Compact NS 80 A
045345
Things
will never be
Compact NS 400 to 630 A
the same
E45151
Protection for:
c distribution systems supplied by transformers
c distribution systems supplied by engine generator sets
c long cables in IT and TN systems.
push
to
trip
Installation :
c in power switchboards
c on DIN rails (see page 42)
Special applications:
c single-phase and two-phase systems (see page 34)
c 1000 V distribution systems (see page 36)
c 400 Hz distribution systems (see page 38)
c DC systems (see page 40).
All circuit breakers in the Compact NS range offer positive contact indication
and are suitable for isolation in compliance with standards IEC 60947-1 and 2.
When combined with a motor starter, Compact NS circuit breakers protect the
cables and the starter against short-circuits. Equipped with an electronic trip unit,
Compact NS circuit breakers also protect the cables, starter and motor against
overloads.
The exceptional current-limiting capacity of Compact NS circuit breakers
automatically ensures type-2 coordination with the motor starter, in compliance with
standard IEC 60947-4-1.
Protection of machines p. 52
E44356
Earth-leakage protection p. 56
E44357
Additional earth-leakage protection protects life and property against the risks
of faulty insulation in the installation. Depending on the circuit breaker,
earth-leakage protection is provided by:
c adding a Vigi module to the circuit breaker
c using a specific Micrologic control unit
M
G
c using a Vigirex relay and separate toroids.
Service connection p. xx
E56631
push 22 DE
to STR
trip
90 %Ir test
105 50/60Hz
Im
5 alarm
Ir 4 6
.9 3
.85 .95 8 Ir Im
.8 2
.98 10
1.5
.7 xIr
1
.63
xIn
UL 489 applications
Compact NS circuit breakers also meet the requirements of applications governed
by standard UL 489 (see the corresponding catalogue).
E58549
withdrawable, front or rear connections,
manual or electrical operation.
c Compact NS1600 to 3200 A, fixed, front
connection, manual operation.
E27836
N: standard breaking
capacity
E27837
compact
NS 250 H
Ui750V Uimp8kV
Ue Icu
(V) (kA)
220/240 100
380/415 70
440 65
500 50
525 35
660/690 10
250 85
compact
NS 250 L
Ui750V Uimp8kV
Ue Icu .
(V) (kA)
220/240 150
380/415 150
440 130
500 70
525 50
660/690 20
250 100
.
IEC 947-2 cat A
UTE VDE BS CEI UNE NEMA
Total discrimination
as standard
E22051
push
to
trip
053100
Manual Compact NS250 Compact NS250 with motor Plug-in Compact NS250
with thermal-magnetic mechanism on base
041879
trip unit
053100
installation and fewer errors.
All type L Compact circuit breakers
045345
(150 kA) are housed in the same case
046751
as the type N and type H models
with the same ratings.
Compact circuit breakers up to 1600 A
can be easily installed side-by-side
in a minimum amount of space. 80 A 100 to 250 A 400 to 630 A
E45151
E45178
Many connection
possibilities
Numerous connection possibilities, including front and
041650
rear connections for bare cables, cable lugs or bars,
as well as plug-in or withdrawable versions, are
available using accessories that can be rapidly added
to the circuit breaker.
Connection parts
for Compact NS
Busways
Compact NS circuit breakers up to 630 A can be
installed in tap-off units of the Telemecanique Canalis
E32455
048287
041625
041638
TM thermal-magnetic Voltage presence indication
trip unit module
045212
041641
Compact NS250
056480
056479
E24603
c Compact NS630b to 1600
c Compact 1600b to 3200.
8
7
11
9
10
13
2
2
4
3
6
14
1 Breaking unit
2 Trip units or control units
3 Vigi earth-leakage protection module
4 Insulation monitoring module
5 Voltage presence indicator
6 Ammeter module
7 MN and MX voltage releases
8 Multifunction auxiliary contact
9 Direct rotary handle
10 Extended rotary handle
11 Motor mechanism
12 Plug-in base
13 Connection of auxiliary circuits to plug-in base or withdrawable chassis
14 Connection accessories
15 Short terminal shields
16 Long terminal shields
E37615
Equipped with a communications option, Compact NS
circuit breakers fit perfectly in the Digipact installation- PM150 power
management system or other supervision systems. management meter
Via a PC or a PLC, the operator can:
c display the status of each circuit breaker and its
settings
c control the circuit breakers
c display faults
c access measurements supplied by the electronic circuit breaker
control units. or other power
actuator
ModBus / JBus
CLS150 indication
and local-control
module
Digipact internal bus
Multi 9 control
DC150 data concentrator device and ATB 1S
interface
UA150 automatic
source-changeover
controller
RHU residual-
current relay with
separate toroid
RMH earth-
leakage monitor
Tropicalisation
Compact NS circuit breakers have successfully passed the tests prescribed by the
following standards for extreme atmospheric conditions:
c IEC 68-2-1 - dry cold (-55 C)
c IEC 68-2-2 - dry heat (+85 C)
c IEC 68-2-30 - damp heat (95% relative humidity at 55C)
c IEC 68-2-52 - salt mist (severity level 2).
Environmental protection
Compact NS circuit breakers take into account important concerns for
environmental protection. Most components are recyclable and the parts of
Compact NS630b to NS3200 circuit breakers are marked as specified in applicable
standards.
Ambient temperature
c Compact NS circuit breakers may be used between -25 C and +70 C.
For temperatures higher than 40 C (65 C for circuit breakers used to protect
motor feeders), devices must be derated as indicated in the documentation.
c Circuit-breakers should be put into service under normal ambient operating-
temperature conditions. Exceptionally, the circuit breaker may be put into service
when the ambient temperature is between -35 C and -25 C.
c The permissible storage-temperature range for Compact NS circuit breakers in
the original packing is -50 C (1) to +85 C.
Discrimination
As standard, the Compact NS range ensures discrimination between two circuit
breakers positioned in series in an installation.
E22037
CB1
CB2
Degree of protection
As per standards IEC 60529 (IP degree of protection) and EN 50102
(IK degree of protection against external mechanical impacts).
Bare circuit breaker with terminal shields
With toggle IP40 IK07
E18570
push
to
trip
E28439
push
to
trip
O
OFF
push
to
trip
standard / VDE
MCC IP435
CNOMO IP547
ON
I
push
to
trip
O
OFF
ON
I
push
to
trip
ON
O I
OFF
OFF
push
to
trip
1
/auto
I
manu O ON
push
OFF
push
E58563
Protection of distribution systems means
E43842
protection of: G
c systems supplied by a transformer
c systems supplied by an engine
generator set
c long cables in IT and TN systems.
Power distribution
Selection of circuit breakers up to 630 A page 18
Rated current (A) 12.5 12.5 12.5 12.5 60 250
E20999
push
to
trip
053100
045345
Breaking capacity E 16
(kA rms) N 25 36 36 45 45
380/415 V H 70 70 70 70 70
L 150 150 150 150 150
Accompanying trip units up to 630 A page 22
Interchangeable thermal-magnetic and electronic trip units for NS100 to 630 and built-in
thermal-magnetic trip unit for Compact NS125E
Selection of circuit breakers from 630 to 3200 A page 20
+
Rated current (A) 250 320 400 500 640
630 800 1000 1250 1600
E43843
Breaking capacity N 70 70 70
(kA rms) H 85 85 85
380/415 V
Accompanying control units up to 3200 A page 28
Micrologic electronic control units may be used on all Compact NS630b to 3200 circuit
breakers and can be changed on site.
86099
86101
trip units
Breaking capacity 1P 2P 1P 2P 1P
(kA rms) 220 V N 25 85 25 85 25
H 40 100 40 100 -
053182
10 kA rms at 1000 V
page 42
Rated current (A) 16 160
Compact installation on NSA160
a DIN rail Breaking capacity
048016
Number of poles
Control manual toggle
direct or extended rotary handle
electric
Connections fixed front connection
rear connection
withdrawable front connection
rear connection
Mounting on backplate or rails
on DIN rail
Electrical characteristics as per IEC 60947-2 and EN 60947-2
Compact NB50N Rated current (A) In 50 C
Rated insulation voltage (V) Ui
Rated impulse withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
052163
DC
Type of circuit breaker
Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz 220/240 V
380 V
415 V
440 V
500 V
660/690 V
DC 250 V (1P)
500 V (2P in series)
Service breaking capacity Ics % Icu
Suitability for isolation
Utilisation category
Compact NB250N
Endurance (C-O cycles) mechanical
electrical 440 V - In
Electrical characteristics as per Nema AB1
Breaking capacity (kA) 240 V
056605
480 V
600 V
Protection
Trip units thermal-magnetic
Overload protection Ir at 50 C
threshold (A) at 60 C
Instantaneous short-circuit protection Im
threshold (x Ir)
Indication and control auxiliaries
Indication contacts
Voltage releases MX shunt release
MN undervoltage release
Remote communication by bus
Communicating auxiliary contacts
Installation
Accessories terminal extensions and spreaders
Compact NB400N terminal shields and interphase barriers
escutcheons
DIN rail plate
Dimensions (mm) WxHxD
Weight (kg)
Source changeover system
Manual source changeover systems
non interchangeable non interchangeable non interchangeable non interchangeable non interchangeable
15 20 30 40 50 15 20 30 40 50 60 80 100 100 125 150 175 200 225 250 250 300 350 400 500 600
15 20 30 40 50 15 20 30 40 50 60 80 100 94 119 142 165 190 210 230 250 300 350 - 500 -
11 10 11 11 9 11 10 11 11 9 12 8 11 12 12 12 12 12 12 11 10 10 10 10 10 10
c c c c c
c c c c c
- - c c c
- - - - -
- - c c c
- - c c c
- - c c c
c c - - -
75 x 130 x 68 90 x 155 x 68 105 x 161 x 86 140 x 255 x 110 140 x 255 x 110
0.7 1.2 1.9 6.0 6.0
- - - - -
DC
Type of circuit breaker
Ultimate breaking capacity (kA rms) lcu AC 220/240 V
50/60 Hz 380/415 V
440 V
500 V
525 V
660/690 V
DC 250 V (1P)
500 V (2P in series)
Service breaking capacity lcs % Icu
Suitability for isolation
Utilisation category
Endurance (cycles F/0) mechanical
electrical 440 V In/2
In
Electrical characteristics as per NEMA AB1
Breaking capacity (kA) 240 V
480 V
600 V
Electrical characteristics as per UL508
Compact NS630L Breaking capacity (kA) 240 V
480 V
600 V
Protection
Trip units
Overload protection long time Ir (In x )
Short-circuit protection short time lsd (Ir x )
instantaneous Ii (In x )
Earth-fault protection lg (In x )
Zone selective interlocking ZSI
Add-on earth-leakage protection add-on Vigi module
combination with Vigirex relay
Current measurements
Additional measurement, indication and control auxiliaries
Indication contacts
MX shunt and MN undervoltage releases
Voltage-presence indicator
Current-transformer module and ammeter module
Insulation-monitoring module
Remote communication by bus
Device-status indication
Device remote operation
Transmission of settings
Indication and identification of protection devices and alarms
Transmission of measured current values
Installation
Accessories terminal extensions and spreaders
terminal shields and interphase barriers
escutcheons
Dimensions (mm) W x H x D fixed, front connections 2-3P / 4P
Weight (kg) fixed, front connections 3P / 4P
(1) 2P in 3P case for type N only Source changeover system (see section on source changeover systems)
(2) specific trip units are available for operational Manual, remote-operated and automatic source changeover systems
voltages > 525 V
(3) operational voltage i 500 V.
c c c
c c c
- c c
- c c
- c c
- c c c c
- c c c c
- - - - c
- - - - c
- - - - c
c c c
c c c
c c c
105 x 161 x 86 105 x 161 x 86 / 140 x 161 x 86 140 x 255 x 110 / 185 x 255 x 110
1.7 / 2.3 1.6 to 1.9 / 2.1 to 2.3 6.0 / 7.8
- c c
Number of poles
Control manual toggle
direct or extended rotary handle
electric
Type of circuit breaker
Connections fixed front connection
rear connection
withdrawable (on chassis) front connection
rear connection
Electrical characteristics as per IEC 60947-2 and EN 60947-2
Rated current (A) In 50 C
65 C (1)
Rated insulation voltage (V) Ui
Rated impulse withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
Compact NS800H DC
Type of circuit breaker
Ultimate breaking capacity (kA rms) lcu AC 220/240 V
50/60 Hz 380/415 V
440 V
500/525 V
E45178
660/690 V
DC 250 V
500 V
Service breaking capacity (kA rms) lcs Value or % Icu
Short-time withstand current (kA rms) lcw 0.5 s
V AC 50/60 Hz 1s
Suitability for isolation
Utilisation category
Endurance (C-O cycles) mechanical
electrical 440 V In/2
In
690 V In/2
In
Compact NS2000H
Pollution degree
Electrical characteristics as per Nema AB1
Breaking capacity at 60 Hz (kA) 240 V
480 V
600 V
Protection and measurements
Interchangeable control units
Overload protection long time Ir (In x )
Short-circuit protection short time Isd (Ir x )
instantaneous Ii (In x )
Earth-fault protection lg (In x )
Residual earth-leakage protection In
Zone selective interlocking ZSI
Protection of the fourth pole
Current measurements
Additional indication and control auxiliaries
Indication contacts
Voltage releases MX shunt release
MN undervoltage release
Remote communication by bus
Device-status indication
Device remote operation
Transmission of settings
Indication and identification of protection devices and alarms
Transmission of measured current values
Installation
Accessories terminal extensions and spreaders
terminal shields and interphase barriers
escutcheons
Dimensions fixed devices, front connections (mm) 3P
HxWxD 4P
Weight fixed devices, front connections (kg) 3P
4P
Source changeover system (see section on source changeover systems)
Manual, remote-operated and automatic source changeover systems
Micrologic 2.0 Micrologic 5.0 Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 A
c c c c c c
- c - c c c
c c c c c c
- - - - c -
- - - - - c
- - c c c c
c c c c c c
- - c c c c
c c
c c
c c
c c c c c c
c c c c - -
- - c c c c
- - c c c c
- - c c c c
c -
c -
c c
327 x 210 x 147 350 x 420 x 160
327 x 280 x 147 350 x 535 x 160
14 24
18 36
E23160
types N, H and L, may be equipped with
TM-D
either a TM thermal-magnetic trip unit or an
STR22 electronic trip unit. A mechanical STR22SE
mismatch-protection system avoids TM-G
breaker and trip unit mismatches.
