Project: Design & development of a laboratory building of CRES,

with implementation of RES technologies, in Pikermi, Attiki

Building Volume OWNER:


Total area 1464 m3 C.R.E.S.
3
Basement area 483 m Center for Renewable Energy Sources
3
Ground floor area 519 m 19th km. Marathonos Ave.
st 3
1 floor area 462 m GR-190 09 Pikermi
Building Area Tel. : +30 10 66.03.300, fax. +30 10 66.03.305
2
Total area 529 m e-mail groiko@cres.gr
2
Basement area 173 m www.cres.gr
2
Ground floor area 189 m
FUNDING:
st 2
1 floor area 167 m
Roof 171 m
2
General Secretariat for Research & Technology
Net Headed Building Area - Construction Service
Total area 428 m
2
14-18, Messogion Ave. GR- 11510, Áthens
Basement area 127 m
2
Tel.:+30 10 77.03.564, fax. +30 10 77.11.071
2
Ground floor area 154 m
st
1 floor area 147 m
2
Project :
Windows Surface OPERATIONAL PROGRAMM FOR REASERCH
Total area 53 m
2
& TECHNOLOGY MEASURE 3.1
2
North 8 m
South 17 m
2 Construction:
East 14 m
2 Ålectromec S.A.
West 14 m
2 Catherine Cristide (Civil Engineer)
Greenhouse Windows Surface Giota Batistatou (mechanical Engineer)
Total 15 m
2 Ourania Flabouri (electrical Engineer)
South 12 m
2 18, Êïmninon Str.,
GR- 114 72, Áthens

Bioclimatic and Low


2
West 3 m
Clerestories Windows
Tel.: +30 10 64.57.352, fax. +30 10 64.64.538
Total area 14 m
2 e-mail electromec@tee.gr
2
North 7 m
2 Preliminary Report:
South 7 m
C.R.E.S.

Energy Office Building


Greenhouse Area
2 Gregory Economides (Dr. Civil Engineer)
Total area 8,25 m
Evi Tzanakaki (Architect Engineer MSc)
Solar Wall Surface (thermosyphonic)
2 Michael Karagiorgas (Dr. Mechanical Engineer)
Total area 17 m
2
Right 8 m Final Report :
2
Left 9 m Á.Spiropoulou (Architect Engineer)
2
Transparenti insulation Surface 8 m Ålectromec S.A
Thermal characteristics
2
Roof from Reinforced concrete slabs 0,33 W/m K Supervisory Team:
2
Reinforced concrete vertical structural elements 0,65 W/m K Savvas Tsilenis G.S.R.T. C.S.
2
Brickwork vertical structural elements 0,52 W/m K Alex kastanis G.S.R.T. C.S.
P. Hatzinicolaou G.S.R.T. C.S.
2
Brickwork vertical structural elements 0,53 W/m K
with transparent insulation Gregory Economides C.R.E.S.
Michael Karagiorgas C.R.E.S.
2
Reinforced concrete floor in non-heated areas 0,58 W/m K
2
Openings 3,72 W/m K
Thermal conductance coefficient of the 0,044 W/mK Monitoring Team:
Transparent Insulation[ë] Gregory Economides (Dr. Civil Engineer)
Thermal conductance coefficient of Tektalan [ë] 0,04 W/mK Michael Karagiorgas (Dr. Mechanical Engineer)
2
Overall heat transfer coefficient [km] 0,82 W/m K Maria Bololia (Technical Mechanical Engineer)
-1
Overall external surface / Volume [F/V] 0,66 m
Photovoltaic panels, 600 Wp 8,64 m
2
ÂÌS Installation:
Users 20 Persons ÅÉÂ Shop,
Site and Climate Christos Dokios
Longitude 23°.55´ E 64, Ádelfon Didaskalou Str.
Latitude 38°.01´ N GR- 156 69 Papagou, Athens
Altitude 153 m Tel.: +30 10 65.26.920, fax. +30 10 65.26.920
Average ambient temperature (annual) 18,7 °C e-mail xdoki@tee.gr
January 9,4 °C
July 28,7 °C Solar Appliances Manufacturer :
Degree Days (base 19 °C) 1218 days SOLE S.A.
Global irradiation on horizontal (annual) 1747 KWh/m
2 Leftktron & Laikon Agonon,
Costs (1999 prices) GR- 13671 Acharnes CENTER FOR RENEWABLE ENERGY SOURCES
Tel.: +30 10 23.88.088, fax. +30 10 28.25.690 19th km MARATHONOS AVE. PIKERMI GREECE
Conventional construction 352.000 EURO
e-mail export@sole.gr - http//www.sole.gr 1
Energy systems 39.780 EURO
Detail of external
brickwork with
external insulation

