Documente Academic
Documente Profesional
Documente Cultură
SA Power Networks
www.sapowernetworks.com.au
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 1 of 149
Service & Installation Rules
Revision Notice:
Date Details Author Authorised
SA Power Networks:
SA Power Networks, ABN 13 332 330 749, a partnership of:
Spark Infrastructure SA (No.1) Pty Ltd, ABN 54 091 142 380
Spark Infrastructure SA (No.2) Pty Ltd, ABN 19 091 143 038
Spark Infrastructure SA (No.3) Pty Ltd, ABN 50 091 142 362
each incorporated in Australia
CKI Utilities Development Limited, ABN 65 090 718 880
PAI Utilities Development Limited, ABN 82 090 718 951
each incorporated in The Bahamas
1 Anzac Highway, Keswick, South Australia, 5035.
Preface:
These SA Power Networks Service and Installation Rules incorporate the Technical Installation Rules
referred to in Regulation 76 of the Electricity (General) Regulations 2012 under the Electricity Act 1996.
The Technical Installation Rules within this document are denoted by the symbol TIR adjacent to the
relevant clause.
In accordance with Regulation 76 of the Electricity (General) Regulations 2012, the Technical Installation
Rules have been prepared by SA Power Networks, and approved by the Technical Regulator.
The parts of the SA Power Networks Service and Installation Rules which are not part of the Technical
Installation Rules have been prepared and approved by SA Power Networks.
If a provision of the SA Power Networks Service and Installation Rules which is not part of the Technical
Installation Rules is inconsistent with the Technical Installation Rules, the Technical Installation Rules shall
prevail, and the provision shall, to the extent of the inconsistency, be invalid.
These SA Power Networks Service and Installation Rules supersede the SA Power Networks Service and
Installation Rules 2016, effective from 7th August 2017.
Contents
1. General ..................................................................................................... 15
1.1 About this Manual .............................................................................................. 15
1.1.1 What this document is about ..........................................................................15
1.1.2 Application of this document ..........................................................................15
1.1.3 How to use this document...............................................................................15
1.1.4 Revisions and Alterations ................................................................................15
1.2 References.......................................................................................................... 15
1.2.1 Acts & Regulations ..........................................................................................15
1.2.2 Codes & Guidelines .........................................................................................16
1.3 Definitions .......................................................................................................... 16
2. Introduction .............................................................................................. 22
2.1 Objective ............................................................................................................ 22
2.2 Scope ................................................................................................................. 22
2.3 Innovation .......................................................................................................... 22
2.4 Publication & Revision ........................................................................................ 22
2.4.1 Administration ................................................................................................22
2.4.2 Publication .....................................................................................................23
2.4.3 Revision ..........................................................................................................23
2.5 Service & Installation Rules Management Contact .............................................. 23
2.6 Dispute Resolution ............................................................................................. 23
2.7 Application Responsibilities ................................................................................ 23
2.8 Failure to Comply with these Rules ..................................................................... 23
2.9 Exceptional Circumstances .................................................................................. 24
2.10 Offences ............................................................................................................. 24
2.11 Necessity for Employing a Licensed Person ......................................................... 24
2.12 Basic Industry Relationship ................................................................................. 24
2.12.1 Responsibilities ...............................................................................................25
2.12.1.1 Distributor ............................................................................................... 25
2.12.1.2 Retailers................................................................................................... 25
2.12.1.3 Customer Agents ..................................................................................... 25
3. Customer Solutions Manager Areas & Contact Details............................... 26
3.1 State Customer Solutions Manager Area Boundaries ........................................ 26
3.2 Metro Customer Solutions Manager Area Boundaries ...................................... 27
Issued August 2017 Page 5 of 149
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2017
Service & Installation Rules
1. General
1.1 About this Manual
1.1.1 What this document is about
This document is designed to assist customers and electrical contractors by detailing:
the method and type of supply from SA Power Networks distribution network;
the requirements for electrical installations connected to SA Power Networks
distribution network; and
some of the customers obligations relating to that supply.
Additional requirements are contained in the Electricity Distribution Code, Connection
and Supply Contract and the Electricity Metering Code, copies of which are available on
SA Power Networks internet site or from SA Power Networks on request.
1.1.2 Application of this document
This document is intended for use by SA Power Networks staff, engineers, building work
contractors, licensed electrical contractors and registered electrical workers who are
directly engaged in activities associated with the connection of electricity supply to a
customers property from the SA Power Networks distribution network.
The requirements of this document apply to customers and their agents in relation to
electrical installations connected to or intended to be connected to SA Power Networks
distribution networks. Alterations of, or, additions to an existing electrical installation
shall be deemed to be a new electrical installation and are covered by the requirements
of this document.
In accordance with the Electricity Act 1996 and Electricity (General) Regulations 2012,
the requirements within this document also apply to electricity retailers and other
parties such as meter providers participating in or executing duties under the National
Electricity Rules in relation to installations connected (or intending to be connected) to
SA Power Networks distribution network.
Unregistered persons may use this document for information purposes only, but are
forbidden by law from undertaking electrical work and may be subject to criminal
prosecution should they do so.
1.1.3 How to use this document
This is a self-contained document except where it specifically refers to other related
documents. It supersedes previous versions of the SA Power Networks Service &
Installation Rules.
1.1.4 Revisions and Alterations
SA Power Networks reserves the right to revise this publication. The current edition of
this document is available on our website at www.sapowernetworks.com.au.
1.2 References
This list of references has been made as comprehensive as possible at the time of publication.
However, other references may have been applicable at the time. The references listed may have
been amended or made obsolete and new references may be applicable. The user is responsible
to correct references applied.
1.2.1 Acts & Regulations
Electricity Act 1996 and Electricity (General) Regulations 2012
Work Health & Safety Act 2012 and Work Health & Safety Regulations 2012
The demand capacity as detailed in the Offer for Supply which was accepted
by the customer. This is the maximum demand capacity that the Service
Authorised Protection Device, Consumer Terminals and upstream Distribution System
Service Capacity have been designed to provide for. When a customer requests a reduction to
their Agreed Maximum Demand the new Agreed Maximum Demand will
become the Authorised Service Capacity.
Community Lot Is a separately owned Lot within a Community Title Scheme.
Is the division of land into at least two lots and generally an area of common
property. The Community Title Act provides for implied easements within a
Community
Community Title development. These implied easements only relate to
Title Scheme
private service infrastructure and do not apply to infrastructure that is owned
by SA Power Networks.
Property within a Community Title Scheme that is owned by the community
corporation. The community corporation is comprised of all lot owners within
Common the Community Title Scheme. Common property relates to those parts that
Property do not form part of a lot and typically includes the land for the service
infrastructure and driveways that are shared. Roads within Community Title
Schemes are generally common property.
A connection point to a transmission or distribution network. For the purpose
Connection
of this document connection point also has the same meaning as Point of
Point
Supply as defined in AS/NZS 3000.
Are the electrical conductors, owned and maintained by the customer,
Consumer
connecting the point of supply and the main switchboard and form part of
Mains
the customers installation.
The junction at which the consumer mains connect to the SA Power Networks
Consumer
service cable or main supply conductors. Refer to Clause 6.3 (Consumer
Terminals
Terminals).
A meter where electricity flow is measured by a meter using current
CT Metering transformers (CTs). Note: CT meters are used where the maximum demand
of the installation is more than 100 amps.
Customer agents are parties representing the customers. Such parties may
Customer
include registered electrical workers, licensed electrical contractors,
Agent/s
consulting engineers, architects, and equipment manufacturers.
Distributor A person who holds a Distribution Licence, or who is exempted from holding
a licence of the Electricity Act.
A Distributor is also known as the Local Network Service Provider (LNSP).
For the purpose of this document SA Power Networks is the Distributor.
The whole or a part of a system for the distribution of electricity, but does
not include anything declared by regulation not to be a distribution network
or part of a distribution network. For the purposes of these rules references
Distribution
to Distribution Network means the network poles, wires, underground
Network
cables, transformers, substations etc, operated by SA Power Networks,
which transports electricity from the transmission system to a customers
Connection Point.
Determined The electrical demand, both instantaneous and sustained load, in kVA or
Maximum amps required from the Distributors supply system as assessed by the
Demand Responsible SA Power Networks Officer.
Distribution A licence authorising the operation of a distribution network, granted under
Licence the Electricity Act 1996.
A property that has a frontage on two independent boundaries, one of
Dual Fronted
which is the street address and the other being another public area. Note:
Property
does not apply to corner properties.
Electricity
The Electricity Distribution Code administered by the Essential Services
Distribution
Commission of SA.
Code
A set of wires and associated fittings, equipment and accessories installed in
a place for the conveyance, control, measurement and/or use of electricity
that is, or is to be, or has been, supplied for consumption in the place, but
Electrical does not include:
Installation Electricity infrastructure owned or operated by an electricity entity
Any wires, fittings, equipment or accessories connected to and beyond any
electrical outlet at which fixed wiring terminates (other than any such
outlet used to connect sections of fixed wiring).