STR22GE
TM-D
TM-G
t 1 2
1
E19528
Ir Im TM 250 D
10 5
250A / 40C
9 6
1 .8 8 7
2 .9
x 250A x 250A Ir Im
0 Ir Im I
1 7 3 6
1
E24096
In=100A STR 22 SE alarm %Ir
90
105
Io Ir Im
3 .8 .9 .9 .93 5 6
.7 1 .88 .95 4 7 + -
4 .63 .85 .98 3 8
5 .5 .8 1 2 10
Ir Im x In x Io x Ir test
0 Ir Im I
Protection
1 long-time threshold (overload protection)
2 long-time tripping delay The protection functions may be set using the adjustment dials.
3 short-time pick-up (short-circuit protection) Overload protection
4 short-time tripping delay True rms long-time protection with an adjustable threshold.
5 instantaneous pick-up (short-circuit protection)
6 test connector
Short-circuit protection
7 percent load indication Short-time and instantaneous protection:
c short-time protection with an adjustable pick-up and fixed tripping delay;
c instantaneous protection with fixed pick-up.
Protection of the fourth pole
E58711
Indications
A LED on the front indicates the percent load:
Protection of the fourth pole c ON - load is > 90% of Ir setting
c flashing - load is > 105% of Ir setting.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
Setting example
E25979
E23161
types N, H and L, 3-pole and 4-pole, may STR23SE / STR53UE
be equipped with any of the STR23SE, STR23SE / STR53UE
STR23SV, STR53UE and STR53SV
electronic trip units. STR23SV / STR53SV
The STR53UE and STR53SV trip units MP
offer a wider range of settings and the
STR53UE offers a number of optional Standard protection Protection of systems supplied by
with selectivity generators. Protection of long cables
protection, measurement and
Protection of DC
communications functions. distribution systems
Protection of systems U > 525 V
For DC applications, the Compact NS400H
and 630H circuit breakers are equipped Selection of the trip unit depends on the type of distribution system protected and
with a built-in MP magnetic trip unit. the operational voltage of the circuit breaker.
Protection for all types of circuits, from 60 to 630 A, is possible with only four trip-
unit catalogue numbers, whatever the circuit-breaker operational voltage:
c U i 525 V: STR23SE or STR53UE
c U > 525 V: STR23SV or STR53SV.
Trip units do not have a predefined rating. The tripping threshold depends on the
circuit breaker rating and the LT (long time) current setting.
For example, for an STR23SE trip unit set to the maximum value, the tripping
threshold is:
v 250 A, when installed on a Compact NS400 250 A
v 630 A, when installed on a Compact NS630.
2 STR 23 SE alarm 90
105 %Ir
E24094
Io Ir Isd
.8 .9 .9 .93 5 6
3 .7 1 .88 .95 4 7
.63 .85 .98 3 8
4 .8 1 2 10
.5
5 x In x Io x Ir
Ir Isd
+ -
0 Ir Im I test
Indications
A LED on the front indicates the percent load:
c ON - load is > 90% of Ir setting
c flashing - load is > 105% of Ir setting.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
8 1 2 3 4 5 6 (*) 9 7 (*)
1
2 6
7 STR 53 UE %Ir >Ir >Isd >Ig test fault
E33944
Io Ir Isd Ii Ig P
3 .7
.8 .9
1 .88
.9 .93
.95 3
4 5
6 3
4 6
8 .4
.5 .6
.7 > Ir
4 .6 .85 .98 2 8 2 10 .3 .8 A
.5 1 .8 1 10 11 1 tr
1.5 1.5 .2 > Im
x In x Io x Ir x In x In
5 tsd
tr tsd tg > Ih
test 8 16 .3 .3 .4 .4 In I1 I2 I3
4 (s).2 (s) .3
+ - .2 .3 Ir Isd li
0 Ir Isd Ii I 2 .1 .1 .2 .2
1 16 0 0 .1 .1
Fault indications
A LED signals the type of fault:
c overload (long-time protection) or abnormal internal temperature (> Ir)
c short-circuit (short-time protection) or instantaneous (> Isd)
c earth fault (if earth-fault protection option installed) (> Ig)
c microprocessor malfunction:
v both (> Ig) and (> Isd) LEDs ON
v (> Ig) LED ON (if earth-fault protection option (T) installed).
Battery powered. Spare batteries are supplied in an adapter box. The LED
indicating the type of fault goes OFF after approximately ten minutes to conserve
battery power. The information is however stored in memory and the LED can be
turned back ON by pressing the battery/LED test pushbutton. The LED
automatically goes OFF and the memory is cleared when the circuit breaker is reset.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
The test pushbutton tests the battery and the (% Ir), (> Ir), (> Isd) and (> Ig) LEDs.
Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature
is detected.
Options
Four options are available:
c earth-fault protection T
c ammeter I
c zone selective interlocking ZSI
c communications option COM.
Setting example
E25979
Io Ir
What is the overload-protection threshold of a .8 .9 .9 .93
.7 1 .88 .95
Compact NS400 circuit breaker equipped with .63 .85 .98
an STR23SE (or STR23SV) trip unit set .5 .8 1
to Io = 0.5 and Ir = 0.8 ?
x In x Io
Answer.
In x Io x Ir = 400 x 0.5 x 0.8 = 160 A.
The identical trip unit, with identical settings but
installed on a Compact NS630 circuit breaker, will
have an overload-protection threshold of:
630 x 0.5 x 0.8 = 250 A.
MP DC trip units
E26028
Im(A)
30005000
4400
2500
3800 3500
5700
2000 4000
In Im
Magnetic trip units for Compact NS400/630 three-pole, type H circuit breakers.
These trip units are specifically designed to protect DC distribution systems.
They are not interchangeable. The circuit breaker and trip unit are supplied
fully assembled.
Built-in trip units MP1 MP2 MP3
Circuit breaker Compact NS400H c c -
Compact NS630H c c c
Short-circuit protection (magnetic)
Pick-up (A) Im adjustable adjustable adjustable
800...1600 1250...2500 2000...4000
Indications
Overload indication by alarm LED on the front; the LED goes on when the current
exceeds the long-time trip threshold.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
long time
2
Ir tr alarm
1 .7
.8
.9 (s) 4
8
12 5
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In @ 6 Ir
Note.
Micrologic control units that do not include measurement
functions are equipped with a transparent lead-seal cover as
standard.
E46022
Current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Ir
Tripping between 1.05 and 1.20 Ir other ranges or disable by changing rating plug
Time delay (s) accuracy 0 to -30% tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
accuracy 0 to -20% tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
tr
accuracy 0 to -20% tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
Instantaneous Isd
Pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10
accuracy 10% 0 I
Time delay fixed: 20 ms
Protection Micrologic 5.0
Long time t
E46023A
Ir
Current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 Ir other ranges or disable by changing rating plug
Time delay (s) accuracy 0 to -30% tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600 tr
accuracy 0 to -20% tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
Isd
accuracy 0 to -20% tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping tsd
Short time Ii
Pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10
accuracy 10% 0 I
Time delay (ms) at 10 x Ir settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On 0.1 0.2 0.3 0.4
tsd (max resettable time) 20 80 140 230 350
tsd (max break time) 80 140 200 320 500
Instantaneous
Pick-up (A) Ii = In x 2 3 4 6 8 10 12 15 off
accuracy 10%
Overload alarm
A red alarm LED goes on when the current exceeds the long-time trip threshold.
menu
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units,
the operation of earth-fault or earth-leakage protection can be checked by pressing
the test button located above the test connector.
Note.
Micrologic A control units come with a transparent lead-seal
cover as standard.
E46022
current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 t
Ir
tripping between 1.05 and 1.20 x Ir other ranges or disable by changing rating plug
time delay (s) accuracy 0 to -30% tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
accuracy 0 to -20 % tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
accuracy 0 to -20 % tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6 tr
thermal memory 20 minutes before and after tripping
instantaneous
pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10 Isd
accuracy: 10 % 0 I
time delay fixed: 20 ms
menu
Ammeter Micrologic 2.0 A
continuous current measurements
measurements from 20 to 200 % of In I1 I2 I3 IN
accuracy: 1.5% (including sensors) no auxiliary source (where I > 20 % In)
maximeters I1 max I2 max I3 max IN max
E46023
current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Ir
tripping between 1.05 and 1.20 x Ir other ranges or disable by changing rating plug
time delay (s) accuracy 0 to -30 % tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
tr
accuracy 0 to -20 % tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
accuracy 0 to -20 % tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
thermal memory 20 minutes before and after tripping Isd
short time tsd
pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10 Ii
accuracy: 10 %
time delay (ms) at 10 Ir settings I2t Off 0 0.1 0.2 0.3 0.4 0 I
I2t On 0.1 0.2 0.3 0.4
tsd (max resettable time) 20 80 140 230 350
tsd (max break time) 80 140 200 320 500
instantaneous
pick-up (A) Ii = In x 2 3 4 6 8 10 12 15 off
accuracy: 10 %
earth fault Micrologic 6.0 A
t
E46024
pick up (A) Ig = In x A B C D E F G H J 2
accuracy: 10 % In i 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 I t on
Ig
400 A < In i 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2
In > 1200 A 500 640 720 800 880 960 1040 1120 1200 I t off
tg
time delay (ms) settings I2t Off 0 0.1 0.2 0.3 0.4
at In or 1200 A I2t On 0.1 0.2 0.3 0.4
tg (max resettable time) 20 80 140 230 350 0 I
tg (max break time) 80 140 200 320 500
residual earth leakage (Vigi) Micrologic 7.0 A
In t
E46243A
Note.
All current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
Used in conjunction with the Micrologic A control units, this module maintains three
functions when the circuit breaker is OFF or the current is less than 20% In:
c display of measurements
c screen backlighting
c operation of maximeters.
Characteristics:
c power supply:
v 110/130, 200/240, 380/415 V AC (+ 10% - 15%), consumption 10 VA
v 24/30, 48/60, 100/125 V DC (+20% -20%), consumption 10 W
c output voltage: 24 V DC; power delivered: 5 W / 5 VA
c ripple < 5%
c class 2 isolation.
Spare battery
A battery supplies power to the LEDs identifying the tripping causes. Battery
service life is approximately ten years.
Lead-seal cover for
Micrologic A A test button on the front of the control unit is used to check the battery condition.
The battery may be replaced on site when discharged.
50/60 Hz 277 V
380/415 V
440 V
500 V
525 V
660/690 V
DC 250 V (1P)
500 V (2P)
Service breaking capacity (kA rms) lcs % Icu
Suitability for isolation
Utilisation category
Endurance (C-O cycles) mechanical
electrical 277 V In/2
In
Electrical characteristics as per NEMA AB1
Breaking capacity (kA) 240 V
V AC 50/60 Hz 277 V
Compact NS100N two-pole 480 V
600 V
Protection and measurements
Type of trip units
Ratings In
Overload protection (thermal) long time Ir
threshold
Short-circuit protection (magnetic) instantaneous lm
pickup
Add-on earth-leakage protection add-on Vigi module
combination with Vigirex relay
Additional indication and control auxiliaries
Indication contacts
Voltages releases MX shunt release
MN undervoltage release
Remote communication by bus
Device status indication via communicating auxiliary contacts
Installation
Accessories terminal extensions and spreaders
terminal shields and interphase barriers
escutcheons
Dimensions (mm) WxHxD
Weight (kg)
Source changeover system
Interlocking systems
- c - c -
- c - c -
- c - c -
- c - c -
c c c c c
c c c c c
c c c c c
35 x 161 x 86 70 x 161 x 86 35 x 161 x 86 70 x 161 x 86 35 x 161 x 86
0.7 1.2 0.7 1.2 0.7
- - - - -
1150
10
100%
STR23SP
c
c
c
-
c
-
-
c
-
c
c
c
c
c
-
-
-
c
c
c
480 x 140 x 110
-
13
-
consult us
Tripping thresholds
The 400 Hz current settings are obtained by multiplying the 50 Hz values by the
following coefficient:
b K1 for thermal trip units;
b K2 for magnetic trip units.
On adjustable trip units, these adaptation coefficients are independent of the unit
adjustment knob position.
Thermal trip units
The current settings are lower at 400 Hz than at 50 Hz (K1 < 1).
Magnetic trip units
The current settings are conversely higher at 400 Hz than at 50 Hz (K2 > 1).
Adjustable trip units should be set to minimum, or use Compact circuit breakers
equipped with low magnetic trip units
(type G).
