GE Zenith Controls

Power Contactor Type ATS


vs. Circuit Breaker Type ATS
1. Fewer parts, Fewer problems. fact that two drive mechanisms need to
a. The Power Contactor ATS is specifically be triggered independently and sequen-
designed to switch between two power tially. Assuming two power breakers are
sources and has one drive mechanism. used, each having a 5 cycle operate time
equates 10 cycles or 167ms. This would
b. A circuit breaker ATS has three mechanisms: be the best case scenario. Breakers which
two individual add-on/motorized mecha- are not power breakers or stored energy
nisms joined by a third mechanism, an type may have a greater operate time if
add-on interlock assembly which may be external operators are used such as with
chain or cable drive. These mechanisms MCCB style breakers.
are mechanically in series with each other.
Failure of any one will render the others 4. UL listing
useless for an automatic transfer.
a. The Power contactor ATS is often UL1008
listed. This requires certain testing:
2. Integrated mechanical interlock.
a. The Power contactor ATS is a true double i. Overload and endurance to ensure:
throw device, interlocking is inherent. 1. In rush handling capabilities.
The interlock is built into the drive mech-
anism. This interlock is not optional. 2. Switching at worst-case power factor.

b. A circuit breaker ATS is made of two single 3. Minimum life of 3000 to 6000
throw devices, this makes it necessary to operations.
add an interlock. The interlock rides on
ii. Withstand and closing ratings ensure:
top of the single throw motorized breaker
mechanisms. This interlock is required 1. The ability to remain closed
to prevent the possibility of the individual during faults.
mechanisms moving independently closed
a. To allow the fault to be isolated, by
simultaneously.
a down stream breakers and keep
remaining circuits operational.
3. Speed of operation
2. The ability to close into a fault
a. The Power contactor ATS has a 30 to 100ms
and remain closed.
transfer time, from live source to live
source. This fast transfer time can allow a. To allow the fault to be isolated, by
the use of in-phase monitoring during a down stream breakers and keep
transfer. The in-phase monitor prevents remaining circuits operational.
out of sync transfers that can cause circuit
breakers to trip. Short dead time can also b. A circuit breaker ATS is not always UL1008
allow some loads to stay on-line and/or listed. Especially those that are not com-
not require a manual restart. pletely packaged by the manufacturer.

b. A circuit breaker ATS has a longer and


unpredictable transfer time due to the

O-50XX (6/01)
5. Various models for different applications. iv. Remote controls
a. The Power contactor ATS is available in v. Load shed, and add
a variety of models.
vi. Field adjustable timers
i. The Standard model transfers in
30 to 100ms. vii. Generator exerciser clocks

ii. The Delay model can be programmed viii. Communication capabilities


to stop in a center off position during ix. Adjustable voltage & frequency sensing
transfer, for an adjustable time to
allow loads to decay. b. A circuit breaker ATS is often controlled by
a generic controller. These controllers are
iii. Closed transition models can provide usually manufactured and designed by a
zero interruption during live source third party. Not the breaker manufacturer
to live source transferring. and not the assembler, and therefore can-
iv. Bypass isolation transfer switches provide not always provide specific features:
a draw-out transfer switch with a manual i. In-phase monitoring, due unknown
transfer switch to route power around operating speed of the power section.
the ATS for maintenance and testing.
The bypass can switch to either source, ii. Drive mechanism coil burn out preven-
and can be safely used as a manual tion, due to unknown power section.
transfer switch also.
b. A circuit breaker ATS primarily operates A Breaker ATS can be used when:
as a delay transition only.
UL1008 LISTED
i. When provided in other configurations
even more add-on components become Engineered, packaged, backed, and
necessary, such as Kirk-key interlocks. serviced by a conventional transfer
switch or circuit breaker manufacturer.
ii. Bypass configurations become very
This will ensure custom controllers and
large and are not always built to be
a controlled manufacturing process.
capable of bypassing to either source.
Utilized in multiple generator synchroniz-
6. Controls ing gear line ups, with systemic redundancy
and master controls executed via a pro-
a. The Power contactor ATS is provided with
grammable logic controller(s).
a custom microprocessor controller.
This provides many standard and Medium voltage applications, due to the
optional features: fact that the availability of a vacuum bottle
double-throw contact structure is not com-
i. In-phase monitor
monly available.
ii. Diagnostics
iii. Drive mechanism monitoring
to prevent coil burn out Carl Kyrk, 2001

g GE Zenith Controls
GE Industrial Systems Power Equipment Business
General Electric Company
830 West 40 th Street, Chicago, IL 60609 USA