Documente Academic
Documente Profesional
Documente Cultură
t
* School of Engineering Sciences, University of Southampton, SOl? IBX, UK
t
*bh I k06@soton.ac.uk, suleiman@soton.ac.uk
Keywords: Distributed Generation, Microgrid, Protection 2 Key protection challenges for distribution
networks with embedded DG
Abstract
2.1 Fault current level modification
An effective introduction of distributed generation (DG) into
existing distribution networks (DNs) calls for a review of Connection of a single large DG unit or a large number of
traditional power system protection concepts and strategies. small DG units that use synchronous or induction generators
New issues such as activeness of DNs and bidirectional to the DN will alter the fault current level (FCL) as both types
power flow require new protection solutions. This paper of generator contribute to it. This change in FCL can disturb
discusses protection issues and challenges arising from the fuse-breaker coordination [2]. A different scenario results
integration of DG into the grid. It presents and critically when IIDG units are connected to the DN; due to the
reviews traditional and state of the art protection strategies. controller of these interfaces (Le. inverters), the fault current
Moreover, some alternate protection strategies are proposed is limited electronically to typically twice the load current or
and their merits and demerits are discussed. even less [2-81, and hence an independent relay will not be
able to distinguish between normal operation and a fault
1 Introduction condition without communicating with the inverter. This is
true especially in the case of large PV installations in a DN,
The integration of distributed generation (DG) into where there is hardly any increase in phase current in case of
distribution networks (DNs) requires rethinking of traditional a fault or failure. As fault current is not clearly
protection practices to meet new challenges arising from distinguishable from the operational current, some of the
changes in system parameters, e.g., fault current level and overcurrent (OC) relays will not trip; others that might
direction [1, 2]. Coordination problems between different respond would take many seconds instead of responding in a
protective equipments, i.e., between relay, autoreclosure and fraction of a second. The undetected fault situation can lead to
sectionalizer, can also occur. The level of penetration of DG high voltages despite the low fault currents. Moreover, if the
and the type of interfacing scheme, i.e., whether the DG fault remains undetected for long, it can spread out in the
system is based on direct coupling of rotating machines like system and cause damage to equipment.
synchronous or induction generators or it is interfaced
through a power electronic converter, have a fundamental The fault impendence can also decrease when DG is
impact on the protection scheme as these determine the level introduced into the network in parallel with other devices.
of short circuit current in the system. The key protection The reduced impedance results in high fault levels if the DG
issues, which the protection engineer has to take into unit is a rotating machine or a converter with a low output
consideration, in the new scenario, are short circuit power and impedance (e.g., with an output LC filter) without means of
fault current level, device discrimination, reduction in reach isolation from the DN. In case of a failure, there can be
of overcurrent and impedance relays, bi-directionality and unexpected high fault currents that would put the system
voltage profile, sympathetic tripping, islanding, and mal components at risk.
operation of auto reclosures [2-8].
The position of a fault point relative to a DG unit and a
This paper critically discusses these issues and their solutions substation transformer also affects the operation of the
in the light of long established rules for the design and protection system. When a fault occurs downstream of the
coordination of protective relays in a power system i.e. point of common coupling (PCC), both the main source and
selectivity, redundancy, grading, security, and dependability. the DG will contribute to the fault current as shown in Figure
Section 2 outlines key protection challenges for DNs with 1. But the relay situated upstream of the DG will only
DG. Possible solutions to these challenges including the ones measure the fault current supplied by the upstream source. As
for an islanded microgrid with inverter interfaced DG (IIDG) this is only one part of the actual fault current, the relays,
units are discussed in section 3. Finally, section 4 concludes especially the ones with inverse time characteristics, may not
the findings of the paper. function properly resulting in coordination problems. When
the fault is between the main source and the DG unit, then the
fault current from the main source would not change case of highly loaded or weak networks, DG can also have a
significantly as, generally, a DG unit is comparatively small. positive impact and can improve the network power quality.
