Code No: 117CT Set No.

1
JAWAHARLAL NEHRU TECHNOLOGICAL UNIVERSITY HYDERABAD
IV B.Tech. I Sem., I Mid-Term Examinations, September - 2017
ELECTRICAL DISTRIBUTION SYSTEMS
Objective Exam
Name: ______________________________ Hall Ticket No. A
Answer All Questions. All Questions Carry Equal Marks. Time: 20 Min. Marks: 10.

I. Choose the correct alternative:

1. The load of a consumer is generally measured in terms of [ ]


a) Volts b) Amperes c) Ampere hour d) kW

2. The ratio of the observed peak of the group of consumers to the sum of the individual peaks is
[ ]
a)load factor b) loss factor c) diversity factor d) coincidence factor

3. The empirical relation used between load factor (l.f) and loss factor is, loss factor= [ ]
a) 0.7(l.f)+ 0.3(l.f)2 b) 0.3+ l.f c) 0.3(l.f)+ 0.7(l.f)2 d) 0.7[(l.f) +(l.f)2]

4. The coincidence factor for lighting loads in residential loads is about [ ]


a) 0.1 b) 0.5 c) 1.0 d) 0.9

5. For a given percentage of voltage drop, the length of feeder and loading are direct functions of the
feeder_________________ [ ]
a) Conductor size b) current rating c) voltage level d) power rating

6. Primary feeder loading is the loading of feeder during _____________loading conditions as measured at
the source [ ]
a) light b) medium c) maximum d) small

7. The secondary distribution system is the _____ sub system of the power system [ ]
a) initial b) medium c) zero d) final

8. If feeder voltage level is doubled for the same permissible drop, the power transmitted capacity of the
feeder is four times and length of the feeder can be increased by ____ times [ ]
a)1 b)2 c) 3 d) 4

9. The size of conductor for primary feeder is based on acceptable voltage drop and ____ in the conductor.
[ ]
a) current b) power loss c) power d) voltage

10. Voltage drop is basically refers to the reduction in the voltage between the ___ end and receiving end.
[ ]
a) sending b) generation c) distribution d) transmission

Cont..2
Code No: 117CT :2: Set No. 1

II Fill in the Blanks

11. The distribution substation must be located as closed as possible to the __________________ .

12. In loop distribution system _______ number of paths between the substation and every consumer .

13. Generally primary distribution feeder voltage is ______ kV .

14. The secondary distribution systems are generally____________________ type of distribution system
used in rural areas .

15. For constant current load model, power is varied with proportional to __________________ .

16. The peak load of a primary feeder is 1000kW at which the power loss is 50kW with loss factor is 0.2.
The peak power loss _____________ kW

17. The consumer receives power from__________________ side of the distribution transformer .

18. Under very short duration of peak load, the loss factor will be approximately equal to the square of the
______________________ .

19. The demand factor for municipal loads are __________________%

20. The overall power factor of induction motor is ____________________ lagging .

-oOo-
Code No: 117CT Set No. 2
JAWAHARLAL NEHRU TECHNOLOGICAL UNIVERSITY HYDERABAD
IV B.Tech. I Sem., I Mid-Term Examinations, September - 2017
ELECTRICAL DISTRIBUTION SYSTEMS
Objective Exam
Name: ______________________________ Hall Ticket No. A
Answer All Questions. All Questions Carry Equal Marks. Time: 20 Min. Marks: 10.