Sun protection systems


on the south and east
facades
F o r t h e
insulation of Daylighting
vertical building
elements, 5 cm Parallel to and in conjunction with the passive
Tektalan panels solar systems, daylighting systems were studied in
were used(glass order to provide the building with natural light for
fibre with panels of dried seaweed). the greatest possible part of the day resulting in a
At chosen sites on the south face, 5 cm Sto Therm reduction of electricity required for lighting. For
Solar transparent insulation panels were used and this purpose, the following were designed:
the roof was insulated with 5cm extruded • Roof lighting system partially glazed roof
polystyrene Dow Roofmate panels. to let in natural light for the central part of the Geothermal water to water heat pump
The floors were laid with 30x30 cm ceramic tiles. building.
• Atrium onto which internal doors open to
The windows are Europa aluminum, white, double allow daylighting to enter the innermost parts of
paned 22 mm thick, with a space between them the building.
of 12 mm and two glass panes, each 5 mm thick.

• Natural cross ventilation techniques


with window openings, fans or skylights.
• Natural ventilation systems through
Passive and Hybrid mechanically operated openings in the roof
and backed up with fans.
Solar Sytems
The building design specified the
incorporation of passive solar systems (P.S.S.),
the aim of which is to use solar energy for
Use of Renewable Energy Solar assisted water - air heat pump

heating: Sources in the HVAC System technology with a reciprocating compressor and
a Direct gain systems (openings on the set step at 0-100. The COP factor of the heat
south face with a total area of 17 m2) for Geothermal water to water heat pump
collecting solar radiation for passive heating pump for the above temperatures is 4.2 and the
during the winter. water heat exchanger is a concentric type.
During the winter period, water from the well
a Greenhouse with an area of 8.25 m2 comes through the evaporator of the
added to the south face of the building, with Solar assisted water-air heat pump
geothermal water to water heat pump and
openings of 12 m2 where solar radiation is provides heat to the chilling cycle (the design
collected as heat and is distributed through The cooling and heating load of the first floor is
openings in the building. temperatures for the circulation of the stored covered by a solar assisted 18 Kw air-water heat
water are 18/2 C). At the same time, the heat pump.
a Solar air collectors air panels with a total The solar atrium is used as a passive cooling system, During the winter, the air, pre-warmed by the
for direct natural lighting and solar radiation pump condenser heats the separate circulation
area of 17 m2 incorporated into the south solar air collectors with a total area of 17 m2 and
face of the building which collect solar of the water in the fan coil network on the
with a specified supply rate of 1700 m3/h, is
radiation and give off heat either through ground floor and provides heat for it, thus raising drawn into the evaporator of the solar assisted
the temperature which was reduced by the heat
openings (direct) or as preheated air to a
heat pump on the roof (indirect). Passive Cooling loss load of the building(the temperatures
air-water heat pump, aided by centrifugal fans
and supplies heat to the refrigeration cycle ( the
a Solar atrium (glazed part of the roof of
the building with an area of 14 m2) to collect
Techniques specified for the fan coil units is 45/40 C). The
system works the same way during the summer
temperatures specified for the circulation of the
prewarmed fresh air is 10/3 C)
solar radiation and produce thermal energy period. The unit uses the stored water of the
to heat the central internal part of the To avoid overheating and reduce air The distribution network of the first floor heat
conditioning requirements were the goals of the existing well which is 80 m deep, located 10 m
building. pump is similar to that of the ground floor heat
passive cooling systems. The following were north of the building. The temperature of the pump.
a Transparent insulation with a total area installed or applied: well water was measured in May at 21 C and the
of 8 m2 to reinforce solar gains on the south well provides water at a rate of 1.2m3/h. The The heat pump has a chilling power of 16.5 Kw and
facing parts of the building.. • Shading systems (vertical awnings) on
the south facade, vertical window blinds on the heat pump has a refrigeration power of 16 Kw heating at 18 Kw.
east west facades) combined with internal and a heating power of 17.5 Kw. It is R22
venetian blinds.