---CID=+ _
FDG
I.O_
--
,---_ ,----
IF F_ _ Ir._ oo_
_I.O+
_ T' ___ '=--. DG can also have an impact on the role of tap changing
---,--;- ;;:-- transformers for voltage regulation in distribution networks. If
Main Grid
'i F the location of DG is close to the network infeed, it affects the
tap changing by reducing the load for the transformer. As a
GDG
result of shift in tap changing characteristics, the regulation of
infeed voltage will be incorrect [2, 3]. Moreover, transformer
configuration and grounding arrangements selected for DG
Figure I Fault current contributions from grid and DG connection to the grid must be compatible with the grid to
save the system from voltage swells and overvoltages, and
So in respect of short circuit faults, the incorporation of DG consequent damage [2].
affects the amplitude, direction and duration of fault currents.
The last phenomenon happens indirectly due to the inverse 2.5 Sympathetic tripping
time-current characteristics of relays.
This phenomenon can occur due to unnecessary operation of
a protective device for faults in an outside zone, i.e., a zone
2.2 Device discrimination
that is outside its jurisdiction of operation [3-8]. An
In traditional power systems that have a generation source at unexpected contribution from a DG can lead to a situation
one end of the network, as the distance of the fault point from when a bidirectional relay operates along with another relay
the source increases, the fault current decreases [9]. This is which actually sees the fault, thus resulting in malfunctioning
due to the increase of the impedance in proportion to the of the protection scheme. For example, a relay on line L2 can
distance from the source. This phenomenon is used for unnecessarily operate for a fault Flat line Ll as a result of
discrimination of devices that use fault current magnitude. infeed from a DG to the fault current as shown in Figure 2.
But in case of an islanded microgrid with IIDG units, as the
maximum fault current is limited, so the fault level at QlI LI
locations along the feeder will be almost constant. Hence, the
HVILV
traditional current based discrimination strategies would not
work. New device discrimination strategies are therefore
required to protect the system effectively. Main Grid
the feeder breaker. Use of communication channel between units for grid connection
source components for different types of faults since the -----,- ---:----
Higher tripping time
---,-
theory of the interconnection of equivalent sequence networks characteri sties are
in the event of a fault is applicable here [16]. Log (I)
selected when there is
no big change in the
voltage
Another voltage detection method makes use of the fact that Figure 3 Voltage restrained overcurrent protection
the sum of two squared orthogonal sinusoidal waveforms is scheme logic circuit [14].
equal to a constant value [19]. The necessary 90 degree phase
shift is achieved by passing each phase voltage through an all This scheme although appears to be sound, it has its
pass filter. The output is obtained by summing the squared drawbacks. It is not clear how the scheme will perform if
there is a little difference in magnitude of voltage depression [5] "Distribution System Design for Strategic Use of
resulting from short circuit and overload conditions. The Distributed Generation", EPRI, Palo Alto, CA. (2005).
scheme seems to make use of the principle of relays with [6] T. K. Abdel-Galil et aI., "Protection Coordination
inverse time characteristics, i.e., the larger is the fault current, Planning With Distributed Generation", Qualsys Engco.
the smaller would be the response time. Also it will suffer Inc. , Report Number -CETC 2007-49, (2007).
from a long clearing time in case of faults that cause small [7] W. E. Feero et aI., "White paper on Protection Issues of
voltage drop, thus posing the risk of fault current spreading in The MicroGrid Concept", CERTS, (2002).
the entire network. [8] Power System Relaying Committee, IEEE PES, "The
Impact of Distributed Resources on Distribution
3.1.6 Protection based on symmetrical and differential Relaying Protection", (2004).
current components [9] R.M. Tumilty et aI., "Coordinated Protection, Control &
Automation Schemes for Microgrids", Int. Journal of
An islanded microgrid can be protected against Single Line Distributed Energy Resources, vol. 3, pp. 225-241,
to-Ground (SLG) and Line-to-Line (LL) faults with a (2007).
