Sunteți pe pagina 1din 36

Instruction book for compressors

GA11 - GA15 - GA18 - GA22

Important
This book applies exclusively:
F1042 1. To GA11 - GA15 - GA18 - GA22 equipped with an electronic regulator as shown on the
left above. For these compressors, this book must be used together with the "User
manual for electronic regulator for GA5 up to GA45 compressors"
2. To GA11 - GA15 - GA18 - GA22 with an electro-pneumatic regulator as shown on the left
below.

From serial number AII-217 792 onwards

F051 This instruction book meets the requirements for instructions specified by the
machinery directive 89/392/EEC and is valid for CE as well as non-CE labelled machines

Registration code
Collection: APC G11-22
Tab: 38
Sequence:0992

Replaces
No. 2920 1256 00

No. 2920 1256 01


Industrial Air Division Instruction book

This instruction book describes how to handle the machines to ensure safe operation, optimum efficiency and long service life.
Read this book before putting the machine into operation to ensure correct handling, operation and proper maintenance from the beginning.
The maintenance schedule comprises measures for keeping the machine in good condition.
Keep the book available for the operator and make sure that the machine is operated and that maintenance is carried out according to the
instructions. Record all operating data, maintenance performed, etc. in an operator's logbook available from Atlas Copco. Follow all relevant
safety precautions, including those mentioned on the cover of this book.
Repairs must be carried out by trained personnel from Atlas Copco who can be contacted for any further information.
In all correspondence always mention the type and the serial number, shown on the data plate.
For all data not mentioned in the text, see sections "Preventive maintenance schedule" and "Principal data".
The company reserves the right to make changes without prior notice.

CONTENTS
Page Page
1 Leading particulars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
1.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4.1 Compressor motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
1.1.1 Air flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4.2 Preventive maintenance schedule for the compressor 27
1.1.2 Oil system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4.3 Oil and oil filter change interval . . . . . . . . . . . . . . . . . . 28
1.1.3 Cooling and condensate drain systems . . . . . . . 5 4.4 Oil specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1.2 Unloading/loading system . . . . . . . . . . . . . . . . . . . . . . . 5 4.4.1 Atlas Copco Roto-injectfluid. . . . . . . . . . . . . . . 28
1.2.1 Unloading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 4.4.2 Mineral oil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1.2.2 Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 4.5 Oil and oil filter change . . . . . . . . . . . . . . . . . . . . . . . . . 28
1.3 Electrical system for GA Pack / Full-feature . . . . . . . . . 6 4.6 Storage after installation . . . . . . . . . . . . . . . . . . . . . . . 29
1.4 Electronic control module for GA Pack / Full-feature . . . 8 4.7 Service kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.4.1 Electronic regulator . . . . . . . . . . . . . . . . . . . . . . 8
1.4.2 Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.5 Electrical system for GA Standard Pack . . . . . . . . . . . 14 5 Adjustments and servicing procedures . . . . . . . . . . . . . . 29
1.5.1 Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 5.1 Air filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.5.2 Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . 15 5.2 Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.6 Air dryer on GA Full-feature . . . . . . . . . . . . . . . . . . . . . 15 5.3 Safety valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.6.1 Compressed air circuit . . . . . . . . . . . . . . . . . . . 15 5.4 Belt set exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.6.2 Refrigerant circuit. . . . . . . . . . . . . . . . . . . . . . . 15 5.5 Fan control switch on GA Full-feature . . . . . . . . . . . . . 29
5.6 High pressure shut-down switch on GA Full-feature . . 29
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.7 Expansion valve on GA Full-feature . . . . . . . . . . . . . . . 29
2.1 Dimension drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 5.8 Load/unload pressure switch on GA Standard Pack . . 30
2.2 Electric cable size, settings of overload relay and main
5.9 Temperature shut-down switch on GA Standard Pack. 30
fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.2.1 Electric cable size . . . . . . . . . . . . . . . . . . . . . . 18
2.2.2 Setting of motor overload relay and fuse value 18 6 Problem solving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.3 Installation proposals . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.4 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.5 Pictographs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 7 Principal data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3 Operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7.1 Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.1 Before initial start-up . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7.1.1 Readings on display on GA Pack / Full-feature 33
3.1.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . 24 7.1.2 Readings on gauges on GA Standard Pack . . 33
3.1.2 User manual (GA Pack / Full-feature only) . . . 24 7.2 Setting of safety valve . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.1.3 Outdoor/altitude operation . . . . . . . . . . . . . . . . 24 7.3 Dryer control switches and refrigerant specifications on
3.1.4 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 GA Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.1.5 External compressor status indication 7.4 Compressor specifications . . . . . . . . . . . . . . . . . . . . . . 33
(GA Pack / Full-feature only) . . . . . . . . . . . . . . 24 7.4.1 Reference conditions . . . . . . . . . . . . . . . . . . . . 33
3.1.6 Compressor control modes (GA Pack / Full- 7.4.2 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
feature only) . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7.4.3 Specifications of GA 7.5 bar . . . . . . . . . . . . . . 34
3.2 Initial start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7.4.4 Specifications of GA 10 bar . . . . . . . . . . . . . . . 34
3.3 Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 7.4.5 Specifications of GA 13 bar . . . . . . . . . . . . . . . 34
3.4 During operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 7.4.6 Specifications of GA 100 psi . . . . . . . . . . . . . . 35
3.4.1 Checking the display (GA Pack / 7.4.7 Specifications of GA 125 psi . . . . . . . . . . . . . . 35
Full-feature only) . . . . . . . . . . . . . . . . . . . . . . . 25 7.4.8 Specifications of GA 150 psi . . . . . . . . . . . . . . 36
3.5 Manual control for GA Pack / Full-feature . . . . . . . . . . 26 7.4.9 Specifications of GA 175 psi . . . . . . . . . . . . . . 36
3.6 Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 7.5 Conversion list of SI units into US/British units . . . . . . 36
Instruction book Industrial Air Division

1 LEADING PAR
PARTICULARS
ARTICULARS Options and special versions

1.1 General description


Full- Pack Standard
GAare stationary, single-stage, oil-injected screw compressors driven feature Pack
by an electric motor. GA11 up to GA22 are air-cooled.

GA Standard Pack (Figs. 3) Energy recovery kit ............................. 0 0 NA


The compressors are enclosed in a sound-insulated bodywork. A Integrated oil separator (OSD) 1) ....... 0 0 0
control panel including the start/stop switch is provided. An electric High ambient version (up to 50 C)...... NA 0 0
cabinet comprising the relay-controlled regulator and motor starter is Public works version ........................... 0 0 0
located behind this panel. Oil protecting frame plate .................... 0 0 0
Modulating control regulator ............... 0 0 0
GA Pack (Figs. 2) Integrated condensate
The compressors are enclosed in a sound-insulated bodywork. The separator (WSD) ................................. S S 0
front panel comprises an electronic control module including the start Integrated dryer................................... S 0 NA
and stop buttons. An emergency stop button is also provided. An 8 bar version ....................................... 0 0 0
electric cabinet comprising the motor starter is located behind this Electronic drain ................................... 0 0 0
panel. An automatic condensate drain system is provided. Dryer by-pass ...................................... 0 0 NA
Silencing kit ......................................... 0 0 0
GA Full-feature (Fig. 1) Relay expansion box........................... 0 0 NA
GA Full-feature are GA Pack compressors additionally provided with
an air dryer integrated in the bodywork. The dryer removes moisture
from the compressed air by cooling the air to near freezing point and 0 = optional S = standard NA = not available
automatically draining the condensate. See section 1.6.

1.1.1 Air flow (Fig. 4)

Air drawn through filter (AF) and open inlet valve (IV) into compressor
1 E OF 2 Ca/Co 8 VP 7 element (E) is compressed. The compressed air flows through oil
separator (OS), minimum pressure valve (Vp) and air cooler (Ca) to
outlet valve (AV).

1.1.2 Oil system (Fig. 4)

Air pressure forces the oil from air receiver (AR) through oil cooler
(Co) and filter (OF) to compressor element (E) and the lubrication
points.

The system comprises a by-pass valve (BV). When the oil temperature
is below 40 C (104 F) 2)2), there is no oil flow to the oil cooler. At
approx. 55 C (131 F) 2)
2), the valve is closed so that all the oil passes
through the cooler.