Embedded A generator such as solar PV, wind or battery storage that is owned,
Generating operated or controlled by a customer and is connected to the customers
Unit electrical installation.
Licensed A contractor licensed to perform electrical work under the Plumbers, Gas
Contractor Fitters and Electricians Act 1995.
A circuit breaker that isolates the supply to the metering equipment
Meter
(including CTs where installed) and the corresponding installation or
Isolator
tenancy.
Meter Is a person registered with AEMO who provides and maintains metering
Provider installations in accordance with the National Electricity Rules requirements.
Is metering instruments and associated fuses, links, transformers and wiring
Metering installed by a Meter Provider at the Metering Point as required by the
National Electricity Rules.
Metering A person registered by AEMO who engages in the coordination and
Coordinator provision of metering services at the connection point.
Metering Is the physical and electrical location at which metering equipment is
Point connected.
MNSP Manager Network Standards & Performance.
Must Is to be understood as mandatory.
NATA National Association of Testing Authorities
NER National Electricity Rules.
Issued August 2017 Page 18 of 149
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2017
Service & Installation Rules
Requested The maximum demand that the Customer or their agent have requested to
Maximum be provided (as determined under AS/NZS3000 or by other method).
Demand
Retailer A holder of a licence under the South Australian Electricity Act, 1996
authorised to retail electricity.
Torrens Title A Torrens Title land division is a division of land into at least two allotments,
which are held / owned independently of one another. A Torrens Title land
division requires that each new allotment has frontage to a public road or
adequate access to a public road. There are generally no shared facilities or
infrastructure as each allotment must have its own infrastructure
arrangements in place.
UG Underground Service
Underground
The electricity distributors supply network to the point of supply.
Service
Un-metered An authorised supply that is not metered.
Supply
Whole Current A meter where the electricity flow is directly measured by the meter ie the
Meter current under measurement passes through the meter itself.
Note: Whole current meters are generally used where the maximum
demand of the installation is less than 100Amps.
2. Introduction
2.1 Objective
The objective of these Rules is to provide South Australian electricity customers, registered
electrical workers and other people in the industry with the technical requirements for electrical
installations connected to the SA Power Networks distribution network. Customers electrical
installations must comply with the Wiring Rules in AS/NZS 3000 as they apply from time to time.
2.2 Scope
These Service and Installation Rules apply to new installations, alterations or additions to existing
installations that are or are intended to be connected to the SA Power Networks distribution
network.
It is not intended to apply any additional requirements to installations that were compliant at the
time of the original installation and are not being altered. For the purpose of these Rules, a
relocatable premise is considered a new installation when it is relocated.
This document is designed to assist users by detailing:
the method and type of supply from the SA Power Networks distribution network
the requirements for customer electrical installations connected to SA Power Networks
distribution network
some of the customers obligations relating to that supply
Additional requirements may be contained in the Electricity Distribution Code, Connection and
Supply Contract and the Electricity Metering Code, copies of which are available on SA Power
Networks internet site or from SA Power Networks on request.
There may be situations the Rules do not cover. This may include unusual connections, and
alterations to legislation and codes. SA Power Networks must be consulted where these situations
are encountered.
Where an electrical installation consists of an embedded network (as defined in the (SA)
Electricity Metering Code) the requirements of these Rules apply to the operator of the
embedded network (parent) and their electrical installation.
An embedded network child customer (sub-metered) must liaise with the operator of the
embedded network for conditions relating to their supply.
SA Power Networks has no obligation, responsibility or involvement with the embedded network
child customer except as noted below.
Note: These Rules are not intended for application to off-grid networks. Conditions relating to
these off-grid networks should be sought from the appropriate operator.
2.3 Innovation
These Rules do not preclude other methods, innovation, or technology that achieves the same
outcomes as the specifications detailed in this document. Any such proposal should be put to SA
Power Networks Manager Network Standards & Performance (MNSP) for acceptance during
concept/design phase and prior to commencement of work.
2.4.2 Publication
The latest version is currently available on SA Power Networks website.
2.4.3 Revision
SA Power Networks reserves the right to revise this publication. Although changes to
regulations are usually the catalyst for revision, users and interested parties are invited
to provide written comment and suggestions to assist further development of the Rules
at any time.
Correspondence for this purpose should be forwarded to the SA Power Networks MNSP.
Any approved written submissions will be incorporated in the annual review of this
document and subject to Technical Regulator approval.
2.5 Service & Installation Rules Management Contact
Contact for any matters related to the content of these Rules may be made through written
correspondence to the SA Power Networks MNSP or website (www.sapowernetworks.com.au).
Any enquiries relating to a specific installation are to be directed to the SA Power Networks
Responsible Officer assigned to the specific project.
If specific installation is not assigned to a Responsible Officer, then direct enquiry to the Builders
and Contractors Line.
2.6 Dispute Resolution
Where a customer has a complaint involving these Rules, they should firstly contact the SA Power
Networks Responsible Officer and register their concern.
If not resolved, the complaint may be referred to a higher level person than the SA Power
Networks Responsible Officer within the management structure.
Where this does not result in a resolution, the complaint will be resolved in accordance with the
SA Power Networks Customer Complaint & Inquiries Procedure.
2.7 Application Responsibilities
These Rules are applicable from 7th August 2017. As per Regulation 12, work on an electrical
installation completed within 6 months of the publication of this version of these Rules may be
carried out in accordance with the previous version of the Service and Installation Rules.
Transitional arrangements or exemptions may be able to be made with SA Power Networks where
it is deemed necessary to do so.
Meter Providers are responsible for compliance with the metering requirements contained within
these Rules. Up until, and including the 30 November 2017, the metering requirements are to be
carried out in accordance to the previous version of the Service and Installation Rule, which is
available on SA Power Networks website.
Each customer has an initial and ongoing responsibility to ensure their electrical installation
complies with these Rules and AS/NZS 3000 when carrying out any alterations, additions and
repairs and any other conditions for supply. This is normally accomplished through their agents,
eg their Registered Electrical Worker or Licensed Electrical Contractor. Refer to Section 5 for
complete details on Supply Applications.
2.8 Failure to Comply with these Rules
Should an installation not satisfy the requirements of these Rules, connection of electricity supply
may be delayed or withheld, and installations with supply may be disconnected until such time as
the non-compliance/s has been rectified.
A fee will be charged where a failure to comply with these Rules occurs and in the Responsible
Officers opinion a subsequent attendance is required to verify that the non-compliances within
these Rules have been rectified.
Refer to SA Power Networks website for current fees.
2.9 Exceptional Circumstances
In exceptional circumstances, the stated requirements contained in these Rules may be waived or
modified by submission of a written request.
The written request shall be accompanied by:
a detailed statement of the reasons why non-compliance with these Rules is sought; and
a Statement of Consent from the owner or controlling body of the installation.
No action should be taken until a written reply to such a request has been received.
Any request in this regard shall be addressed to: Manager Network Standards & Performance, SA
Power Networks, GPO Box 77, Adelaide 5001.
Where SA Power Networks agrees to a variation to the requirements of these Rules, a copy of SA
Power Networks written acceptance to the variation must be provided to the Connecting Officer
with the valid ECC at the time of connection.
2.10 Offences
The Electricity Act 1996 and Electricity (General) Regulations 2012, codes and guidelines enacted
under those and other legislation include regulations for protection of Distributor assets and
qualification of persons who may work on those assets. Offences under these regulations include:
1. Any work on SA Power Networks network assets unless authorised by SA Power Networks.
2. The damage or interference of any SA Power Networks assets such as:
fuse link removal
break a seal or lock
dismantle or detach any SA Power Networks cables or equipment
interference with electricity meters, time switches, equipment and/or service cables
obtaining electricity by fraud
3. Unauthorised entry of SA Power Networks assets eg substations and infrastructure.
If a person is found guilty of an offence, it could result in the imposition of substantial fines
together with an order for damages to compensate SA Power Networks for any loss and court
costs. It may also cause that person to have a criminal record.
2.11 Necessity for Employing a Licensed Person
The Plumbers, Gas Fitters and Electricians Act 1995 requires that all electrical work carried out on
electrical installations connected to or intended to be connected to the SA Power Networks
distribution network, subject to certain exemptions, will be performed by a registered Electrical
Worker(s) who is suitably licensed for such work in South Australia.
2.12 Basic Industry Relationship
This section is intended to provide an understanding of the basic relationships of industry
stakeholders, (regulators and distributor, retailers, meter providers, customer and their agents),
in respect to connection of electrical installations to SA Power Networks distribution network.
Refer to figure 2.1 Stakeholders.
2.12.1 Responsibilities
2.12.1.1 Distributor
Negotiate provision and connection of supply with customers.
Transport and deliver electricity purchased by retailers and sold to customers.
Connect customer electrical installations to SA Power Networks distribution network
and administer technical supply aspects of the connection.
Determine the network tariff to be applied to the installation.
Energise up to the line side of the meter isolator.
Is responsible for matters such as electricity supply quality and reliability.
2.12.1.2 Retailers
Purchase electricity and retail the electricity (transported by Distributors) to
customers.
Nominate rates and arrange customers contract for the purchase of electricity.