4 5
A significant amount of energy consumed in buildings can be saved with a
simultaneous improvement in conditions for their occupants through:
! Bioclimatic design
!
!
Construction with suitable insulation
The application of energy conservation technologies and renewable
Location - Climate
energy sources CRES is located 20 kilometres from the center
! The rational energy management of building functions of Athens in the Mesogeia area on Marathon
We have applied all of these to the new office building at CRES and are Avenue in the village of Pikermi, an
following closely the impact on energy consumption, in effect making this agricultural area with olive groves and
building an energy laboratory.The preliminary results are impressive, indicating vineyards, which has been rapidly built up
energy saving in the range of 55% in comparison with similar conventional buildings. over the last 20 years.
The new building at CRES is an example of the possibilities provided by the application of current
energy technologies in the built environment for the reduction of energy consumption and it The location is quite favourable with minimal
complies with all the standards and building regulations in the Regulation on the Rational Use and noise and air pollution. The vegetation
Conservation of Energy. around the building does not have an
impact as it leaves the south face open to
Dimosthenis Agoris direct sunlight.
President
The buildings adjacent to the north face and
the small trees to the west provide partial
protection from cold north winds. The External insulation on the north face of the building
The bioclimatic office-laboratory building average ambient
was designed in 1998 by associates of air temperature in
CRES as a demonstration building for the January is 9.4 C
application of energy technologies. and 28.7 C in July.
Following the call for tenders, The building is
construction began in November 2000. heated from mid-
The building was completed in July 2001 October to the
and in November 2001, regular collection end of April and
of data began on the building's energy the degree days
consumption, thermal energy for heating are
and the performance of the 1217.5 (19 C base).
Topographi
energy technologies. diagram of
the building
(south face
o CLIMATE DATA FOR PIKERMI - ATTIKI 1999-2001
variance 15
to the east)
Aim 300 35

AVER. AMBIENT
30

TEMPERATURE
250

RADIATION 0°
25
The design and construction of a

[kWh/m2]
200

SOLAR
20

[°C]
AIR
bioclimatic and low energy 150

Building Layout - Use Southeast face of the building during bricklaying


15

consuming building which would use 100 10

different soft energy forms and energy 50 5

saving techniques was the aim of the


0 0

project. The building includes a large

R
N

V
G
PR

EC
B

T
AY
regulations.

LY

O
SE
N
A
JA

FE

U
JU
M
A

D
JU
M

N
A
number of systems based on renewable The building was constructed as a single two MONTHS
energy sources (RES) and energy storey structure with a basement which The building envelope was constructed
technologies for demonstration purposes includes: DIRECT SOL. RADIATION [kWh/m2] DIFFUSE SOL. RADIATION [kWh/m2]
using reinforced concrete C20/25 with
as well as for monitoring and evaluation of ! Offices for researchers AMBIENT AIR TEMPERATURE [°C]
S500 steel. The walls are double brick and
their efficiency. Finally, the researchers in ! Library bookstacks the insulation was placed on the outside to
the role of the <user> interact with these ! Small meeting room avoid creating thermal bridges.
systems so that conclusions can be drawn ! Washrooms
concerning user behaviour which is a very
important parameter in assessing the
! Small kitchen
! Common areas and corridors
Construction The internal walls are made of
drywall(gypsum board), internally
performance of energy technologies. ! Basement utility areas insulated with fiberglass(?). The external
! HVAC unit The building was constructed according to surfaces were constructed of 3 coats of
its design specifications and Greek building cement plaster.

