AURORA MODEL 383 PUMPS Section 911 Page 201

INLINE FIRE PUMP Date September, 2011


Supersedes Section 911 Page 201
TO DISASSEMBLE AB Dated Nov., 2000
P BW
NOTES:
1. All dimensions in inches (mm).
1/4 NPT GAUGE
CONNECTIONS 2. Dimensions may vary + 1/4.
AG
3. Not for construction purposes unless certified.
4. Suction and discharge flanges are 125# ANSI
SUCTION BASE FLANGE - as standard. 250# suction and discharge or
DISCHARGE 125# suction/250# discharge available as option
2" - 125# ANSI
CP FLANGE FOR 2" for 9 inch and 10 inch case bore pumps only.
DF DISCHARGE PUMP.
3" - 125# ANSI
FLANGE FOR
3" AND 4"
DISCHARGE PUMP.
VD 7" AND 9" CASE BORE.
4" 125# ANSI FLANGE FOR
10" AND 13" CASE BORE.
YY X DC DE

Pump Size DF Pump Wt. Lbs. (Kg) Approx.


GPM
Pump Disch. x BW 213JP 213JP 284JP
Pump X YY VD DC DE
Model Suct. x (Min.) 184JP through 184JP through through
Rating
Case Bore 365JP 256JP 365JP
9.5 9.5 4.5 9.25 7.81 8.63 5.75 6.25 117 130
2-383-9C 2x2x9 50, 100
(241) (241) (114) (235) (198) (219) (146) (159) (53.1) (59)
9.5 9.5 4.5 10.25 8.0 8.81 5.19 6.13 140 153 159
3-383-7A 3x3x7 100, 150, 200
(241) (241) (114) (260) (203) (224) (132) (156) (63.5) (69.4) (72.1)
9.5 9.5 4.5 10.25 8.81 5.19 6.13 153 159
3-383-7B 3x3x7 250
(241) (241) (114) (260) (224) (132) (156) (69.4) (72.1)
11 11 3.75 10.75 9.13 5.13 6.38 130
3-383-7C 3x4x7 250, 300
(279) (279) (95) (273) (232) (130) (162) (59)
11 11 4.5 9.88 8.25 8.88 5.75 6.5 178 191 196
3-383-9 3x4x9 250
(279) (279) (114) (251) (210) (225) (146) (165) (80.7) (86.6) (88.9)
11 11 4.5 10.25 7.94 8.75 6 6.75 152 165 170
3-383-9A 3x3x9 150, 200
(279) (279) (114) (260) (202) (222) (152) (171) (68.9) (74.8) (77.1)
11 11 4.25 10.88 9.25 5.75 6.63 150
3-383-9B 3x4x9 300
(279) (279) (108) (276) (235) (146) (168) (68)
300, 400, 11 11 4.5 11.25 9.31 5.56 7.31 191 197
4-383-7B 4x4x7
450, 500 (279) (279) (114) (286) (237) (141) (186) (86.6) (89.4)
11 11 4.5 11.25 9.63 5.5 7.38 175
4-383-7C 4x4x7 400, 450, 500
(279) (279) (114) (286) (244) (140) (187) (79.4)

CP
ODP AG AB Motor Wt.
P 3-383-7A
Frame Approx. Approx. Lbs. (Kg) 2-383-9C 3-383-7C 3-383-9 3-383-9A 3-383-9B 4-383-7B 4-383-7C
3-383-7B*
15 10.38 7 95 32.13 28.63 33.13 33.25
184JP
(381) (264) (178) (43.1) (816) (727) (841) (845)
17 12.25 7.63 135 35 36 35.75 36
213JP
(432) (311) (194) (61.2) (889) (914) (908) (914)
17 12.25 7.63 155 35 36 35.75 36 37.75
215JP
(432) (311) (194) (70.3) (889) (914) (908) (914) (959)
21 13 8.88 195 39 40 37.88 39.75 40 41.63
254JP
(533) (330) (225) (88.5) (991) (1016) (962) (1010) (1016) (1057)
21 13 9.25 256 39 37.88 39.75 40 41.63
256JP
(533) (330) (235) (116.1) (991) (962) (1010) (1016) (1057)
22 15.75 11.38 271 40.75 41 38.13 42.63 38.88
284JP
(559) (400) (289) (122.9) (1035) (1041) (968) (1083) (987)
22 15.75 11.38 320 40.75 41 38.13 42.63 38.88
286JP
(559) (400) (289) (145.1) (1035) (1041) (968) (1083) (987)
24 17.75 13.25 420 43
324JP
(610) (451) (337) (190.5) (1092)

* Not available with 184JP frame.

