Design Guide: Epoxy Coatings
CCS Grouts
CCS Coatings High performance epoxy coating materials are used to
protect concrete and steel from chemical and
CCS Binders
mechanical attack in interior, exterior and marine
Coating and Crack environments. Epoxy coating systems consist of two or
Quantity Calculator more components which, when blended and applied as
Product Spec Template a film, react chemically to form a protective film of high
integrity, excellent adhesion, toughness and impact
resistance.
Solventless ("100% solids") coatings contain no volatile ingredients, therefore, the final
thickness of the cured coating is the same as the applied thickness. Advantages of
solventless over solvent-borne coating materials are:
When used on floors and decks, epoxy coatings can be skid-proofed by imbedding grit into
the surface layer or reinforced by incorporating glass cloth. Trowelable coating materials of
http://chemcosystems.com/tech_coatguide.html 1/8
8/1/2017 Epoxy Coating Guide for Concrete
nonsag or mastic consistency are used for applications of thick layers on vertical and
overhead surfaces.
Some high performance epoxy coatings for steel and concrete surfaces may chalk and
discolor upon exposure to direct sunlight that causes their finish to turn dull. These
features should be considered in exterior architectural coating applications.
> Refineries, electroplating plants, chemical processing plants, battery handling rooms.
> Food processing plants, meat packing areas, tanneries and dairies.
> High nuclear radiation exposure areas.
> Manufacturing plants, particularly where cutting oils are used.
Areas that receive heavy wear due to high traffic speed and volume require a surface
texture that will not be worn away or polished smooth. Skid resistant coatings are used to
surface:
http://chemcosystems.com/tech_coatguide.html 2/8
8/1/2017 Epoxy Coating Guide for Concrete
> Coating piles, piers, sea walls and abutments in the splash zone.
> Coating water tanks, fish ladders, dams, and outfall structures.
> Coating piles, piers, seawalls and abutments underwater.
Design Guide
http://chemcosystems.com/tech_coatguide.html 3/8
8/1/2017 Epoxy Coating Guide for Concrete
measured for both leather and rubber (see section 6.5. 1 ).
1.7.2 Vehicular Traffic: Besides surface texture, the skid resistance for vehicular traffic
surfaces depends on the velocity of the vehicle and the slope of the surface. Test
methods that take these variables into account have been developed and are in
use by several highway agencies (see section 6.5.2). When exposed to vehicular
traffic, the surface texture can be worn and polished causing a reduction in skid
resistance; therefore, skid resistance is monitored periodically to assure that it is
maintained within safe limits.
1.8 Architectural: The ultraviolet component of sunlight may cause chalking and
discoloration of certain epoxy materials in exterior applications. These changes are
a surface phenomenon and do not influence performance of the coating material in
hostile environments. It is important that the designer is aware of these potential
changes.
2.0 Material Considerations
2.1 Application Characteristics
2.1.1 Solvent-borne Coatings: Solvent borne coatings are best applied with either air-
atomized or conventional airless spray, although application by brush, roller or
squeegee may also be employed. Wet film thickness should not exceed the
maximum recommended for the individual product in order to avoid solvent
entrapment or sag.
2.1.2 Solventless Coatings: Solventless coatings are most often applied by brush, roller,
squeegee or trowel but may also be applied with plural component, heated, meter-
mix, air-atomized or airless spray equipment.
2.2 Curing Characteristics: Epoxy cure is accelerated by an increase and retarded by a
decrease in temperature. The rate of evaporation of solvent is also retarded by a
decrease in temperature.
2.2.1 Pot Life: Pot life is the useful life of the mixed epoxy system in the bulk mixing
container and is dependent on material temperature.
2.2.2 Recoat Time: Subsequent coats must be applied within minimum and maximum
limits. The minimum recoat time is the time required for the coat to become tack
free. The maximum recoat time is the time after which a subsequent coat will not
adhere to a previous coat without mechanically roughing the cured surface.