1) If an oil separator is desired for Pack and Full-feature compressors


equipped with an energy recovery kit, a freestanding OSD must be
F058 applied.
DP2 M1 4 3 FN 2) For 13 bar/175 psi compressors, these temperatures are 60 C (140 F)
Industrial Air Division Instruction book

MT SV AF VI E

OF

BV

AV

F057

Dm1 Da DP2 M1

Fig. 2a. GA Pack, motor side

AF. Air filter FC. Oil filler plug 1. Dryer


AR. Air receiver FN. Compressor cooling fan 2. Control panel
AV. Air outlet valve Gl. Oil level indicator 3. Arrow, direction of rotation of drive
BV. By-pass valve, oil circuit M1. Motor motor
Ca. Air cooler MT. Moisture trap 4. Motor voltage supply
Co. Oil cooler OF. Oil filter 5. Belt tensioning bolt
Da. Automatic condensate drain PSR19. Load/unload pressure switch 6. Transport spacer/bolt
outlet SV. Safety valve 7. Side panel
Dm1. Manual condensate drain valve VI. Air filter service indicator 8. Bolt
DP1/DP2. Oil drain plugs VP. Vent plug, oil circuit 9. Bolt
E. Compressor element Vp. Minimum pressure valve 10. Arrow, direction of rotation of drive
motor
Instruction book Industrial Air Division

F059
F059
10 FN

Fig. 2b. GA Pack/Full-feature, receiver side

1.1.3 Cooling and condensate drain systems the net pressure increases. When the net pressure reaches the
unloading pressure, solenoid valve (Y1) is de-energized. The plunger
of the valve returns by spring force:
The cooling system comprises air cooler (Ca-Fig. 1) and oil cooler
(Co). The cooling air is generated by fan (FN).
1. The control pressure present in the chambers of loading plunger
(LP) and unloading valve (UV) is vented to atmosphere via
Amoisture trap (MT-Fig. 2a) is provided in the air outlet system of GA
solenoid valve (Y1).
Pack and Full-feature compressors. 1)1). The trap is equipped with a
2. Loading plunger (LP) moves upwards and causes inlet valve (IV)
valve for automatic condensate draining during operation (Da) and a
to close the air inlet opening.
manually operated valve for draining after stopping the compressor
3. Unloading valve (UV) is opened by receiver pressure. The
(Dm1).
pressure from air receiver (AR) is released towards unloader (UA).

Air output is stopped (0 %), the compressor runs unloaded.


1.2 Unloading/loading system (Fig. 4)

1.2.1 Unloading
Industrial Air Division Instruction book

Fig. 3a. GA18 Standard Pack, motor side Fig. 3b. GA18 Standard Pack, receiver side

1.2.2 Loading 1.3 Electrical system for GA Pack / Full-feature

When the net pressure decreases to the loading pressure, solenoid The system comprises:
valve (Y1) is energized. The plunger of the valve moves against
spring force: 1. Compressor motor (M1-Fig. 2a)
2. Electronic control module (Fig. 7a)
1. Control pressure is fed from air receiver (AR) via solenoid valve 3. Compressor start button (I) and stop button (O) (Fig. 7a)
(Y1) to loading plunger (LP) and unloading valve (UV). 4. Emergency stop button (S3-Fig. 7a)
2. Unloading valve (UV) closes the air blow-off opening. Loading 5. Electric cabinet (Fig. 5a)
plunger (LP) moves downwards and causes inlet valve (IV) to 6. Sensors for the compressor element outlet temperature (TT11)
open fully. and for the air outlet pressure (PT20)
7. Dewpoint temperature sensor (TT90) for Full-feature compressors
Instruction book Industrial Air Division

AF. Air filter IV. Inlet valve 1. Oil scavenging line


AR. Air receiver LP. Loading plunger 2. Flexible, control air
AV. Air outlet valve M1. Compressor motor 3. Belts
BV. Oil cooler by-pass valve MT. Moisture trap
Ca. Air cooler OF. Oil filter On Full-feature also:
Co. Oil cooler OS. Oil separator element FN1. Fan, dryer condenser
Da. Automatic condensate drain PT20. Pressure sensor, air outlet M1. Refrigerant compressor
outlet SV. Safety valve M2. Motor, condenser fan
Dm1. Manual condensate drain valve TT90. Temperature sensor, dewpoint 4. Expansion valve
DP1/DP2. Oil drain plugs UA. Unloader 5. Air/air heat exchanger
E. Compressor element UV. Unloading valve 6. Air/refrigerant heat exchanger
E1. Control module VI. Air filter service indicator (evaporator)
FC. Oil filler plug Vp. Minimum pressure valve 7. Liquid separator
FN. Fan VP. Vent plug, oil circuit 8. Condenser
Gl. Oil level indicator Y1. Loading solenoid valve 9. Liquid receiver
Industrial Air Division Instruction book

1.4 Electronic control module for GA Pack / Full- The regulator stops the compressor whenever possible to reduce the
feature power consumption and restarts it automatically when the net pressure
decreases. In case the expected unloading period is too short, the
The control module consists of an electronic regulator and a control compressor is kept running to prevent too-short standstill periods.
panel.
Protecting the compressor
If the compressor element outlet temperature exceeds the
programmed shut-down level, the compressor will be stopped. This
1.4.1 Electronic regulator (E1-Fig. 6a) will be indicated on the control panel (Fig. 7a). The compressor will
also be stopped in case of overload of compressor motor (M1).
The regulator has following functions:
If the compressor element outlet temperature exceeds a programmed
Controlling the compressor value below the shut-down level, this will also be indicated to warn
The regulator maintains the net pressure between programmable limits the operator before the shut-down level is reached.
by automatically loading and unloading the compressor. Anumber of
programmable settings, e.g. the unloading and loading pressures,
the minimum stop time and the maximum number of motor starts are
taken into account.

See legend of Figs. 6 for denomination of components See legend of Figs. 8 for denomination of components
Instruction book Industrial Air Division
Industrial Air Division Instruction book

Fig. 6b. Electrical diagram, dryer on GA Full-feature

SENSORS/LOADING SOLENOID VALVE F21. Overload relay, compressor motor K05. Auxiliary relay, high/low air pressure
PT20. Pressure sensor, air outlet K11. Auxiliary contactor for dryer 1) K10. Auxiliary relay, dryer
TT11. Temperature sensor, compressor K21. Line contactor O. Stop button
element outlet K22. Star contactor S3. Emergency stop button
TT90. Temperature sensor, dewpoint 1) K23. Delta contactor 2X1/6. Connectors
Y1. Loading solenoid valve T1/T2. Transformers
Y2. Solenoid valve, modulating control 1X1. Terminal strip On GA Full-feature also:
(optional) 1X2. Terminal strip F0. Fuses (customer's installation)
C1. Capacitor
MOTORS CONTROL MODULE (E1) M1. Refrigerant compressor/motor
M1. Compressor motor I. Start button M2. Motor, condenser cooling fan
K01. Blocking relay S3. Control switch, condenser cooling
ELECTRIC CABINET K02. Auxiliary relay, star contactor fan
E2. Relay expansion box (optional) K03. Auxiliary relay, delta contactor
F1/F5. Fuses K04. Auxiliary relay, loading/unloading 1) Only for Full-feature compressors.

Figs. 6. Electrical diagrams for GA Pack / Full-feature

Monitoring components subject to service Automatic restart after voltage failure


The regulator continuously monitors the oil, oil filter, oil separator and For compressors leaving the factory, this function is made inactive. If
air filter. Each input is compared to programmed time intervals. If desired, the function can be activated. Consult Atlas Copco.
these limits are exceeded, a message will appear on the display (Fig.
7a) to warn the operator to replace the indicated component. The If activated and provided the module was in the automatic operation
number of the service kit will appear on the display. mode, the compressor will automatically restart if the supply voltage
Instruction book Industrial Air Division

1.4.2 Control panel (Fig. 7a)

Indicators, keys and buttons

To control the compressor and to read and modify programmable


parameters, the regulator is provided with a panel including:

1 Automatic operation LED


Indicates that the regulator is automatically controlling the
compressor: the compressor is loaded, unloaded, stopped
and restarted depending on the air consumption and the
limitations programmed in the regulator.

2 Voltage on LED
Indicates that the voltage is switched on.

3 General alarm LED


Is normally out. Is alight or blinks in case of an abnormal
condition. See below.

4 Display
Indicates:
- the name of the sensor of which the actual reading is
displayed
- the unit and actual reading S3. Emergency stop button 8. Start button
- messages regarding the operating status, a sensor 1. LED, automatic operation 9. Stop button
error, a service need or a fault 2. LED, voltage on 10. Pictograph, emergency
3. LED, general alarm stop
5 Function keys 4. Display 11. Pictograph, automatic
Keys to control and program the compressor. The actual 5. Function keys operation
function of each key is abbreviated and indicated on the bottom 6. Scroll keys 12. Pictograph, voltage on
line. The most common ones are listed below. 7. Tabulator key 13. Pictograph, alarm

6 Scroll keys Fig. 7a. Control panel of GA Pack / Full-feature


As long as an arrow is shown on the right side of the display,
the key with the same symbol can be used to scroll through
the display.