Electronic trip units
The use of electronics offers the advantage of greater operating stability when the
frequency is varied. However, the devices are still subjected to frequency related
temperature effects which may sometimes pose restrictions on their use.
Column K1 of the table gives the maximum permissible current to be used for the
current setting (knob position).
R MN or MX auxiliary releases
MN/MX For Compact NS100-630
U volt For circuit breakers on 400 Hz systems, only 125 V DC rated releases can be
125 V CC
400 Hz
used. The release must be supplied by the 400 Hz system via a rectifier bridge (to
be selected from the table below) and an additional resistor with characteristics
Connection depending on the system voltage and the type of circuit breaker.
U (V) 400 Hz rectifier additional resistor
220/240 V Thomson 110 BHz or 4.2 k-5 W
General Instrument W06 or
Semikron SKB at 1,2/1,3
380/420 V Semikron SKB at 1,2/1,3 10.7 k-10 W
Note : other models of rectifier bridges can be used if their characteristics are at least
equivalent to those stated above.
Selection criteria
The selection of the type of circuit breaker most suitable for protection of a
DC installation depends mainly on the following criteria:
b the rated current, which determines the rating of the equipment;
b the rated voltage, which determines the number of poles in series necessary for
breaking;
b the maximum short-circuit current at the point of installation, which determines
the breaking capacity;
b the type of network (see below).
E22348
E22349
a a a
and various
cases of faults + + +
U/2
U R + R U R
B U/2 B B
A A A
b C b b
C C
fault effect fault A max. Isc Isc close to max. Isc no effect
the positive polarity the positive polarity is the only
is the only one involved one involved, voltage U/2
fault B max. Isc max. Isc max. Isc
both polarities are involved both polarities are involved both polarities are involved
fault C no effect same as fault A but this is the no effect
negative polarity which is involved
most unfavorable case fault A faults A and C fault B
distribution of the the poles required to perform on each polarity there must be the the poles required to perform
breaking poles the break are in series number of poles required to perform the break are shared between
on the positive polarity the break of max. Isc at U/2 the 2 polarities
E79370
240 V DC Calculation the short-circuit current (Isc) across the terminals of a battery
300 A When a short-circuit occurs across its terminals, a battery discharges a current
Isc 500 Ah given by Ohm's law:
Ri = 0.5 m/cell
Vb
Isc =
Ri
where Vb = the maximum discharge voltage (battery 100 % charged).
and Ri = the internal resistance equivalent to the sum of the cell resistances (figure
generally given by the manufacturer according to the capacity of the battery).
Example
What is the short-circuit current at the terminals of a standing battery with the
following characteristics:
b capacity: 500 Ah;
b max. discharge voltage: 240 V
(110 cells of 2.2 V);
b discharge current: 300 A;
b autonomy: 1/2 hour;
b internal resistance: 0.5 m per cell.
Ri = 110 x 0.5 10-3 = 55 10-3
240
Isc = = 4.4kA
55 103
As the above calculation shows, the short-circuit current is relatively weak.
Note: If the internal resistance is not known, the following approximate formula can be used:
Isc = kC, where C is the capacity of the battery expressed in Ampere-hours, and k is a
coefficient close to 10 but in any case always lower than 20.
Example 1
+
125 V = Determine the protection required for a 80 A feeder on a 125 V DC network with an
- earthed negative pole and an Isc of 15 kA.
The table below indicates that a NC100H circuit breaker (30 kA, 2P, 125 V) should
NC100 H be used.
3P
80 A The table opposite indicates that both circuit breaker poles should be fitted on the
positive pole of the network.
load An additional circuit breaker pole can be fitted on the negative pole of the network
for isolation purposes.
E79372
Example 2
+
250 V = Determine the protection required for a 100 A feeder on a 250 V DC network with
- an earthed middle point and an Isc of 15 kA.
Each pole will be exposed to a maximum of U/2 = 125 V.
NC100 H The table below indicates that NC100H (30 kA, 2P, 125 V), NS100N (50 kA, 1P,
4P 125 V) or NS160N (50 kA, 1P, 125 V) circuit breakers should be used.
100 A
The table opposite indicates that both circuit breaker poles must take part in the
load breaking at a voltage of 125 V.
E79373
Example 3
+
250 V = Determine the protection required for a 400 A feeder on an unearthed 250 V DC
- network with an Isc of 35 kA.
The table above indicates that NS400H circuit breakers (85 kA, 1P, 250 V) should
NS400H be used. At least 2 poles must take part in breaking.
2P The table opposite indicates that the half the number of circuit breaker poles
400 A
required for breaking should be fitted on the positive pole of the network and the
load other half on the negative pole.
Characteristics
Number of poles 3, 4
Sensitivity (A) 0.03 / 0.3 / 1 / 3
Time delay intentional (ms) 0 60 (1) 150 (1)
max. break time < 40 < 140 < 150
Vigicompact NSA Rated voltage (V) 50/60 Hz 200 to 440 V
Reset pushbutton
Test pushbutton
Protection against nuisance tripping c
DC-component withstand class A
(1) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
046751
by standard IEC 60947-2.
For complete protection of the motor and
its control device, overload protection may
be provided by either the circuit breaker or
a separate Telemecanique thermal relay. Breaking H 70
capacity (kA rms)
The control device may be of the direct 380/415 V
on-line type (with or without reversing) General circuit-breaker characteristics page 46
or of the star-delta type. The Compact NS80H-MA circuit breaker is specially designed for motor protection.
Combinations are governed by standard Accompanying trip unit page 46
IEC 60947-4.1. A built-in MA magnetic trip unit provides short-circuit protection.
045198
041624
Breaking N 25 36 45
capacity (kA rms) H 70 70 70
380/415 V L 150 150 150
General circuit-breaker characteristics page 18
Compact NS100 to 630 circuit breakers for motor protection are the same as those for
distribution systems, but are fitted with specific motor trip units.
Accompanying trip units pages 47 to 51
MA magnetic trip units provide short-circuit protection. Interchangeable ME electronic trip units
provide protection against short-circuits, overloads and phase imbalance.
Ir (A) 1.5 2.5 12 40 50 80 100 160 200 220 320 500 800 1000 1350
Compact
MA
NS80H-MA
Compact MA
NS100 NS250
STR22ME
Compact MA
NS400 NS630
STR43ME
Compact
Micrologic 2.0 A / 5.0 A / 7.0 A
NS630b NS1600
This circuit breaker is specially designed for Compact circuit breakers NS80 H-MA
the protection of motors rated up to 37 kW: Number of poles 3
c due to its high current-limiting capacity, Control manual (toggle, c
direct or extended rotary handle) c
it effectively protects motor starters (type-2 electric -
coordination as per IEC 60947-4, with Connections fixed front connection c
contactors) rear connection -
withdrawable front connection -
c small size for easy installation in motor rear connection -
control centre (MCC) switchboards. Electrical characteristics as per IEC 60947-2
Rated current (A) In 65 C 80
Rated insulation Ui 750
voltage (V)
046751
Compact NS250H
045198
Compact NS400H-MA
Short-circuit protection
Short-time and instantaneous protection:
c short-time protection with fixed pick-up (Im = 13 x Ir) and tripping delay
c instantaneous protection with fixed pick-up (15 x In).
Phase-imbalance protection
This function complies with the stipulations of standard IEC 60947-4.1 and trips the
circuit breaker whenever a phase-current imbalance of 40 % or more occurs. The
circuit-breaker opening time is between 3.5 and 6 seconds.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
E26984
Ir
In=50A ImSTR 22 ME u1,05 Ir
Ir 37.5 40
7,2Ir IEC 947.4 / cl.10
35.5 42.5
3
33.5 45 7,0s
4
31.5 47.5
5 30 50
A Ir 13 Ir test
0 Ir 13Ir I
Fault indications
LEDs indicate the type of fault that caused tripping:
c overload (long-time protection) or abnormal component temperature (> Ir)
c short-circuit (short-time protection) or instantaneous (> Isd)
c phase imbalance (LED on the right)
c microprocessor malfunction:
v all four (% Ir), (> Ir), (> Isd) and (phase imbalance) LEDs ON.
Battery powered. Spare batteries are supplied in an adapter box. When a fault
occurs, the LED indicating the type of fault goes OFF after approximately ten
minutes to conserve battery power. The information is however stored in memory
and the LED can be turned back ON by pressing the battery/LED test pushbutton.
The LED automatically goes OFF and the memory is cleared when the circuit
breaker is reset.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
The test pushbutton tests the battery and the LEDs.
Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature is
detected.
Options
Three options are available:
c ammeter (I)
c contactor tripping module (SDTAM)
c communication (COM).
6 1 2 3 7
1
2
E32566
STR 43 ME %Ir >Ir >Isd test fault
Io Ir Isd P
3 .71 .8 .90 .93 9 10
.63 .88 .95 8 11 > Ir
4 .56 .85 .98 7 12 A
.5 .8 .8 1 13 tr
5 x In x Io
6
x Ir
> Im
tsd
tr 20 20 > Ih
test 10 Ir I1 I2 I3
10
0 Ir Isd Ii I + - 10A 10A
Ir Isd li
Communication (COM)
This option transmits data to Digipact distribution monitoring and control modules.
Transmitted data:
c settings;
c phase currents (rms values);
c highest current of the three phases;
c overload-condition alarm;
c cause of tripping (overload, short-circuit, etc.).
Compact NS circuit breakers are specially Compact NSC100 ( UL 508 / IEC 60947-2 / CSA22-2)
designed to protect incoming feeders and Rated current (A) 12.5100
groups of outgoing circuits on industrial
054556
control panels:
c compliance with standards applicable
worldwide including IEC 60947-2
and UL 508 / CSA 22-2 no. 14
Breaking N 18
c overload and short-circuit protection capacity (kA rms)
c isolation with positive contact indication, 380/480 V
making it possible to service machines General circuit-breaker characteristics page 53
safely by isolating them from all power Compact NSC100 circuit breakers are specially designed to protect industrial control panels.
Accompanying trip unit page 53
sources The built-in TMD thermal-magnetic trip unit provides:
c installation in universal and functional c overload protection (adjustable-threshold thermal device)
type enclosures c short-circuit protection (fixed-pick-up magnetic device).
045198
push
to
trip
041624
Breaking N 25 35 35 42 42
capacity (kA rms) H 65 65 65 65 65
380/480 V
General circuit-breaker characteristics page 18
Compact NS100 to 630 circuit breakers are designed for protection of distribution systems and
are also suitable for protection of industrial control panels.
Accompanying trip unit page 22 to 27
The trip units are interchangeable.
Compact NS100 to 250 circuit breakers are equipped with TMD thermal-magnetic or STR
electronic trip units.
Compact NS400 to 630 circuit breakers are equipped exclusively with STR electronic trip units.
Characteristics
Number of poles 3, 4
Sensitivity (A) 0.03 / 0.3 / 1 / 3
Time delay intentional (ms) 0 60(1) 150(1)
max. break time < 40 < 140 < 150
Rated voltage (V) 50/60 Hz 200 to 440 V
Reset pushbutton
Vigicompact NSC100N
Test pushbutton
Protection against nuisance tripping c
DC-component withstand class A
(1) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
Compact
TMD
NSC100N
Compact
NS100 NS250 STR22ME
Compact
STR43ME / STR23SE / STR53UE
NS400 NS630
Auxiliaries
All auxiliaries can be added to the circuit breaker by the user:
c padlocking devices (in the OFF position);
c rotary handle
c status-indication auxiliary contacts (ON, OFF and tripped)
c shunt (MX) or undervoltage (MN) releases
c early-make or early-break contacts.
Rotary handle
Available in direct or extended versions for mounting up to 590 mm behind front.
Versions include:
c black front with black handle
c yellow front with red handle (for machine tools or emergency off as per IEC 204 /
VDE 0013).
All rotary handles can be padlocked in the OFF position.
Optional door interlock, recommended for MCC panels (motor control centres).
Early-make or early-break contacts
These auxiliary contacts make it possible to de-energise the downstream auxiliary
circuits of the control panel as well as the auxiliary circuits supplying the MN
release, if applicable.
W D
Installation in an enclosure
Compact circuit breakers can be installed in a metal enclosure together with other
devices (contactors, motor-protection circuit breakers, LEDs, etc.)
E44458
Installation enclosure
E42651
The UL 508 / CSA 22-2 no. 14 approval is LISTED MAN. MOTOR. CTRL.
34XL
R
UL / CSA logo
NS100-160-250 N/H/NA
Equipped with TMD/DE or STR trip unit
This MMC is suitable for use on a circuit capable of delivering
not more than the short-circuit current rating of this MMC
indicated here below, or the upstream protective device
interrupting capability, whichever is less, when protected by
any protective device for Group fusing or Group installation.
SC current rating kA 50/60 Hz Breaking capacity
Vac NS100 NS160 NS250
N H N H N H
240 85 85 85 85 85 85
480 25 65 35 65 35 65
600 10 10 10 10 18 18
tripping current 125% 100% rated
temperature rating tightening torque Terminal kit
75C reference
wire size lb-inch Nm 3P 4P
14 AWG to 3/0 AWG Cu
12 AWG to 4/0 AWG Al
130 11.3 29242 29243 Cable cross-section
and tightening torques
4 AWG to 2 AWG Cu,Al 180 20
29259 29260
1 AWG to 350 kcmil Cu,Al 230 26
Trip-unit marking
Earth-leakage protection is obtained by: Circuit breakers equipped with an add-on Vigi module
c fitting a Vigi module on the circuit breaker (Vigicompact)
(Compact NS100 to 630) Rated current (A) 100 630
Vigicompact NSC100 N NS100 to 250 N/H/L
c installing a Micrologic 7.0 A control unit
NSA160 N/E NS400 and 630 N/H/L
(Compact NS630b to 3200) NS125 E
c using a Vigirex relay and separate toroids
044333
(all Compact circuit breakers).