Engage a Meter Provider.
Request Distributors to connect or disconnect the customer installations to the
Distributors network in accordance with the customers contract with the Retailer.
2.12.1.3 Customer Agents
Customer agents are parties representing the customers. Such parties may include
registered electrical workers, licensed electrical contractors, consulting engineers,
architects, and equipment manufacturers.
Meter Provider
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 25 of 149
Service & Installation Rules
4. General Rules
4.1 Safety (TIR)
All persons and contractors are responsible for all aspects of safety related to work performed by
those persons and employees. The works should be performed in accordance with all relevant
Acts, Regulations, Codes of Practice, Standards and the Rules within this document that are
related to the safety of the work being performed.
Electrical contractors (including meter providers) are not to connect any wires that form part of
the customers electrical installation to the SA Power Networks network at the connection point.
SA Power Networks will make the final service connection. Where any SA Power Networks
employee discovers that there is an immediate safety risk resulting from:
exposed live electrical parts which pose an immediate threat to safety
a customers meter box is in such a condition as to pose a threat to electrical equipment
integrity and safety
a customers structure interferes with access to the SA Power Networks service point and
would also pose a threat to SA Power Networks personnel in performing their service delivery
to customers safely
a customers structure reduces the prescribed safety clearances detailed in Regulation 10,
Schedule 1 of the Electricity (General) Regulations 2012 under the Electricity Act 1996
The employee will arrange to have the supply to the customers premise de-energised to make
the installation safe. In these situations, where possible, the customer at the premise will be
notified immediately. Written notification of the disconnection will be left at the premise when a
customer is not in attendance at the premise.
4.2 Compliance with Regulations, Codes of Practice and these Rules (TIR)
Any connection or reconnection to SA Power Networks distribution network is required to comply
with the Electricity Act 1996 and the Electricity (General) Regulations 2012, all codes and any
other relevant legislation or guidelines.
4.2.1 Electrical Installations (TIR)
The above clause 4.2 applies to the following electrical installations:
New installations;
Alteration to existing installations as prescribed in AS/NZS 3000;
Addition to existing installations as prescribed in AS/NZS 3000; or
Special electrical installations.
4.2.2 Building & Structural Clearances (TIR)
The above clause 4.2 applies to buildings and structures constructed in the vicinity of:
Service pits/pillars where a minimum clearance of 1.2m is required as per Figure 4.1.
Aerial lines where for clarification, the relevant SA Power Networks Manager is to be
contacted in relation to the specific voltage level of the aerial line and the OTR is to
be contacted in relation to specific clearance details.
Padmounted transformers and switching cubicles, refer to NICC-802 Padmount
Transformer Brochure, and TS102 Easement Standard for Distribution Networks.
Both these documents are available on the SA Power Networks website.
1.2m
CM
Customer Lock Refer supplier
ie. Master Locksmith
Medium Security
or electrical
Customer enclosures such as
wholesaler. 5 Pin
provides lock. Switch rooms, Gates,
tumbler mechanism,
etc.
diam. 30mm & depth
28mm.
CM
Customer Pad Lock
Refer supplier
Customer ie. Master Locksmith Locking of personal
provides lock. or electrical access gates.
wholesaler.
Table 4.1 Customer Supplied SA Power Networks Master Key System Locks
Locking of HV switchgear
SA Power
and earthing switches.
Networks
Used by SA Power
provides lock.
Networks personnel only.
A = 170mm
B = 50mm
C = 120mm
D = Dia. 10mm
D
SA Power Networks Meter
readers lock
C
A
SA Power Locking of LV meter
Networks isolators by SA Power
B
provides lock. Networks personnel.
A = 132mm
B = 45mm
C = 87mm
D = Dia. 5mm
Table 4.2 SA Power Networks Supplied SA Power Networks Master Key System Locks
Greater than 10m and less than 50m from Supply Transformer
Table 6.2 shows the prospective fault current (kA) applicable to installations with a 63A
service. Testing may indicate a lower fault current, therefore an appropriate size
protection device may be used.
These maximum prospective phase to earth bolted fault currents are expected to occur
on the load side of the consumer mains for commonly used cable sizes when the
customers connection point is greater than 10m and less than 50m from the supply
transformer.
Total Consumer Mains Size (mm2 Copper)
Mains Length 6 10 16 25 35 50 70 95
0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
5m 8.1 8.8 9.2 9.5 9.6 9.7 9.7 9.8
10m 6.3 7.6 8.5 9.0 9.2 9.4 9.5 9.6
15m 5.0 6.6 7.7 8.5 8.8 9.0 9.2 9.4
20m 4.2 5.7 7.0 8.0 8.4 8.7 9.0 9.2
25m 3.5 5.0 6.4 7.5 8.1 8.4 8.8 9.0
50m 2.0 3.0 4.3 5.6 6.4 7.1 7.7 8.1
100m 1.0 1.7 2.5 3.6 4.4 5.2 6.1 6.7
200m 0.5 0.9 1.3 2.0 2.6 3.3 4.1 4.8
Table 6.2 Prospective Fault Current (kA) for 63A service between 10 and 50m from supply transformer (Non TIR)
In residential environments where the installation requires a service greater than 63A,
please consult the relevant SA Power Networks Manager.
Commercial / Industrial Environment Installations
Where a customer is supplied direct from a transformer greater than 315kVA, consult
the relevant SA Power Networks Manager.
1 Phase, 3 Wire 230/460 Volt System (SWER, Rural or some Underground Residential
Distribution Networks)
A three-phase service is not available to customers supplied via a single phase 230/460
Volt system. The number of phases (up to a maximum of two) will be based on the
service capacity required as specified in Table 6.5.
Note:
Where a 4 core cable is used to connect an installation as a 3 wire system, then the
unused wire shall be terminated in a suitable connector and labelled at both ends.
total 1.67 %
any individual odd harmonic 1.33 %
any individual even harmonic 0.67 %
Table 6.8
All switchboards associated with the inverter energy system must be clearly and
permanently labelled as having an Inverter Energy System connected to it. The circuit
breaker, fuse or switch must also be clearly labelled.
A label indicating that an alternative power supply system is connected to the
electrical installation shall be fitted at the meter position and main switchboard.
Refer to clause 4.5.
6.6.4.3 Metering (TIR)
Under the Metering Code, a meter with import and export registers is required. This
meter will be provided by the relevant meter provider.
It is recommended that the customer advise their Retailer of this requirement at the
earliest opportunity.
6.6.4.4 Standard Networks Connection Agreement (TIR)
SA Power Networks can only agree to provide connection services for an Inverter Energy
System to its distribution network in accordance with the terms and conditions of an
approved standard connection agreement.
For a copy of the approved standard connection agreement for Small Embedded
Generator Connection, refer to SA Power Networks website.
6.6.5 Storage Systems
Storage systems such as batteries shall be installed in accordance to the relevant
Australian Standards (ie AS/NZS 4777, AS/NSZ 3000, etc) which are published at the time
of installation. Due consideration shall be given to ventilation, prevention of
unauthorised access and electrical safety.
Padmount Transformer
150kVA Copper cables suitable for loads no greater than 700A. Maximum size
300kVA conductor per phase single fuse disconnect - 2x300mm Cu or 1x500mmCu.
500kVA
750kVA Copper cables suitable for loads no greater than 1,000A and 1,400A. Maximum
1.0MVA size conductor per phase 4x500mm Cu 1,250A Fuse Disconnect.
1.5MVA Copper cables suitable for loads no greater than 3,000A. Maximum size
2.0MVA conductor per phase - 6x500mm Cu.
Table 7.2 Maximum Size of Customer Cables
Notes:
1. By prior arrangement, aluminium cables of the same number and dimensions are acceptable
provided the required bi-metal lugs are provided and installed.
2. Where non-compliant cables are installed, they shall be converted to compliant cables prior to
being connected to SA Power Networks equipment.
3. SA Power Networks must be consulted where the suitability of proposed connection facilities is in
doubt.
Where consumer mains enter into an SA Power Networks transformer vault, they must
enter through the aperture or ducting system provided for consumer mains as shown in
the SA Power Networks Transformer Brochure (NICC-802).
It is recommended that a seal is installed to prevent the transmission of liquids, termites
and vermin through the conduit or duct that is the entry into SA Power Networks
transformer vault.
(The ends of the cable not connected must be protected by the equivalent of double
insulation to prevent inadvertent contact with live conductors within the transformer
vault). For further details, refer to the relevant SA Power Networks Manager.
7.2.2.4 Terminals of an Open Bushing Transformer
The relevant SA Power Networks Manager will provide advice to the method of
connection to the LV bushings of the transformer.
7.3 Overhead Distribution Network Areas
In general, the service connection point will be of a type as detailed below, however, due to
circumstances in some localities or due to the nature of the customers load, an underground
supply arrangement may be provided.
SA Power Networks shall be contacted where any clarification is required. The supply shall be
placed underground where the required clearances and all other provisions of these Rules cannot
be achieved or are not maintained.
In overhead distribution areas, the SA Power Networks Manager will nominate a standard service
configuration as indicated in Table 7.4.