7 Tabulator key
Key to go to the next field of the display. Delivery air
bar 7.0
8 Start button Auto loaded
Push button to start the compressor. LED (1) lights up Menu More Unld
indicating that the regulator is operative (in automatic
operation). The LED goes out after unloading the compressor F1 F2 F3
manually.
Fig. 7b. Example of the main display
9 Stop button
Push button to stop the compressor. LED (1) goes out. The
compressor will stop after running in unloaded condition for
30 seconds.
Status data
S3 Emergency stop button
Push button to stop the compressor immediately in case of Main Slct
emergency. Must be unlocked before restarting.
F1 F2 F3
Industrial Air Division Instruction book
Instruction book

. Fuses P1. Hourmeter, total running time


Overload relay, compressor PSR19. Load/unload pressure switch
motor S1. Start/stop switch
Line contactor T1. Transformer
Industrial Air Division

Star contactor TSHH11. Temperature shut-down switch


Delta contactor Y1. Loading solenoid valve
Time relay, star/delta switch-over (10 sec) Y2. Solenoid valve, modulating control (optional)
Time relay, delayed motor stopping (5 min) 1X1. Terminal strip
Compressor motor 1X2. Terminal strip Figs. 8. Electrical diagrams, GA Standard Pack
Industrial Air Division Instruction book

General alarm LED (3-Fig. 7a) 1) Selecting a menu


- The LED blinks in case of a shut-down (due to either too high To facilitate controlling the compressor, menu-driven programs are
a compressor element outlet temperature or overload of the implemented in the electronic module. Use the function keys (5) to
compressor motor); at the same time the shut-down screen select the menus in order to program and monitor the compressor.
appears. Remedy; see section 6. After eliminating the cause The "User manual for electronic regulator for GA5 up to GA45
of the trouble and when the abnormal condition has compressors" deals elaborately with all regulator functions.
disappeared, press key <<Rset>> (5).
- The LED blinks and the compressor is shut down if the sensor Function keys
of the compressor element (TT11) is out of order; at the same
time the display will show a fault message. Switch off the
Abbre- Desig- Function
voltage, depressurize and check the sensor and its wiring.
viation nation
- The LED is alight in case of a shut-down warning; at the same
time a warning message appears. Remedy; see section 6.
- The LED is alight if the dewpoint sensor (TT90) is out of order Add Add To add compressor start/stop commands (day/
(on Full-feature compressors); at the same time a fault hour)
message is shown. Stop the compressor, switch off the Canc Cancel To cancel a programmed setting when
voltage, depressurize and check the sensor and its wiring. programming parameters
Del Delete To delete compressor start/stop commands
Lim Limits To show limits for a programmable setting
List List To list programmed start/stop commands (day/
hour)
Load Load To load the compressor manually
Main Main To return from a menu to the main display (Fig.
7b)
Menu Menu Starting from the main display (Fig. 7b), to
initiate the main menu (Fig. 7c) which gives
access to submenus
Starting from a submenu, to return to the main
menu (Fig. 7c)
Mod Modify To modify programmable settings
More More To have a quick look at the compressor status
Prog Program To program modified settings
Rset Reset To reset a timer or message
Rtrn Return To return to a previously shown option or menu
Slct Select To select a submenu or to read more details of
a selection shown on display
Unld Unload To unload the compressor manually

1.5 Electrical system for GA Standard Pack

The system comprises:


1. Compressor motor (M1-Fig. 3a)
2. Regulator (Fig. 5b)
Gp. Gauge indicating the working pressure 3. Control panel with start/stop switch (S1-Fig. 9)
P1. Hourmeter indicating the total motor running time 4. Temperature shut-down switch (TSHH11-Fig. 9)
S1. Switch to start or stop the compressor 5. Load/unload pressure switch (PSR19-Fig. 14)
TSHH11. Gauge/switch, indicating the temperature at the outlet
of the compressor element as well as the shut-down
temperature; the regulator then stops the compressor
1. Pictograph, working pressure
2. Pictograph, outlet temperature of compressor element
3. Pictograph, running hours
4. Pictograph, compressor stop
5. Pictograph, compressor start
1) Consult the User manual for the electronic regulator, section "Status
Instruction book Industrial Air Division

1.5.1 Regulator (Fig. 5b) 1.6 Air dryer on GA Full-feature (Fig. 4)

The regulator loads, unloads, stops and restarts the compressor GA Full-feature are provided with a dryer which removes moisture
according to the air consumption, and protects the compressor and from the compressed air. See Fig. 6b for the electrical diagram.
motor from overloads. The unloading and loading pressures are the
opening and closing pressures respectively of switch (PSR19). See
section 5.8. 1.6.1 Compressed air circuit
Delayed motor stopping Compressed air enters heat exchanger (5) and is cooled by the
The time relay for delayed motor stopping (K26) limits the frequency outgoing, cold, dried air. Water in the incoming air starts to condense.
of automatic motor starts by stopping the motor only after a set time The air then flows through heat exchanger (6) where the refrigerant
of 5 minutes of uninterrupted unloaded operation. If the net pressure evaporates and withdraws heat from the air. This cools the air to
drops to the loading pressure within the set unloading time, the close to the evaporating temperature of the refrigerant. More water
compressor will be loaded without stopping. in the air condenses. The cold air then flows through moisture trap
(MT) where all the condensate is separated from the air. The
Compressor temper ature shut-do
temperature wn sswitch
shut-down witch (TSHH11) condensate is automatically drained through outlet (Da). The cold
The switch prevents damage resulting from too high a temperature dried air then flows through heat exchanger (5), where it is warmed
at the outlet of the compressor element. up by the incoming air.

Motor overload relay (F21)


The relay prevents damage resulting from too high a motor current. 1.6.2 Refrigerant circuit

Compressor (M1) delivers high-pressure refrigerant gas which flows


1.5.2 Control panel (Fig. 9) via liquid separator (7) through condenser (8) where most of the
refrigerant condenses. The cooled refrigerant then collects in receiver
Gp. Gauge indicating the working pressure (9).
P1. Hourmeter indicating the total motor running time
S1. Switch to start or stop the compressor The liquid flows to expansion valve (4) where it expands to evaporating
TSHH11. Gauge/switch, indicating the temperature at the outlet of pressure. The refrigerant enters evaporator (6) where it withdraws
the compressor element as well as the shut-down heat from the compressed air by further evaporation. The vapour
temperature; the regulator then stops the compressor refrigerant leaving evaporator (6) flows into liquid separator (7) and
1. Pictograph, working pressure is sucked in by compressor (M1).
2. Pictograph, outlet temperature of compressor element
3. Pictograph, running hours
4. Pictograph, compressor stop
5. Pictograph, compressor start
Industrial Air Division Instruction book

2 INSTALLATION
INSTALLA
2.1 Dimension drawings (Figs. 10)
Instruction book Industrial Air Division
Industrial Air Division Instruction book

2.2 Electric cable size, settings of overload relay (F21) and main fuses

Attention
- Local regulations remain applicable if they are stricter than the values proposed below.
- The voltage drop must not exceed 5 % of the nominal voltage. It may be necessary to use cables with a larger section than those stated
to comply with this requirement.
- Max. cable length = 25 m, max. ambient temperature = 40 C, cables in free air or in raceway, copper conductors.

2.2.1 Electric cable size 1)

Frequency Supply voltage Cable size


(Hz) (V) (mm2 or A WG)
AWG)
GA11 GA15 GA18 GA22

Star-delta starter
50 3 x 230 10/16 16/16 25/25 35/35
50 3 x 400 4/6 6/10 10/16 10/16
50 3 x 500 4/4 6/6 6/10 10/10
60 3 x 220/230 10/16 16/25 25/35 35/35
60 3 x 380 4/6 10/10 10/16 16/16
60 3 x 440/460 4/6 6/10 10/10 10/16
Direct-on-line starter
60 3 x 220/230 AWG6/4 AWG4/4 AWG4/3 AWG3/2
60 3 x 440/460 AWG10/8 AWG8/6 AWG8/6 AWG6/6
60 3 x 575 AWG10/10 AWG10/8 AWG8/6 AWG8/6

2.2.2 Setting of motor overload relay and fuse value 2)


For star-delta starter 3)

GA11 GA11 GA15 GA15 GA18 GA18 GA22 GA22


Voltage Relay Fuse Relay Fuse Relay Fuse Relay Fuse Unit

230 26/- 63/- 35/- 80/- 43/- 100/- 48/- 100/- A


220-230 -/26 -/63 -/37 -/80 -/43 -/100 -/50 -/100 A
380 -/15 -/35 -/21 -/50 -/25 -/63 -/29 -/63 A
400 15/- 35/- 20/- 50/- 25/- 63/- 28/- 63/- A
440-460 -/13 -/35 -/19 -/50 -/22 -/50 -/25 -/63 A
500 12/- 25/- 16/- 35/- 20/- 35/- 22/- 50/- A

For direct-on-line starter (60 Hz) 4)