I. Choose the correct alternative:

1. The coincidence factor for lighting loads in residential loads is about [ ]


a) 0.1 b) 0.5 c) 1.0 d) 0.9

2. For a given percentage of voltage drop, the length of feeder and loading are direct functions of the
feeder_________________ [ ]
a) Conductor size b) current rating c) voltage level d) power rating

3. Primary feeder loading is the loading of feeder during _____________loading conditions as measured at
the source [ ]
a) light b) medium c) maximum d) small

4. The secondary distribution system is the _____ sub system of the power system [ ]
a) initial b) medium c) zero d) final

5. If feeder voltage level is doubled for the same permissible drop, the power transmitted capacity of the
feeder is four times and length of the feeder can be increased by ____ times [ ]
a)1 b)2 c) 3 d) 4

6. The size of conductor for primary feeder is based on acceptable voltage drop and ____ in the conductor.
[ ]
a) current b) power loss c) power d) voltage

7. Voltage drop is basically refers to the reduction in the voltage between the ___ end and receiving end.
[ ]
a) sending b) generation c) distribution d) transmission

8. The load of a consumer is generally measured in terms of [ ]


a) Volts b) Amperes c) Ampere hour d) kW

9. The ratio of the observed peak of the group of consumers to the sum of the individual peaks is
[ ]
a)load factor b) loss factor c) diversity factor d) coincidence factor

10. The empirical relation used between load factor (l.f) and loss factor is, loss factor= [ ]
a) 0.7(l.f)+ 0.3(l.f)2 b) 0.3+ l.f c) 0.3(l.f)+ 0.7(l.f)2 d) 0.7[(l.f) +(l.f)2]

Cont..2
Code No: 117CT :2: Set No. 2

II Fill in the Blanks

11. The secondary distribution systems are generally____________________ type of distribution system
used in rural areas .

12. For constant current load model, power is varied with proportional to __________________ .

13. The peak load of a primary feeder is 1000kW at which the power loss is 50kW with loss factor is 0.2.
The peak power loss _____________ kW

14. The consumer receives power from__________________ side of the distribution transformer .

15. Under very short duration of peak load, the loss factor will be approximately equal to the square of the
______________________ .

16. The demand factor for municipal loads are __________________%

17. The overall power factor of induction motor is ____________________ lagging .

18. The distribution substation must be located as closed as possible to the __________________ .

19. In loop distribution system _______ number of paths between the substation and every consumer .

20. Generally primary distribution feeder voltage is ______ kV .

-oOo-
Code No: 117CT Set No. 3
JAWAHARLAL NEHRU TECHNOLOGICAL UNIVERSITY HYDERABAD
IV B.Tech. I Sem., I Mid-Term Examinations, September - 2017
ELECTRICAL DISTRIBUTION SYSTEMS
Objective Exam
Name: ______________________________ Hall Ticket No. A
Answer All Questions. All Questions Carry Equal Marks. Time: 20 Min. Marks: 10.

I. Choose the correct alternative:

1. Primary feeder loading is the loading of feeder during _____________loading conditions as measured at
the source [ ]
a) light b) medium c) maximum d) small

2. The secondary distribution system is the _____ sub system of the power system [ ]
a) initial b) medium c) zero d) final

3. If feeder voltage level is doubled for the same permissible drop, the power transmitted capacity of the
feeder is four times and length of the feeder can be increased by ____ times [ ]
a)1 b)2 c) 3 d) 4

4. The size of conductor for primary feeder is based on acceptable voltage drop and ____ in the conductor.
[ ]
a) current b) power loss c) power d) voltage

5. Voltage drop is basically refers to the reduction in the voltage between the ___ end and receiving end.
[ ]
a) sending b) generation c) distribution d) transmission

6. The load of a consumer is generally measured in terms of [ ]


a) Volts b) Amperes c) Ampere hour d) kW

7. The ratio of the observed peak of the group of consumers to the sum of the individual peaks is
[ ]
a)load factor b) loss factor c) diversity factor d) coincidence factor

8. The empirical relation used between load factor (l.f) and loss factor is, loss factor= [ ]
a) 0.7(l.f)+ 0.3(l.f)2 b) 0.3+ l.f c) 0.3(l.f)+ 0.7(l.f)2 d) 0.7[(l.f) +(l.f)2]

9. The coincidence factor for lighting loads in residential loads is about [ ]


a) 0.1 b) 0.5 c) 1.0 d) 0.9

10. For a given percentage of voltage drop, the length of feeder and loading are direct functions of the
feeder_________________ [ ]
a) Conductor size b) current rating c) voltage level d) power rating

Cont..2
Code No: 117CT :2: Set No. 3

II Fill in the Blanks

11. The peak load of a primary feeder is 1000kW at which the power loss is 50kW with loss factor is 0.2.
The peak power loss _____________ kW

12. The consumer receives power from__________________ side of the distribution transformer .

13. Under very short duration of peak load, the loss factor will be approximately equal to the square of the
______________________ .