2.2.3 Hard Dry Time: The time required for a coating to become hard enough to support
light duty traffic (e.g. foot traffic).
2.2.4 Full Cure Time: The time required for a coating to achieve its full potential
mechanically and chemically.
2.3 Cured Characteristics
2.3.1 Adhesion: The bond strength of a coating is dependent on the surface
preparations, the bonding ability of the coating material to the substrate in question
and coating thickness. The substrate could be wet or dry concrete, steel, prime
coated concrete, prime coated steel and various other substrates. The bond
strength can be determined with a suitable adhesion tester (see section 6.3).
2.3.2 Chemical Resistance: The resistance to chemicals is dependent on the inherent
resistance of the resin/curing agent system in the coating formulation and integrity
of the coating. Acceptable coatings are free of pinholes, holidays, crazing cracks
and other surface defects.
2.3.3 Toughness: To maintain integrity in use, coatings must be tough and impact
resistant to resist gouging and chipping.
2.3.4 Skid Resistance: Both aggregate and coating material contribute to skid resistance
properties: The amount of aggregate and its gradation, wear, polish and hardness
characteristics all affect the degree and longevity of skid resistance. The thickness,
cohesive and bond strength of the coating material all contribute to the capacity of
the coating to bind the aggregate in place.
3.0 Estimating Quantities
3.1 When the desired dry film thickness is known:
a. Determine the number of gallons per square foot to achieve the required dry film
thickness:
Gallons per square foot = mils of dry film
% solids by volume x 16.04
http://chemcosystems.com/tech_coatguide.html 4/8
8/1/2017 Epoxy Coating Guide for Concrete
Multiply this value by the number of square feet to be coated to obtain the total
number of gallons of material required.
3.2 When using the manufacturer's recommended spreading rate:
a. Determine the dry film thickness per coat by:
mils of dry film = %solids by volume x 16.04
spreading rate (sq. ft. per gallon)
b. Determine the number of coats required by dividing dry film thickness desired by
mils of dry film per coat.
c. Divide the recommended spreading rate (in square feet per gallon) into the total
area to be coated and multiply by the number of coats to get gallons required.
4.0 Surface Preparation
4.1 Surface Preparation
4.1 General. Surfaces to be bonded must be clean and sound, which in all cases
requires some form of preparation.
4.2 Surface Evaluation: The following tests can be used to evaluate the condition of the
substrate and the effectiveness of the surface preparation procedures.
4.2.1 Strength: The direct tensile strength of the surface may be determined by a pipe
cap pull-off test or a commercially available adhesion tester. The strength of
concrete bond should be a minimum of 200 psi.
4.2.2 Contaminants: The presence of grease, wax or oil may be detected by dropping a
small amount of muriatic acid onto the surface. No reaction indicates that
contaminants are present. If oil has penetrated into a concrete surface, it may be
detected by raising the temperature of a small area to about 150F with a heat lamp.
Presence of the contaminant is indicated if oil appears or the area becomes
"greasy" to the touch.
4.3 Cleaning Procedures
4.3.1 Concrete Surfaces:
a. Grease, wax and oil contaminants may be removed by scrubbing with an
industrial grade detergent or degreasing compounds followed with mechanical
cleaning.
b. Weak or deteriorated concrete must be removed to sound concrete. This may be
accomplished by bush hammering, gritblasting, scarifying, waterblasting or other
suitable mechanical means.
c. Dirt, dust, laitance and curing compounds are removed by gritblasting, sanding
or etching with 15% hydrochloric acid. Acid etching should only be used if there is
no practical alternative. It must be followed by scrubbing and flushing with copious
amounts of clean water. Check for removal of acid with moist pH paper. Reading
should be more than 10.
d. Mechanical cleaning is followed with vacuum cleaning or oil-free, dry air blast.
4.3.2 Steel Surfaces:
a. Dirt, grease and oil are removed with suitable industrial grade cleaning and
degreasing compounds.
b. Rust and mill scale are removed by gritblasting to white metal. Gritblasting is
followed with vacuuming or oil-free, dry airblast.
