MOOSAPET, HYDERABAD
DESIGN CALCULATIONS
FOR PUMPS & WTP
M/s. Cyber city Developers is coming up with Rainbow vistas proposed Residential Building at
Q.
Block K water supply pumps to be provide separate set of pumps due to increasing of floors
Assuming above demand (cumulative) being consumed during 4.0 hrs in a day, Peak flow in the System
would be
= 241/4 pumps
= 60.25 m3/hr of each pump
: Recommended duty of pumps for domestic water distribution pumps 67.5 m3/hr at 95.0 mt head
Assuming above demand (cumulative) being consumed during 4.0 hrs in a day, Peak flow in the System
would be
= 165.5/4 pumps
: Recommended duty of pumps for domestic water distribution pumps 45.0 m3/hr at 95.0 mt head
Assuming above demand being treated during 18 hrs cycle, Peak flow in the System would be
= 56.80/2 pumps
Pumps & treatment plant split into modular design having two Working units for ease of operation &
optimum sizes
Head = Minimum 2.5 kg/cm2 pressure required for water treatment process so considered 30m head.
: Recommended duty of pumps for domestic water distribution pumps 29.0 m3/hr at 30.0 mt head
(2 Nos. Working + 1 No. Stand By )
Assuming above demand being pumped during 20 mins, Peak flow in the System would be
= 8 LPS pump
: Recommended duty of pumps for domestic water distribution pumps 0.5 m3 at 12.0 mt head
(2 Nos. Working)
= 27.0 cum
6.0 DESIGN CALCULATION FOR IRRIGATION WATER LIFT TO IRRIGATION OHT PUMPS
Assuming above demand being pumped during 60 min. Peak flow in the System would be
= 3.0 lps
: Recommended duty of pumps for above mentioned water distribution pumps 3.0 lps at 80.0 mt head
Assuming above demand being treated during 18 hrs cycle, Peak flow in the System would be
= 53.5/2 Nos.