Once nominated, all remaining options shown in column 3 of Tables 7.3 and 7.4 become
alternative configurations.
Alternate Connection
Service Capacity Required Standard Connection Configuration
Configuration
Over/under service on a Stobie Overhead 25mm2 Aluminium
Not exceeding 63A per
Pole; or ABC service; or
phase
An existing service pit / pillar new service pit.
Exceeding 63A per phase 100A over under on a pole New service pit
200A over/under service on pole; or
Exceeding 100A per phase 200A isolators on pole, or None
200A service pit / pillar
With agreement of SA Power Networks
Manager
Overhead transformer
Exceeding 200A per phase
Padmount transformer
Service fuse enclosure
Service pit / pillar
Table 7.4
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 68 of 149
Service & Installation Rules
The minimum height of the service conductors above ground level (including the entry
point into the service fuse box) must not be less than 2.7m at any point along the
conductor.
The service fuse box must not be mounted more than 4m above the surrounding ground
level. All service lines must be more than 600mm from overhead telephone, cable
television or other services, if present.
The point of attachment must be capable of supporting the mechanical force that will be
placed upon it by the overhead cable(s). For all services, the mechanical force may be up
to 1kN along the service lines at the point of attachment. (Refer to clause 7.3.6 for
service bracket specifications).
Where a customer requests an overhead line to a customers support pole, (ie free
standing meter enclosure or temporary builders supply) it is the customers
responsibility for providing a pole of adequate strength and height for mounting SA
Power Networks overhead equipment. This pole shall be identified with a permanent
tag (eg metal) stamped with Private Pole. The customers support pole must comply
with the requirements of AS/NZS 3000.
For further details, refer to Figure 7.4.
The customer is responsible for providing and maintaining all consumer mains and
equipment from the point of supply to the customers main switchboard.
For further details, refer to Figure 7.6.
Overhead Lines
At the load side terminals of the service fuse, mounted on the fascia or faade of the
customers building or structure.
Isolators on Pole
At the load side terminals of the LV isolator, on a pole nominated by the relevant SA
Power Networks Manager on or adjacent the property where supply is requested.
Service Pit/Pillar
At the terminals or block inside the LV service pit/pillar nominated by the relevant SA
Power Networks Manager on or adjacent to the property where supply is requested or
from the nearest service pit if Council agrees to the installation of consumer mains in
the road reserve.
Terminals of a Pad Mounted Transformer
At the LV terminals of the LV transformer fuses or LV isolators inside the LV
compartment of a pad mounted transformer nominated by the relevant SA Power
Networks Manager on or adjacent to the property where supply is requested.
Service Fuse Enclosure within 10m of the Boundary
At the load side terminals of the service fuse nominated by the relevant SA Power
Networks Manager.
7.3.5 Point of Attachment
7.3.5.1 Overhead Distribution Network
The Electricity Act 1996 and Electricity (General) Regulations 2012 regulate
requirements for poles and posts including supports and structures used to support SA
Power Networks aerial lines.
All supports for service brackets used to support aerial conductors are required to
comply with the Act and Regulations. AS/NZS 3000 deals with the requirements of the
customers installation.
The point of attachment, whether it be a structure, an extension or strut attached to a
building or structure, or a private pole must be of sufficient strength to support the
specified service bracket load applied by the service cable as detailed in clause 7.3.7.3(c)
(Strength Rating).
The point of attachment of an aerial service cable to a customers electrical installation:
Shall be selected in accordance with this clause and the details provided in Figures
7.2 and 7.3.
Shall be not less than 2.7m or higher than 4.0m from the ground.
Will not be installed above verandas, carports and roofs.
Must be located to limit the length of service line to 20m. Refer Figure 7.7.
The service line route needs to consider site use ie private roadways carrying
commercial vehicles, site access and additional minimum height requirements in
accordance with Electricity (General) Regulations 2012.
Shall be located on the foremost portion of any structure facing the pole or point
where the aerial service line originates, and in a position where the service lines can
achieve and maintain all clearances unless a more appropriate location is available.
SA Power Networks shall be consulted where:
The customers maximum demand is greater than 63A on a single phase basis
The customers support pole must comply with the requirements of AS/NZS 3000 and an
Electrical Certificate of Compliance, validly completed is required before a connection
will be made. Refer to Figure 7.4
The point of attachment on a customer support pole shall be located to achieve or
exceed the required clearances and all other requirements of these Rules.
7.3.5.3 Transformers
For the requirements relating to transformers or other SA Power Networks equipment
on customer premises, consult the relevant SA Power Networks Manager.
7.3.5.4 Access to Point of Supply
Customers are required to provide unimpeded access to the point of supply at all times.
Overhead Supply Points
For a point of supply attached to a customers structure or a SA Power Networks pole on
a customers property, a clearance area of at least 1.5m in front and 600mm both sides
of the supply point shall be maintained to enable a ladder to be placed to gain
unimpeded, safe access.
The customer must not erect a structure (such as a carport) beneath the point of supply,
or have plants, trees or other obstructions which prevents access to the point of supply
from a location on the ground immediately beneath the point of supply.
Underground Supply Points
The customer is required to keep access to service pillars (or pits) installed on the
customers premises free from obstruction caused by fences or the like and maintain the
appropriate ground level around the pillar/pit and over service lines and consumer
mains. Refer Figure 7.8
1m
1m
1m
Service
Pit/Pillar 1m
Road Reserve
Property Boundary
Required operating work zone
Figure 7.8 Service Pit Work Zone
No metal parts of the service bracket shall enter the service fuse enclosure.
7.3.6.2 Provision
The customer shall provide, install and maintain a service bracket that complies with
these Rules at the point of attachment for the attachment of the service line.
7.3.6.3 Specification, Acceptance and Installation
Service Bracket
For the purpose of this specification, there are two types of service brackets:
(i) Standard Service Bracket
A standard service bracket, which is supplied by SA Power Networks, is defined as
a bracket attached to a building or structure to provide a point of attachment for
the service line at the point where the bracket is fixed.
Refer to Figures 7.2 and 7.3.
Corrosion Resistance
The corrosion resistance of all components of a service bracket shall be not less than
that provided by galvanising in accordance with Australian Standard 4689 Hot Dipped
Galvanised (Zinc) Coatings on Fabricated Ferrous Articles; Australian Standard 4791 Hot
Dipped Galvanised (Zinc) Coatings on Open Section Ferrous Articles; Australian Standard
4792 Hot Dipped Galvanised (Zinc) Coatings on Hollow Section Ferrous Articles; and
Australian Standard 1214-1983 Hot-Dip Galvanised Coatings for Threaded Fasteners
ISO Metric Coarse Thread Series.
Prevention of Conductor Insulation Damage
There shall be no sharp edges and projections that the service or consumer mains cables
may come in contact with whether on external or internal surfaces. The connection box
mounting plate shall not protrude beyond the edge of the connection box.
The service line bracket shall be constructed and installed in a manner to enable the
service line and equipment to maintain clearance from the connection box and bracket
in situ. All connection box access covers must be able to be removed without the
necessity for the covers to contact the service line or equipment.
Provision for Earthing
Where single insulated consumer mains are installed, the raiser must be earthed in
accordance with the requirements of AS/NZS 3000.
7.3.7 Aerial Service Lines Clearances
7.3.7.1 Existing Service Lines
The customer is responsible to ensure that modifications to the property they occupy do
not breach the minimum clearances from ground, structures, objects, trees and
vegetation to the service lines supplying the property they occupy required by the Rules
and Regulations at the time of the service cables installation and the current Electricity
Act, Legislation and Regulations relating to line vegetation clearance.
7.3.7.2 New and Replacement Service Lines
Unless advised otherwise by SA Power Networks, clearances for new and replaced aerial
service lines initiated by the customer must comply with the requirements of the
following:
These Rules
The Electricity (Principles of Vegetation Clearance) Regulations 2010
The customer is responsible to:
Provide a point of attachment and arrangements on their property to ensure the
clearances and conditions of these Rules, the current Electricity Act and Regulations
are achieved and maintained; and
Ensure that modifications to the property they occupy do not breach the minimum
clearances require by these Rules and the current Electricity Act and Regulations
from ground, structures, objects, trees and vegetation to the service cable supplying
the property.
7.3.7.3 Achievement and Maintenance of Clearances
Where the customer is unable to provide facilities for the aerial service line to meet and
maintain the required clearances within their property in accordance with these Rules,
the property shall be supplied by an underground service at the customers expense.
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 79 of 149
Service & Installation Rules
SA Power Networks will make arrangements with the customer for appropriate
clearances to be met where the aerial service line is to be replaced in circumstances
other than by works initiated by the customer.
If the customer fails to maintain clearances prescribed by Electricity Regulations from
vegetation within their property to the aerial service line supplying the property, SA
Power Networks may clear that vegetation in accordance with the Electricity Act and
Regulations at the customers expense.
The customer shall advise SA Power Networks where alterations to their property may
in any way affect the clearances required for an aerial service line.