054556
General circuit-breaker characteristics page 18 & 55
Compact NS100 to 630 and NSA160 circuit breakers are presented in the Protection of
distribution systems section and the Compact NSC100 circuit breaker is presented in the
Protection of industrial control panels section.
Accompanying Vigi modules
Earth-leakage protection is achieved by installing a Vigi module directly on the circuit-breaker
terminals.
E45178
150
310 before dielectric test
remove this cover
vigi
Compliance with standards:
60
0
t(ms)
vigi MH
T R NS 250
200 / 440 V - 50 / 60 Hz c IEC 60947-2, appendix B
1
3 10
N 1 3 5
c French decree dated 14 November 1988
0,3 In(A) T c IEC 60255-4 and IEC 60801-2 to 5 covering protection against nuisance tripping
HS 0,03 ( t = 0 )
2 4 6
due to transient overvoltages, lightning strikes, switching of devices on the
distribution system, electrostatic discharges, radiofrequency interference.
1 sensitivity setting c IEC 60755, class A, immunity to DC components up to 6 mA
2 time-delay setting (for selective earth-fault protection)
c VDE 664, operation down to -25 C.
3 lead-seal fixture for controlled access to settings
4 test button simulating an earth-fault for regular Remote indications
checks on the tripping function Vigi modules may be equipped with an auxiliary contact (SDV) to remotely signal
5 reset button (reset required after earth-fault tripping) tripping due to an earth fault.
6 rating plate
7 housing for SDV auxiliary contact Power supply
Vigi modules are self-supplied internally by the distribution-system voltage and
therefore do not require any external source. They continue to function even when
supplied by only two phases.
Plug-in circuit breaker
The Vigi module can be installed on a plug-in base.
Special accessories are required (see the section Vigi module selection table
on part numbers). Vigi ME Vigi MH Vigi MB
Number of poles 3, 4 (1) 3, 4 (1) 3, 4 (1)
NS125 E c c -
NS100 N/H/L c c -
NS160 N/H/L c c -
NS250 N/H/L - c -
NS400 N/H/L - - c
NS630 N/H/L - - c
Protection characteristics
Sensitivity fixed adjustable adjustable
In (A) 0.3 0.03 - 0.3 - 1 - 3 - 10 0.3 - 1 - 3 - 10 - 30
Time delay
Intentional fixed adjustable adjustable
delay (ms) < 40 0 60 (2) 150 (2) 310 (2) 0 60 150 310
Max. breaking < 40 < 40 <140 <300 <800 < 40 < 140 < 300 < 800
time (ms)
Rated voltage 200...440 200... 440 - 440...550 200...440 - 440...550
V AC 50/60 Hz
(1) Vigi 3P modules may also be used on 3P circuit breakers used for single-phase or two-
phase protection.
(2) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
Note.
The Vigi module for the Compact NSA160 circuit breaker is presented on page 39.
E58562
Masterpact Masterpact
NT source coupling
NW switch-disconnector Masterpact
NW or NT
main power
main power distribution board distribution board for
for commercial applications industrial applications
15 -40 kA 20 -80 kA
i 1000 A i 1600 A
replacement
source
industrial
modular sub- distribution automation
distribution board board cabinet
source-
i 160 A : 15 - 25 kA changeover
i 160 A 15 - 25 kA i 400 A : 20 - 80 kA system
i 400 A
final distribution
local enclosure for local local
isolation commercial isolation isolation
enclosure applications enclosure control panel enclosure
i 10 kA i 25 kA
i 63 A i 10 kA i 5 kA 5-15 kA
i 40 A
i 63 A i 630 A
i 125 A
M M M M M
N.B. adjacent to or built into the machine
Circuit breaker-
disconnector
Switch-disconnectors
056470
E58880
86087
052164
086106
056385
054361
054629
035050
053041
044313
Compact switch-disconnector Compact switch-disconnector MN/MX
equipped with a Vigi earth- equipped with a motor mechanism voltage
leakage module release
rear connection
Built-in connectors for 1.5 to 90 mmv cables
Mounting on DIN rail
Front-panel cutout 45 mm high
Electrical characteristics as per IEC 60947-3 and EN 60947-3
Conventional thermal current (A) Ith 60 C
Rated insulation voltage (V) Ui
Rated impulse withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Compact NSA125NA Rated operational current le AC 50/60 Hz
220/240 V
380/415 V
440/480 V (1)
500 V
Short-circuit making capacity lcm (kA peak) minimum (switch-disconnector alone)
maximum (with protection circuit
breaker upstream)
Short-time withstand current lcw (A rms) 1s
3s
20s
Suitability for isolation
Endurance (C-O cycles) mechanical
electrical AC 690 V AC 22A
440 V AC 23A
electrical AC 250 V AC 23A
Positive contact indication
Pollution degree
Protection
Add-on earth-leakage protection add-on Vigi module
combination with Vigirex relay
Additional indication and control auxiliaries
Indication contacts
Voltage releases
Installation and connection
Accessories
125 160
500 500
8 8
500 500
250 250
AC 22 A AC 23 A AC 22 A AC 23 A
125 125 160 160
125 125 160 160
125 125 160 160
125 100 160 125
2.1
330
1500
1500
580
c
10 000
5 000
5 000
5 000
c
III
c
c
1 OF + 1 SD
MN or MX
terminal shields
depth adjuster
90 x 120 x 82.5
120 x 120 x 80
1.1
1.4
rear connection
withdrawable (on chassis) front connection
rear connection
Electrical characteristics as per IEC 60947-3 and EN 60947-3
Conventional thermal current (A) Ith 60 C
Rated insulation voltage (V) Ui
Rated impulse withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational current le AC 50/60 Hz
220/240 V
380/415 V
440/480 V (2)
500/525 V
Compact NS100NA
660/690 V
DC
250 V (1 P)
500 V (2 P in series)
Short-circuit making capacity lcm (kA peak) minimum (switch-disconnector alone)
maximum (with protection
circuit breaker upstream)
Short-time withstand current lcw (A rms) 1s
3s
20 s
Suitability for isolation
Endurance (C-O cycles) mechanical
electrical AC 690 V AC 22A
440 V AC 23A
DC 250 V DC 23A
Positive contact indication
Pollution degree
Protection
Add-on earth-leakage protection add-on Vigi module
combination with Vigirex relay
Additional indication and control auxiliaries
Indication contacts
Voltage releases MX shunt release
MN undervoltage release
Voltage-presence indicator
Current-transformer module
Ammeter module
Insulation-monitoring module
Remote communication by bus
Device status indications (communicating auxiliary contacts)
Device remote operation (communicating motor mechanism)
Installation
Accessories terminal extensions and spreaders
terminal shields and interphase barriers
escutcheons
Dimensions (mm) fixed, front connection 2/3P
WxHxD 4P
Weight (kg) fixed, front connection 3P
4P
Source-changeover system (see section on source-changeover systems)
Manual source-changeover systems
Remote-operated and automatic source-changeover systems
(1) 2P in 3P case
(2) Suitable for 480 V NEMA
c c c
c c c
c c c
c c c
c c c
- c c
- c c
- c c
- c c
c c c
- c c
c c c
c c c
c c c
90 x 120 x 80 105 x 161 x 86 140 x 255 x 110
120 x 120 x 80 140 x 161 x 86 185 x 255 x 110
0.9 1.5 to 1.8 5.2
1.2 2.0 to 2.2 6.8
c (locking) c c
c c
25 25 25 25 25
17 17 17 17 17
4 4 4 4 4
c c c c c
10000 10000 10000 10000 10000
2000 2000 2000 2000 1000
2000 2000 2000 2000 1000
c c c c c
III III III III III
c
c
c
c
c
c
c
c
327 x 210 x 147
327 x 280 x 147
14
18
40 40 40 40
28 28 28 28
4.7 4.7 4.7 4.7
c c c c
6000 6000 6000 6000
1000 1000 1000 4000
1000 1000 1000 2000
c c c c
III III III III
c
c
c
c
350 x 420 x 160
350 x 535 x 160
23
36
Industry
c assembly lines.
c engine rooms on ships.
c critical auxiliaries in thermal power stations.
IMG0021
Infrastructure
c port and railway installations.
c runway lighting systems.
c control systems for military installations.
The rotary handles are padlocked with the devices in the OFF position.
The mechanism inhibits the two devices being closed at the same time, but does
allow for both to be open (OFF) at the same time.
Combinations of Normal and Replacement devices
All Compact NS100 to 1600 circuit breakers and switch-disconnectors with rotary
handles can be interlocked. Interlocking of a Compact NS100 to 630 with a
Compact NS630b to 1600 is not possible.
Interlocking of two toggle-controlled devices
Interlocking of a number of devices using keylocks
(captive keys)
Interlocking uses two identical keylocks with a single key. This solution enables
interlocking between two devices that are physically distant or that have
ON significantly different characteristics, for example between a low and a medium-
E21399
I
ON
I voltage device, or between Compact NS circuit breakers and switch-disconnectors.
I
ON A system of wall-mounted units with captive keys makes possible a large number
tripped
ON
I
reset
of combinations between many devices.
O
OFF
Interlocking of two devices with rotary handles Interlocking of two devices on a base plate
A base plate designed for two Compact devices can be installed horizontally or
vertically on a mounting rail. Interlocking is carried out on the base plate by a
mechanism located behind the devices. Access to the device controls and trip units
is not blocked.
E26766
ON
Combinations of Normal and Replacement devices
All manually operated Compact NS100 to 630 circuit breakers and switch-
I
ON
I reset
O
disconnectors can be interlocked.
Devices must be fixed or plug-in versions, with or without earth-leakage protection
OFF
O
or measurement modules.
OFF
push
to
trip
push
to
trip
E32699
QN
053060
3 2
1
053058
IN
E32700
LIN GER
0 . OFF MER O
UN =
N
0 . OFF
UR 0,5s
R
UN
N I 0,5s
ON /
I /O
ON / R
Test
OFF
1
UN =
/O
Test OFF
fault
fault
O stop
test
FFO
hsup O u
FFO man
I hsup
NO hsup
NO h
I
sup R
N
FFO
O
d e gr
FFO
O
ahcs
id degr
ahcs
id
352
10 352
10
B US
IN
LIN GER UN =
O
MER
N
UR
R
UN
N I
ON /
I R
ON / /O 1
OFF UN =
/O
OFF
fault
fault
auto
5
stop
test
u
man rator
STOP
gene
R
O
FFO
hsup
I
6
NO h
sup O
FFO
hsup
NO h
I
sup
FFO
O
d e gr
ahcs
id
FFO
O
degr
ahcs
id
352
10
Coupling accessory
This accessory may be used with the source-changeover system (with or without a
352
10
Integration of the circuit breaker or the There are two possibilities for the 100 to 630 A range:
switch-disconnector in a supervison system b communicating auxiliaries
requires either the communicating They replace the standard auxiliaries and connect directly to the Digipact bus.
Three equipment levels:
auxiliaries or the SC150 interface. Compact v communicating auxiliary contacts, comprising:
devices fit perfectly in the SMS Powerlogic - OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts
electrical installation management system - electronic module
by communicating using Digipact protocols. - prefabricated wiring.
v communicating auxiliary contacts and motor-mechanism module, comprising:
An external gateway offers communication - OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts
via other networks including: - motor-mechanism module (220 V AC) (1)
b Profibus - electronic module
b Ethernet - prefabricated wiring.
v communicating carriage switches for the chassis, comprising:
- CE / CD (connected/disconnected position) contacts
- electronic module
053172
- wiring connector.
b SC150 interface
Using the SC150 interface, it is possible to integrate a device equipped with non-
communicating auxiliaries into a supervison system.
The SC150 interface is used to connect:
v the auxiliary contacts on the circuit breaker (OF, SD, SDE, SDV, CD, CE)
v the remote-operation system (on, off, reset)
v the communication output for the STR53UE and STR43ME electronic trip units
equipped with the COM option
v an unassigned digital input.
(1) For voltages other than 220 V AC, use a standard motor-mechanism module (non-
communicating) together with an SC150 indication and control interface.
Software
Communication
interface RS 232C,Ethernet
RS 485
Communication
Bus
IN JBus
LIN GER
MERSV
pulsar BBus
com
com error
24V
Data concentrator
OK
error
1 3
DC150
N1
N1
Device
act
comp
0NH
NB25 Uimp 8kV.
Ui 750V. Icu
(kA)
Ue
(V) 100
0
220/245
70 2
65
380/41 ed
50 discharg
440 5
10
500/520
660/69
85
compactL
NS250 Uimp 8kV.