GA11 GA11 GA15 GA15 GA18 GA18 GA22 GA22


Voltage Relay Fuse Relay Fuse Relay Fuse Relay Fuse Unit

220-230 45 80/70 64 125/125 75 150/150 87 200/175 A


440-460 23 60/60 32 80/70 37 80/70 43 80/70 A
575 17 60/60 25 60/60 29 80/70 33 80/70 A

1) Figures before the slant apply to Standard Pack, figures behind it apply to Pack and Full-feature.
2) The indicated value is the maximum fuse value with regard to short circuit protection of the starter. The cable size of the used supply cables may impose
fuses of a lower value.
Instruction book Industrial Air Division

2.3 Installation proposals (Figs


(Figs.. 11)
Industrial Air Division Instruction book
Instruction book Industrial Air Division

Ref. Description/recommendation For Standard P ac


Pac k also (Fig. 11b):
ack

1 Install the compressor on a level floor suitable for taking the 8 Optional filters can be installed in the pressure line
weight of the compressor, and with a minimum clearance of downstream of the outlet valve:
1.2 m above the unit except for ventilation proposals 2 and - A DD filter for general-purpose filtration (filter traps
4. solid particles down to 1 micron with max. oil carry-
over of 0.5 mg/m ).
2 Position of compressed air outlet valve. - A high-efficiency PD filter (traps solid particles down
to 0.01 micron with max. oil carry-over of 0.01 mg/m ).
3 The maximum total pipe length (including interconnecting A PD filter must be installed downstream of a DD
piping between compressor and receiver) can be calculated filter.
as follows: - If oil vapour and odours are undesirable, a filter of the
QD type should be installed downstream of the PD
P x d5 x P filter.
_________________
L =
450 x Qc1.85 9 Position of receiver safety valve

L = pipe length in m - A condensate trap is available as option


P = maximum allowable pressure drop
(recommended 0.1 bar) - The air receiver (optional) should be installed in a frost-free
d = inner diameter of pipe in mm room and on a level concrete foundation.
P = compressor outlet pressure in bar absolute
Qc = free air delivery of compressor in l/s For normal air consumption, the volume of the air net
(receiver and piping) can be calculated as follows:
4 Ventilation: the inlet grids and ventilation fan should be
installed in such a way that any recirculation of cooling air 7.5 x Q x P
_______________
to the compressor or dryer is avoided. The air velocity to V =
the grids must be limited to 5 m/s. The maximum allowable P
pressure drop over the cooling air ducts is 30 Pa. If this
pressure drop is exceeded, a fan is needed at the outlet of V = volume of air net in l
the cooling air ducts. The maximum air temperature at the Q = free air delivery of compressor in l/s
compressor intake opening is 40 C (minimum 0 C). P = compressor air inlet pressure in bar absolute
P = Punload - Pload in bar
The required ventilation to limit the compressor room
temperature can be calculated as follows: For Pac
Pac k and Full-f
ack eature also (Fig. 11a):
Full-feature

For alternatives 1 and 3: Qv = 0.92 N/T 8 Provision for energy recovery system

Qv = required ventilation capacity in m3/s 9 Optional filters can be installed in the pressure line
N = shaft input of compressor in kW downstream of the outlet valve, see reference 8 above.
T = temperature increase in compressor room
10 Position of receiver safety valve
For alternatives 2 and 4, the fan capacity should match the
compressor fan capacity at a pressure head equal to the 11 Dryer by-pass pipe, to be used to by-pass the dryer in case
pressure drop caused by the cooling air outlet ducts. of servicing the dryer. Consult Atlas Copco.

5 Position of condensate drain flexibles. The flexibles 12 Optional condensate trap and valve, can be used during
towards the drain collector must not dip into the water of servicing of the dryer. Consult Atlas Copco.
the drain collector. Atlas Copco has oil separators (type
OSD) to separate the major part of oil from condensate to 13 Provision for oil separation system (Atlas Copco OSD-type
ensure that the condensate meets the requirements of the oil separator). Consult Atlas Copco.
environmental codes (see also reference 13 below)
- The air receiver (optional) should be installed in a frost-free
6 Position of control panel. room and on a level concrete foundation.

7 Position of mains cables entry. See section 2.2 for the For normal air consumption, the volume of the air net
recommended electric cables. See section 2.4 for (receiver and piping) can be calculated as described above.
connecting the power supply.
Industrial Air Division Instruction book

2.4 Electrical connections

General
- The installation must include an isolating switch near to and visible
from the compressor. Mak Makee sure that this sswitch
witch is open to
isolate the compressor from the mains before carrying out
any connection
connection.
- See section 2.2 for the size of the electric cables.
- The installation must be earthed and protected against short
circuits by fuses of the inert type in each phase. See section 2.2.
- The electrical connections must correspond to the local codes.
- The indications on the data plate of the drive motor must
correspond to the mains supply voltage and frequency.
- Check the fuses and the setting of the overload relay. See section
2.2.
- Lay-out the power supply cables under the compressor frame
and then through the bottom of the electric cabinet via a 90 elbow
(is delivered loose).

On GA Standard Pack
Connect the power supply to terminals (L1, L2 and L3) of terminal
strip (1X2-Fig. 5b).
For compressors with voltage transformer, check that the connections
at the primary side of the transformer correspond to the mains voltage.
For compressors without voltage transformer, check the connection
of wire (2):
- either towards the neutral terminal (N) in case of a 3 x 400 Vplus
neutral mains; connect the neutral conductor to terminal (N).
- or towards terminal (2) of fuse F2 in case of a 3 x 230 V mains

On GA Pack
Connect the power supply to terminals (L1, L2 and L3) of terminal
strip (1X2-Fig. 5a). Connect the neutral conductor to terminal (N).
Consult section 2.2.

On GA Full-feature
- Connect the power supply to terminals (L1, L2 and L3) of terminal
strip (1X2-Fig. 5a). Connect the neutral conductor to terminal
(N). Consult section 2.2.
- The voltage to the dryer is supplied over the contacts of relay
(K11-Fig. 5a), which close when the compressor is started.
- The vvoltage
oltage supply to the dr yer m
dry ust be single-phase 230 V.
must
The voltage may be branched off directly from the mains supply
or via an optional voltage transformer.

1. The dryer voltage supply is branched off from the mains


supply Fig. 12. Dryer connections on GA Full-feature

- For a compressor supply voltage of 3 x 400 V plus neutral


conductor (A-Fig. 12):
The dryer supply voltage is branched off between a phase
provided. Use wiring of minimum 1.5 mm . The dryer must
conductor and the neutral conductor.
be protected by fuses of 10 A (except for 60 Hz CSA/UL: 8 A
- For a compressor supply voltage of 3 x 230 V (B-Fig. 12):
for GA11/15 and 12 A for GA18/22).
The dryer supply voltage is branched off between two phase
conductors.
2. The dryer voltage is branched off from the optional
- For all other supply voltages (C-Fig. 12):
voltage transformer
Instruction book Industrial Air Division

2.5 Pictographs

Fig. 13 shows typical examples of pictographs used for GAcompres-


sors. See also Fig. 9.

1. Water outlet
2. Water inlet
3. Manual condensate drain
4. Automatic condensate drain
5. Before connecting compressor electrically, consult instruction
book for motor rotation direction
6. Torques for steel (Fe) or brass (CuZn) bolts
7. Consult Instruction book before greasing
8. Switch off voltage before removing protecting cover inside
electric cubicle
9. Switch off voltage and depressurize compressor before
repairing

Fig. 13. Pictographs


Industrial Air Division Instruction book

3 OPERATING INSTRUCTIONS
INSTRUCTIONS CMS1 CMS2
CMS2 Compressor mode

3.1 Before initial start-up


0 0 Compressor off
3.1.1 Safety precautions
1 0 Compressor in local control mode (remote
control is made inactive).
The operator must apply all relevant safety precautions, including
those mentioned in this book.
0 1 or
1 1 Compressor in remote control mode (local
control is made inactive).
3.1.2 User manual (GA Pack / Full-feature only)
For remote starting and stopping: Connect
Read the "User manual for electronic regulator for GA5 up to GA45 one side of a remote start button (normally open
compressors" to familiarize yourself with all regulator functions. contact) to terminal 3 of connector (2X4) 1)
1).
Connect one side of a remote stop button
(normally closed contact) to terminal 4 of
3.1.3 Outdoor/altitude operation connector (2X4) 1)
1). Bridge the other sides of
these buttons. Connect this common joint to
If the compressor is installed outdoors or if the air inlet temperature terminal 2 of connector (2X4).
can be below 0 C (32 F), precautions must be taken. In this case,
and also if operating at high altitude, consult Atlas Copco. Bridge terminal 28 of strip (1X1-Fig. 5a) and
terminal 6 of connector (2X4) 1)1). In this mode,
the outlet pressure is still sensed by pressure
3.1.4 Handling transducer (PT20), resulting in loading and
unloading of the compressor at the pressures
The bottom frame of the compressor is designed for easy handling programmed in the electronic regulator. If
with a pallet truck. The compressor can pass through a standard terminals 28 and 6 are not bridged, the
door (width 800 mm) compressor is switched out of automatic load/
unload operation and remains running
unloaded.
3.1.5 External compressor status indication (GA
Pack / Full-feature only) For remote loading/unloading (via external
pressure switch): Bridge terminal 28 of strip
(1X1-Fig. 5a) and terminal 7 of connector (2X4)
A relay box for external compressor status indication (E2-Fig. 5a) is
1) and connect a load/unload switch between
available as option. It can be connected to the electronic control
terminal 28 of strip (1X1-Fig. 5a) and terminal 6
module (E1). The relay box has relays for indication of:
of connector (2X4) 1)1). This results in loading
and unloading of the compressor at the closing
- manual load/unload or automatic operation (K06)
and opening pressures of the external pressure
- warning condition (K07)
switch respectively.
- shut-down condition (K08)

Maximum load for these contacts: 1 A/ 240 VAC. Stop the compressor Have the modifications checked by Atlas Copco. Stop the compressor
and switch off the voltage before connecting external equipment. and switch off the voltage before connecting external equipment. Only
voltage-free contacts are allowed.