In all cases where clearances cant be achieved and maintained, the property shall be
supplied by means of an underground service at the customers cost.
7.3.8 Aerial Service Lines Sag
Aerial service lines will sag after installation due to temperature rise and construction
loadings.
SA Power Networks will make appropriate allowances for this additional sag during the
provision of these service arrangements to maintain clearances in accordance with the
Electricity Act and Regulations.
Customers should make allowances for the maintenance of building and vegetation
clearances as set out in the Electricity Act and Regulations.
7.4 Service Protection
In general, SA Power Networks will provide the service fuses and carriers for the protection of SA
Power Networks service line. Refer to clause 7.4.5.
7.4.1 Customers Protective Equipment (TIR)
The customers protective equipment including the meter isolator must effectively grade
with the SA Power Networks service protection device. Customers are also advised to
install protective equipment to limit possible damage to their electrical installation or
equipment which may be sensitive to voltage variation, transients, loss of one or more
phases of supply or due to leakage current.
Refer to clause 6.5 and the Electricity Distribution Code.
To satisfy the Electricity Distribution Code, customers must control sustained overload,
short circuits, phase loading, power factor, transient current, harmonic current, inrush
current and other negative effects originating within the electrical installation to
minimise adverse effects on other customers and the distribution network.
Compliance with this clause and clause 6.7 will assist control of sustained overload,
short circuits and phase loading arising from electrical installations, and limit adverse
voltage fluctuations on other customers and the distribution network.
Further to the above, the customer must ensure that the installation is kept within the
required limits.
7.4.2 Application of SA Power Networks Protection Devices TIR)
7.4.2.1 Enclosures (TIR)
Enclosures containing SA Power Networks protective devices must have sufficient
stability and strength to withstand distortion and contain any energy which might be
caused in both normal and fault conditions.
Where the service protective device(s) are to be installed in a metering enclosure, it
shall comply with the requirements of AS/NZS 3000 Wiring Rules. The customer will
provide facilities for the securing of the incoming consumer mains conductor(s) to
the panel.
Metal enclosures which contain SA Power Networks service protection equipment
must be neutralised or earthed in accordance with AS/NZS 3000 Wiring Rules.
In general, SA Power Networks metal enclosures containing service protection
equipment shall be earthed by a conductor, with a cross sectional area not less than the
consumer mains neutral conductor, connected to the main neutral conductor or bar.
The termination shall be labelled Unprotected Mains Bonding Conductor.
7.4.2.2 Access (TIR)
Where the customer is required to make provisions for the service protection devices,
the position provided shall be free of obstruction and access must be continuously
available for SA Power Networks to safely operate on the device or devices at all hours.
7.4.2.3 Location (TIR)
Enclosures containing the SA Power Networks service protection equipment must be
located in an exterior location that is accessible at all times.
The enclosure must be a minimum of 0.3m above the finished ground level and no
greater than 4.0m to the top of the enclosure.
Where the location is greater than 2.0m in height, then the clearance for ladder access
as stated in 7.3.6.2 is applicable.
7.4.2.4 Common Enclosure (TIR)
The electrical wiring associated with service protection devices installed in a common
enclosure with other electrical installation control or protective equipment shall be
segregated by barriers from that associated with such other equipment.
7.4.3 Security
7.4.3.1 General
Service protection devices should be located and arranged to limit the ability of
unauthorised persons to interfere with and operate the device(s).
An acceptable method to restrict unauthorised interference is to locate device(s) other
than those associated with an overhead line mains within an enclosure fitted with a lock
in accordance with clause 4.7.
7.4.3.2 SA Power Networks Operation
Where a separate enclosure is provided for the service fuse protection, the enclosure
shall be secured by means of a lock. The locking facility shall be capable of accepting an
SA Power Networks service fuse enclosure lock. Refer to clause 4.7.
Where the service fuses are installed within a meter enclosure, the customer may elect
to lock the enclosure with a ES or CM lock as shown in clause 4.7.
Subject to the agreement of the Responsible Officer, other methods of security may be
acceptable. Such other methods may include location of the device in an area restricted
to authorised persons and locking with a lock in accordance with clause 4.7.
Persons interfering with SA Power Networks seals or locks or operating service
protection devices other than in accordance with the conditions of these Rules may be
subject to action, including legal action.
Approval will only be given for the following service fuse arrangements where Service
rated at or below 100Amps:
Overhead service mounted on a building in good condition (excludes damaged or
open wire services) and must be in an accessible location that complies with the
required clearances.
Over/under service fuse box arrangement on a pole.
Service fuse mounted on a meter panel.
Multiple customers will require the appropriate notification.
Note: It is the responsibility of the Electrical Worker/Contractor to ensure that they are
appropriately qualified and trained with a relevant Safe Work Method Statements.
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 82 of 149
TS 100: Electrical Design Standards for Underground Distribution Cable Networks (up to and including 33kV)
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 83 of 149
Service & Installation Rules
4m
Figure 7.9
Refer also to 8.5.9 for unsuitable metering locations. The main switchboard cannot be
within 4m of the transformer to ensure a 4m separation between the transformers HV
earthing and the MSBs LV earthing. The MSB doors should open away from the
transformer to reduce the risk of shock from step touch potential.
If the transformer is located within a CMEN area, the main switchboard may be closer
than 4m provided a non-conductive wall or barrier is present to prevent step touch
potential.
The circuit breaker which is used in place of a low voltage service protection device
shall:
have, or be installed with, a facility for preventing the handle to be operated when in
the off position by an SA Power Networks padlock as defined in clause 4.7;
have access to any adjustable settings capable of being restricted to authorised
persons by sealing or equivalent means;
have all live terminals and connections enclose;
will not have an auto reclosing facility;
if installed as a combined supply protection/load control device, the circuit breaker
shall operate so as to prevent the authorised service capacity being exceeded if
installed to control supply capacity in accordance with clause 6.7.1.2;
if it is required by other standards that the essential services supply bypasses the
main service protection device, those circuits must be individually protected at the
main switchboard.
The circuit breaker required by this clause shall:
comply to AS/NZS 3947.2:2002; and
have an instantaneous tripping characteristic settable between 2xIN and 10xIN; and
ensure grading, with the upstream (SA Power Networks) and downstream
(customers) protective devices; and
have a rated short circuit current capacity equal to or greater than the prospective
short circuit current at the point it is installed; and
where the current carrying capacity of the neutral is less than that of the associated
active conductors, then the circuit breaker shall have earth fault protection capable
of preventing over-current in the neutral conductor. (See Note).
Short circuit ratings and SA Power Networks protection characteristics are available
from the relevant SA Power Networks Manager.
Issued August 2017 Page 84 of 149
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2017
Service & Installation Rules
Note:
1. It is suggested that the use of a circuit breaker that does not break the neutral with
current settings to trip at neutral current greater than maximum out of balance
current and less than neutral conductor current carrying capacity will satisfy the
earth fault required.
7.4.6 Acceptable Applications
7.4.6.1 Underground Supply
This clause covers the service protection requirements where supply is provided from an
underground service line or unfused service pit.
A customer shall supply an enclosure to accommodate the service protection devices.
The enclosure shall be installed at ground operating level at a minimum height of 0.3m
and in a position free of obstruction and where access is readily available for:
manual operation of the service protection device(s) from ground level; and
safe work on the service protection device(s).
Alternatively, for enclosures rated at 200A or less, the enclosure may be installed in a
location accessible by a service ladder and in all cases, the top of the enclosure must be
no greater than 4m from ground level.
All locks required to be operated to gain access to the service protection devices will be
the type approved by SA Power Networks. Refer to clause 4.7.
The enclosure must:
have sufficient stability and strength to withstand distortion and contain any energy
which might be caused in both normal and fault conditions;
be neutralised or earthed in accordance with A/NZS 3000 where the enclosure is
metallic.
In general, metal enclosures containing service protection equipment shall be earthed
by a conductor, with a cross sectional area not less than the customers main neutral
conductor, connected to the main neutral conductor or bar.
Where the service protection device(s) are to be installed in a metering enclosure, it
shall comply with the requirements of AS/NZS 3000. The customer will provide facilities
for the securing of the incoming consumer mains active conductor(s) to the panel.
7.4.6.2 Overhead Supply
7.4.6.2.1 General
This clause covers supply from an aerial service line.
The customer shall provide mounting facilities for the enclosure of the SA
Power Networks service protection device.
The facility shall be located in a position free of obstruction and where
access is readily available for:
1. manual operation of device(s) from a service ladder and in all cases, the
top of the enclosure must be no greater than 4m and no less than 2.7m
from ground level; and
2. safe access to work on the device(s) in accordance with clause 7.3
(Overhead Distribution Network Areas).
7.4.6.2.2 Supply to Customer Support Poles
SA Power Networks services can be attached to the customers support
pole in accordance with clause 7.3.6.7 and 7.4.6.2.2. Refer to Figure 7.4.
shall be provided with facilities for locking it in both the on (closed) and off (open)
positions.
Except where safety services exist, for all single and multiple residential installations, the
meter isolator shall be regarded as the main switch and shall be marked accordingly.