O OFF
Ui 750V. Icu(kA)
250 act
0% Icu Ue(V) 150
comp
Compact NS with
Ics=10 220/240 150
0NH
380/415 130
5...8 NB25 Uimp 8kV.
cat A
70
440
500
20
100
Ui 750V. Icu
600/690
Digipact Bus
-2 NEMA (kA)
UNE 0 250
250
D Ue
IEC947 BS CEI cat A TM Icu C 100
VDE 125/16 (V)
UTE push
to
100%
Ics = 250A/40
VDE 220/245
0 70 2
trip
UTE
947-2UNE NEMA 65
IEC
CEI 380/41 ed
5
BS
50 discharg
Im 10 440 5
10
6 500/520
85
compactL O OFF
1
.9
.8
8
x 250A I Ics=10
Ue(V)
220/240
380/415
150
130
5...8
x 250A auto O push
ON cat A 440
500
70
20
100
600/690
manu OFF -2 UNE
NEMA
0 250 D
push IEC947
VDE
BS CEI
125/16
250
cat A TM Icu C
100%
UTE push Ics = 250A/40
to VDE
UTE
trip 947-2UNE NEMA
: hard wire
: communication bus Compact with
communicating SC150
auxiliaries
Device identification
Address c c
Rating - -
Indication of status conditions
OF (on/off) c c
SD (trip indication) c c
SDE (fault-trip indication) c c
CE/CD (connected/disconnected position) c c
Controls
ON/OFF c c
LED reset c c
Protection settings
Reading of the protection settings c
Operating and maintenance aids
Measurements: currents c
Fault readings: type of fault c
Indications: operation counter c c
The COM option is required for integration For fixed circuit breakers, the COM option is made up of:
of the circuit breaker or switch-disconnector c a "device" communication module, installed behind the Micrologic control unit
in a supervision system. and supplied with its set of sensors (OF, SD, SDE micro-contacts for manually
operated devices; OF, SDE micro-contacts for electrically operated devices) and its
Compact uses the Digipact or Modbus kit for connection to a communicating motor-mechanism module.
communications protocol for full For withdrawable circuit breakers, the COM option is made up of:
compatibility with the SMS PowerLogic c a "device" communication module, installed behind the Micrologic control unit
electrical-installation management systems. and supplied with its set of sensors (OF, SD, SDE micro-contacts for manually
An external gateway is available for operated devices; OF, SDE micro-contacts for electrically operated devices) and its
kit for connection to a communicating motor-mechanism module.
communication on other networks: c a "chassis" communication module supplied separately with its set of sensors
c Profibus (CE, CD and CT contacts).
c Ethernet Status indication by the COM option is independent of the circuit breaker indication
contacts. These contacts remain available for conventional uses.
056431
Digipact "chassis"
E59437A
communication module
Communication Communication
bus bus
OF
SD OF
SDE SDE
3 3
1 1 5
056431
Modbus "device"
communication module I on
tripped
reset
F
0 OF
Communication Communication
bus ++ bus ++
CCM
modb
us
2 CCM
modb
us
2
+ +
CE
CE
CD
CD
CT
CT
C 4 C 4
C CT C CT
CE C CE
CD OF CD
OF
E45183
Modbus "chassis"
SD SDE
communication module SDE 3
3
1 5
1
Compact switch-disconnectors are compatible only with the Digipact COM option.
E47071
Compact circuit breakers are compatible with the Digipact or Modbus COM option.
Time Event Module The COM option may be used with all types of control units to:
Phase A-N Voltage - Harmonics Analysis
c identify the device
Phase 1-N
1,20
Harmonics(RMS)
c indicate status conditions
1,00
Fundamental: H1: 118.09
H2: 0.01
H3: 0.45
c control the device.
RMS:
H4: 0.03
RMS-H:
H5: 0.45
H6: 0.04
H7: 1.27
Depending on the different types of Micrologic (S, A) control units, the COM option
0,80 Peak: H8: 0.05
H9: 0.42
also offers:
% Fundamental
0,40
c analysis of the AC-power parameters for operating-assistance and maintenance
purposes
0,20
0,00
H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 switch-disconnector with circuit breaker with
Harmonics
communication bus communication bus
Ready ONLINE: DEMO No working system 9:30
Digipact Modbus Digipact Modbus
device identification
address c - S A S A
rating - - A A
type of device - -
type of control unit - - A A
type of long-time rating plug - - A A
status indications
OF (on/off) c - S A A
SD (trip indication) c - S A A
SDE (fault-trip indication) c - S A A
CE/CD (connected/ c - S A A
disconnected position)
controls
MX/XF ON/OFF - - S A A
spring charging - -
reset of the mechanical - -
indicator
protections settings
reading of protections settings A A
operating and maintenance aids
measurements
current A A
fault readings
type of fault A
Note.
See the description of the Micrologic control units for further details on protection.
Software
Communication
interface RS 232C,Ethernet
RS 485
Communication
Bus
IN JBus
LIN GER
MERSV
pulsar BBus
com
com error
24V
Data concentrator
OK
error
1 3
DC150
N1
N1
Device
Compact Compact
Devices
Circuit breakers equipped with Micrologic control units may be connected to either
a Digipact or Modbus communication bus. The information made available
depends on the type of Micrologic control unit (S, A) and on the type of
communication bus (Digipact or Modbus).
Switch-disconnectors may be connected exclusively to the Digipact communication
bus.
Communication bus
Digipact
The Digipact bus is the internal bus of the low-voltage switchboard in which the
Digipact communicating devices are installed (Compact with Digipact COM,
PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 data
concentrator (see the Powerlogic System catalogue).
Addresses
Addressing is carried out by the DC150 data concentrator.
Number of devices
The maximum number of devices that may be connected to the Digipact bus is
calculated in terms of communication points. These points correspond to the
amount of traffic the bus can handle. The total number of points for the various
devices connected to a single bus must not exceed 100.
If the required devices represent more than 100 points, add a second Digipact
internal bus.
Communicating device Number of points
DC150 data concentrator 4
Micrologic + Digipact COM 4
PM150 4
SC150 4
UA150 4
Length of bus
The maximum recommended length for the Digipact internal bus is 200 meters.
Bus power source
Power is supplied by the DC150 data concentrator (24 V)..
Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Compact with Modbus COM, PM300, Sepam,
Vigilohm, etc.), the baud rate (19200 is recommended), the volume of data
exchanged and the desired response time. The RS485 physical layer offers up to
32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device).
A drawout device uses two connection points (communication modules on the
device and on the chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20% ripple, insulation class II).
Communication interface
The Modbus bus may be connected to the central processing device in any of
three manners:
b direct link to a PLC. The communication interface is not required if the PLC is
equipped with a Modbus port;
b direct link to a computer. The Modbus (RS485) / Serial port (RS232)
communication interface is required;
b connection to a TCP/IP (Ethernet) network. The Modbus (RS485) / TCP/IP
(Ethernet) communication interface is required.
Software
To make use of the information provided by the communicating devices, software
with a Modbus driver must be used.
Micrologic utilities
This is a set of Modbus drivers that may be used with a PC to:
b display the variables (I, U, P, E, etc.) with the DDS (Data Display Software)
application;
b read/write the settings with the RSS (Remote Setting Software) application;
b remotely control (ON / OFF) the device with the CSS (Control Command
Software) application.
This software is available on request.
The COM option is required for integration For fixed circuit breakers, the COM option is made up of:
of the circuit breaker or switch-disconnector c a "device" communication module, installed behind the Micrologic control unit
and supplied with its set of sensors (OF, SD, SDE micro-contacts).
in a supervision system.
Status indication by the COM option is independent of the circuit breaker indication
Compact uses the Digipact or Modbus
contacts. These contacts remain available for conventional uses.
communications protocol for full
Digipact or Modbus "device" communication module
compatibility with the SMS PowerLogic This module is independent of the control unit. It receives and transmits information
electrical-installation management systems. on the communication network. An infra-red link transmits data between the control
An external gateway is available for unit and the communication module.
Consumption: 30 mA, 24 V.
communication on other networks:
c Profibus
E59438
c Ethernet Communication
bus
056431
Digipact "device"
communication module.
OF
SD
SDE
2
1 OFF
OFF
COM
module
056431
Modbus "device"
communication module 1 "Device" communication module
2 OF, SD, SDE "device" sensors
Compact switch-disconnectors are compatible only with the Digipact COM option.
E47071
Compact circuit breakers are compatible with the Digipact or Modbus COM option.
Time Event Module The COM option may be used with all types of control units to:
Phase A-N Voltage - Harmonics Analysis
c identify the device
Phase 1-N
1,20
Harmonics(RMS)
c indicate status conditions
1,00
Fundamental: H1: 118.09
H2: 0.01
H3: 0.45
c control the device.
RMS:
H4: 0.03
RMS-H:
H5: 0.45
H6: 0.04
H7: 1.27
Depending on the different types of Micrologic (S, A) control units, the COM option
0,80 Peak: H8: 0.05
H9: 0.42
also offers:
% Fundamental
0,40
c analysis of the AC-power parameters for operating-assistance and maintenance
purposes
0,20
0,00
H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 switch-disconnector with circuit breaker with
Harmonics
communication bus communication bus
Ready ONLINE: DEMO No working system 9:30
Digipact Modbus Digipact Modbus
device identification
address c - S A S A
rating - - A A
type of device - -
type of control unit - - A A
type of long-time rating plug - - A A
status indications
OF (on/off) c - S A A
SD (trip indication) c - S A A
SDE (fault-trip indication) c - S A A
protections settings
reading of protections settings A A
operating and maintenance aids
measurements
current A A
fault readings
type of fault A
Note.
See the description of the Micrologic control units for further details on protection.
E58520
Sealable terminal
shield
Interphase barriers
Voltage release
Auxiliary contact
DIN-rail
adapter
Sealable terminal
shield
E58519
pact
com
NH
NB250Uimp 8kV.
V.
Ui 750 Icu
(kA)
Ue
(V) 100
70
220/240
380/415
440
500/525
660/690
65
50
10
85
Sealable terminal
250
Ics=
100%
cat A
Icu
-2 CEI NEMA
shield
UNE
947BS
IECVDE
UTE
125/160
push
to
trip
NB400/600
connectors
Terminal extensions
pact
com N
NB400 Uimp
8kV.
. Icu
Ui 750V (kA)
Ue 35
(V)
240 22
220/
415 18
380/
440
Interphase barriers
cat A
Icu
50%
Ics =
400
push
to
trip
Auxiliary
contact
Rear insulating
screens
Voltage release
Sealable terminal
shield
Installation
Compact NB50 and 100 circuit breakers may be mounted vertically, horizontally or
E59278
E58524
E58526
E58525
Mounting on a backplate Mounting on rails Mounting on DIN rail (with
adapter)
The Compact NB50 to 100 devices are equipped as standard with terminals
comprising snap-in nuts with screws (M8) for direct connection to insulated bars or
cables with lugs.
Terminal shields
Insulating accessories used for protection against
direct contact with power circuits (degree of protection
IP 40, IK07). They are supplied with sealing
accessories.
Interphase barriers
Safety accessories for maximum insulation at the
power-connection points.
c they clip easily onto the circuit breaker.
c not compatible with terminal shields.
Terminal shields
E58528
Interphase barriers
Contacts are available in three versions that all comply with international standard
IEC 60947-5 and offer the following indication functions:
c OF (ON/OFF): indicates the position of the circuit-breaker main contacts
c SD (trip indication): indicates that the circuit-breaker has tripped due to:
v overload
v short-circuit
Common-point changeover contacts can be used to remote
circuit-breaker status information for indications, electrical
v operation of a voltage release.
locking, relays, etc. Returns to de-energised state when the circuit breaker is reset.
c OF + SD
Electrical characteristics of indication contacts
Rated thermal current (A) 6
Minimum load 10 mA at 24 V
Utilisation category (IEC 60947-5-1) AC12 AC15 DC12 DC14
Operational 24 V 6 6 2.5 1
current (A) 48 V 6 6 2.5 0.2
110 V 6 5 0.8 0.05
220/240 V 6 4 - -
250 V - - 0.3 0.03
380/440 V 6 3 - -
660/690 V 6 0.1 - -
Remote tripping
E59277A
MX shunt release
The MX release trips the circuit breaker when the control voltage rises above 0.7 x Un.
Control signals can be of the impulse type (u 20ms) or maintained.
Operation
When the circuit breaker has been tripped by a release, it must be reset locally.
MN or MX tripping has priority over manual closing. In the presence of a standing
MX shunt release trip order, the main contacts cannot be closed, even temporarily.
Mechanical characteristics
c endurance: 50% of the rated circuit-breaker mechanical endurance
c releases snap in behind the front of the circuit breaker
c connection using wires with a cross-sectional area of up to 1.5 mm2, to a built-in
terminal block.
Electrical characteristics
c consumption:
v pick-up (MX): < 10 W
v seal-in (MN): < 5 VA.
c response time < 50 ms.
Installation
Compact NB250 to 600 circuit breakers may be mounted vertically, horizontally or
E59278
E58529
E58530
Mounting on back plate Mounting on rails
Connection
E58531
E58534
Compact NB50 and 100 circuit breakers are equipped
as standard with terminals receiving snap-in nuts and Right-angle terminal
screws (M8 for NB250, M10 for NB400 and 600) for extensions
direct connection of insulated bars or cables with lugs.
Terminal extensions (right-angle, edgewise,
spreaders) are available to solve all connection
E58535
problems. For Compact NB600, connection most often
requires the 52.5 mm or 70 mm pitch spreaders.
Lugs
Straight terminal extensions
Lugs are different for copper and aluminium cables.
for NB250
They are supplied with interphase barriers and are
compatible with the long terminal shields.
c the small lugs for copper cables may be used for
E58536
E58539
Spreaders
E54471
Front connection of bare cables
E58540
Bare-cable connectors for Compact NB circuit
breakers may be used for both copper and aluminium
cables.
