of the line was
computed for rain conditions. &I all cases, it will be cdmpletely negligible.
Radio Noise .
.??IC radio noise currents injected in the ground wires were compared with those
injected in the phase conductors. The increase in the line noise is shown in Figure A2.2.
This is a very conservative approach, since the ground wire currents will not travel along
the lhlc without a strong attenuation.
Corona Loss
The corona losses were compared according to the gradients 'of the gound.wires
and compared with those of the line. A sizeable increase results for all diameters with a 1
dB increase (10%) for the 314 in. (1.9 c h ) ground.wire.
For .transmission lines of 1'100' kV, tolerable visual corona, audible noise, and
ladio noise will bc produced by gyo1111d wires gcn.ter than 112 in. (1.27 cm). However, a
substantial increase in corona loss will occur. More investigation, both theoretical and
experimental, of this effect has to be made in order to confirm these findings.
Crnund IYire h e t o - an
FIG. M . 2 ,
APPENDIX A3
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUI?INAL
VERTICAL
TRANSVERSE.
LONGITUDINAL
VIII VERTICAL
TRANSVERSE
LONGI'I'UDINAL
500 kV "BASE CASE9' STRUCTURE LOADS
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL. '
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONCITLJDIN AL
VERTICAT ,
TRANSVERSE,
LONGITUDINAL
VERTICAL
TRANSVERSE
1,ONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
VII TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE.
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
VII TRANSVERSE
LONGlTUDlNAL
VERTICAL
VIII TRANSVERSE
LONGITUDINAL
I
,'
VERTICAL 1.8 1.8 33.0 33.0 33.0 96 kmlhr.
IV TRANSVERSE 1.14 1.14 11.0 11.0 11.0
LONGIT-UDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
VII TRANSVERSE
LONGITUDINAL
VERTICAL
VIII TRANSVERSE
LONGITUDINAL
+ 600 kV "BASE CASE" STRUCTURE LOADS
(In Metric Tons)
VERTICAL
I TRANSVERSE
LONGITUDINAL
VERTICAL
TRANS,VERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE .
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
VERTICAL
TRANSVERSE
LONGITUDINAL
+ 800 kV. "BASE CASE" STRUCTURE LOAM
(In Metric Tons)
LOADS ARE U L m T E
I
VERTICAL
'I TRANSVERSE
LONGITUDINAL
VERTICAL
I11 TRANSVERSE ./
* LONGITUDINAL
VERTICAL
IV TRANSVERSE
LONGITUDINAL
VERTICAL
V TRANSVERSE
LONGITUDINAL
i,
LONGITUDINAL
[21 Perry, D. E., Sabath, J., "Conductor Selection for DC Transmission Lines," a
paper presented for the U.S.-U.S.S.R. Symposium on DC Transmission, September
8-1 8, 1975, Leningrad, Russia.
[31 ' CSA Standard C108.3.1- 1975, "Tolerable Limits and Methods of Measurement of
Electromagnetic interference from Alternating Current High Voltage Pcwer
Systems, 0.01 5 MHz-30 MHz."
[4] Sforzini, Mr., Cortina, R., "Proposal for RI Limits of Electric Power Lines." -
Report L6/8 1-12 presented to Task Force on Technical Basis for Selection of
Interference Limits 'from Electric Power Lines and Stations, IEEE Radio Noise
and Corona Subcommittee, January 1976.
\
[51 IEEE Committee Report, "Transmission System Radio Influence," IEEE
Transactions on Power Apparatus and Systems, Vol. PAS-84, No. 8, August 1965,
pp. 714-724.
[6] .ANSI C63.11, "Standzird Procedures for the Measurement of Radio Noise .from
Overhead Power Lines," American National Standards Institute.
[71 IEEE F77 591-1, "Measurement of Electric and Magnetic Fields from Alternating
Current Power Lines," presented at PES Summer Meeting, 1977, Mexico City.
[8] Bracken, T. D., et al, "Ground Level Electric Fields and Ion Currents on the
Celilo-Sylmar + 4 0 0 . k ~Intertie During Fair Weather," F77 617-4, presented at
PES summer Meeting, Mexico City.
[91 EPRI Transmission Line Reference Book HVDC to f 600 kV, 1977.
[I01 EHV Transmission Line Reference Book - Edison Electric Institute, 1968.
[Ill Electric Power Research Institute, Transmission Line Reference Book - 345 kV
and Above, Fred Weidner and Sons Printers, Inc., 1975.
[12] IEEE Committee Report, "Guide for Application of Insulators to Withstand
Switching Surges," IEEE Trans. on Power Apparatus and Systems, Vol. PAS-94,
January-Febniary, 1975, pp. 58-67.
[13] Melvold, D. J.,, Annestrand, S. A., Denbrock, F. A., and Shah, K. R., "Basic
Principles of Switching Surge, Fault Surges, anii Lightning Protection of HVDC
Lines," U.S.-U.S.S.R. Symposium on DC Transmission, September 8-18, 1975,
Leningrad, U. S.S.R.
[ 151 Annestrand, S. A., Hill, H. L., and Capon, A. S., "Direct Current: Transmission
Line Air Clearance Requirements and Selection of Line and Station Insulators,"
US.-U. S.S.R. Symposium on DC Transmission, September 8-18, 1975, Leningrad,
U.S.S.R.
[ 161 ASCE Paper No. 3269, "Wind Forces on Structures," Transactions Vol. 126, Part
11, 196 I, p. 1124.
[ 171 Farr, F. W., Ferguson, C. M., McMurtrie, N. J., Steifler, J. R., Whito, H. B., and
Zobel, E. S., "A Guide to Transmission Structure Design Loadings," IERE Paper
64 62 presented a.t PES Winter Meeting, February 1977, New York.
[ 191 lEEE Paper C-72- 130-2, "Creep Equations of Conductors for Sag-Tension
Calc~ilations."