UPS Training

Fundamental of UPS
Training Center Gong Jian Bo
Tel.0755-26862543
Email: gjb@emersonnetwork.com.cn
Content
 UPS Overview
 UPS Principle
 UPS Key Technology
 UPS Technical Data
 UPS Battery
 UPS Monitoring System

2 Emerson Confidential
UPS Overview

 Whats UPS?
 Why need UPS?
 Function of UPS
 Classification of UPS

3 Emerson Confidential
Whats UPS
A device that can uninterruptible provide AC power to
user.
UPS Uninterruptible Power Supply

UPS

AC mains

load

battery

4 Emerson Confidential
UPS history

UPS develop through two periods:


Rotary UPS and Static UPS.

5 Emerson Confidential
Rotary UPS

DC motor;
diesel
engine;
flywheel;
generator;
rectifier and
battery.

6 Emerson Confidential
UPS history

2Static UPS is consisted of


semiconductor power devices.

7 Emerson Confidential
UPS Overview

 Whats UPS?
 Why need UPS?
 Function of UPS
 Classification of UPS

8 Emerson Confidential
Why need UPSPower Problem

Surge spike transient over voltage sag

noise Frequency drift low voltage blackout

9 Emerson Confidential
Why need UPS
Power Cause phenomenon
problem
surges Huge equipment turn off Higher than 110%
or lighting strike rated Value
last
many cycle.
spikes Lighting, electric switch 6000V last time is 10
on/off, electric welding 100ms

Transient Like spike 20000V


last time
over voltage 0.1ms

sag Huge equipment turn on, smaller than 80-85%


AC mains change rated value
last
many cycle.

10 Emerson Confidential
Why need UPS
Power Cause phenomenon
problem
noise High frequency Wireless and
interference. microwave equipment

Frequency hydropower
generator Frequency change
drift over 3HZ.

low voltage Huge equipment start, Smaller than rated


overload value and last long
time.

blackout AC cut offcircuit Zero voltage last over


breaker trip. 2 cycles.

11 Emerson Confidential
Why need UPS?

Above AC power problems will


damage equipment,
lose data
and interrupt operations.

12 Emerson Confidential
UPS Overview

 Whats UPS?
 Why need UPS?
 Function of UPS
 Classification of UPS

13 Emerson Confidential
UPS Function

1. High reliable and Keep


power continuous
uninterruptible power

2. Eliminate noise Clean


source of power

3. Battery management Prolong


battery life

4. Monitoring Help
UPS maintenance

14 Emerson Confidential
UPS Overview

 Whats UPS?
 Why need UPS?
 Function of UPS
 Classification of UPS

15 Emerson Confidential
UPS Classification
By principle

back-up UPS
line-interactive UPS
on-line UPS
By power mode:
single phase input/single phase output UPS
three phase input/single phase output UPS
three phase input/ three phase output UPS
By output power

small power
<10 kVA
medium power10 to 30kVA

large power
>30 kVA

16 Emerson Confidential
UPS Classificationcontinued
By transformer

high frequency UPS
industrial frequency UPS

By waveform

square wave UPS
sine wave UPS

17 Emerson Confidential
Content
 UPS Overview
 UPS Principle
 UPS Key Technology
 UPS Technical Data
 UPS Battery
 UPS Monitoring System

18 Emerson Confidential
Back--Up UPS Principle
Back
When AC power normal, load power comes directly
from the AC mains, when AC power fails, a battery
powered inverter almost immediately turns on to
continue to supply power.

load

AC mains
charger inverter

battery

19 Emerson Confidential
Line--interactive UPS principle
Line

load
Back--Up UPS Principle
Back 264-276V
150-264V
150-175V
AC mains
double
converter

AC normal/rectify
AC fail/invert

battery

20 Emerson Confidential
On-
On-Line UPS Principle
Whether AC mains is normal or not, inverter is
always operating.

21 Emerson Confidential
UPS Comparing
Back-up Line-interactive On-line
Inverter Back up Hot back up operating
state

Output Low Middle High


quality

Transferrin 5
12ms 4ms 0
g time

Cost Low Middle High

22 Emerson Confidential
Content
 UPS Overview
 UPS Principle
 UPS Key Technology
 UPS Technical Data
 UPS Battery
 UPS Monitoring System

