Documente Academic
Documente Profesional
Documente Cultură
Notes: The requirements for direct-buried conductors and raceways are given in 300.5(A) and Table
300.5. As noted in Column 4 of Table 300.5, conductors under residential driveways must be at least 18
in. below grade. However, if the conductors are protected by an overcurrent device rated at not more
than 20 amperes and provided with ground-fault circuit-interrupter (GFCI) protection for personnel, the
burial depth may be reduced to 12 in. Exhibits 300.6 and 300.7 show examples of underground
installations of 18 in. and 12 in., respectively. See 300.50 where circuits exceed 600 volts.
Exhibit 300.6 Rigid polyvinyl chloride conduit, Type PVC, buried in compliance with Column 3 of Table 300.5
and 300.5(A).
Notes:
1. Cover is defined as the shortest distance in millimeters (inches) measured between a point on
the top surface of any direct-buried conductor, cable, conduit, or other raceway and the top
surface of finished grade, concrete, or similar cover.
2. Raceways approved for burial only where concrete encased shall require concrete envelope not
less than 50 mm (2 in.) thick.
3. Lesser depths shall be permitted where cables and conductors rise for terminations or splices or
where access is otherwise required.
4. Where one of the wiring method types listed in Columns 13 is used for one of the circuit types
in Columns 4 and 5, the shallowest depth of burial shall be permitted.
5. Where solid rock prevents compliance with the cover depths specified in this table, the wiring
shall be installed in metal or nonmetallic raceway permitted for direct burial. The raceways shall
be covered by a minimum of 50 mm (2 in.) of concrete extending down to rock.
Notes: Section 300.5(B) requires that the inside of all raceways and enclosures installed underground
be classified as a wet location. Conductors installed in such underground locations must be listed for
use in wet locations and comply with 310.10(C).
Exception No. 1: Type MI Cable shall be permitted under a building without installation in a raceway
where embedded in concrete, fill, or other masonry in accordance with 332.10(6) or in underground runs
where suitably protected against physical damage and corrosive conditions in accordance with
332.10(10).
Exception No. 2: Type MC Cable listed for direct burial or concrete encasement shall be permitted under
a building without installation in a raceway in accordance with 330.10(A)(5) and in wet locations in
accordance with 330.10(A)(11).
Notes: This section was revised for the 2011 Code with the addition of the two exceptions. The main
rule is that underground cable installed under a building must be installed in a suitable raceway.
Notes: The warning ribbon required in 300.5(D)(3) reduces the risk of an accident, an electrocution, or
an arc-flash incident during excavation near underground service conductors that are not encased in
concrete. This provision does not extend to feeders and branch circuits, because these circuits contain
short-circuit and overload protection.
Notes: Underground splices are not required to be in a box where made in accordance with 110.14(B),
which requires the splicing means to be listed for underground use. Sealed wire connector systems are
listed for underground splicing. They restore the insulation integrity of the spliced conductors in a
permanent joint. Sealed wire connectors are used where it will not be necessary to access the splices in
the future.
A difference exists between multiconductor cables labeled for direct burial and single conductors
labeled for direct burial. Because direct-burial multiconductor cables may or may not contain individual
conductors labeled for direct burial, the overall cable jacket may be the only underground protection
technique for the contained conductors. Although the direct-burial splicing techniques used on
multiconductor cables can differ widely from the techniques used on direct-burial single-conductor
cables, the Code requirements are generally the same. The splicing technique must be listed for the
cable type and listed for direct burial. See 250.8 for spliced grounding and bonding conductors. An
example of a sealed wire connector system listed for direct burial used to splice single-conductor
installed underground cables is shown in Exhibit 300.8.
(F) Backfill
Backfill that contains large rocks, paving materials, cinders, large or sharply angular substances, or
corrosive material shall not be placed in an excavation where materials may damage raceways, cables, or
other substructures or prevent adequate compaction of fill or contribute to corrosion of raceways,
cables, or other substructures.
