Sunteți pe pagina 1din 6

7SJ612 V4_9_prn

al ain hospital / switching station


SIMATIC income / 7SJ612 V4.9/7SJ612 12.09.17 11:45:40

al ain hospital / switching station income / 7SJ612 V4.9

MLFB: 7SJ6122**B901FB0
Parameter-set version: V04.93.01
Device path: C:\Siemens\DIGSI4\D4PROJ\al_ain_h\P7DI\GV\SD\0000000a
Author:
Creation date: 12.09.17 11:43:59
Last modified: 12.09.17 11:44:56
Operating mode: Offline
Comment:
Setting values in: Secondary value description

Page 1 of 6
7SJ612 V4_9_prn
Device Configuration
al ain hospital / switching station
SIMATIC income / 7SJ612 V4.9/7SJ612 12.09.17 11:45:40

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0104 Oscillographic Fault Records Enabled
0112 DMT / IDMT Phase Time Overcurrent Curve IEC
0113 DMT / IDMT Earth Time Overcurrent Curve IEC
0127 DMT 1Phase Disabled
0117 Cold Load Pickup Disabled
0122 2nd Harmonic Inrush Restraint Disabled
0131 (sensitive) Earth fault Disabled
0140 Unbalance Load (Negative Sequence) Disabled
0142 Thermal Overload Protection Disabled
0170 Breaker Failure Protection Disabled
0172 Circuit Breaker Wear Monitoring Disabled
0182 Trip Circuit Supervision Disabled
Flexible Function

Page 2 of 6
7SJ612 V4_9_prn
Power System Data 1
al ain hospital / switching station
SIMATIC income / 7SJ612 V4.9/7SJ612 12.09.17 11:45:40

2 Power System Data 1

2.1 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0214 Rated Frequency 50 Hz All


0209 Phase Sequence L1 L2 L3 All
0276 Unit of temperature measurement Degree Celsius All
0201 CT Starpoint towards Line All
0280 Holmgreen-conn. (for fast sum-i-monit.) NO All
0251A CT Connection IL1, IL2, IL3, (IE) All
0235A Storage of th. Replicas w/o Power Supply NO All
0250A Time Overcurrent with 2 phase prot. OFF All

2.2 Group Power System Data 1; Group CT's

Group Power System Data 1; Group CT's


No. Settings Value Group

0204 CT Rated Primary Current 100 A All


0205 CT Rated Secondary Current 1A All
0217 IE-CT rated primary current 60 A All
0218 IE-CT rated secondary current 1A All

2.3 Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker


No. Settings Value Group

0210A Minimum TRIP Command Duration 0.15 sec All


0211A Maximum Close Command Duration 1.00 sec All
0212 Closed Breaker Min. Current Threshold 0.04 A All

Page 3 of 6
7SJ612 V4_9_prn
Settings groups
al ain hospital / switching station
SIMATIC income / 7SJ612 V4.9/7SJ612 12.09.17 11:45:40

3 Settings groups

3.1 Group Power System Data 2; Group General

Group Power System Data 2; Group General


No. Settings Value Group

1102 Measurement: Full Scale Current (100%) 100 A A

3.2 Group DMT / IDMT Phase/Earth Overcurrent; Group General

Group DMT / IDMT Phase/Earth Overcurrent; Group General


No. Settings Value Group

1201 Phase Time Overcurrent ON A


1213A Manual Close Mode I>> instantaneously A
1215A Dropout Time Delay DMT Phase 0.00 sec A
1301 Earth Time Overcurrent ON A
1313A Manual Close Mode IE>> instantaneously A
1315A Dropout Time Delay DMT Earth 0.00 sec A

3.3 Group DMT / IDMT Phase/Earth Overcurrent; Group DMT Ph

Group DMT / IDMT Phase/Earth Overcurrent; Group DMT Ph


No. Settings Value Group

1219A I>>> measurement of Fundamental component A


1216A I>>> active Always A
1217 I>>> Pickup oo A A
1218 T I>>> Time Delay 0.00 sec A
1220A I>> measurement of Fundamental component A
1214A I>> active Always A
1202 I>> Pickup 2.00 A A
1203 T I>> Time Delay 0.00 sec A
1221A I> measurement of Fundamental component A
1204 I> Pickup 1.00 A A
1205 T I> Time Delay 0.50 sec A

Page 4 of 6
7SJ612 V4_9_prn

al ain hospital / switching station


SIMATIC income / 7SJ612 V4.9/7SJ612 12.09.17 11:45:40

3.4 Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT Ph

Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT Ph


No. Settings Value Group

1222A Ip measurement of Fundamental component A


1207 Ip Pickup 1.00 A A
1208 T Ip Time Dial 0.50 sec A
1210 Drop-Out Characteristic Disk Emulation A
1211 IEC Curve Normal Inverse A

3.5 Group DMT / IDMT Phase/Earth Overcurrent; Group DMT E

Group DMT / IDMT Phase/Earth Overcurrent; Group DMT E


No. Settings Value Group

1319A IE>>> measurement of Fundamental component A


1316A IE>>> active Always A
1317 IE>>> Pickup oo A A
1318 T IE>>> Time Delay 0.00 sec A
1320A IE>> measurement of Fundamental component A
1314A IE>> active Always A
1302 IE>> Pickup 0.50 A A
1303 T IE>> Time Delay 0.10 sec A
1321A IE> measurement of Fundamental component A
1304 IE> Pickup 0.20 A A
1305 T IE> Time Delay 0.50 sec A

3.6 Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT E

Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT E


No. Settings Value Group

1322A IEp measurement of Fundamental component A


1307 IEp Pickup 0.20 A A
1308 T IEp Time Dial 0.20 sec A
1310 Drop-Out Characteristic Disk Emulation A
1311 IEC Curve Normal Inverse A

Page 5 of 6
7SJ612 V4_9_prn

al ain hospital / switching station


SIMATIC income / 7SJ612 V4.9/7SJ612 12.09.17 11:45:40

3.7 Group Measurement Supervision; Group General

Group Measurement Supervision; Group General


No. Settings Value Group

8101 Measurement Supervision ON A

3.8 Group Measurement Supervision; Group MeasSupervision

Group Measurement Supervision; Group MeasSupervision


No. Settings Value Group

8104 Current Balance Monitor 0.50 A A


8105 Balance Factor for Current Monitor 0.50 A
8111A T Current Balance Monitor 5 sec A

Page 6 of 6