Consequently, the enclosure housing this device becomes the main switchboard and the
MEN connection shall be made within that enclosure. Refer to AS/NZS 3000 clauses
2.3.3 and 2.3.4 and their associated sub-clauses.
7.5.1.3 Rating (TIR)
The rating of the circuit breaker for the meter it isolates must be sized or adjusted as
close as practical to the maximum demand specified in the connection agreement
between the customer and SA Power Networks.
The meter isolator will be required to grade with the SA Power Networks service
protection device. Refer to clause 7.4.5.1.1 and Appendix 2 for SA Power Networks
service fuse characteristics. Where approved motor starting prevents effective grading
with SA Power Networks service fuse, then the meter isolator circuit breaker may be
selected for effective grading for sustained overload protection characteristics only.
When selecting a suitable circuit breaker, consideration should be given to the
environment in which it is to be installed (ie high ambient temperatures may affect
some circuit breakers performance).
7.5.1.4 Application (TIR)
The requirement to install a meter isolator applies:
to all new installations including Whole Current (WC), Current Transformer (CT) and
High Voltage (HV);
to existing installations where an alteration and/or upgrade has, or is being
undertaken, including:
change of whole current meter via the Retailer that requires disconnection and
reconnection to SA Power Networks distribution network;
where an additional tenancy is added;
where attendance is required to change metering where the maximum demand
has changed;
where the meter enclosure or meter panel is replaced;
where the consumer mains are upgraded due to the installations maximum
demand being increased or intended to be increased;
an additional tariff is requested (eg feed-in tariff due to PV installation) and a
meter change is required;
where the meter location is changes; or
where the metering is changed from a CT to a WC or vice versa.
Notwithstanding the above, a meter isolator is not required to be installed on existing
installations in the following situations:
a change in tariff is requested and no metering change is required;
a change in tariff is requested and no electrical work has been conducted on the
consumer mains or main switchboard that will or would have required disconnection
from SA Power Networks distribution system;
a CT or HV meter is changed at the customers request and there is no change to the
consumer mains, meter location, the authorised capacity, or the current/voltage
transformer ratio;
Issued August 2017 Page 88 of 149
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2017
Service & Installation Rules
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 90 of 149
Service & Installation Rules
Note that damage to a high voltage earthing system can cause an extremely hazardous
situation.
7.6.4 Poles and Aerial Lines (TIR)
Any works carried out by a customer or a customers agent in the vicinity of overhead
lines or poles shall be carried out in accordance with 7.6.1 and the Electricity Act 1996
and Electricity (General) Regulations 2012.
Unless specifically authorised by the relevant SA Power Networks Manager, the
customers:
underground wiring; or
wiring embedded in a concrete floor; or
structural metalwork or metallic cladding which is in contact with the electrical
installation including switchboards and metering enclosures
must not be located within 4.0m of a steel pole supporting SA Power Networks HV
distribution network, or a transformers HV earthing system. Consumer mains can be
installed within this zone subject to all other requirements of sub-section 7.6.
7.6.5 Service Pits/Pillars (TIR)
Any cables within a service pit/pillar shall be treated as ALIVE and shall not be handled
without taking appropriate safety precautions. Access to service pits/pillars is only
available via a Network Access Permit.
7.6.6 Supply Isolation (TIR)
SA Power Networks shall be contacted at the earliest opportunity to isolate supply
where required to enable work to be performed safely. Refer to SA Power Networks
website for further details in relation to Network Access Procedure.
Figure 7.10 Underground Consumer Mains Entry with and without gas meter
Figure 7.11 Protected Consumer Mains Entry with and without gas meter
required for metal armoured cable, metal sheathed cable, neutral screened cable or
where other types of cables or conductors are readily open to view or located in
normally inaccessible places or underground.
Metal and non-flexible enclosures, sheathing or armouring of the consumer mains
must not be joined rigidly to SA Power Networks service protection enclosures.
The connection of any wiring enclosure to SA Power Networks service protection
enclosure must be through adaptors etc that will enable convenient replacement of
the service protection enclosure.
For all overhead services, the minimum requirement is:
Neutral Screen cable, or
wiring systems in:
UV stabilised flexible conduit; or
UV stabilised Black Nylon corrugated conduit.
For over/under services, the minimum requirement is:
UV stabilised flexible conduit; or
UV stabilised Black Nylon corrugated conduit.
It is recommended that precautions be taken to avoid moisture entering the building
via consumer mains enclosure.
The requirements of other authorities for use of a common trench including
clearances and minimum depth are to be met.
Armoured cables, mineral insulated metal-sheathed cables, neutral screened cables and
metallic piping must not enter into SA Power Networks service pit/pillar.
7.7.9 Connections (TIR)
7.7.9.1 Pit/Pillar Connections (TIR)
Consumer mains to be terminated in service pits shall be prepared and installed by the
customers agent in accordance with clause 7.7.3.
It is the responsibility of the contractor to ensure that the conductor or lugs used are
compatible with the connection point terminals.
For installations with a maximum demand of less than 100A, stranded copper
conductors with a cross sectional area between 6mm2 and 35mm2 as single conductors
per phase or neutral will be suitable. Flexible cables must have ferrules installed. Refer
clause 7.1.3 for compatibility details.
For installations with multiple cables per phase, only one cable per phase or neutral is to
enter the pit.
The consumer mains cables for each electrical installation that are supplied from any
pit/pillar shall be identified with a permanent water resistant label at ground level and
left neatly coiled within the pit. The label shall be a minimum of 400mm from the cut
end of the tail provided for the connection.
The label shall be permanently marked specifying the lot or street number of the
premises it supplies or for street lighting, the location, direction and number of lights on
the circuit.
7.7.9.2 Termination on a Distribution Pole (TIR)
7.7.9.2.1 Work Practices (TIR)
Termination of consumer mains on a distribution pole must be carried out
in accordance with clause 7.6 and all applicable industry requirements.
Issued August 2017 Page 96 of 149
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2017
Service & Installation Rules
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 100 of 149
Service & Installation Rules
7.8.6 Subdivisions
7.8.6.1 General
A copy of any Plan of Subdivision should be submitted to SA Power Networks during its
planning stage or as soon as a decision is made to proceed.
References that should be considered that may affect the subdivisions design include:
Clause 6.2 and the definition of property and points of supply
Clause 7.3.5 and other Rules such as metering arrangements in Section 8
The Electricity Act and Regulations
Consideration for a Torrens Titles subdivision should include provision of an individual
POS for each residential allotment with the service pillar being located in the standard or
agreed position to ensure the pillar can supply more than one allotment. Refer to
7.7.6.2.
Where an electrical installation is being designed and the development, property or
building is of a type which may be subdivided, the design should be such as to minimise
rectification at the time of sub-division to comply with these Rules.
To assist with a subdivision or potential subdivision electrical design, it is recommended
that an electrical contractor; electrical design consultant or similarly qualified person be
engaged to assist with the design and development of the application.
Applicants should nominate proposed loadings for any proposed lot with a load above
63A and consider existing supply arrangements and the potential necessity for existing
arrangements to be altered where applicable, prior to presenting any submission.
7.8.6.2 No Existing Electrical Installation or Supply
Where there is no electrical installation or supply within the area to be subdivided, the
application should include the proposed lots and the proposed loadings that have been
determined in accordance with clause 7.8.6.1.
7.8.6.3 Existing Electrical Installations or Supply
Where there is an existing electrical installation/s and supply within the area to be
subdivided, the application should include the proposed lots and proposed loadings that
have been determined in accordance with clause 7.8.6.1.
Where an area is subdivided into individual lots and does not contain common property,
the point of supply and consumer terminals must be in accordance with clauses 6.2 and
6.3 and each electrical installations wiring shall not extend outside the property
boundary or common property, except if and where permitted by the Electricity Act,
Regulations and these Rules.
7.8.6.4 Multiple Occupancies
Where a multiple occupancy is to be subdivided and contains common property, the lots
with access to the common property shall be supplied from and arranged such that the
consumer terminals, unmetered switchboards and metering equipment are installed in
common property in accordance with clauses 6.3, 7.8.2, 8.9 and 8.10, and all other
supply arrangements must comply with these Rules.
Where a multiple occupancy is subdivided and does not contain common property, the
point of supply and consumer terminals must be in accordance with clauses 6.2, 6.3 and
all the electrical installations wiring shall not extend outside the property boundary,
except if and where permitted by the Electricity Act, Regulations and these Rules.
8.5 Location
8.5.1 General
The National Electricity Rules requires that metering is installed as close as practicable to
the connection point.
The meter enclosure, in most cases, is the main switchboard and must be readily
accessible to provide efficient and effective isolation of electricity supply from the
electrical installation in emergency situations by persons such as emergency services
personnel.
In addition, meters shall be located in accordance with these Rules to enable safe and
ready access in accordance with clause 8.6 for installing, fixing, reading, testing,
maintenance and removal of metering equipment without difficulty or hazard.
The meter isolator should be located:
in a position as close as practicable to the public entrance to the property or
premises;
in areas to eliminate the necessity to enter secured areas and rooms or areas that are
not normally entered by visitors or available for public access.