3.1.6 Compressor control modes (GA Pack / Full-


feature only) 3.2 Initial start-up
The electronic regulator has two switches (CMS1/2-Fig. 5a) on strip 1. Remove the transport bolts and spacers (6-Figs. 2 and 3).
(1X1) to select following compressor control modes (0 = open / 2. Check that the electrical connections correspond to the local codes
1 = closed): and that all wires are clamped tight to their terminals. See section
2.4.
Instruction book Industrial Air Division

3. Check the voltage selecting wires at the primary side of 4. If installed, close the condensate drain valve. 2)
transformer (T1-Fig. 5a) 1) 1), the setting of compressor motor 5. Open air outlet valve (AV-Fig. 3a).
overload relay (F21), and that overload relay (F21) is set for 6. Move switch (S1-Fig. 9) to "I".
automatic resetting.
4. Fit air outlet valve (AV-Figs. 2 and 3). Close the valve. Connect
the air net to the valve. 3.4 During operation
5. Fit valve (Dm1-Fig. 2a). Close the valve. Connect the valve to a
drain collector. 2) 1. Check the oil level during loaded operation
operation: the pointer of level
6. Connect the automatic drain outlet (Da-Fig. 2a) to a drain collector. indicator (Gl-Figs. 2 and 3) must be in the green range.
2) For GA Pack / Full-feature (Fig. 7a)
7. The drain pipes to the drain collector must not dip into the water. 2. If automatic operation LED (1) is alight, the regulator is
For draining of pure condensate water, install an oil/water automatically controlling the compressor, i.e. loading, unloading,
separator which is available from Atlas Copco as option. If the stopping of the motors and restarting.
pipes have been led down outside the room where freezing is
possible, they must be insulated.
8. Check the oil level. The pointer of level indicator (Gl-Figs. 2 and 3.4.1 Checking the display (GA Pack / Full-feature
3) should register in the green range or above it.
9. Stickers dealing in short with the operating instructions and
only) 5)
explaining the pictographs are delivered with the literature set.
Affix the stickers next to the control panel. Make yourself familiar 1. Regularly check the display for readings and messages. Normally
with the instructions and pictographs explained, as well as with the main display (Fig. 7b) is shown, indicating the compressor
those mentioned in section 2.5. outlet pressure, the status of the compressor and the abbreviations
10. Check the motor (M1-Figs. 2 and 3) for correct direction of rotation. of the functions of the keys below the display. See section 1.4.
The rotation direction can be checked through the grating of the 2. Always check the display (4) and remedy the trouble if alarm LED
compressor cooling fan. See Fig. 2b. The direction is indicated (3) is alight or blinks. See section 1.4.
by an arrow (10) stuck on the fan (FN). 3. The display (4) will show a service message if one of the monitored
The correct direction of rotation of the motor is counter-clockwise components is to be serviced; replace the component and reset
when facing the cooling fan. the relevant timer.
Switch off the voltage and reverse two of the voltage supply lines Notes:
if the direction of rotation is wrong. - Whenever a shut-down, shut-down warning, service request,
11. On GA Pack / Full-feature, check the programmed settings. 3) sensor error or motor overload message is displayed, the free
12. Start and run the compressor for a few minutes. Check that the spaces on the display between the function keys (5) are filled
compressor operates normally. with blinking indicators (**).
- When more than one message needs to be displayed (e.g.
both warning and service), the messages will be displayed
one after the other for 3 seconds.
3.3 Starting
4. Regularly press the key <<More>> (5) 6) to call up information
For GA Pack / Full-feature (Fig. 7a) about the actual compressor condition:
1. Check the oil level: the pointer of level indicator (Gl-Fig. 2b) should - the status of controlling the compressor (automatic or manual,
register in the green range or above it. local or remote)
2. Switch on the voltage. Check that voltage on LED (2) lights up. - the status of the compressor start/stop timer (on or off) 7)
The message <<compressor off>> appears.
3. If the red part of service indicator (VI-Fig. 2a) shows completely
red, replace the air filter (AF-Fig. 2a).
4. Close condensate drain valve (Dm1-Fig. 2a).
5. Open air outlet valve (AV-Fig. 2a). 1) For GA Standard Pack: if a transformer is provided.
6. Press start button I (8). The compressor starts running and 2) An automatic drain system for GAStandard Pack is available as option.
automatic operation LED (1) lights up. Ten seconds 4) after 3) Consult the User manual for the electronic regulator, sections regarding
starting, the compressor motor switches over from star to delta. the submenus "Measured data", "Service", "Modify settings", "Timer"
At the same time 4) the compressor starts running loaded. The and "Programmable settings".
message on display (4) changes from <<Auto unloaded>> to 4) Programmable. See the User manual for the electronic regulator, section
<<Auto loaded>>. "Programmable settings".
5) Consult the User manual for the electronic regulator, sections "Status
data submenu" and "Service submenu".
For GA Standard Pack
6) If the <<More>> function is not indicated on the bottom line of display
1. Check the oil level: the pointer of level indicator (Gl-Fig. 3b) should (4-Fig. 7a), press key <<Menu>> (5) until function <<Main>> appears
register in the green range or above it. above key (F1), then press the key <<Main>>.
2. Switch on the voltage. 7) The compressor is automatically started and stopped if these start/stop
3. If the red part of service indicator (VI-Fig. 3a) shows completely commands are programmed and activated; consult the User manual for
Industrial Air Division Instruction book

- the maximum allowable unloading pressure 3.7 Taking out of operation at end of compressor
operation
- the outlet pressure service life
- the compressor element outlet temperature
- the dewpoint temperature (on Full-feature compressors) 1. Stop the compressor and close the air outlet valve.
- the status of the motor overload protection (normal or not) 2. Switch off the voltage and disconnect the compressor from the
- the total running and loading hours mains.
3. Depressurize the compressor by opening plug (FC-Figs. 2 and 3)
one turn and opening valve (Dm1-Fig. 2a). 2)
3.5 Manual control for GA Pack / Full-feature 4. Shut off and depressurize the part of the air net which is connected
(Fig. 7a) 1) to the outlet valve. Disconnect the compressor air outlet pipe
from the air net.
Normally, the compressor runs in automatic operation, i.e. the 5. Drain the oil (DP1/DP2-Figs. 2 and 3) and condensate circuits
electronic regulator loads, unloads, stops and restarts the compressor (Dm1-Fig. 2a). 2)
automatically. LED (1) is then alight. 6. Disconnect the compressor condensate piping (Da/Dm1-Fig. 2a)
from the local condensate drain system. 2)
If required, the compressor can be unloaded manually. In this case,
the compressor is switched out of automatic operation, i.e. the
compressor remains running unloaded unless it is loaded again
manually. 4 MAINTENANCE
Manually unloading Attention
Press the key <<Unld>> (unload) (5). LED (1) goes out. The message Before starting any maintenance:
<<Manual Unloaded>> appears on the display.
1. Stop the compressor:
Manually loading - On GA Standard Pack, move switch (S1-Fig. 9) to "O"
Press the key <<Load>> (5). LED (1) lights up. The command - On GA Pack / Full-feature, press button O (9-Fig. 7a), wait
<<Load>> does not force the compressor in loaded condition, but it until the compressor has stopped (approx. 30 seconds) and
will switch the compressor to automatic operation again, i.e. the press button (S3-Fig. 7a).
compressor will be loaded if required by the air net pressure. 2. Switch off the voltage. If a separate voltage supply is provided
for the dryer of GA Full-feature (see section 2.4), make sure that
Manually starting/number of motor starts the voltage to the dryer is also switched off.
In automatic operation, the regulator limits the number of motor starts. 3. Close air outlet valve (AV-Figs. 2 and 3) and depressurize the air
If the compressor is stopped manually, it must not be restarted within system.
5 minutes. 4. Apply all relevant safety precautions, including those mentioned
in this book.