2 3
Room thermostat, occupancy sensor,
The central control unit and eight function switch installed
and the first floor control board throughout the building's rooms

The COP factor for the heat pump, if there is • Greenhouse The decoders have one address of room temperature adjustment
solar assistance is 4.8 and the water heat and control, either in groups or 3.5 C by the system thermostat).
exchanger is of concentric type. • Solar atrium individually, the control points Additionally, BEMS computer
In the basement of the building (the library), • Walls with connected to them. In this way, breakdowns often created malfunctions in
two air to air heat pumps of semi-central type transparent grouping, programming and control of the various controlled systems, especially
have been installed. insulation building parameters is achieved. The pair of the air conditioning one.
• Lighting twisted cables connects and serves control
system points (i.e. switches, relays, dimmers,
• Cooling occupancy sensors, etc.) of the installation (
beginning at the first connect point and

systems
Air quality
stopping at the final one), without returning, Photovoltaic Panels
in two ways. It transports communications
Artificial Lighting System • Building
electricity consumption monitoring
signals and at the same time it supplies the
control points with the low voltage power (24
On the sloping part of the roof which covers
the solar atrium, 12 photovoltaic panels
V DC) needed for them to function. The (dimensions 132 cm x 64 cm x 5 cm) were
Artificial light is supplied through the general lighting route of the power cables (230 V AC) is installed with a total power output of 600 W
installation of the building which is automatically limited to going from the distribution board (amorphous silicon), directly connected to
controlled by the BEMS. The luminaires used have panel to the electrical loads. the building's electricity supply through an
The control points receive commands inverter. The inclination of the photovoltaic
low energy consumption fluorescent pipes or panels is 20 for architectural and aesthetic
simultaneously through a common bus
compact PLC type lamps). Ceiling light fixtures have without the danger of overloading with the reasons, although for maximum yearly output
high frequency electronic ballasts, metal lengthwise use of the protocol <Carrier Sense Multiple it should be 40 . Also, a solar collector for
parabolic blinds and double parabolic elements or Access/Collision Avoidance (CSMA/CA)>. producing hot water (60 lit) was installed to
ceiling spots with shiny reflectors. Each point has a certain address by means of cover the building's limited needs for hot
which it is determined if the message water.
transferred on the bus is directed at the point
or not and whether the point executes the
command or simply receives it without taking
Building Energy action.
Management System (BEMS)
Appropriate programmable modules are
connected to the bus, such as occupancy Economic Analysis
BMS screen which controls the performance sensors, control systems with switches,
of the solar air collectors. temperature sensors, daylight measurement The energy technologies and systems
The reason for installing a BEMS was the system, etc. installed in the building cost, in 1999 prices,
monitoring and/or automatic control of the The control system consists of a Central Control 11% ( 39.780€) of the total cost of the
building's electrical and mechanical installations and Monitoring Station, the EIB system sensors, EIB building. Based on the results of the first 126
so that it will be possible to have immediate days of energy measurements in the building
access, uninterrupted operation, settings command execution devices and connecting
cables.. The programming and operation of the and on the calculated energy saving (53165
adjustment and data analysis for all the building Kwh/year) compared with similar
and system functions from a single control system is easily carried out through the central “conventional” buildings, there is a simple
station. At the same time, it is possible to monitor control station. In certain rooms, the operation payback period of 14.5 years. The payback
and record the performance of the renewable and selection of different modes is carried out period would have been much smaller, but
energy systems installed in the building as well as with local controls which have mode options. because the building was a demonstration
the creation of an archive of statistical data. The
system is based on the EIB (European Installation The system is composed of independent
User Behaviour problems project, systems were installed which
increased the cost of energy technologies
Bus) communication protocol. The energy
management system monitors and controls the structural elements which have been selected whisch were Encountered (three air conditioning systems, double
number of sensors and actuators for the
following: and connected to each other so as to allow
control and monitoring of the building from a BEMS, etc.) and therefore, the payback
• Comfort conditions Due to the many different systems which period.
• Heating air conditioning system central point by computer. The Control Station is were installed for demonstration, the building
connected by a RS232 interface. requires systematic monitoring by an energy
• Production of chilled/hot water through the manager. In particular, maintenance
operation of a water chilled geothermal heat The latest digital technology EIB has been use. problems were encountered with the
pump. automatic controls and controlled devices
• Production of chilled/hot water through the The guiding commands are transferred through a
(relays, filters, etc.) of the well pump. There
operation of an air cooled heat pump. pair of twisted reinforced cables from the central were also complaints from building
• Thermosiphonic panels- solar air collectors occupants who work in rooms facing a site
unit to the decoders. The system is supplied with orientation associated with adverse thermal
loads because it was not possible to control
low voltage power (up to 24 V).
effectively the room air temperature (range
P/V 600W on the
sloping part of the roof

6 7