14. The demand factor for municipal loads are __________________%

15. The overall power factor of induction motor is ____________________ lagging .

16. The distribution substation must be located as closed as possible to the __________________ .

17. In loop distribution system _______ number of paths between the substation and every consumer .

18. Generally primary distribution feeder voltage is ______ kV .

19. The secondary distribution systems are generally____________________ type of distribution system
used in rural areas .

20. For constant current load model, power is varied with proportional to __________________ .

-oOo-
Code No: 117CT Set No. 4
JAWAHARLAL NEHRU TECHNOLOGICAL UNIVERSITY HYDERABAD
IV B.Tech. I Sem., I Mid-Term Examinations, September - 2017
ELECTRICAL DISTRIBUTION SYSTEMS
Objective Exam
Name: ______________________________ Hall Ticket No. A
Answer All Questions. All Questions Carry Equal Marks. Time: 20 Min. Marks: 10.

I. Choose the correct alternative:

1. If feeder voltage level is doubled for the same permissible drop, the power transmitted capacity of the
feeder is four times and length of the feeder can be increased by ____ times [ ]
a)1 b)2 c) 3 d) 4

2. The size of conductor for primary feeder is based on acceptable voltage drop and ____ in the conductor.
[ ]
a) current b) power loss c) power d) voltage

3. Voltage drop is basically refers to the reduction in the voltage between the ___ end and receiving end.
[ ]
a) sending b) generation c) distribution d) transmission

4. The load of a consumer is generally measured in terms of [ ]


a) Volts b) Amperes c) Ampere hour d) kW

5. The ratio of the observed peak of the group of consumers to the sum of the individual peaks is
[ ]
a)load factor b) loss factor c) diversity factor d) coincidence factor

6. The empirical relation used between load factor (l.f) and loss factor is, loss factor= [ ]
a) 0.7(l.f)+ 0.3(l.f)2 b) 0.3+ l.f c) 0.3(l.f)+ 0.7(l.f)2 d) 0.7[(l.f) +(l.f)2]

7. The coincidence factor for lighting loads in residential loads is about [ ]


a) 0.1 b) 0.5 c) 1.0 d) 0.9

8. For a given percentage of voltage drop, the length of feeder and loading are direct functions of the
feeder_________________ [ ]
a) Conductor size b) current rating c) voltage level d) power rating

9. Primary feeder loading is the loading of feeder during _____________loading conditions as measured at
the source [ ]
a) light b) medium c) maximum d) small

10. The secondary distribution system is the _____ sub system of the power system [ ]
a) initial b) medium c) zero d) final

Cont..2
Code No: 117CT :2: Set No. 4

II Fill in the Blanks

11. Under very short duration of peak load, the loss factor will be approximately equal to the square of the
______________________ .

12. The demand factor for municipal loads are __________________%

13. The overall power factor of induction motor is ____________________ lagging .

14. The distribution substation must be located as closed as possible to the __________________ .

15. In loop distribution system _______ number of paths between the substation and every consumer .

16. Generally primary distribution feeder voltage is ______ kV .

17. The secondary distribution systems are generally____________________ type of distribution system
used in rural areas .

18. For constant current load model, power is varied with proportional to __________________ .

19. The peak load of a primary feeder is 1000kW at which the power loss is 50kW with loss factor is 0.2.
The peak power loss _____________ kW

20. The consumer receives power from__________________ side of the distribution transformer .