First Floor
Dead Load Calculation
1. Slab
Dead load of slab= (1.08x0.223+1.325x(1.08+2.23+2.21)+2.21x23x0.15x25=54.94KN
2. Floor Finish
Marble Floor 25mm thick=0.025x14.65x2.65=9.71KN
Ceiling Plaster 12.5 mm thick= 0.0125x14.65x20.4=3.74 KN
Total load due to floor finish = 13.45KN
Second Floor
Dead Load Calculation
1. Slab
Dead load of Slab= (1.08x0.223+1.325x(1.08+2.23+2.21)+2.21x23x0.15x25=54.94KN
Roof Floor
Dead Load Calculation
1. Slab
Dead load of Slab= (1.08x0.223+1.325x(1.08+2.23+2.21)+2.21x23x0.15x25=54.94KN
2. Floor Finish
12.5 mm Screeding with Punning = 0.0125x21x14.65 = 3.846 KN
Ceiling Plaster 12.5 mm =0.0125x20.4x14.65= 3.735KN
Total= 7.581KN
Machine Floor
Dead Load Calculation
1. Self Weight of Slab= 2.23x2.23x0.15x25= 18.648 KN
2. Self Weight of Lift= 6.69x0.2x3/2x25= 50.175KN
Total Dead Load= 68.82KN
1.20 m
2.673 m
X
2.673 m
Additional eccentricity
IS 456- 4
2000 H 2 we 3202.5 2
Cl.32.2.5 ea = 20.51 mm ea=20.51mm
2500 t 2500 x 200
Mu 688.377 x 10 6
0.0346
f ck bd 2 20 x 200 x 2230 2
Pu 723.076 x 1000
0.081
f ck bd 20 x 200 x 2230
p
SP-16, 0.01
f ck
Chart 35
p = 0.01 x 20 = 0.2 %
p= 0.2 %
Min, Ast = 0.12 % of bD < 0.2 %
.
. . Ast = 0.002 x 200 x 2230= 892 mm2
IS 456-
2000 Area of 12 mm = 113.09 mm2
Cl.32.5 a
892
No. of Bars = =7.88 8 nos
113 .09
2230 40 12
.
. . Spacing of Bars, Sv = 311.14 mm
8 1
Check for Spacing
Spacing of vertical steel reinforcement should be least of
3t = 3 x 200 = 600 mm
IS 456- 450 mm
2000
Cl.32.5 b To take account of the reversal effect, Provide 12 mm bars @ 300
mm c/c on both faces of the wall
Mu 688.377 x 10 6
0.0346
f ck bd 2 20 x 200 x 2230 2
Pu 723.076 x 1000
0.081
f ck bd 20 x 200 x 2230
p
0.01
f ck
p = 0.01 x 20 = 0.2 %
SP-
16,Chart
35 Min, Ast = 0.12 % of bD < 0.2 %
.
. . Ast = 0.002 x 200 x 2230= 892 mm2 p= 0.2 %
Area of 12 mm = 113.09 mm2
892
IS 456- No. of Bars = =7.88 8 nos
2000 113 .09
Cl.32.5 a
2230 40 12
.
. . Spacing of Bars, Sv = 311.14 mm
8 1
Check for Spacing
Spacing of vertical steel reinforcement should be least of
3t = 3 x 200 = 600 mm
450 mm
To take account of the reversal effect, Provide 12 mm bars @ 300
IS 456- mm c/c on both faces of the wall
2000
Cl.32.5 b
Calculation of Horizontal Steel Reinforcement 12 @ 300
Area of horizontal steel reinforcement = 0.2 % bH mm c/c
= 0.002 x 200 x 4270
Vu Vu 65.072 x 10 3
v 0.182 N / mm 2
td t x 0.8 Lw 200 x 0.8 x 2230
8 Allowable Shear Stress,
a)
allowable 0.17f ck 0.17 x 20 3.4 N / mm 2 > v
IS 456- H w 4270
2000 1.91 1 ( High Wall )
Cl.32.4.2 Lw 2230
H w 1
L 1.91 1
cw K 2 f ck w
0.045 20 0.643N / mm
2
H w 1 1.91 1
IS 456-
2000
Cl.32.4.3 b Lw
But not less than 0.15 f ck 0.15 20 0.671 N / mm 2
IS 456- .
cw =0.6716 N/mm2 > v cw =0.643
2000 . .
Cl.32.4.3 b N/mm2
Hence, Safe