2012 Pentair Pump Group, Inc.


Section 911 Page 202 AURORA MODEL 383 PUMPS
Date April, 2014 INLINE FIRE PUMP
Supersedes Section 911 Page 202 TO DISASSEMBLE AB
Dated November, 2012 P BW

1/4 NPT GAUGE


CONNECTIONS
AG NOTES:
1. All dimensions in inches (mm).
SUCTION DISCHARGE
BASE FLANGE -
2" - 125# ANSI
2. Dimensions may vary + 1/4.
CP
DF
FLANGE FOR 2" 3. Not for construction purposes unless certified.
DISCHARGE PUMP.
3" - 125# ANSI 4. Suction and discharge flanges are 125# ANSI
FLANGE FOR
3" AND 4" as standard. 250# suction and discharge or
DISCHARGE PUMP.
VD 7" AND 9" CASE BORE. 125# suction/250# discharge available as option
4" 125# ANSI FLANGE FOR
10" AND 13" CASE BORE.
for 9 inch and 10 inch case bore pumps only.
YY X DC DE

Pump Size DF Pump Wt. Lbs. (kg) Approx.


GPM
Pump Disch x BW 213JP 364HP 364TCVZ 213JP 284JP 364HP 364TCVZ
Pump X YY VD DC DE
Model Suct x (Min.) 184JP through through through 184JP through through through through
Rating
Case Bore 365JP 445HP 445TCVZ 256JP 365JP 445HP 445TCVZ
300, 400,
11 11 4.5 11 8.38 9 6 7.13 214 227 232
4-383-9 4x5x9
450 (279) (279) (114) (279) (213) (229) (152) (181) (97.3) (103) (105.2)
300, 400,11 11 4.5 11 8.38 9 6 7.13 214 227 232
4-383-9B 4 x 5 x 9
450, 500
(279) (279) (114) (279) (213) (229) (152) (181) (97.3) (103) (105.2)
11 11 4.5 11 9 6 7.13 232
4-383-9C 4x5x9 500
(279) (279) (114) (279) (229) (152) (181) (105.2)
4-383-10 4 x 6 x 10 400, 450, 14 14 5 13.06 9.06 7 8.5 351