Clearances for meter panels shall be in accordance with clause 8.13.1 for Whole Current
Metering and clause 8.14.2.3 for LV Current Transformer Metering.
Any gas meter, fittings, fixtures, enclosures or other obstructions installed below the
metering panel shall not project further than 300mm from the face of the wall on or in
which the metering panel is mounted.
Metering equipment is required to be installed outside hazardous areas defined in
AS/NZ60079.10.2004.
Where a perimeter fence restricts access between the building and the public access
point, the metering equipment shall be:
located to ensure convenient and safe access from the public access side of the
fence; and
installed in a suitable vandal resistant lockable enclosure which is located in a
externally accessible part of the fence, which does not protrude outside the building
line; or
subject to the approval of the Responsible Officer, where an access door or gate is
fitted, a lock shall be installed in accordance with clause 4.7. This lock shall be
accessible from outside the door or gate; or
subject to availability and agreement between the customer and the meter provider
an alternative metering system may be installed by the meter provider. Additional
costs may be incurred in adopting this option.
Legend:
Acceptable Location
Main Entrance
Driveway
Figure 8.1 Suitable Metering Locations for Single Domestic Installation with Single Frontage
Figure 8.2 Suitable Metering Locations for Single Domestic Installation on corner blocks
Figure 8.3 Suitable Metering Locations for Single Domestic Dual Fronted Properties
Figure 8.4 Suitable Metering Locations for Torrens Titles Allotments Main Public Access via Reserve
Figure 8.5 Suitable Metering Locations for Torrens Titles Allotments Main Public Access via Lane
Figure 8.6 Suitable Metering Locations for Single Domestic Installations with High Security Perimeter Fence.
The design and structure of the building are such that the meter box cannot be located
within the 1.5 metres of the corner of the building (eg where windows are installed
within 1.5 metres of the corner of the building).
Figure (2)
Non lockable personal access gate or gate locked with SA Power Networks master key
system.
Figure (3)
The building is constructed up to the Principal Frontage Property Boundary and access
is available along a side walkway on the real property. The meter position should be
accessible to the same extent as the primary dwelling entrance ie between property
entry point and the front door. The building is built to all boundaries thereby eliminating
any access to the meter box except through a low security area.
Figure (4)
Figure 8.8 Suitable Metering Locations for Single Non-residential Installation built to the boundary
Figure 8.10 Multiple units or homes with single supply point eg Community Titled development
Refer to
clause 8.5.4
Figure 8.11 Multiple units or homes with multiple supply points eg Community Titled development.
Figure 8.14 Multi Non Residential Installation with single supply point
Figure 8.15 Multi Non Residential Installation with multiple supply point (Torrens Title)
Figure 8.16 High Density Non Residential Installation with single supply point
Multi-Storey
Refer 8.5.5
A minimum vertical clearance of 2 metres from ground level shall be maintained in this
clearance zone. The removable enclosure door must be capable of moving through an
arc of at least 120o.
8.6.2 Multiple Residential and Commercial Installations
A minimum horizontal clearance of not less than 0.6 metres, from any part of the meter
box or equipment, including doors enclosing the meter board, in any normal position of
opening, must be maintained as shown in the figure below.
Figure 8.19 Meter enclosure clearance for multiple residential and commercial installations
As per the individual residential installations an egress path must be in at least one
direction. This egress path must be at least 750mm wide and 1980mm high.
A minimum vertical clearance of 2 metres from ground level shall be maintained in this
clearance zone.
Issued August 2017 Page 119 of 149
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2017
Service & Installation Rules
8.8.2 Locks
Where locks are considered necessary by the customer or are required by these Rules,
the customer shall arrange for the lock/s in accordance with clause 4.7 to be installed.
Locks shall be used only on doors or gates which provide access to the property and/or
to an enclosure or room housing metering equipment, and shall be accessible from
outside the door or gate.
8.9 Metering Panels, Surrounds & Enclosures (TIR)
8.9.1 General (TIR)
Meter mounting facilities shall be provided:
in an approved metering enclosure with the customers switchboard equipment; or
on an approved surround; or
within or on facilities that are acceptable to SA Power Networks;
that is of a type and in a location, accessible and prepared for the meter installation
in accordance with these Rules.
However, facilities which meet equal or better outcomes than these Rules may be
considered in accordance with clause 2.7. Whole current metering enclosures and
surrounds that are intended to be stocked and marketed by Electrical Wholesalers and
similar distributors are recommended to be accepted for use in accordance with clause
4.4 prior to being manufactured or connected to supply.
All metering panels, enclosures, surrounds and supplementary equipment shall comply
with:
the relevant Australian or IEC Standard/s applicable at the time of manufacture;
the relevant Electricity Regulations, Metering Codes and the Rules applicable at the
time of connection to the electricity supply network; and
be suitable for use in normal service conditions of:
Ambient Air Temperature -
Maximum 45oC
Minimum -5oC
Average 35oC (over 24-hour period)
maximum altitude (above mean seal level) 2000m.
maximum temperature above ambient inside an enclosure 15C
8.9.2 Meter panels (TIR)
8.9.2.1 Size (TIR)
Meter panels shall be of a size to adequately accommodate the metering equipment to
be installed upon it, and be of an equal or greater size than the meter panels dimensions
detailed in these Rules for the metering equipment to be installed subject to the
maximum dimensions detailed in clause 8.13.2 Whole Current Metering Meter
Panels and clause 8.14.2.1 LV CT Metering Panel.
Consideration should be given to a larger size meter panel to accommodate:
extra metering equipment for possible future tariff changes;
extra SA Power Networks equipment such as service fuses;
additional communication equipment as provided by approved meter provider; and
meter isolator - refer Section 7.5.
Issued August 2017 Page 121 of 149
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2017
Service & Installation Rules
Table 8.3: Service Protective Device Panel Space and Drilling Requirements
Height (mm) Width (mm) No. of cable holes
Single Phase 210 55 1 top, 1 bottom
Two Phase 210 110 2 top, 2 bottom
Three Phase 210 165 3 top, 3 bottom
15
210
12
15
55
110
165
8.10 Equipment
8.10.1 Acceptance (TIR)
Refer to clause 4.4 for information regarding equipment acceptance and suitability of
equipment.
8.10.2 On Meter Panels or Within Enclosures (TIR)
Equipment installed on meter panels shall be mounted to allow sufficient space to
accommodate all equipment to be installed upon the panel in a manner which enables
connection, disconnection and reconnection of all wiring and access to all terminals
without dismantling other equipment, or creating a need to remove covers off
equipment other than that being worked upon.
Equipment must be securely fixed to meter panels in accordance with the Wiring Rules.
Fixing screws and fasteners should not protrude through the rear of the panel in a
manner that could damage conductors, or create un-earthed exposed metal.
Customers equipment installed on the metering panel shall not in any way compromise
or affect the integrity, accuracy or performance of the metering equipment.
With the exception of circuit breakers, unscreened magnetic devices such as
transformers shall not be installed on the meter panel.
8.10.3 Security Seals
SA Power Networks and meter providers security seals used in an electrical installation
shall be in accordance with clause 4.8.
8.10.4 Customers Equipment
Customers equipment including devices that consume or measure electricity must not
be connected to the supply side of the metering point.
This does not include metering equipment supplied by SA Power Networks or registered
metering provider or equipment required by 7.4.5.2, 7.8.2.5 and 8.13.3.
8.11 Meter Panel Labelling (TIR)
All labels shall be in accordance with clause 4.5 and shall remain clearly visible after installation of
all equipment.
8.11.1 Single Occupancy (TIR)
Every single occupancy meter panel shall be equipped with a label in accordance with
clause 4.5 displayed on the meter panel indicating the correct street address.
The correct street address can be obtained from the local Municipal Council.
8.11.2 Multiple Occupancies (TIR)
Each multiple occupancy meter panel, shall be labelled with the correct street address
for each occupancy, and to indicate the relationship of meters, fuses and other
equipment supplied from the meter panel.
A corresponding marking shall also be made on the conductors for each occupancy at
the meter panel location to enable resent and future identification of conductors.
Additional labelling of multiple occupancies shall be in accordance with clause 7.8.2.7.
8.12 Protection (TIR)
The customer shall provide adequate and reasonable protection to prevent any physical damage
to metering equipment.
The metering equipment and facilities shall be adequately protected against both advertent and
inadvertent damage including; mechanical damage, vibration, effects of the weather, sea air,
corrosion, damage from vehicles, vandalism and spread of fire etc.
Examples of adequate protection requirements include:
Where metering is located within an area or in any position capable of being struck by vehicles,
suitable protective barriers shall be provided and installed by the customer; and
Where metering is installed in a location that is protected from the weather, the metering
equipment shall be located:
in a meter enclosure; or
on a hinged meter panel mounted on a suitable metering surround; and
Where metering is installed in locations exposed to the weather, the metering shall be
installed in suitable enclosures conforming to these Rules; and
be constructed of galvanised steel or an equivalent material;
have an IP rating suitable for the environment;
installed in a manner to provide protection against vibration, vandalism, weather and all
other external factors; and
may be locked with a suitable lock in accordance with clause 4.7.