3.6 Stopping The air outlet valve (AV-Figs. 2 and 3) can be locked during
maintenance or repair as follows:
For GA Pack / Full-feature (Fig. 7a) - Close the valve.
1. Press stop button O (9). LED (1) goes out. The message - Remove the bolt fixing the handle.
<<Programmed stop>> appears. The compressor runs unloaded - Lift the handle and turn it until the slot of the handle fits over the
for 30 seconds and then stops. blocking edge on the valve body.
2. To stop the compressor in case of emergency
emergency,, press button - Lock the handle using the special bolt and wrench delivered loose
(S3). Alarm LED (3) blinks. After remedying the fault, unlock the with the compressor.
button by turning it anticlockwise and press key <<Rset>> (5)
before restarting. The message <<All conditions are OK>>
appears. Press keys <<Menu>> and <<Main>>. 4.1 Compressor motor (M1-Figs. 2 and 3)
3. Close air outlet valve (AV-Fig. 2a) and switch off the voltage.
4. Open condensate drain valve (Dm1-Fig. 2a). The motor bearings are greased for life.
For GA Standard Pack
1. Move switch (S1-Fig. 9) to position "O".
2. Close air outlet valve (AV-Fig. 3a) and switch off the voltage.
3. If installed, open the condensate drain valve. 2)

1) If the <<Load>> or <<Unld>> (unload) function is not indicated on the


bottom line of display (4), press key <<Menu>> (5) until the function
<<Main>> appears above key (F1), then press the key <<Main>>.
Instruction book Industrial Air Division

4.2 Preventive maintenance schedule for the compressor 1)

Attention
For overhauling or carrying out preventive maintenance, service kits are available. See section 4.7. Atlas Copco offers several types of
Service contracts, relieving you of all preventive maintenance work. For more details, consult your nearest Atlas Copco representative.

The schedule comprises a summary of the maintenance instructions. Read the respective section before taking maintenance measures.
The "longer interval" checks must also include the "shorter interval" checks. When servicing, replace all disengaged packings, e.g.
gaskets, O-rings, washers.

Period 2) Running See See Operation


hours 2) section note

Daily Before starting


" -- 3.3 -- Check oil level
During operation
" 8 3.4/7.1 -- Check readings on display or gauges
" 8 -- 11/13 Check that condensate is discharged during loading (Da)
" 8 3.4 -- Check oil level (Gl)
After stopping
" -- 3.6 13 Drain condensate (Dm1)

3-monthly -- 5.3 -- Operate safety valve (SV)


" -- -- 9 Carry out a LED/display test (not on GA Standard Pack)
" -- -- 8 Check for possible leaks
" -- -- -- Check condition of belts
" 500 5.2 1/8 Inspect coolers (Ca/Co); clean if necessary
" 500 -- 1/7 Remove air filter element (AF), inspect

6-monthly -- -- 1 On GA Full-feature
eature,, brush or blow off the finned surface of condenser
Full-feature

Year ly
early -- 5.3 -- Have safety valve tested
" -- -- -- Have operation of electrical components tested
" -- -- 10 Test temperature shut-down protection
" 2000 -- 13 Remove, dismantle and clean float valve of moisture trap (MT)
" 4000 4.4/4.5 2/6 Replace oil filter (OF)
" 4000 4.4/4.5 3/5/6 If Roto-injectfluid is used, change oil
" 4000 5.1 6 Replace air filter (AF)
For 13 bar and 175 psi compressors
" 500 4.4/4.5/4.6 2/6 If oil as specified in section 4.4.2 is used, change oil and oil filter (OF)
For 7 bar
bar,, 10 bar
bar,, 100 psi, 125 psi and 150 psi compressors
" 1000 4.4/4.5/4.6 2/6 If oil as specified in section 4.4.2 is used, change oil and oil filter (OF)
" -- -- 4 Have all flexibles inspected
" -- 2.5 -- Switch off voltage. Check terminals in electric cabinet for tightness
-- 8000 5.4 -- Replace belts

2-Yearly
early 8000 -- 6/12 Have oil separator (OS) replaced

1) Use only author iz


authoriz
izeded par ts
ts.. An
parts y damage or malfunction caused bby
Any y the use of unauthoriz
unauthoriz ed par
ized ts is not co
parts vered bby
cov y Warranty or
arranty
Liability..
Product Liability
2) Whiche
Whichevver inter
intervval comes first. The local Sales Company may overrule the maintenance schedule, especially the service intervals,
Industrial Air Division Instruction book

Notes
1. More frequently when operating in a dusty atmosphere.
2. Use an oil filter as specified in the Parts list.
3. Special Atlas Copco oil for screw compressors keeping the compressor in excellent condition.
4. Damaged flexibles must be replaced immediately.
5. It is strongly recommended to use Atlas Copco Roto-injectfluid.
6. Consult the User manual for the electronic regulator for resetting the service timer (not for GA Standard Pack).
7. Replace the filter if damaged.
8. Any leak should be attended to immediately.
9. Consult the User Manual for the electronic regulator, section "Display test" (not for GA Standard Pack).
10. For GA Pack / Full-feature: Consult the User Manual for the electronic regulator, section "Modify settings submenu", before modifying the
temperature protection settings.
Decrease the shut-down warning level and shut-down level for the compressor element outlet temperature to the minimum settings. Run
the compressor: when reaching the setting, the unit must shut down. Afterwards, reset the warning and shut-down levels to their original
values.
For GA Standard Pack, consult Atlas Copco for testing.
11. Atlas Copco has oil separators to separate the major part of the oil from the condensate to ensure that the condensate meets the
requirements of the environmental codes.
12. 6000 hours in severe conditions
13. An automatic condensate drain system is available as option on GA Standard Pack.

4.3 Oil and oil filter change interval Ambient temperature Viscosity Viscosity
grade index
Consult section 4.2 for the change intervals and section 4.4 for the oil
specifications.
Consistently above 25 C (77 F) . . . . . . . ISO VG 68 Minimum 95
Between 25 C(77 F) and 0 C(32 F) . . . ISO VG 46 Minimum 95
4.4 Oil specifications

It is strongly recommended to use Atlas Copco Roto-injectfluid. See Consult Atlas Copco for the recommended oils. Use only non-toxic
below. Never mix oils of different brands or types. oils where there is a risk of inhaling delivered air.

4.4.1 Atlas Copco Roto-injectfluid 4.5 Oil and oil filter change

It is strongly recommended to use Atlas Copco Roto-injectfluid. This 1. Run the compressor until warm. Stop it and close valve (AV-
is special oil for screw compressors which keeps the compressor in Figs. 2 and 3). Wait a few minutes. Depressurize the oil system
excellent condition. by opening oil filler plug (FC) one turn to permit any pressure to
escape.
Atlas Copco Roto-injectfluid can be ordered in following quantities: 2. Remove plug (VP-Fig. 1). Drain the oil by unscrewing plugs (DP1/
DP2-Figs. 2 and 3). Collect the oil in a collector and deliver it to
Quantity Ordering number the local oil collection service. Reinstall the plugs.
5-litre can 2901 0245 01 3. Remove oil filter (OF-Figs. 2 and 3).
15-litre can 2901 0086 01 4. Clean the filter seat on the manifold. Oil the gasket of the new
25-litre can 2901 0001 01 element. Screw the element into place and tighten firmly by hand.
209-litre drum 2901 0045 01 5. Remove filler plug (FC-Figs. 2 and 3) and fill with oil until the level
reaches the plug. Reinstall and tighten plug (FC).
6. Run the compressor for a few minutes. Check the level during
4.4.2 Mineral oil loading: the pointer of level indicator (Gl-Figs. 2 and 3) must be in
the green range.
Although Roto-injectfluid is recommended, a high-quality mineral oil 7. Reset the oil and oil filter service warning. 1)
with oxidation inhibitors and anti-foam and anti-wear properties can
also be used after taking some precautions. The previously used oil
should first be drained and the system flushed. The oil filter should
be replaced. The viscosity grade must correspond to the ambient
1) Consult the User manual for the electronic regulator, section "Service
Instruction book Industrial Air Division

4.6 Storage after installation Testing


The valve can be tested on a separate compressed air line. If the
Run the compressor twice a week until warm. Load and unload the valve does not open at the pressure marked on the valve, consult
compressor a few times. Atlas Copco. No adjustments are allowed. Never run the
compressor without safety valve.
If the compressor is stored without running from time to time, protective
measures must be taken. Consult Atlas Copco.
5.4 Belt set exchange (Fig. 14)