protection strategy that makes use of symmetrical current [1O]J.A.P. Lopes et aI., "Defining control strategies for
components [20]. Based on these facts, a symmetric approach microgrids Islanded operation", IEEE Transactions on
for protection of a microgrid is proposed in [21]. This scheme Power Systems, vol. 21, no. 2, pp. 916-924, (2006).
makes use of differential and zero-sequence current [11]N. Jayawarna et al., "Safety analysis of a microgrid", Int.
components as a primary protection for SLG faults and coriference on future power systems, pp.l-7, (2005).
negative-sequence current component as a primary protection [12] A. V. Timbus, et aI., "Control strategies for distributed
against LL faults. It is recommended that a threshold should power generation systems operating on faulty grid",
be assigned to each of the symmetrical current components to IEEE Int. Symposium on Industrial Electronics, vol 2, pp.
prevent the microgrid protection from operating under 1601-1607, (2006).
unbalanced load conditions. This threshold should be selected [13]M.E. Baran, I. El-Markaby, "Fault analysis on
carefully to avoid any mal-operation of relays. distribution feeders with distributed generators", IEEE
Transactions on Power Systems, vol.20, no. 4, pp. 1757-
4 Conclusion 1764, (2005).
[14] R.M. Tumilty et aI., "Approaches to network protection
Different protection issues caused by integration of DG into for inverter dominated electrical distribution systems",
DNs have been discussed in the paper. These issues should be PEMD, vol.l, pp.622-626, (2006).
taken into account for designing a reliable protection scheme [15] H. H. Zeineldin et aI., "Distributed Generation Micro
in the new scenario. Various protection schemes for Grid Operation: Control and Protection," Power Systems
microgrids, both in grid connected and islanded mode of Conference, pp. 105-111, (2006).
operation, are explored. The techniques and strategies like [16] M. Brucoli, T. C. Green, "Fault behaviour in islanded
analysis of current using digital signal processing for microgrids", 9th In!. Conference on Electricity
characteristic signatures of faults [22], development of a real Distribution Vienna, pp. 21-24, (2007).
time fault location technique having capability of determining [17] M.E. Baran, I. El Markaby, "Fault analysis on
exact fault location in all situations, use of impedance distribution feeders with distributed generators", IEEE
methods, zero sequence current and/or voltage detection Transactions on Power Systems, vol. 20, no. 4, pp. 1757-
based relaying, and differential methods using current and 1764 (2005).
voltage parameters [23], have the potential for developing [18] A. Sannino, "Static transfer switch: analysis of switching
more robust protection schemes to cope with the new conditions and actual transfer time," in
challenges. PowerEngineering Society Winter Meeting, IEEE, 2001,
vol. 1, pp. 120-125, (2001).
References [19] T. Ise et aI., "Hybrid transfer switch with fault current
limiting function," Proceedings of the rfh Int. Coriference
[1] N. Jenkins et al. "Embedded Generation", lEE Power on Harmonics and Quality of Power, vol.l, pp.189-192,
and Energy Series 31, London, (2000). (2000).
[2] P. P. Barker, R. W. De Mello, "Determining the impact [20]A.R. Bergen "Power System Analysis", Prentice Hall
of distributed generation on power system: part 1 - radial Publications, (1986).
distribution systems", IEEE Power Engineering Society, [21] H. Nikkhajoei, R.H. Lasseter, "Microgrid Fault
vol. 3, pp. 1645-1656, (2000). Protection Based on Symmetrical and Differential
[3] Martin Geidl, "Protection of Power Systems with Current Components", CEC, Public Interest Energy
Distributed Generation: State of the Art", Power Systems Research Program, (2006).
Laboratory, ETH Zurich, (2005). [22]J.D. kueck, B.I. Kirby, "The distribution system of the
[4] K. Maki et aI., "Effect of wind power based distributed future", The Electricity Journal, 16(5): 78-87, 2003.
8t
generation on protection of distribution network", h [23] R. H. Lasseter et aI., "White Paper on Integration of
International Conference on Developments in power Distributed Energy Resources: The CERTS MicroGrid
System Protection, pp. 327-330, (2004). Concept", CERTS, (2002).