500 (356) (356) (127) (332) (230) (178) (216) (159.2)
14 14 5 13.06 9.06 7 8.5 351
4-383-10B 4 x 6 x 10 750
(356) (356) (127) (332) (230) (178) (216) (159.2)
16 16 5.38 13.81 9.19 9 10.5 421
4-383-13 4 x 6 x 13 750
(406) (406) (137) (351) (233) (229) (267) (191)
17.63
8-383-15 8 x 8 x 15 1000, 1250, 22.5 22.5 12.91 19 10.38 12.94 812
(448)
1500 (572) (572) (328) (483) (263) (329) (368)
25 22.5 8.06 18.38 10.75 11.75 14.38 1020
8-383-18 8 x 8 x 18 1000, 1250 (635) (467)
(572) (205) (273) (298) (365) (463)
25 22.5 8.06 18.38 10.75 11.75 14.38 1020
8-383-18A 8 x 8 x 18A 1500 (467)
(635) (572) (205) (273) (298) (365) (463)
CP
ODP AG AB Motor Wt.
P 4-383-9 4-383-10 8-383-18
Frame Approx. Approx. Lbs. (kg) 4-383-13 8-383-15
4-383-9B&C* 4-383-10B 8-383-18A
15 10.38 7 95 34.38
184JP
(381) (264) (178) (43) (873)
17 12.25 7.63 135 37
213JP
(432) (311) (194) (61) (940)
17 12.25 7.63 155 37
215JP
(432) (311) (194) (70) (940)
21 13 8.88 195 41
254JP
(533) (330) (225) (89) (1041)
21 13 9.25 256 41
256JP
(533) (330) (235) (116) (1041)
22 15.75 11.38 271 42
284JP
(559) (400) (289) (123) (1067)
22 15.75 11.38 320 42 44.13
286JP
(559) (400) (289) (145) (1067) (1121)
24 17.75 13.25 420 44 46.13 46.25
324JP
(610) (451) (337) (191) (1118) (1172) (1175)
24 17.75 13.25 460 44 46.13 46.25
326JP
(610) (451) (337) (209) (1118) (1172) (1175)
26 20 16 600 48.13 48.25
364JP
(660) (508) (406) (272) (1222) (1226)
26 20 16 750 48.13 48.25
365JP
(660) (508) (406) (340) (1222) (1226)
25 21 16 870 61.63
364HP
(635) (534) (406) (395) (1565)
25 21 16 940 61.63
365HP
(635) (534) (406) (426) (1565)
28 22 16.5 1091 64.63
404HP
(711) (559) (419) (495) (1642)
28 22 16.5 1273 64.63
405HP
(711) (559) (419) (577) (1642)
32 24 19.13 1290 68.63
444HP
(813) (610) (486) (585) (1743)
32 24 19.13 1440 68.63
445HP
(813) (610) (486) (653) (1743)
28 20.5 18 1015 57.63
364TCZ
(711) (521) (457) (461) (1464)
28 20.5 18 1065 57.63
365TCZ
(711) (521) (457) (484) (1464)
33.5 22.5 20 1188 63.13
405TCZ
(851) (572) (508) (540) (1604)
36 24.5 21 1629 65.63
444TCZ
(914) (622) (533) (740) (1667)
36 24.5 21 1629 65.63
445TCZ
(914) (622) (533) (740) (1667)
* Not available with 184JP frame.

2014 Pentair Ltd.


AURORA MODEL 383 PUMPS Section 911 Page 203
FIRE PUMP ACCESSORIES Date November, 2012
Supersedes Section 911 Page 203
DISCHARGE FITTINGS Dated September, 2011

DISCHARGE FITTINGS FOR


INSTALLATION OF VALVES

AIR RELEASE
CIRCULATION VALVE
RELIEF VALVE

L
L
TYPE A
TYPE B
Discharge Fitting Only
Pump Flow Fitting Fitting
150# Flanges 300# Flanges
Size Rating Type Size
Opt. No. L Wt. (Lb.) Opt. No. L Wt. (Lb.)
100
3 x 3 x 7A
150
200 A 3x3 74BA 14 25 N/A N/A N/A
3 x 3 x 7B
250
3 x 4 x 7C 250
3 x 4 x 7C 300
B 3x4 74BP 10 32 N/A N/A N/A
3 x 4 x 9B 300
300
4 x 4 x 7B
400 A 4x4 74BB 16 39 N/A N/A N/A
4 x 4 x 7C 400
450
4 x 4 x 7B
500
B 4x5 74BC 11.75 42 N/A N/A N/A
450
4 x 4 x 7C
500
50
2 x 2 x 9C A 2x2 74BD 14 14 74BJ 14 14
100
150
3 x 3 x 9A
200 A 3x3 74BA 14 25 74BK 14 35
3x3x9 250
4x4x9 300
4 x 4 x 9B 400 A 4x4 74BB 16 39 74BL 16 57
4 x 6 x 10 400
4 x 6 x 10 450 A 4x4 74BB 16 39 74BL 16 57
4 x 5 x 9B
4 x 5 x 9C 500 B 4x5 74BC 11.75 45 74BM 12.5 65
4 x 6 x 10
4 x 6 x 10B 750 B 4x6 74BH 12.25 52 74BN 13 82
4 x 6 x 13 750 B 4x6 74BH 12.25 52 74BN 18.725 82
1000
8 x 8 x 18/18A 1250 N/A N/A N/A N/A N/A N/A N/A N/A
1500

NOTES:
1. All dimensions in inches and may vary by 3/8".
2. Flanges are ANSI Class 150 or Class 300 steel.
N/A Not Applicable

2012 Pentair Pump Group, Inc.


Section 911 Page 204
Date October 1, 2005

THIS PAGE LEFT INTENTIONALLY BLANK

2012 Pentair Pump Group, Inc.

S-ar putea să vă placă și