4.7 Service kits The belts must be replaced as a set, even if only one of them
seems w
wororn. Use Atlas Copco belts only
orn. only..
Service kits are available offering the benefits of genuine Atlas Copco
parts while keeping the maintenance budget low. The kits comprise 1. Lift side plate (7-Fig. 1) from the bodywork after unscrewing bolts
all parts needed for servicing. Consult the Parts list for the contents (8-Fig. 1) which are accessible through the grating above the
of all service kits. cooler block (Ca/Co).
2. Loosen bolts (9). Unscrew bolt (5) to loosen the spring force on
the belts. Bolt (5) can now be pushed inwards to facilitate taking
Service kit for Ordering number out of the belts.
3. Loosen bolts (2) and take out support (3) together with fan duct
(1).
- oil filter and air filter . . . . . . . . . . . . . . . . . . 2901 0000 00
4. Take out the belts.
- oil separator . . . . . . . . . . . . . . . . . . . . . . . . 2901 0343 00
5. Install new belts.
6. Fully screw in bolt (5) until bracket (7) touches bracket (8).
7. Tighten bolts (9).
8. Fit support (3) with duct (1) on the frame and tighten bolts (2) by
hand. Position the support so that it fits 3 mm inside duct (4).
Check that a gap of minimum 2 mm exists between duct (1) and
duct (4) to allow the fan to rotate freely. Tighten bolts (2).
5 ADJUSTMENTS AND SERVICING
SERVICING 9. Refit side plate (7-Fig. 1).
PROCEDURES 10. Retension after 25 running hours: Loosen bolts (9). If the belt
tension is insufficient, brackets (7 and 8) will come apart. In this
5.1 Air filter (AF-Figs. 2 and 3) case, fully screw in bolt (5) until bracket (7) touches bracket (8).
The belt tension is now correct. Tighten bolts (9).
1. Stop the compressor. Remove the air filter element. Discard
damaged elements.
2. Fit the new element. 5.5 Fan control switch on GA Full-feature
3. Reset the air filter service warning. 1)
The switch is factory-adjusted and must be replaced if the switch-on
or cut-out pressure deviates from the values given in section 7.3.
5.2 Coolers (Co/Ca-Fig. 1)

Keep the coolers clean to maintain the cooling efficiency. 5.6 High pressure shut-down switch on GA Full-
feature (T V-approved units only)
-approv
Lift side plate (7-Fig. 1) from the bodywork after unscrewing bolts (8-
Fig. 1) which are accessible through the grating above the cooler The switch is factory-adjusted and must be replaced if the shut-down
block (Ca/Co). value deviates from the value given in section 7.3.

Remove any dirt from the coolers with a fibre brush. Never use a
wire brush or metal objects. Then clean by air jet in reverse direction 5.7 Expansion valve on GA Full-feature
of normal flow. If it should be necessary to wash the coolers with a
cleansing agent, consult Atlas Copco. The valve is a regulator which keeps the evaporator pressure, and
consequently also the temperature, stable. The valve is controlled

5.3 Safety vvalv


Safety alv
alvee (SV-Figs
-Figs.. 2 and 3)
(SV-Figs

Operate the safety valve by unscrewing the cap one or two turns and
retightening it (or by pulling the valve lifting lever, if provided).
1) Consult the User manual for the electronic regulator, section "Service
Industrial Air Division Instruction book

by its own outlet pressure. The valve is factory-set to keep the effective 5.8 Load/unload pressure switch (PSR19-Figs. 3) on
evaporator pressure at no-load at a minimum of 2 bar (29 psi) 1) 1), GA Standard Pack
which corresponds to 1 C (34 F). If necessary, have the valve
adjusted. The switch allows the operator to select the unloading pressure and
the pressure difference between the unloading and loading pressures.
The unloading and loading pressures are the opening and closing
pressures of the air pressure switch.
Adjustment can only be carried out when the air pressure switch
is pressurized. Remove blocking device (1-Fig. 15) before adjusting
knob (2).

The unloading pressure is controlled by adjusting knob (2). Turn


the knob clockwise to raise the unloading pressure, anti-clockwise to
lower it.

The pressure difference between unloading and loading is adjusted


by means of the same knob. The adjustment range is given in Figs.
16. Push down the knob and turn it clockwise to reduce the pressure
difference, anti-clockwise to increase it.

5.9 Temperature shut-do


emperature wn sswitch
shut-down witch on GA Standard
Pack

Switch (TSHH11-Fig. 9) has an adjusting screw in the centre at the


back of the housing of the switch.

The reset screw is located in the centre of the indicator scale and is
protected by a cap. To reset the switch after tripping, unscrew the
cap and turn the reset screw with a screwdriver anti-clockwise.

1) For GA18/22 High ambient version : 4.2 bar (61 psi)

1. Fan duct
2. Bolt
3. Support
device (to
4. Duct
ved before
5. Bolt
turning knob 2)
6. Fan
2. Adjusting knob
7. Bracket
3. Switch
8. Bracket
4. Spring housing
9. Bolt
Instruction book Industrial Air Division

Fig. 16a. Switch MDR 53/11 Fig. 16b. Switch MDR 53/16

Example (see Fig. 16a):

- unloading pressure(e): 8 bar


- loading pressure(e): adjustable between 5 bar and 7.6 bar

Figs. 16. Pressure difference adjustment ranges

6 PROBLEMSOLVING
PROBLEM
Attention Message Action
System failure 10 or 106 Switch off the voltage. Check the
- Before starting any maintenance: terminals on connector (2X1) and
- Stop the compressor: emergency stop button (S3) for
On GA Standard Pack, move switch (S1-Fig. 9) to "O". correct connection.
On GA Pack / Full-feature, press button O (9-Fig. 7a), wait
until the compressor has stopped (approx. 30 seconds) and System failure 11 Switch off the voltage. Check for
press button (S3-Fig. 7a). possible connection with the ground
- Switch off the voltage. If a separate voltage supply is provided of one of the digital inputs at
for the dryer of GA Full-feature (see section 2.4), make sure connector (2X4).
that the voltage to the dryer is also switched off.
- Close the air outlet valve and depressurize the air system. System failure 104 Switch off the voltage. Check that
The outlet valve can be locked in closed position. See section the contacts to the digital inputs at
4. the connectors of the module are
- Apply all relevant safety precautions, including those voltage-free.
mentioned in this book.
Connector (2X5) must only be used for connecting the Atlas Copco
- The chart helps to solve mechanical problems. An electrical fault Relay expansion box (optional) which allows indication of manual/
must be traced by an electrician. Check that the wires are not automatic operation, warning condition or shut-down condition.
damaged and that they are clamped tight to their terminals.
- Consult the User manual for the electronic regulator if a service
For GA Pack / Full-feature also: message or fault message appears on the display (4-Fig. 7a) or
- To facilitate solving some problems, a number of messages may when alarm LED (3-Fig. 7a) is alight or blinks.
Industrial Air Division Instruction book

Mechanical faults and suggested remedies (Fig. 4) 5. Excessive oil consumption; oil carry-over through discharge
line
1. Compressor starts running, but does not load after a delay a. Oil level (Gl) too high
time a. Check for overfilling. Release pressure and drain oil to correct
a. Solenoid valve (Y1) out of order level
a. Have valve inspected b. Incorrect oil causing foam
b. Inlet valve (IV) stuck in closed position b. Change to correct oil
b. Consult Atlas Copco c. Oil separator element (OS) defective
c. Leak in control air flexibles c. Have element checked. Replace, if necessary.
c. Have leak repaired
d. Minimum pressure valve (Vp) leaking (when net is 6. Safety valve (SV) blows after loading
depressurized) a. Inlet valve (IV) malfunctioning
d. Consult Atlas Copco a. See 1b
b. Minimum pressure valve (Vp) malfunctioning
2. Compressor does not unload, safety valve blows b. See 1d
a. Solenoid valve (Y1) out of order c. Safety valve (SV) out of order
a. See 1a c. See 4h
b. Inlet valve (IV) does not close d. For Full-feature: dryer pipes clogged by formation of ice
b. See 1b d. Have refrigerant system checked. Consult Atlas Copco

3. Condensate is not discharged from moisture trap 1) during 7. Element outlet 2) or air outlet temperature above normal
loading a. Insufficient cooling air or cooling air temperature too high
a. Discharge flexible clogged a. Check for cooling air restriction or improve ventilation of
a. Check and correct as necessary compressor room. Avoid recirculation of cooling air. If
b. Float valve malfunctioning installed, check capacity of compressor room fan
b. Consult Atlas Copco b. Oil level too low (Gl)
b. Check and correct as necessary
4. Compressor air output or pressure below normal c. Oil cooler (Co) clogged
a. Air consumption exceeds air output of compressor c. Clean cooler
a. Check equipment connected d. By-pass valve (BV) malfunctioning
b. Choked air inlet filter element (AF) d. Have valve replaced
b. Replace filter element e. Air cooler (Ca) clogged
c. Solenoid valve (Y1) malfunctioning e. Clean cooler
c. See 1a f. Compressor element (E) out of order
d. Leak in control air flexibles f. See 4i
d. See 1c
e. Inlet valve (IV) does not fully open
e. See 1b
f. Oil separator element (OS) clogged
f. Have element replaced. Consult Atlas Copco
g. Air leakage
g. Check and correct as necessary
h. Safety valve (SV) leaking
h. Have valve replaced. Consult Atlas Copco
i. Compressor element (E) out of order
i. Consult Atlas Copco

1) Available as an option on GA Standard Pack.


