Sunteți pe pagina 1din 2

Jiangsu Zhongtian Technology Co., Ltd.

3. The placement of damper


In the open area, the lower wind speed(Vm) causes vibration usually is 0.5m/s and the
upper wind speed(VM) causes vibration usually is 5~6m/s.
b=/2=2.5 x (D/VM x(T'/M) 1/2) here VM=6m/s , simplify the formula into the following formula
b=0.415xDx (T'/M) 1/2)
A. The 1st damper placement L1 calculated as below formula:
1/2
L1 =b= 0.415xDx (T /M) = 0.415x10.50x(0.2x60.0/384)1/2= 0.77m

:Min vibration wavelength


D: Cable diameter (mm)
T: Everyday Tension of conductor (KN)
M: Mass per unit length (kg/km)
Generally, According to our field experience, the 1stdamper should be located onto the
structural reinforced rods and about 50-80mm away from the end.

B. The other damper


The space between the 1st damper and the 2nd, 3rd dampers is that:
L2=L3= 0.58m;
Installing direction: In general, the installing direction of the damper will not influence damper
efficiency; ZTT Company advises that the large weight of the damper will be the same direction
toward the tower.
4. Numbers of Damper
The numbers of dampers per span is determined by terrain, climate, span length and
performance of the damper.
Please refer to the below table for best effecting of Stock-bridge damper:

Quantity of the damper Quantity of each


SPAN (M)
in that span (SET) side (SET)
SPAN< 200 0 0
200< SPAN < 400 2 1
400 < SPAN 700 4 2
700<SPAN<1000 6 3
SPAND > 1000 Please refer to the ZTT for special design.

Anti Vibration Schedule for OPGW 3


Jiangsu Zhongtian Technology Co., Ltd.

5. Protection of clamping-point
ZTT recommend installing a special armor rod to protect the OPGW where the damper clamp is
fixed for reducing the stress of clamping-point and improving the anti- vibration ability.
6. Installation position scheme:
Suspension string installation scheme:

OPGW Out rods Structural Reinforcing Rods Armour Rods Vibration Damper
420
400

80

580 580

Tension string installation scheme:

Dead-end Structural Reinforcing Rods Armour Rods OPGW


420
400
JD

80

580 580

Anti Vibration Schedule for OPGW 4