23 Emerson Confidential
UPS Key Technology

 Double Conversion
 Digital Control
 Redundancy
 Battery Management

24 Emerson Confidential
Double Conversion
Conversion

AC
DC Rectify

DC
AC Invert

25 Emerson Confidential
3-Phase SCR Bridge Rectifier

1 3 5
A
B
C
C
4 6 2

6 pulse

26 Emerson Confidential
12-
12-Pulse Rectifier

L
o
a
d Battery and
Inverter
30

Two 6-
6-Pulse
Rectifiers
Phase shift Transformer

27 Emerson Confidential
Boost CircuitPFC Circuit
L D 1

T
V i C V O
-
- -

L

-
iL
V i C V O
-
- -

L

-
iL
V i C V O
-

- -

28 Emerson Confidential
3-Phase IGBT Rectifier

29 Emerson Confidential
Comparing

Input power factor:0.7-0.85,harmonic current>30%

Input power factor>0.99,harmonic current<3%

30 Emerson Confidential
Single Phase half bridge invert Circuit
U
+ 380

D1 -3 8 0

Q1
C1 L
+380V
L

C3 220V

N N

C2 Q2 D2
-380V

31 Emerson Confidential
Inverter Control SignalSPWM

SPWM signal generation

32 Emerson Confidential
3-Phase Bridge Inverter

R S T R
R
S S

T
T

33 Emerson Confidential
3-Phase SCR Rectifier UPS


bypass

main
output

34 Emerson Confidential
3-Phase IGBT Rectifier UPS

bypass

main

output

35 Emerson Confidential
UPS Key Technology

 Double Conversion
 Digital Control
 Redundancy
 Battery Management

36 Emerson Confidential
Digital Control

Digital signal Processor


DSP

Microprocessor
Provide all kinds of driving signal to
control rectifier, inverter and transferring.

37 Emerson Confidential
DSP
Speed: 10-20 times that of micro-processor
improve integrated degree

Directly give PWM signal

Avoid device parameter shifting, ensure product
accordance.
No need any hardware adjusting .

Third generation
generationDSP

micro-processor
Second generation

device
First generation IC

38 Emerson Confidential
UPS Key Technology

 Double Conversion
 Digital Control
 Redundancy
 Battery Management

39 Emerson Confidential
Series Connection standby
main

AC mains
UPS1 load

bypass

standby
UPS2

Solution for medium power case, easy installation, but


power is NOT extended.

40 Emerson Confidential
Parallel Connection

UPS1 load
AC mains

Parallel logic control

UPS2

Solution for large power case, each UPS shares load,


high reliability
but requires complex technology.

41 Emerson Confidential
Double Power Bus
UPS1 AC PPC

Bus1

battery

Signal Double feed


STS
LBS feed load
load

UPS2
UPS
Bus2

AC PPC
battery

42 Emerson Confidential
UPS Key Technology

 Double Conversion
 Digital Control
 Redundancy
 Battery Management

43 Emerson Confidential
Battery FC/EC
1. Current limit 0.1C

2. FC to EC
Ic0.05C or C 80%
EC to FC
Ic 0.01C

FC: Floating Charge


EC: Equalizing Charge

44 Emerson Confidential
Content
 UPS Overview
 UPS Principle
 UPS Key Technology
 UPS Technical Data
 UPS Battery
 UPS Monitoring System

45 Emerson Confidential
Technical Data

Input Specification

Output Specification

46 Emerson Confidential
Input Voltage Range

adaptability to the power network.


The wider the better.

47 Emerson Confidential
Bypass Voltage Range

Typical range : 10%

48 Emerson Confidential
Input Frequency Range

adaptability to the power network.

The wider the better.

50Hz
4%

49 Emerson Confidential
Input Power Factor

Power Factor = active power /apparent power

The higher the better.


Smaller PF means larger reactive power, more
harmonic current , which will pollute AC mains
network.

50 Emerson Confidential
Total Harmonic Distortion

THD
=harmonic current/Base100

The smaller the better.

51 Emerson Confidential
Technical Data

Input Specification

Output Specification

52 Emerson Confidential
Output Voltage Stability

Input voltage in 220V25%output voltage


fluctuation range when load change from 0 to
100%.

53 Emerson Confidential
Output Frequency Stability

Output Frequency Stability0.5%

UPS local oscillation frequency stability

In battery mode, it comes from crystal


oscillator.

54 Emerson Confidential
Frequency Regulation and Frequency Slew Rate

Frequency Regulation :50Hz


4%,
Frequency Slew Rate1Hz/s

For Frequency Regulation, the wider the better.

Frequency Slew Rate speed of Output


frequency tracing input frequency.

55 Emerson Confidential
Overload Capability

Withstanding duration at 125% rated load,


after that, transfers to bypass.

56 Emerson Confidential
Output Current Crest Factor
Crest Factor =current peak value/ RMS value.
Index of UPS load capability,
the larger the better.

3:1
For PCServer, the factor is between 2.5 to
3.0.

RMS: Root Mean Square

57 Emerson Confidential
Output Power Factor
0.7 or 0.8

NOT the higher the better.

PC need not only active power but also


reactive power.

So unit is VA not W.

58 Emerson Confidential
Voltage Distortion

Voltage Distortion
= harmonic /Base + harmonic100

The smaller the better.