1-cable connectors for Compact NB250
The connectors snap directly onto the device
terminals or clip onto right-angle and straight terminal Distribution connector for
extensions as well as spreaders. Compact NB250
E54468
1-cable and 2-cable connectors for Compact
NB400 and 600
The connectors are screwed to device terminals or
right-angle terminal extensions. 1-cable connector for
Distribution connectors for Compact NB250 Compact NB250
These connectors are screwed directly to device
E54470
terminals. Interphase barriers are supplied with
distribution connectors, but may be replaced by long
E54469
terminal shields. Each connector can receive six
cables with cross-sectional areas ranging from 1.5 to
35 mm2 each. 1-cable and 2-cable
connectors for Compact
NB400 and 600
E58541
direct contact with power circuits (degree of protection
IP 40, IK07). They are supplied with sealing
accessories.
Terminal-shield selection
c Mandatory for voltages > 400 V
c Special shield for Compact NB400 and 600 with
spreaders. Terminal shields
Interphase barriers
E58542
Interphase barriers
E58543
Indication contacts
These common-point changeover contacts can be used to remote circuit-breaker
status information for indications, electrical locking, relays, etc.
They comply with international standard IEC 60947-5.
Functions
c OF (ON/OFF): indicates the position of the circuit-breaker contacts
c SD (trip indication): indicates that the circuit-breaker has tripped due to:
v overload
v short-circuit
v operation of a voltage release
Indication contacts v operation of the push-to-trip button
Returns to de-energised state when the circuit breaker is reset.
c SDE (fault trip indication): indicates that the circuit-breaker has tripped due to:
v overload
v short-circuit
Returns to de-energised state when the circuit breaker is reset.
Installation :
c One model serves for all indication functions, depending on where it is fitted in
the circuit breaker. The contacts snap into slots behind the front of the circuit
breaker. On a Compact NB250N, the SDE function requires the SDE actuator.
Electrical characteristics of indication contacts
Rated thermal current (A) 6
Minimum load 10 mA at 24 V
Utilisation category (IEC 60947-5-1) AC12 AC15 DC12 DC14
Operational 24 V 6 6 2.5 1
current (A) 48 V 6 6 2.5 0.2
110 V 6 5 0.8 0.05
220/240 V 6 4 - -
250 V - - 0.3 0.03
380/440 V 6 3 - -
660/690 V 6 0.1 - -
Remote tripping
044313
E58544
E58545
Locking of the toggle using a Locking of the toggle using a
removable device. fixed device.
Front-panel escutcheons
These optional auxiliaries, mounted on the front panel, ensure a degree of
protection IP 40, IK 07.
E23936
E58546
Sealing accessories
This option includes the elements required to fit lead seals to prevent:
c front removal
c access to auxiliaries
c terminal-shield removal
c access to power connections.
E18596
Sealing accessories
E58516
Sealable terminal
shield
Direct rotary
handle
Auxiliary
com
pact
H-M
A
NS 80 Uimp 8kV
Ui75
0V.
Ue (V)
.
Icu (kA)
100
contact
70
220/240 65
380/415 25 ON
440 6
500/525 10 I
660/690
250
cat A Icu
100%
Ics =
DIN-rail
push
to
2 UNE
947. BS CEI trip
IEC
VDE
UTE
plate
push O
to
trip OFF
1
2
push
to
trip
ON
I
ed
tripp 5...8
Voltage release
C2
SHT z
C1
MX/
/50-60H
240V
220-
t
rese
O
OFF
Auxiliary
contact
E58517
pact
com
125E .
NSA p 6kV
V. Uim (kA)
U 500 Icu
25
Ue (V) 16
220/240 10
380/415 5
440
125
Icu
50%
Ics =
UNE
947.2 CEI
IEC VDE BS
UTE
45 mm front
E58518
Sealable terminal
shield
com
NSA
pact
125E
p 6kV
V. Uim (kA)
.
Auxiliary
U 500
Ue (V)
220/240
380/415
440
Icu
25
16
10
5
contact
125
Icu
Ics = 50%
UNE
947.2 CEI
IEC VDE BS
UTE
ON
I
ed
tripp 5...8
C1
MX/
C2
SHT z
Voltage release Extended rotary
220-
240V
/50-60H
rese
t
O
handle
OFF
Sealable terminal
shield
horizontally or flat on their back without any derating of characteristics. They are
designed for easy installation in the various types of switchboards of each market
and country.
Mounting on a DIN rail is possible using a special adapter.
The NSA160 circuit breaker may be mounted exclusively on a DIN rail.
Installation positions
These three circuit breakers are available in the fixed, front-connection version.
E43597
E43596
E43595
OFF
push
to
trip
E39432
breakers are equipped as standard with connectors
for bare copper or aluminium cables from 1.5 to 70
mm2.
Distribution connector
This connector screws directly to the standard
connectors. It is used to connect up to three cables: Distribution connector
c flexible cables from 1 to 10 mm2
c rigid cables from 1.5 to 16 mm2
c with crimped or self-crimping ferrules from 1.5 to 4 mm2.
Terminal shields
Indication contacts
A single type of contact, complying with the IEC 60947-5 international
recommendation, provides different indication functions, depending on where it is
inserted in the device.
c OF (ON/OFF) - indicates the position of the circuit breaker contacts
c SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault (Compact NSC100N and NSA160)
v operation of a voltage release.
Indication contacts Returns to de-energised state when the circuit breaker is reset.
c SDV (earth-leakage fault indication) - inserted in the Vigi module on Compact
Common-point changeover contacts provide remote circuit-
NSC100N and NSA160 devices, it indicates that the circuit breaker has tripped due
breaker status information. They can be used for indications,
electrical locking, relaying, etc.
to an earth fault. Returns to de-energised state when the circuit breaker is reset.
All the above auxiliary contacts are also available in low-level versions capable of
switching very low loads (e.g. for the control of PLCs or electronic circuits).
Characteristics
Contacts Standard Low level
Rated thermal current (A) 6 5
Minimum load 10 mA at 24 V 1 mA at 4 V
Utilisation category (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14
Operational 24 V 6 6 2.5 1 5 3 5 1
current (A) 48 V 6 6 2.5 0.2 5 3 2.5 0.2
110 V 6 5 0.8 0.05 5 2.5 0.8 0.05
220/240 V 6 4 - - 5 2 - -
250 V - - 0.3 0.03 5 - 0.3 0.03
380/440 V 6 3 - - 5 1.5 - -
054550
Remote tripping
MX or MN voltage releases are used to trip the circuit breaker.
MN undervoltage release
This release trips the circuit breaker when the control voltage drops below a
tripping threshold:
c tripping threshold between 0.35 and 0.7 times the rated voltage
c circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.
Circuit breaker tripping by an MN release meets the requirements of standard
IEC 60947-2.
MX or MN voltage release
Time-delay unit for an MN release (Compact NS80H-MA)
Eliminates nuisance tripping due to transient voltage dips lasting i 200 ms :
It is used in conjunction with:
c a 250 V DC MN release, control voltage 220/240 V AC
c a 48 V DC MN release, control voltage 48 V AC.
MX shunt release
Trips the circuit breaker when the control voltage rises above 0.7 x Un.
Control signals can be of the impulse type (u 20 ms) or maintained.
Operation
When the circuit breaker has been tripped by an MN or MX release, it must be
reset locally.
MN or MX tripping takes priority over manual closing.
In the presence of a standing trip order, closing of the contacts, even temporary,
is not possible.
Mechanical characteristics
c endurance is equal to 50% of the mechanical endurance of the circuit breaker
c the releases clip in behind the front cover
c connection using wires up to 1.5 mm2 to integrated terminal blocks.
Electrical characteristics
c consumption:
v pick-up (MX): < 30 VA
v seal-in (MN): < 5 VA
c response time: < 50 ms.
E58552
Toggle locking using a removable device
Outgoing-circuit identification
Compact NS80H-MA and NSC100N devices come with clip-in labels for hand-
written indications.
It is also possible to use pre-printed Telemecanique labels (part number AB1-** (8 digits).
E18595
.P
DE P
P O
D E P. P O M push
to
trip
Identification accessories
E58523
Sealable terminal
shield
que
dilectri rnes
Voltage-presence
test
avant ce cache-bo
enlever c test
dielectri shield
before terminal
this
L3
remove L2
L1
z
50/60H
0V -
indicator
220/60
Rear connector
Connectors
One-piece
spreader
Interphase barriers
2
arged
disch
compa L
0
ct
1
I
5..
.8 auto O push
ON
OFF
push
manu
ct
compa L
0
pact ON NS25 Uimp 8kV.
Ui 750V. Icu(kA)
com
50NH I Ue(V) 150
reset
0
NB2 . Uimp 8kV. 220/245 150
130
380/41
Ui 750V Icu 440
70
(kA) 20
Motor-mechanism
500 0
Ue
(V) 100
600/69
250
100
push
to
O
220/2
40
15
70
65
cat A
Ics =
100%
Icu trip OFF
380/4 UTE
VDE
50 947-2UNE NEMA
440 IEC
CEI
25 10 BS
500/5
90 85
module
660/6
250 Icu
Direct rotary
00%
Ics=1
cat A act
comp L
0
47-2 UNE
NEMA
D NS25 Uimp 8kV.
IEC9 BS CEI 160 TM 250 Ui 750V. Icu(kA)
UTE
VDE 125/ 250A/
40C
push Ue(V) 0 150
reset
handle
to 220/245 150
trip 380/41 130
70
5 440
Im 10 20
500 0
6
600/69
250
100
push
to
O
OFF
Ir 9 cat A Icu trip
100%
7 Im Ics =
8 Ir UTE
VDE
.8 947-2UNE NEMA
1 x 250A IEC
BS
CEI
.9
x 250A
Rear insulating ON
I
Voltage release
80
40 120
0
A
test
enlever
dilectri
before this
que
dilectri le
avant ce couverc
c test
cover
Ammeter module
remove
vigi
NS 250 V-50/60
Hz
-25
200/525
310
5
50
t(ms)
60
0 H
vigiM
6
10 2 4
3
Current-transformer
1
In(A)
0,3 t=0)
0,03(
HS
90 %Ir
160/25
0A
STR
22 SE
module
105 test
Im
5 alarm
Ir 4 6 + -
.9 3
Insulation-monitoring
0A .85 .95
In=25 8 Ir Im
.8 2
.98 10
1.5
.7 xIr
1
.63
xIn
module
Trip unit
Sealable terminal
shield
E58715
Sealable terminal
shield
que
dilectri rnes
test
Voltage-presence
avant ce cache-bo
enlever c test
dielectri shield
before terminal
this
L3
remove L2
L1
z
50/60H
0V -
indicator
220/60
Rear connectors
Connectors for
withdrawable One-piece Connectors
devices spreader
Interphase barriers
Plug-in base
2
arged
disch
compa L
0
ct
I 250
cat A Icu
100%
Ics =
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS
Control-wire
1
I
Chassis side 5..
.8
manu
auto O
push
OFF
push
ON
Ue(V)
220/245
380/41
ct
0
)
Ui 750V. Icu(kA
150
150
130 reset
plate
70
440
(kA) 20
500 0
Ue
100
600/69 100
push O
Motor-mechanism
(V) 250 to
40 70 cat A
OFF
1
Icu trip
2 220/2 Ics =
100%
15 65
3 380/4 UTE
VDE
50 947-2UNE NEMA
440 IEC
CEI
4 25 10 BS
5 500/5
90 85
6 660/6
module
250 Icu
Direct rotary
7 00%
8 Ics=1
9 cat A
act
comp L
0
47-2 UNE
NEMA
D NS25 Uimp 8kV.
IEC9 BS CEI 160 TM 250 Ui 750V. Icu(kA)
UTE
VDE 125/ 250A/
40C
push Ue(V) 0 150
reset
to 150
handle
220/245
trip 380/41 130
70
5 440
Im 10 20
500 0
6
600/69
250
100
push
to
O
OFF
Ir 9 cat A Icu trip
100%
7 Im Ics =
8 Ir UTE
VDE
.8 947-2UNE NEMA
1 x 250A IEC
BS
CEI
.9
x 250A
ON
I
0
A
test
avant ce couverc
enlever
dilectri
que
dilectri le
c test
cover
Ammeter module
before this
remove
vigi
NS 250 V-50/60
Hz
-25
200/525
310
5
50
t(ms)
60
0 H
vigiM
6
10 2 4
3
Current-transformer module
1
In(A)
0,3 t=0)
0,03(
HS
160/250A 22 SE
STR
90 %Ir
105 test
Im
5 alarm
Ir 4 6 + -
.9
Insulation-monitoring
0A 3
.85 .95
In=25 8 Ir Im
.8 2
.98 10
1.5
.7 xIr
1
.63
xIn
module
Trip unit
Sealable terminal
shield
Installation
045345
E58529
E58714
E58530
Fixed Compact NS250H
E59278
connections
c allow for the addition of future circuits at a
later date.
E21019
041632
front connections
c safety trip, installed on the circuit breaker, that causes automatic tripping if the
circuit breaker is ON, before engaging or withdrawing it. The safety trip does not
prevent circuit breaker operation, even when it has been removed.
c mandatory short terminal shields.
Installation positions Accessories
Insulating accessories can be used to:
c protect against direct contact
c increase insulation between phases.
E21282
still on the chassis and may still be operated
(ON, OFF, push-to-trip).
c the circuit breaker may be locked using
1 to 3 padlocks (shackle diameter 5 to 8 Connected Disconnected Removed
mm), to prevent connection.