5.0
5.1 General
5.1.1 Preconditioning: To facilitate mixing and application of epoxy coatings,
preconditioning of the material to room temperature 24 hours before use is
recommended.
5.1.2 Mixing: As with other coating materials, pigmented epoxy coatings must be agitated
to redisperse pigments and fillers which may have settled during storage. To
ensure proper cure, it is important that the components of the coating are carefully
measured and adequately mixed. Thorough mixing will take from 3-5 minutes
during which time the side and bottom of the mixing vessel should be scraped with
the mixing paddle. Solvents should be added only when recommended by the
manufacturer.
5.1.3 Number of Coats: The total dry film thickness desired and the type of coating
material will determine the number of coats. A solvent-borne coating will require
several coats to achieve the same final thickness as one coat of a 100% solids.
5.2 Methods of Application: Liquid coatings may be applied with brush, roller, air spray
or airless spray, and on horizontal surfaces squeegees may be used. Non-sag
http://chemcosystems.com/tech_coatguide.html 5/8
8/1/2017 Epoxy Coating Guide for Concrete
coatings may be applied by squeegee or trowel. The choice of the method of
application is a matter of economics.
Brush
for small areas with corners, edges and odd shapes where masking for spray is not
worthwhile
Roller
for large areas where spraying would require extensive masking, ventilation or may
present a fire or health hazard
Air spray
where areas to be coated are extensive or irregular and the time required to mask
can be offset by a higher production rate
Airless spray
where the high cost of the equipment compared to air spray can be offset by a
higher production rate, reduced masking time and overspray losses.
5.3 Primers: Most epoxy coatings are self-priming. In critical applications priming is
generally desirable, sometimes even required.
5.3.1 Steel Surfaces: Primers are required to protect steel surfaces when there is a delay
between surface preparation and coating application. Coatings applied to primed
steel generally have improved impact resistance and adhesion.
5.3.2 Concrete Surfaces: To prevent pinhole formation due to out-gassing, a fast drying
primer may be used. A primer may also be used to improve the adhesion of the top
coat when the concrete is damp.
5.4 Block Fillers: The texture of cementitious surfaces is sometimes open and porous
(paticularly concrete blocks or CMU). To obtain a smooth, pinhole free coating,
surface irregularities can be filled with a suitable block filler. For maximum chemical
resistance, abrasion resistance and adhesion to both substrate and topcoat, epoxy
block fillers are recommended over latex and cement slurry.
5.5 Top Coats: Top coats are applied over primers, block fillers or directly to the
substrate when they are self-priming. Since there are many types, it is
recommended that the application instructions given on the specific technical
bulletin be followed.
5.6 Skid Resistant Coatings
5.6.1 Foot and Light Vehicular Traffic Surface:
Two methods can be used to incorporate grit into a coating for service in areas
which receive foot and light vehicular traffic. Where it is desired to build up
thickness or develop a high degree of surface aggressiveness, grit is broadcast into
the top coating layer to excess. After the coating has cured, the excess grit is
removed. The resulting sandpaper-like texture can be moderated and rendered
more easily cleanable by a final finish coat applied by roller. Naturally occurring,
clean, kiln dried silica sands of 16 to 20 mesh are suitable for this application.
For light duty, where thinner layers or a less aggressive surface is desired in lieu of
the broadcast system, a fine aggregate of 60 to 80 mesh can be mixed into the
coating material and spread by squeegee as the final coat. Fine silica sands or
emery grit may be utilized for this purpose.
5.6.2 Vehicular Traffic Surfaces: For highway applications or other heavy duty service,
the coating material is used as a matrix for a chipseal application. Suitable, polish
resistant aggregate for chipseal applications include aluminum oxide, emery or
calcined bauxite. The aggregate selected should have a hardness on the Mohs'
scale of 8 or more and the following gradation:
Standard SieveNo. % Weight Passing
1/4 100
6 97-100
8 55-75
816 0-3
Aggregate should be broadcast evenly over the surface and fall in a vertical
direction to avoid displacing the uncured coating. Aggregate should be spread to
an excess until the surface appears dry.