2) A warning message will appear on display (4-Fig. 7a) (not for GA
Instruction book Industrial Air Division

7 PRINCIPAL D
PRINCIPAL ATA
DA 7.3 Dryer control switches and refrigerant
specifications on GA Full-feature
7.1 Readings
Dryer control switches Cut-out Switch-on Unit
7.1.1 Readings on display on GA Pack / Full-feature pressure pressure
(4-Fig. 7a) 1)
Fan control switch:
Ref.: Air outlet pressure GA11 up to -22 ..............................8.1 10.6 bar(e)
Reading: Modulates between programmed unloading and loading GA11/15 High ambient version .....8.1 10.6 bar(e)
pressures. GA18/22 High ambient version .....13 16 bar(e)
Shown: On main display (Fig. 7b), when:
- switching on voltage Dryer shut-down switch (only on T V-approved units):
- selecting main display with keys <<Menu>> and GA11 up to -22 ..............................18 - bar(e)
<<Main>> (5-Fig. 7a) GA11/15 High ambient version .....18 - bar(e)
Sensor: PT20 GA18/22 High ambient version .....25 - bar(e)

Ref.: Compressor element outlet temperature


Reading: 50-60 C above cooling air temperature
Shown: When using key <<More>> (5-Fig. 7a) on the main
Refrigerant
display (Fig. 7b)
Sensor: TT11
Charge:
On Full-feature also: GA11/15 ................................................. 1.5 kg
GA18/22 ................................................. 2.2 kg
Ref.: Dewpoint temperature GA11 up to -22 High ambient version .... 2.2 kg
Reading: Approx. 4 C
Shown: When using key <<More>> (5-Fig. 7a) on the main Type:
display (Fig. 7b) GA11 up to -22 ................................ Tetrafluorethane R134a
Sensor: TT90 GA11/15 High ambient version ....... Tetrafluorethane R134a
GA18/22 High ambient version ....... Difluormonochlormethane R22

7.1.2 Readings on gauges on GA Standard Pack


7.4 Compressor specifications
(Fig. 9)

Ref.: Air outlet pressure (Gp)


7.4.1 Reference conditions
Reading: Modulates between preset unloading and loading
pressures Nominal working pressure as stated below
Air inlet pressure (absolute) ................ bar 1
Ref.: Compressor element outlet temper ature (TSHH11)
temperature Air inlet temperature ............................ C 20
Reading: 50-60 C above cooling air temperature Relative humidity................................. % 0
Setting: 110 C

7.4.2 Limitations

7.2 Setting of safety valve Maximum inlet temperature


- Standard Pack/Pack...................... C 40
The part number and set pressure are stamped on the valve. Also - Full-feature .................................... C 35
consult the Parts list. If the valve is malfunctioning, replace it by one - Full-feature designed for high
with the same number. No adjustments are allo wed.
allow ambient temperatures ................... C 40
Minimum inlet temperature ................. C 0
Minimum working pressure ................. bar(e) 4

1) See User manual for electronic regulator, sections "Modify settings


Industrial Air Division Instruction book

7.4.3 Specific data of 7.5 bar compressors 1)

Compressor GA11 GA15 GA18 GA22

Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hz 50 50 50 50
Maximum (unloading) pressure
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 7.5 7.5 7.5 7.5
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 7.25 7.25 7.25 7.25
Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 7 7 7 7
Power input
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 13.7 18.5 22.2 27.6
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 14.7 19.5 23.5 28.9
Temperature of air at outlet valve
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 28 28 27 28
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 23 23 23 23
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 2930 2930 2935 2930
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 7 7.5 8.5 8.5
Maximum sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . dB(A) 74 76 77 77

7.4.4 Specific data of 10 bar compressors 1)

Compressor GA11 GA15 GA18 GA22

Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hz 50 50 50 50
Maximum (unloading) pressure
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 10 10 10 10
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 9.75 9.75 9.75 9.75
Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 9.5 9.5 9.5 9.5
Power input
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 13.2 18.1 22.6 27.3
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 14.2 19.1 23.7 28.6
Temperature of air at outlet valve
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 27 27 26 27
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 22 22 22 23
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 2930 2930 2935 2930
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 7 7.5 8.5 8.5
Maximum sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . dB(A) 74 76 77 77

7.4.5 Specific data of 13 bar compressors 1)

Compressor GA11 GA15 GA18 GA22

Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hz 50 50 50 50
Maximum (unloading) pressure
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 13 13 13 13
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 12.75 12.75 12.75 12.75
Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 12.5 12.5 12.5 12.5
Power input
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 13.0 18.2 22.1 27.6
Instruction book Industrial Air Division

Compressor GA11 GA15 GA18 GA22

- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 14.0 19.3 23.2 28.9


Temperature of air at outlet valve
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 28 28 27 28
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 22 22 22 23
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 2930 2930 2935 2930
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 7 7.5 8.5 8.5
Maximum sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . dB(A) 74 76 77 77

7.4.6 Specific data of 100 psi compressors 1)

Compressor GA11 GA15 GA18 GA22

Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hz 60 60 60 60
Maximum (unloading) pressure
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 7.4 7.4 7.4 7.4
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 7.15 7.15 7.15 7.15
Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 6.9 6.9 6.9 6.9
Power input
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 14.3 19.0 22.4 27.0
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 15.5 20.2 24.0 28.8
Temperature of air at outlet valve
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 28 28 27 28
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 23 23 23 23
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 3530 3535 3535 3525
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 7 7.5 8.5 8.5
Maximum sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . dB(A) 76 78 79 79

7.4.7 Specific data of 125 psi compressors 1)

Compressor GA11 GA15 GA18 GA22

Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hz 60 60 60 60
Maximum (unloading) pressure
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 9.1 9.1 9.1 9.1
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 8.85 8.85 8.85 8.85
Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 8.6 8.6 8.6 8.6
Power input
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 14.3 19.3 24.0 28.8
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 15.5 20.6 25.6 30.6
Temperature of air at outlet valve
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 28 28 27 28
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 23 23 23 23
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 3530 3535 3535 3525
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 7 7.5 8.5 8.5
Maximum sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . dB(A) 76 78 79 79
Industrial Air Division Instruction book

7.4.8 Specific data of 150 psi compressors 1)

Compressor GA11 GA15 GA18 GA22

Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hz 60 60 60 60
Maximum (unloading) pressure
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 10.8 10.8 10.8 10.8
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 10.55 10.55 10.55 10.55
Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 10.3 10.3 10.3 10.3
Power input
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 14.3 19.7 23.9 28.6
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 15.5 20.9 25.5 30.4
Temperature of air at outlet valve
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 27 27 26 27
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 22 22 22 23
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 3530 3535 3535 3525
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 7 7.5 8.5 8.5
Maximum sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . dB(A) 76 78 79 79

7.4.9 Specific data of 175 psi compressors 1)

Compressor GA11 GA15 GA18 GA22

Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hz 60 60 60 60
Maximum (unloading) pressure
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 12.5 12.5 12.5 12.5
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 12.25 12.25 12.25 12.25
Nominal working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 12 12 12 12
Power input
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 14.4 19.5 23.9 28.4
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW 15.6 20.7 25.5 30.2
Temperature of air at outlet valve
- Pack/Standard Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 28 28 27 28
- Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C 22 22 22 23
Motor shaft speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r/min 3530 3535 3535 3525
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l 7 7.5 8.5 8.5
Maximum sound pressure level 2) . . . . . . . . . . . . . . . . . . . . . dB(A) 76 78 79 79

7.5 Conversion list of SI units into US/British units

1 bar = 14.504 psi 1 kW = 1.341 hp (UK and US) 1 m = 3.281 ft 1 N = 0.225 lbf
1 g = 0.035 oz 1 l = 0.264 US gal 1 mm = 0.039 in 1 Nm = 0.738 lbf.ft
1 kg = 2.205 lb 1 l = 0.220 Imp gal (UK) 1 m3/min = 35.315 cfm x C = (32 + 1.8x) F
1 km/h = 0.621 mile/h 1 l = 0.035 cu.ft 1 mbar = 0.401 in wc t 1 C = t 1.8 F

1) At reference conditions

S-ar putea să vă placă și