The chassis is made up of two side plates installed on the base and two other
c the auxiliaries can be tested (with manual
plates mounted on the circuit breaker.
auxiliary connector). Accessories
c auxiliary contacts for installation on the fixed part, indicating the connected and
disconnected positions
041879
c toggle collar for circuit breakers with a toggle mounted through a front panel,
intended to maintain the degree of protection whatever the position of the circuit
breaker (supplied with a toggle extension)
c keylock which, depending on the bolt fitted, can be used to:
v prevent insertion for connection
v lock the circuit breaker in the connected or disconnected positions.
c telescopic shaft for extended rotary handles.
Installation positions
E58716
E58718
E58534
Front connection of bars or cables
E58531
Right-angle terminal
with lugs extensions
The Compact NS100 to NS630 devices are equipped
as standard with terminals comprising snap-in nuts
with screws (M8 for NS100 to 250, M10 for NS400 to
E58535
630) for direct connection to insulated bars or cables
with lugs.
Additional terminal extensions (right-angle, edgewise,
spreaders) are available for all connection Straight terminal extensions
requirements. Spreaders (52.5 or 70 mm pitch) may for NS100 to 250
be fitted on the Compact NS400 to 630.
Lugs
Lugs are different for copper and aluminium cables.
They are supplied with interphase barriers and are
E58536
compatible with the long terminal shields.
c the small lugs for copper cables may be used for
cables with the following cross-sectional areas:
v 120, 150 or 185 mm2 (NS100 to 250) Edgewise terminal
v 240 or 300 mm2 (NS400 to 630). extensions for NS400 to 630
E58720
E58537
cables with the following cross-sectional areas:
v 150 or 185 mm2 (NS100 to 250)
v 240 or 300 mm2 (NS400 to 630).
Crimping by hexagonal barrels.
Spreaders
Spreaders increase the pitch of the terminals. Small lug for copper cables
They are not compatible with terminal shields on the
Compact NS100 to 250.
The one-piece spreader increases the pitch, thus
E58538
making it possible to use the connection accessories
of a larger device (e.g. a Compact NS100 to 250 can
be fitted with the accessories of a Compact NS400 to
630). The one-piece spreader also provides protection
against direct contact (see page 101).
E58532
Spreaders
E58721
E58533
One-piece spreader
E54468
Bare-cable connectors for Compact NS devices may
be used for both copper and aluminium cables.
1-cable connectors for Compact NS100 to 250 1-cable connector
The connectors snap directly on to the device for NS100 to 250
terminals or clip onto right-angle and straight terminal
E58540
E54469
extensions as well as spreaders.
1-cable and 2-cable connectors for Compact
NS400 to 630 1-cable connector
The connectors are screwed to device terminals or for NS400 to 630
right-angle terminal extensions.
E54470
Distribution connectors for Compact NS100 to 250
These connectors are screwed directly to device
terminals. Interphase barriers are supplied with
distribution connectors, but may be replaced by long
terminal shields. Each connector can receive six
2-cable connector
cables with cross-sectional areas ranging from 1.5 to for NS400 to 630
35 mm2 each.
E54471
Polybloc distribution block for Compact NS100 to 630
E58722
E54472
Rear connection
E54456
E58724
Four positions
E58726
Connection
of bare cables
to NS100 to 250.
E58717
E58727
E58718
Front connection Front connection with Rear connection
spreaders
E58719
All terminals may be equipped with bare-cable connectors. See the Connection of
fixed devices section.
E58729
E58728
One-piece spreader
E58730
Connection of large cables may require an increase in
the distance between the device terminals. The one-
piece spreader is an accessory that can also be fitted
on Interpact INS switch-disconnectors. It offers the
following features:
c increases the pitch of the circuit-breaker terminals to
correspond to that of the next largest frame size.
c compatible with all the connection accessories
available for the next largest frame size (connectors,
One-piece spreader
terminal extensions, etc.)
c enhances insulation between phases in comparison
with standard spreaders.
NS100 to 250 NS400 to 630
Pitch without 35 45
spreaders (mm)
Pitch with standard 45 52.5 or 70
spreaders (mm)
Pitch with one-piece 45 70
spreader (mm)
Mounting
When equipped with a one-piece spreader, Compact
NS circuit breakers may be installed either at the back
of a switchboard or on the front panel with a raiser.
c devices with different frame sizes can thus be
aligned in the switchboard
c the same mounting plate can be used for all devices
(including Interpact INS switch-disconnectors).
E58731
E58732
E58541
Terminal shields
Terminal shields are sealable insulating accessories
used for protection against direct contact with power
circuits (degree of protection IP40, IK07). They are
supplied with sealing accessories.
Terminal-shield selection
c fixed circuit breaker, front connection - long terminal
shields
c fixed circuit breaker, rear connection - short terminal
shields. Terminal shields
c for voltages u 500 V, terminal shields are mandatory.
c for voltages > 600 V, special connection kit with
terminal shields and insulating screens
c for Compact NS400 to 630 with spreaders, special
E58542
Compact NS equipped with terminal shields. terminal shields for spreaders
c for withdrawable circuit breaker (plug-in and chassis
type), short terminal shields on the device are
mandatory. Terminal shields on the base are possible.
Long terminal shields for plug-in bases are used to:
c protect against direct contact with power circuits
(degree of protection IP40, IK07)
c increase insulation between phases.
Insulating accessories for plug-in bases include:
c an adapter offering the same connection
possibilities as the circuit breaker Interphase barriers
c long terminal shields for the plug-in base.
Interphase barriers
Safety accessories for maximum insulation at the
E58543
power-connection points:
c they clip easily onto the circuit breaker
c not compatible with terminal shields
c special version for plug-in bases.
E18585
SDV
Compact NS100/160/250
E28444
rotary handle
SDV
E21398
connector 2 connector 3
connector 1 OF2/SDV OF3/SDV
connector 2 COM
OF1 SDE/MT connector 1 OF2
SD MT OF1 T
SDE/MT
MN/MX SD MT
MN/MX
Compact NS100 to 250 Compact NS400 to 630
Each auxiliary is equipped with a terminal block with Nine-wire manual auxiliary
numbered terminals for connection of wires up to: connector
c 1.5 mm2 for auxiliary contacts and voltage releases
c 2.5 mm2 for the motor-mechanism module.
Indication contacts
Common-point changeover contacts are used to remote circuit-breaker status
information and can thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
c OF (ON/OFF) - indicates the position of the circuit breaker contacts
c SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault
Changeover contacts v operation of a voltage release
v operation of the push to trip button
v disconnection when the device is ON.
Returns to de-energised state when the circuit breaker is reset.
All the auxiliary contacts opposite are also available
c SDE (fault indication) - indicates that the circuit breaker has tripped due to:
in low-level versions capable of switching very low
v an overload
loads (e.g. for the control of PLCs or electronic
v a short-circuit
circuits).
v an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
c SDV (Earth-leakage fault indication) - indicates that the circuit breaker has
tripped due to an earth fault.
Returns to de-energised state when the circuit breaker is reset.
c CAM (early-make or early-break function) - indicates the position of the rotary
handle. Used in particular for advanced opening of safety trip devices (early break)
or to energise a control device prior to circuit-breaker closing (early make).
c CE / CD (connected/disconnected position) - microswitch type carriage switches
for withdrawable circuit breakers
Installation
c OF, SD, SDE and SDV functions - a single type of contact provides all these
different indication functions, depending on where it is inserted in the device. The
contacts clip into slots behind the front cover of the circuit breaker (or the Vigi
module for the SDV function).
The SDE function on a circuit breaker equipped with a thermal-magnetic trip unit
requires the SDE actuator.
c CAM function - the contact fits into the rotary-handle unit (direct or extended).
c CE / CD (connected/disconnected) function - two parts must be fitted on the fixed
and moving parts of the chassis.
Electrical characteristics of auxiliary contacts
Contacts Standard Low level
Rated thermal current (A) 6 5
Minimum load 10 mA at 24 V 1 mA at 4 V
Utilisation cat. (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14
Operational 24 V 6 6 2.5 1 5 3 5 1
current (A) 48 V 6 6 2.5 0.2 5 3 2.5 0.2
110 V 6 5 0.8 0.05 5 2.5 0.8 0.05
220/240 V 6 4 - - 5 2 - -
250 V - - 0.3 0.03 5 - 0.3 0.03
380/440 V 6 3 - - 5 1.5 - -
660/690 V 6 0.1 - - - - - -
Remote tripping
MX or MN voltage releases are used to trip the circuit breaker.
MN undervoltage release
This release trips the circuit breaker when the control voltage drops below a
tripping threshold:
c tripping threshold between 0.35 and 0.7 times the rated voltage
c circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.
Circuit breaker tripping by an MN release meets the requirements of standard
MX or MN voltage release IEC 60947-2.
Time-delay unit for an MN release
Eliminates nuisance tripping due to transient voltage dips lasting 200 ms.
It is used in conjunction with:
c a 250 V DC MN release, control voltage 220/240 V AC
c a 48 V DC MN release, control voltage 48 V AC.
MX shunt release
Trips the circuit breaker when the control voltage rises above 0.7 x Un.
Control signals can be of the impulse type (u 20 ms) or maintained.
Operation
When the circuit breaker has been tripped by an MN or MX release, it must be
reset locally.
MN or MX tripping takes priority over manual closing.
In the presence of a standing trip order, closing of the contacts, even temporary,
is not possible.
Mechanical characteristics
c endurance is equal to 50% of the mechanical endurance of the circuit breaker
c the releases clip in behind the front cover
c connection using wires up to 1.5 mm2, to integrated terminal blocks.
Electrical characteristics
c consumption:
v pick-up (MX): < 10 VA
v seal-in (MN and MNR): < 5 VA.
c response time: < 50 ms.
Motor-mechanism module
When equipped with a motor-mechanism module, Compact NS circuit breakers
feature very high mechanical endurance as well as easy and sure operation:
c all circuit-breaker indications and information remain visible and accessible,
including trip-unit settings and indications;
c suitability for isolation is maintained and padlocking remains possible;
c double insulation of the front face.
Applications
c local motor-driven operation, centralised operation, automatic distribution control
c normal/standby source changeover or switching to a replacement source to
optimise energy costs
c load shedding and reconnection to optimise energy costs
c synchrocoupling.
Compact NS250H with motor mechanism Automatic operation
c circuit-breaker ON and OFF controlled by two impulse-type or maintained control
signals
1 2 3 4 5 6 c automatic spring charging following voluntary tripping (by MN or MX),
with standard wiring
c mandatory manual reset following tripping due to an electrical fault.
E21006
Manual operation
compact c transfer to manual mode using a switch (9) with possibility of remote mode
NS400 H 2
Ui 750V. Uimp 8kV.
Ue Icu
indication
(V)
220/240
(kA)
100 c circuit-breaker ON and OFF controlled by 2 pushbuttons
380/415 70
440
500/525
65
50 c recharging of stored-energy system by pumping the lever 9 times
600/690 20
c padlocking in OFF position.
cat A
O OFF charged
Installation and connection
Ics = 100% Icu
IEC 947-2
UTE VDE BS CEI
All installation (fixed, plug-in/withdrawable) and connection possibilities are
UNE NEMA
In = 400A maintained.
Motor-mechanism module connections are made behind its front cover to
integrated terminals, for cables up to 2.5 mm2.
manu auto O I 1 Accessories
push OFF push ON
c keylock for locking in OFF position
c operations counter for the Compact NS400 and NS630, indicating the number of
ON and OFF cycles. The counter must be installed on the front of the motor-
mechanism module.
10 9 8 7
Characteristics
Motor mechanism MT100 to MT630
1 contact position indicator (suitability for isolation) Response time (ms) opening < 600
2 outgoing-circuit identification labels closing < 80
3 spring status indicator (charged, discharged) Rate cycles/minute max. 4
4 locking device (keylock) Control voltage (V) DC 24/30 - 48/60
5 locking device (OFF position), using 1 to 3 padlocks, 110/130 - 250
shackle diameter 5 to 8 mm, not supplied AC 50/60 Hz 48 (50 Hz) - 110/130
6 manual spring-charging lever 220/240 - 380/440
7 I (ON) pushbutton Consumption (1) DC (W) opening i 500
8 O (OFF) pushbutton closing i 500
9 manual/auto mode selection switch. The position of this AC (VA) opening i 500
switch can be indicated remotely closing i 500
10 operations counter (Compact NS400/630)
Electrical endurance
Circuit breaker + motor-mechanism module, in thousands of operations
(IEC 60947-2), at 440 V.
E21300
50
40
30 NS100
20 NS160
15
10 NS250
6 NS400
4 NS630
Current-transformer module
This module enables direct connection of a measurement device such as an
ammeter or a Digipact power meter (not supplied).
Compact NS630L with voltage-presence indicator Installation
c directly on the downstream circuit-breaker terminals
c degree of protection IP40, IK04
c class II insulation between front and the power circuits
041892
This module detects and indicates an insulation drop on a load circuit (TN-S or TT
systems).
Operation is identical to that of a Vigi module, but without circuit-breaker tripping.
Indication by a red LED in front.
An auxiliary contact may be installed for remote insulation-drop indications.
Installation
c directly on the downstream circuit-breaker terminals
c degree of protection: IP40, IK04
c double insulation of the front face.
Electrical characteristics
c settings: 100, 200, 500 and 1000 mA
c accuracy: -50 +0%
c time delay following drop: 5 to 10 seconds
c AC-system voltage: 200 to 440 V AC and 440 to 550 V AC.