The quantity of the aggregate required depends on the thickness of the coating.
Typical application rates of 28 to 30 square feet per gallon require 1.3 to 1.5
pounds per square foot of graded aggregate.
http://chemcosystems.com/tech_coatguide.html 6/8
8/1/2017 Epoxy Coating Guide for Concrete
After the aggregate has been spread, all traffic should be prohibited until the
surfacing material has cured sufficiently to bear traffic. Then, the excess aggregate
can be swept up and reused if it is still clean and dry.
5.7 Mastic or Non-Sag Coatings: This system is used where a thick coating is needed
to resist abrasion and impact or level irregularities in a vertical surface. The mastic
is applied by trowel or squeegee. Sand in the amount recommended by the
manufacturer may be blended with the mastic to reduce material cost. Use graded
silica sand; washed, kiln dried and bagged. A good "skip" gradation for low void
content is a blend by weight of two parts #12 or # 16 mesh to one part #80 or #100
mesh.
6.0 Quality Control
6.1 Wet Film Thickness: Wet film gauges are available to measure film thickness. The
measurement is read immediately after the coating is applied (before evaporation
takes place), and the final film thickness is computed from the known percentage of
solids in the coating material.
6.2 Dry Film Thickness: Dry film gauges are available to measure film thickness of a
non-conductive material on a ferrous substrate.
6.3 Adhesion
6.3.1 Scratch Adhesion Test for Steel Substrates:
An instrument with several blades is drawn across the coating making parallel cuts.
At 900 to these cuts another set of cuts are made, producing many small squares.
Masking tape is then applied over the patchwork and quickly removed. The number
of squares removed is an indication of the quality of the adhesion.
6.3.2 Pull-off Test for Concrete or Steel Substrates:
An aluminum or steel "dolly" is cemented to the coating and pulled off with a
calibrated tester. This test is generally performed with the aid of an Elcometer
adhesion tester (ASTM D4547). The minimum pull-off strength for concrete
surfaces is 200 psi. Higher values are obtained for steel substrates. For concrete
substrates, failure should occur within the concrete. For steel surfaces, the failure
should occur within the coating or in the bond between the steel and the coating.
The pull-off strength will depend on the strength of the coating and its thickness.
Therefore, technical information for the specific coating should be consulted.
6.4 Pinhole Detection: Pinhole detection devices are available for both steel and
concrete surfaces.
6.5 Skid Resistance
6.5.1 Foot Traffic: A common method of measuring skid resistance for foot traffic is the
Segler Pendulum Tester. It measures the Kinetic Coefficient of Friction and meets
both "Federal Test Method Standard No. 501 a, Method 7121" and "National
Bureau of Standards Report BMS 100, 'Relative Slipperiness of Floor and Deck
Surfaces'." Typical Kinetic Coefficient of Friction values for floor surfacings range
from 0.46 to 0.7; the smaller values represent a more slippery surface.
6.5.2 Vehicular Traffic: Two test methods used to determine the skid resistance of
vehicular traffic surfaces are AASHTO T242 and ASTM E247.
Applied coating thickness (1000 Coverage per U.S. Gallon 100% Solids
mils=1") System
250 mils (1/4 in) 6.4 ft2
187.5 mils (3/16 in) 8.5 ft2
187.5 mils (3/16 in) 8.5 ft2
125 mils (1/8 in) 12.8 ft2
100 mils 16 ft2
62.5 mils (1/16 in) 25.5 ft2
50 mils 32 ft2
31.25 mils 51 ft2
http://chemcosystems.com/tech_coatguide.html 7/8
8/1/2017 Epoxy Coating Guide for Concrete
20 mils 80 ft2
15.63 mils (1/64 in) 102 ft2
10 mils 160 ft2
5 mils 320 ft2
1 mil 1600 ft2