Sunteți pe pagina 1din 4

DATA SHEET

Fog/Jet Monitor
Electrical FJM-EL

General Description
Powerful fire extinguishing monitor with exceptionally good
flow characteristics and remote control operation. Electric motor
driven elevation and rotation movement with solenoid valve or
linear actuator operated fog/jet pattern adjustment.

Application Description Order Information - Please Specify


Designed for fixed mounting, the FJM-EL is optimised to 1. Part number
deliver water and foam. Varying water to fog pattern delivery is 2. Type
adjustable by remote control.
3 Flange type
4. Capacity: flow and pressure
Product Features 5 Motor and Solenoid voltage
n Wide capacity range 6. Foam induction (S-version)
n Adjustable flow to nominal capacity
n Compact, balanced design Part No. Description

n Easily manoeuvred due to low friction bearings Standard Versions


n 161508107 FJM-80 EL LA DIN/ANSI
n Long throw length
n 161510105 FJM-100 EL Man DIN
n Adjustable stream pattern
n 161510202 FJM-100 EL Man ANSI
n Corrosion resistant construction of stainless steel and bronze n 161510112 FJM-100 EL MV DIN
n Integrated electrical junction box n 161510209 FJM-100 EL MV ANSI
n A
 vailable with ATEX approved electrical equipment n 161510126 FJM-100 EL S MV DIN,
excl. suction hose
n 161510223 FJM-100 EL S MV ANSI,
Connections excl. suction hose
n 161510503 FJM-100 EL Man Exde DIN
n Foam/water inlet: flanged according to DIN PN 16,
JIS 10K or ANSI 150 lbs n 161510601 FJM-100 EL Man Exde ANSI
n 161510552 FJM-100 EL MV Exde DIN
n 161510650 FJM-100 EL MV Exde ANSI
Optional Components n 161550112 FJM-100 EL LA DIN
n Control and operating panel, custom built solutions on request n 161550559 FJM-100 EL LA Exde DIN
n Built-in inductor optional on all models n 161515118 FJM-150 EL MV DIN/ANSI/JIS
n 161515559 FJM-150 EL MV Exde DIN/ANSI/JIS
n Power supply from 24V DC to 440V AC available
n 161555125 FJM 150 EL LA DIN/ANSI/JIS
n Optional suction hose and valve
n 161555566 FJM 150 EL LA Exde DIN/ANSI/JIS
n Special versions with cast iron motors and gearboxes available n 161520115 FJM-200 EL MV DIN
n 161520216 FJM-200 EL MV ANSI
n 161010606 FJM-100 Suction hose 2 3 m
Listings and Approvals
Harsh Environment Versions
n Det Norske Veritas (DNV)
n 163450155 FJM-100 EL LA DIN CI
n Bureau Veritas (BV) FJM-200EL only
n 163650158 FJM-100 EL LA DIN CI
n Russian Maritime Register of Shipping (RMRS) n 163455149 FJM 150 EL LA DIN/ANSI/JIS CI
n CNBOP (Poland) FJM-100EL only n 163655151 FJM 150 EL LA Exde DIN/ANSI/JIS CI
n 163420144 FJM-200 EL MV DIN CI
n 163420243 FJM-200 EL MV ANSI CI

Other versions and options available upon request

Tyco Park l Grimshaw Lane l Newton Heath l Manchester l M40 2WL


Tel: +44 (0) 161 259 4000 l www.tfppemea.com l Copyright 2014 Tyco Fire Products LP.
All rights reserved. l FDS14328 02/14
FJM-80 EL LA FJM-100 EL
~170 ~415 497 ~430 ~700

208
100 DIN PN 16 or
4 ANSI 150 lbs or
100 JIS B 2210 10K

Input voltage supply


Control Joystick
Unit customer specified

FJM-100 EL LA ~180 ~568

~62
~587

~221

FJM-80 Monitor - Range of Jet FJM-100 Monitor - Range of Jet


Deduct 10% for self induction nozzle.

Minimum range at Minimum range at


metres wind still conditions |/min metres wind still conditions |/min
70
90

60 80 6,000
2000 5,000
4,000
50 3,000
1500 70

2,000
40 1000
60

30
50

20 500
40
4 5 6 7 8 9 10 11 12 bar

10 Reaction force (N) = 0.233 x Q (l/min) x p (bar)

4 5 6 7 8 9 10 11 12 bar
FJM-150 EL FJM-200 EL
~590 ~810 ~720 ~1000
264

279
150 DIN PN 16 or 6
ANSI 150 lbs or 150
JIS B 2210 10K
200 DIN PN 16 or
8 ANSI 150 lbs or
200 JIS B 2210 10K

Control Joystick
Unit
Input voltage supply
customer specified Control Input voltage supply
Unit Joystick
customer specified

FJM-150 EL LA ~202 ~636


~198

828
~274

FJM-150 Monitor - Range of Jet FJM-200 Monitor - Range of Jet


Deduct 10& for self induction nozzle.
Minimum range at
metres wind still conditions |/min metres Minimum range at wind still conditions |/min
100 130

11,700 20,000
90 120
10,000
8,000
17,000
6,000
80 110
5,000
15,000

70 100

13,000
60 90

50 80

40 70
4 5 6 7 8 9 10 11 12 bar

60

50

40

30
6 7 8 9 10 11 12 bar

Reaction force (N) = 0.233 x Q (l/min) x p (bar)


Performance Data
FJM Series -
80 100 150 200
Standard

n Water capacity max 2,500 l/min - min max 6,000 l/min - min max 11,700 l/min - min max 20,000 l/min -
500 l/min 1000 l/min 3000 l/min min 8000 l/min

n Design pressure 4-16 bar 4-16 bar 4-16 bar 4-13 bar
(optimum 10-12 bar) (optimum 10-12 bar) (optimum 10-12 bar) (optimum 10-12 bar)

n Rotation 175 175 175 175

n Elevation -65/+70 -70/+70 -70/+70 -60/+70

n Weight 28.5 kg / 63 lbs 69 kg / 152 lbs 98 kg / 216 lbs 139 kg / 306 lbs

FJM Series -
100 150 200
Built-in inductor

n Water capacity max 6,000 l/min - min 1000 l/min max 11,700 l/min - min 3000 l/min max 20,000 l/min - min 8000 l/min

n Design pressure 4-16 bar (optimum 10-12 bar) 4-16 bar (optimum 10-12 bar) 4-13 bar (optimum 10-12 bar)

n Foam capacity max 320 l/min 600 l/min 600 l/min

n Rotation 178 178 178

n Elevation -45/+70 -45/+70 -45/+70

n Suction Connection 2 BSP male 2 BSP male 2 BSP male

n Weight 72 kg / 159 lbs 101 kg / 222 lbs 145 kg / 319 lbs

FJM Monitors - Average


FJM Monitors Fog Pattern
- Average FJM Monitors - Capacity Ranges
(In StillFog
Air)Pattern (in still air)
Foot print

2/3

~1/3 of R
R
~1/3 of R

bar

www.skum.com