Where necessary to prevent physical damage to the raceway or cable, protection shall be provided in the
form of granular or selected material, suitable running boards, suitable sleeves, or other approved
means.
Presence of hazardous gases or vapors may also necessitate sealing of underground conduits or
raceways entering buildings.
Notes: Section 300.5(G) requires either or both ends of conduits and raceways subject to moisture to
be sealed or plugged. One method, shown in Exhibit 300.9, is a conduit sealing bushing that prevents
the entrance of gas or moisture. See 230.8 for sealing service raceways.
(H) Bushing
A bushing, or terminal fitting, with an integral bushed opening shall be used at the end of a conduit or
other raceway that terminates underground where the conductors or cables emerge as a direct burial
wiring method. A seal incorporating the physical protection characteristics of a bushing shall be
permitted to be used in lieu of a bushing.
Notes: Where a conduit or raceway terminates underground and emerges as a direct-burial wiring
method, 300.5(H) requires a protective fitting. Exhibit 300.10 shows such a fitting with a Type UF cable
buried in compliance with Table 300.5. Note the protective bushing where the cable is used with metal
conduit. The bushing will protect the cable from damage by the conduit. Metal conduit is usually used
as this fitting because of the potential to damage a nonmetallic conduit when pulling conductors in an
underground installation. See 300.10, Exception No. 1. See also the commentary following 300.4(G).
Notes: Keeping all circuit conductors together reduces inductive heating and reduces circuit
impedance. Section 300.5(I), Exception No. 1, permits the installation of paralleled conductors in
different raceways provided all circuit conductors, including equipment grounding conductors, are
installed in each of the parallel raceways. Conductors of the same circuit are addressed in 300.3(B). Also
see 310.10(H) for conductors in parallel. This exception was revised for the 2011 Code to make it clear
that it covers single conductors, as well as multiconductor underground cables.
Exception No. 2: Isolated phase, polarity, grounded conductor, and equipment grounding and bonding
conductor installations shall be permitted in nonmetallic raceways or cables with a nonmetallic covering
or nonmagnetic sheath in close proximity where conductors are paralleled as permitted in 310.10(H), and
where the conditions of 300.20(B) are met.
Notes: Isolated phase installations contain only one phase per raceway or cable. The spacing between
isolated phase raceways and cables should be as small as possible, and the length of the run limited, to
avoid increased circuit impedance and the resulting increase in voltage drop inherent in an installation
involving ac circuits. Isolated phase installations may be used in ac circuits to limit available fault
current at downstream equipment.
Isolated phase installations present an inherent hazard of overheating, a risk that must be understood
and carefully controlled. This hazard results from induced currents in metal surrounding a raceway that
contains only one phase conductor. [See 300.20(A) and (B) for more information on induced currents in
raceways.] The surrounding metal acts as a shorted transformer turn. In underground installations, a
single conductor is unlikely to be installed in a metal raceway or, if it were, is unlikely to present a fire
hazard. This is not true, however, for aboveground raceways, and it is the reason isolated phase
installations have limited application for aboveground installations.
See 300.3(B)(3) together with 330.31 and 332.31, which recognize single-conductor Type MI cable and
single-conductor Type MC cable.
This section recognizes S loops in underground direct burial to raceway transitions, expansion
fittings in raceway risers to fixed equipment, and, generally, the provision of flexible connections to
equipment subject to settlement or frost heaves.
Notes: Section 300.5(J) requires that an installation be designed to allow for movement of direct-buried
equipment, cables, and raceways. Slack must be allowed in cables or expansion joints, or other
measures must be taken, if earth movement due to frost or settlement is anticipated.
Notes: Metal and nonmetallic raceways for underground boring-type installations are required by
300.5(K) to be approved for such use. There are a number of metal and nonmetallic raceways that are
suitable for boring installations, such as high density polyethylene conduit (Type HDPE). See Article 353
for more information.