8.13 Whole Current Metering
Whole current metered electrical installations shall comply with clauses 8.1 and 8.13 where
applicable, and the following requirements.
8.13.1 Clearances
Unless otherwise approved by the Responsible Officer, direct metered electrical
installations shall be arranged to meet the following clearances:
A maximum height of 2.0m to the top of the panel space provided for metering
above the floor or ground;
A minimum height of 0.7m to the bottom of the panel space provided for metering
above the floor or ground;
A minimum of 175mm in front of the meter panel to the inner face of the door or any
internal projection where the meter panel is enclosed; and
A minimum of 75mm behind the meter panel.
8.13.2 Meter Panels
Meter panels supplied in accordance with clause 8.3 and 8.9 shall be arranged to
accommodate the required combinations of metering and associated equipment as
detailed in clause 8.13.2.1 and 8.13.2.2. For arrangements other than those detailed in
the following clauses refer to the Responsible Officer for advice.
RATING OF
DISTANCE BETWEEN METER PANEL AND THE NEAREST CONDUCTOR (mm)
CONDUCTOR (Amps)
500 200
1000 400 Interpolate for intermediate values
2000 600
3000 800
Table 8.8 Conductors to Meter Panel Clearances
8.14.2.3 Wiring
The meter panel shall be prepared and wired in accordance with Figure 8.23 and all
wiring shall be connected in accordance with Figure 8.22 and Figure 8.24
The responsibility for provision and installation of the wiring loom shall be in accordance
with clause 8.14.7.2.
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 128 of 149
TS 100: Electrical Design Standards for Underground Distribution Cable Networks (up to and including 33kV)
TS 100: Electrical Design Std for Underground Distribution Cable Networks (up to & including 33kV)
Issued - June 2014
The use of this document is subject to the conditions stated in SA Power Networks disclaimer at the front of this document.
SA Power Networks 2014 Page 129 of 149
Service & Installation Rules
Frequency 50 Hz
Number of Phases 3
Normally, where more than one high voltage supply is provided to a customer, the main
circuit breakers shall be interlocked in such a manner that paralleling of the high voltage
supplies shall not be possible. Approved interlocking methods are:
hard wired electrical interlocking; and/or
mechanical interlocking
In any case, the customer must notify the SA Power Networks Network Operations
Centre prior to transferring load.
Paralleling of high voltage feeders to provide a no break supply may also be considered,
if technically viable and will be subject to the installation of additional protection at the
zone substation and the electrical installation at the customers expense.
These contract conditions are to be a negotiated agreement with SA Power Networks
and included in a network connection contract.
9.7.3 Power Factor (TIR)
Power factor averaged over any 5 minute period must be maintained at better than
detailed in Table 9.2 or as specified in the SA Distribution Code at the time.
Continuous 1%
5 Minutes 1.5%
Instantaneous 3.0%
Table 9.3 Voltage Unbalance Factor
Supporting documentation is required if the customer uses relays that have not been previously
assessed by SA Power Networks.
9.9 Insulation Coordination (TIR)
The safety clearances, separation of live parts and insulation levels (impulse strength) shall be in
accordance with AS 2067 and AS 1824.1.
9.10 Short Time Withstand Current (TIR)
High voltage switchgear, conductors, associated equipment, and earthing systems shall be
capable of withstanding the maximum fault current, which may be imposed for duration of at
least one second, and in some cases for three seconds.
Actual fault currents and their maximum duration at any particular location on SA Power
Networks high voltage system will be made available upon request.
9.11 Earthing (TIR)
9.11.1 General (TIR)
The earthing system of the customers high voltage installation shall comply with
AS/NZS 2067 and these Rules.
In locations where SA Power Networks employs a Common Multiple Earth Neutral
(CMEN) system of earthing, the customers HV and LV earthing systems shall be installed
separately.
A single removable bonding point between the HV and LV earthing systems is required
at each HV/LV customer transformer. The customers HV earthing system shall be
connected to the SA Power Networks common neutral conductor via the customers
neutral conductor.
In locations where SA Power Networks employs a Multiple Earth Neutral (MEN) system
of earthing, the customers HV and LV earthing systems must be kept separate.
An approved earthing device is required to provide an earthing facility on the consumer
mains. A mechanism which is capable of securing the earthing device in both the open
and closed position, shall be fitted to the earthing device. The securing mechanism must
be capable of accepting an SA Power Networks padlock with a 10mm shacking and may
have provision for additional padlocks for the customers requirements.
Special attention should be paid to the management of step and touch potentials that
may occur under earth fault conditions associated with any earthing system installed
within an electrical installation. Particular attention should be paid to the separation of
independent earthing systems and the proximity of earthed infrastructure such as
metallic fences and building to earthing systems so as to avoid the possibility of
hazardous step and touch potentials.
Earthed primary neutral windings are not permitted on any transformer of the nominal
supply voltage. It is recommended that the customer use Delta-Star transformers to
comply with this requirement.
All metallic substation fences, doors or enclosures should be connected to the earthing
system and a grading ring should be installed around the substation enclosure in
accordance with AS 2067. Reinforcing in the substation floor or walls should be
connected to the common earth terminal bar.
9.11.2 Size of Earthing Conductors (TIR)
Earthing systems shall be designed to withstand the maximum system design fault
current levels as specified in clause 9.10.
All conductors used within the electrical installation for combined or separate earthing
systems shall have a minimum equivalent copper cross-sectional area as follows:
Sub transmission voltage earthing conductors: 66kV 120mm2
High voltage earthing conductors:
33kV 70mm2
11kV 95mm2
7.6kV 95mm2
Low voltage earthing conductors: 120mm2
9.11.3 Earthing of Metering Equipment (TIR)
The enclosure of the meter, metering transformers and any metal supporting
structure/s shall be connected to the same earth grid as the Current Transformer and
Voltage Transformer secondaries.
The customer is responsible for providing earthing of the metering enclosure to the
requirements of AS/NZS 3000.
A suitable earth grid is required for all metering installations.
9.12 SA Power Networks Acceptance Requirements
The customer shall submit the following details for written acceptance prior to supply at high
voltage being made available:
Final single line diagram;
A schematic of the metering circuitry
Agreed maximum demand;
Main circuit breaker specification;
Protection settings for main circuit breaker;
Compliance to Distribution Code, eg Systems study etc;
Copy of HV Metering VT and CT test certificates refer to clause 9.13.3;
Before final connection is made the customer must provide:
The Network copy of the Electrical Certificate of Compliance;
A copy of:
o The installations HV operating procedures refer to clause 9.15.1;
o Commissioning and test certificates as determined by the customer and as prescribed by
AS/NZS 3000 which must include trip tests on the incoming circuit breaker refer also to
clause 9.14;
o HV plant and equipment maintenance plan refer to clause 9.15.2; and
o HV clearance to energise the installation.
9.13 Metering
The following high voltage metering requirements are applicable to single feeder high voltage
installations (up to 66kV) and are consistent with the National Electricity Rules, the SA Metrology
Procedures and the Electricity Metering Code.
Other high voltage installations such as dual high voltage feeders and cogeneration installations
will require additional provisions.
9.13.1 General Requirements
Metering equipment shall be installed by the Meter Provider in accordance with the
applicable requirements of Section 8 LV Metering and the following specifications. These
include:
A clear, illuminated (during normal business hours), paved and level space as
specified in clause 8.8, shall be provided in front of the metering position to allow
access for meter reading and to accommodate test personnel and their equipment. A
clear space of 1.0m deep is required in front of the meter position for safe access by
the meter provider and SA Power Networks personnel.
Access must be direct (ground floor), or by stairs or lift. Ladder access is not
acceptable.
Metering equipment must not be subjected to industrial contamination, extremes in
temperature, or vandalism.
Enclosures must comply to the same requirements contained in clause 8.9.
9.13.2 Metering Instrument Enclosure Requirements
9.13.2.1 Panel
The customer shall provide the meter panel/s and a suitable enclosure or surround for
mounting a lift-off hinged panel on which to mount the metering equipment.
A clear space of 2.1m high by 1.2m wide is required to provide access for mounting
metering equipment. See clause 8.5.
The minimum size meter panel for a single HV metering installation shall be in
accordance with 8.14.1.
Meter enclosures shall comply with clause 8.9. The door on meter enclosures shall be
labelled Electricity Meters.
9.13.2.2 Enclosure
The customer shall install and maintain a metering instrument enclosure complying with
the requirements of clause 8.9.
10. Appendices
10.1 Appendix 1 Single Phase URDs
The following localities are served by single phase padmounted transformers. It is not possible to
provide three phase services within these areas without augmentation to the SA Power Networks
distribution mains.
Please note that some streets immediately adjoining those identified may be served from these
transformers.
Reynella Lana St
Gawler Myrtlebank Ct
Para Hills
(including Cornwall Dr Kara Ct McGill Ct
Gulfview Heights)
Glenarbon St Parkeston Ct Nelson Rd
Yulinda Tce
Marion Hersey Ct