59 Emerson Confidential
Content
 UPS Overview
 UPS Principle
 UPS Key Technology
 UPS Technical Data
 UPS Battery
 UPS Monitoring System

60 Emerson Confidential
Content
 Battery structure and Principle
 Battery Characteristic
 Battery Capacity Configuration

61 Emerson Confidential
Lead--Acid Battery Cell
Lead
v

=1cell Form 2V cell

e- Positive plate:
Negative plate:
Lead dioxide PbO2
Lead Pb

Electrolyte

Sulfuric solution H2SO4

Electrical Energy Chemical Energy

62 Emerson Confidential
Lead--Acid Battery
Lead Battery
two general type

Flooded Battery VRLA Battery


or wet type or open vented type Valve Regulated Lead-Acid Battery

63 Emerson Confidential
VRLA Battery
Batteryused with UPS

UPS Battery

64 Emerson Confidential
Structure of VRLA Battery

container & cover

terminal



strap/group bar

Positive & negative plates

AGM

safety valve

AGM: Microporous fibre glass acts as both separator and


electrolyte absorber.

65 Emerson Confidential
Battery principle

discharge

PbO22H2SO4Pb PbSO42H2OPbSO4
charge

(lead dioxide) (sulfuric acid) (spongy lead) (sulfate) (water) (sulfate)


active material electrolyte active material active material electrolyte active material
positive plate negative plate positive plate negative plate

Double sulfatetheory

66 Emerson Confidential
Content
 Battery structure and Principle
 Battery Characteristic
 Battery Capacity Configuration

67 Emerson Confidential
Discharge Characteristic
Terminal voltage(V/cell)

2.1

2.0

1.9 0.1C 10
0.2C 10
0.3C 10
1.8 0.5C 10
0.6C 10
1.0C 10
1.7
2.0C 10
1.6
1min 2 6 10 30 min 1 h 2 3 5 8 10 20 h
discharge time

68 Emerson Confidential
Charge Characteristic

Charging
Charging
Charged
Volume

Voltage
(%) Current
(A) (V) 2.23V Constant Voltage Charging at 25
120

100 0.1C 2.4


Charged Volume

80 0.08C 2.3

Charging Voltage
60 0.06C 2.2

40 0.04C 2.1 After 100% Discharge


After 50% Discharge
20 0.02C 2.0
Charging Current
0
0 4 8 12 16 20 24 28 32 36
Charging Time (hours)

69 Emerson Confidential
Relationship between battery discharge
capacity and ambient temperature
low rate discharge 1h
------ high rate discharge 1h
120

100

80
capacity C 10

60

40

20

0
-30 -20 -10 0 10 20 30 40

Temperature
70 Emerson Confidential
Storage Characteristic
1 0 0

9 0

8 0
C %
Available Capacity (%)

7 0

6 0

5 0

4 0

3 0
0 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2

Storage time (month)

71 Emerson Confidential
Comparison of UPS battery and PS battery
PS UPS

Design Long time


small current
Short time
large current

orientation deep discharge light discharge
Design life Above 10 years 3
5 years

Lead paste Long life formulation, Large power life formulation,


formulation long cycle life short cycle life
separator long life separator ,thick large diameter hole, thin.
small current and deep
discharge will cause life end.
Recovery good So-so
ability of
Over-discharge

72 Emerson Confidential
Content
 Battery structure and Principle
 Battery Characteristic
 Battery Capacity Configuration

73 Emerson Confidential
Battery Capacity Configuration
Ppf
pfT
C =
V K
P: UPS Capacity, VA
pf: UPS output power factor, typically 0.7,
T: backup time
V: battery string voltage
:battery inverting efficiency, typically 85%
K: battery discharge coefficient
T=13h K= 0.6
T=3h5h K= 0.8
T=5h10hK= 0.85
T10h K= 1

74 Emerson Confidential
Battery Capacity Configuration
Example
20kVA UL33 UPS30 battery cells(12V),Carry 35%
load
backup time is 4h
how much battery capacity
does it need?

20000VA
0.7 35%
4
C= = 94.5AH
305V
0.85
0.8

So need 100AH battery.

75 Emerson Confidential
Content
 UPS Overview
 UPS Principle
 UPS Key Technology
 UPS Technical Data
 UPS Battery
 UPS Monitoring System

76 Emerson Confidential
UPS Monitoring System Function
1know and control real operating state,
2provide UPS failure report in time,
3when AC mains abnormalbattery low
voltageautomatically shutdown computer,
4be able to run in LANWAN and
Internet,

77 Emerson Confidential
Composition of Monitoring System
UPS Monitoring System
Intelligent UPS
Network
Monitoring Software

Monitoring Software consists of three parts



SNMP Card
Centralized Monitoring Software
Safe Shutdown Program

78 Emerson Confidential
UPS Networking Scheme

79 Emerson Confidential
Monitoring Screen Display UPS Tree

80 Emerson Confidential
Monitoring Screen DisplayState

81 Emerson Confidential
Monitoring Screen Display Data Curve

82 Emerson Confidential
Monitoring Screen Display Events List

83 Emerson Confidential
Monitoring Screen Display Event Log Query

84 Emerson Confidential
Monitoring Screen Display Data Log Query

85 Emerson Confidential
UPS Events Handling

Administrator
notifying

Pager


Send
EE-mail
-mail

UPS
Events

alarms
audible/visual

log

command
executing

file OFF

86 Emerson Confidential
End

Thank You