Communication
053172
Locking systems
Locking in the OFF position guarantees isolation as per IEC 60947-2.
Padlocking systems can receive up to three padlocks with shackle diameters
ranging from 5 to 8 mm (padlocks not supplied).
Control device Function Means Required
accessories
Toggle lock in OFF position padlock removable device
lock in OFF or padlock fixed device
ON position
Direct rotary handle lock in OFF position padlock
keylock locking
device + keylock
MCC rotary handle lock in OFF position padlock
Rotary handle lock in OFF position padlock
Extended rotary handle lock in OFF position, keylock keylock
door opening prevented
Motor mechanism lock in OFF position, padlock
motor mechanism keylock locking device
locked out (keylock incorporated)
E58544
E58545
E18620
ON
I
pr
of
al
ux
O
OFF
Locking of the toggle using a Locking of the toggle using a Locking of the rotary handle
removable device fixed device using a padlock or a keylock.
Individual enclosures
Compact NS and Vigicompact NS devices with two, three or four poles may be
installed in individual enclosures.
All fixed, front connections are possible, except right-angle and edgewise terminal
extensions. Spreaders may be installed in the enclosures intended for Interpact
Compact and Vigicompact NS250 to 630 devices.
There are two models of enclosures:
c heavy-duty metal individual enclosure, with:
v metal enclosure
v door with keylock and cut-out for rotary handle
v direct rotary handle (CNOMO, IP 55, IK 08)
v device mounting plate
v removable plate (without holes) for cable entry through bottom.
c heavy-duty insulating individual enclosure, with:
v insulating enclosure
v transparent cover, screwed, lead sealable, with cut-out for rotary handle
v extended rotary handle
v device mounting plate
v removable plates (without holes) for cable entry through bottom and/or top.
Dimensions (W x H x D in mm)
c metal enclosures: W D
Heavy-duty insulating individual enclosure for Compact NS v Compact NS100 to 160: 300 x 400 x 200
v Vigicompact NS100 to 160: 400 x 500 x 200
E44458
v Compact NS250 to 400: 400 x 600 x 200
v Compact NS630: 600 x 800 x 275
v Vigicompact NS250 to 630: 600 x 800 x 275
c insulating enclosures: H
v Compact/Vigicompact NS100 to 160: 270 x 360 x 235
v Compact NS250: 270 x 540 x 235
v Compact NS400 to 630: 360 x 720 x 235
v Vigicompact NS250 to 630: 360 x 720 x 235
Escutcheons
E21265
Escutcheons are an optional feature mounted on the
switchboard door. They increase the degree of
protection to at least IP40, IK07.
E23935
E23936
E23938
ON
I
O
OFF
push
to
trip
80
40 120
0
A
E18595
.P
DE P
P O
D E P. P O M push
to
trip
Identification accessories
Sealing accessories
This option includes the elements required to fit lead seals to prevent:
c front removal
c rotary-handle removal
c opening of the motor-mechanism module
c access to auxiliaries
c access to trip-unit settings
c trip-unit removal
c access to earth-leakage protection settings
c terminal-shield removal
c access to power connections.
E18596
Sealing accessories
E59224
Sealable terminal
shield
Phase barriers
Connection kit
for connectors Vertical connection
adapter
Spreader
Phase
barriers
Rear connectors Spreader
Auxiliary contact
Voltage release
I on
I ON
push
O OFF
disch
arged
reset
0 OF
F
Direct rotary
handle
Electrical control with tripped
Extended rotary
handle
Communications
module
Connection kit
for connectors
Sealable terminal
shield
Escutcheon
Vertical connection
adapter
Spreader
Rear connectors
Spreader
Auxiliary contact
Voltage release
Chassis with front or
rear connection
I on
OOFF
I ON
push
Manual operation
push
d
trippe
arged
disch
O OFF
reset
F
I on 0 OF
d
012
53 trippe
reset
0 OF
F Direct rotary
Electrical operation handle
I
ON
Communications tripped
handle
Installation
E45151
Fixed configuration
Compact NS630b to 1600 circuit breakers may be installed vertically, horizontally
or flat on their back without any derating of characteristics.
E59226A
E59227A
Fixed Compact NS800H
E59278
E59231
3
4
5
6
7
8
1
9
10
2
1 mismatch protection
2 door interlock
3 racking interlock
4 keylock locking
5 padlock locking
6 position indicator
7 chassis front plate (accessible with cubicle door closed)
8 crank entry
9 reset button
10 crank storage
E59235
c mixed connections
c a combination of front and rear
connections.
Rear connection
Horizontal Vertical
E59234A
E59233A
Note.
Compact circuit breakers can be connected indifferently with
bare-copper, tinned-copper and tinned-aluminium conductors,
requiring no particular treatment.
E46426A
devices are equipped with terminals comprising
captive screws for direct connection of bars.
Other connection possibilities for bars include vertical-
connection adapters for edgewise bars and spreaders
to increase the pole pitch to 95 mm. Vertical-connection adapters
If the vertical connection adapters are front oriented,
then it is mandatory to install the arc chute screen in
order to comply with the safety clearances.
E46431A
E59238A
E59239A
Spreaders.
E59240A
E70750
Bare cables
E54457
E46887A
be used to connect up to four 240 mm2 copper or
aluminium cables for each phase.
E59241A
4-cable connectors
connection adapters.
One to four cables with crimped lugs (i 300 mm2)
may be connected.
To ensure stability, spacers must be positioned
between the terminal extensions. Cable lug adapters
If the cable lug adapters are installed over the top of
the arc chute chambers, then it is mandatory to install
the arc chute screen in order to comply with the safety
clearances.
E59242A
E70751
E59243A
E46431A
may be directly connected to flat or edgewise bars,
depending on the position of the connectors.
Spreaders are available to increase the pole pitch to
95 mm. Spreaders.
E59257A
E59248A
E59247A
E54456
E46426A
Other connection possibilities for bars include vertical-
connection adapters for edgewise bars and spreaders
to increase the pole pitch to 95 mm.
Vertical-connection adapters
E59253A
E59252A
E46431A
Spreaders
E59254A
E46427A
cables with crimped lugs (i 300 mm2).
E54456
E46431A
connectors may be directly connected to flat or edge-
wise bars, depending on the position of the connectors.
Spreaders are available to increase the pole pitch to
95 mm. Spreaders
E59258A
E59259A
E59260A
E54456
E59262A
E59263A
insulates power-connection points, particularly when
cables with lugs are used
Connection shield
Interphase barriers
These barriers are flexible insulated partitions used to
E79056
reinforce isolation of connection points in installations
with busbars, whether insulated or not.
Barriers are installed vertically between front or rear
connection terminals.
E79057
Safety shutters
Mounted on the chassis, the safety shutters
E59265A
Fixed devices
Connections are made directly to the auxiliaries once the front has been removed.
OF1
CAO1
CAO2
CAF1
CAF2
E59286A
SD
COM MN
SDE
or
MX
Withdrawable devices
SDE
OF3
OF2
OF1
MN
ou
or Auxiliary circuits are connected to terminal blocks located in the top part of the
COM MX
chassis.
The auxiliary terminal block is made up of a fixed and moving part. The two parts
are in contact when the device is in the test and connected positions.
E59287A
CD2
CD1
CE3
CE2
CE1
CT1
Withdrawable device
Indication contacts
Contacts installed in the device
Changeover contacts are used to remote circuit-breaker status information and can
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
c OF (ON/OFF) - indicates the position of the main circuit breaker contacts
c SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
OF, SD and SDE changeover contacts
v a short-circuit
v an earth-leakage fault.
v operation of a voltage release
All the auxiliary contacts opposite are also available v operation of the "push to trip" button
in "low-level" versions capable of switching very low v disconnection when the device is ON.
loads (e.g. for the control of PLCs or electronic Returns to de-energised state when the circuit breaker is reset.
circuits). c SDE (fault indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
c CAF / CAO (early-make or early-break function) - indicates the position of the
rotary handle. Used in particular for advanced opening of safety trip devices (early
break) or to energise a control device prior to circuit-breaker closing (early make).
Installation
c OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on where it is inserted in the device. The contacts
clip into slots behind the front cover of the circuit breaker.
c CAF / CAO function - the contact fits into the rotary-handle unit (direct or
extended).
Electrical characteristics of the OF/SD/SDE/CAF/CAO auxiliary contacts
Contacts Standard Low level
Rated thermal current (A) 6 5
Minimum load 10 mA at 24 V 1 mA at 4 V
Utilisation cat. (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14
Operational 24 V 6 6 2.5 1 5 3 5 1
current (A) 48 V 6 6 2.5 0.2 5 3 2.5 0.2
110 V 6 5 0.8 0.05 5 2.5 0.8 0.05
220/240 V 6 4 - - 5 2 - -
250 V - - 0.3 0.03 5 - 0.3 0.03
380/440 V 6 3 - - 5 1.5 - -
660/690 V 6 0.1 - - - - - -
056456
Rotary handles
There are two types of rotary handle:
c direct rotary handle
c extended rotary handle.
There are two models:
c standard with a black handle
c VDE with a red handle and yellow front for machine-tool control.
c circuit breaker locking capability in the OFF position by one to three padlocks,
shackle diameter 5 to 8 mm (not supplied).
It replaces the circuit-breaker front cover.
Accessories transform the standard direct rotary handle for the following situations:
c motor control centre (MCC) switchboards:
v door opening disabled when the circuit breaker is ON;
v circuit-breaker closing is disabled if the door is open;
c a higher degree of protection (IP 43, IK 07)
c machine-tool control, complying with CNOMO E03.81.501, IP 54, IK 07.
E59433A
E46554A
E46553A
(instantaneous or delayed) may be added. opening opening delayed
order order opening
order 10 12
056421
C2 D2 instantaneous
opening D2
order
MX MN MN
C1 D1 D1
MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply non-adjustable 100/130 - 200/250
V AC 50/60 Hz /DC adjustable 48/60 - 100/130 - 200/250 - 380/480
Operating threshold opening 0.35 to 0.7 Un
closing 0.85 Un
Consumption (VA or W) pick-up: 200 - hold: 4.5
Circuit-breaker response adjustable 0.5s - 0.9s - 1.5s - 3s
time at Un non-adjustable 0.25s
E59434A
E45163
electrical OF1
operation
SDE
A1 81 11
opening closing
order order
A4 A2 B4
electrical
operation
A1
COM
supervisor
OF
SDE
Locking in ON position does not prevent the device from tripping in the event of a fault or
remote tripping order.
Access to pushbuttons
Locking on electrically operated devices
056447
2 OFF pushbutton
3 OFF position locking
3 4 ON pushbutton
5 springs charged indication
6 pushbutton locking
7 contact position indication
1 8 operation counter
4
I
056446
padlock disc
harg
ed
2 O OFF
6
7
53
012
Pushbutton locking
The transparent cover blocks access to the pushbuttons used to open and close
OFF position locking using the device.
056448
padlocks It is possible to independently lock the opening OFF button and the closing ON
button.
The pushbuttons may be locked using either:
c three padlocks (not supplied)
c lead seal
c two screws.
keylock and padlocks Keys may be removed only when locking is effective (Profalux or Ronis type locks).
The keylocks are available in any of the following configurations:
c one keylock
c one keylock mounted on the device + one identical keylock supplied separately
for interlocking with another device.
A locking kit (without lock) is available for installation of a keylock (Ronis, Profalux,
Kirk or Castell).
E59267A
4 keylock locking
5 padlock locking
3 6 position indicator
7 chassis front plate
4 (accessible with cubicle
door closed)
5 8 crank entry
9 reset button
6 10 crank storage
7
8
1
9
10
2
056451
Mounted on the chassis and accessible with the door closed, these devices lock
the circuit breaker in the disconnected position in two manners:
c using padlocks (standard), up to three padlocks (not supplied)
c using keylocks (optional), one or two different keylocks are available.
Profalux and Ronis keylocks are available in different options:
c one keylock
c one keylock mounted on the device + one identical keylock supplied separately,
using the same key, for interlocking with another device
c one (or two) keylocks mounted on the device + one (or two) identical keylocks
supplied separately, for interlocking with another device.
A locking kit (without locks) is available for installation of one or two keylocks
(Ronis, Profalux, Kirk or Castell).
Disconnected position Disconnected position
locking by padlocks locking by keylocks
Connected, disconnected and test position locking
The connected, disconnected and test positions are shown by an indicator.
The racking crank blocks when the exact position is obtained.
056417
Door interlock
A release button is used to free it.
On request, the disconnected position locking system may be modified to lock the
circuit breaker in any of the three positions, connected, disconnected and test.
Door interlock
Mounted on the right or left-hand side of the chassis, this device inhibits opening of
the cubicle door when the circuit breaker is in connected or test position. It the
breaker is put in the connected position with the door open, the door may be closed
without having to disconnect the circuit breaker.
056452
Racking interlock
Racking interlock
This device prevents insertion of the crank when the cubicle door is open (device
cannot be connected).
Mismatch protection
Mismatch protection ensures that a circuit breaker is installed only in a chassis with
compatible characteristics. It is made up of two parts (one on the chassis and one
on the circuit breaker) offering twenty different combinations that the user may
select.
056453
Mismatch protection
Escutcheon (CDP)
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP 40. It is available in fixed and withdrawable versions.
Escutcheon
by a screw. It increases the degree of protection to IP 54 and the degree of
protection against mechanical impacts to IK 10. It may be used for withdrawable
devices only.
Transparent cover
E59987
Blanking plate
E59269B
Vertical-connection adapters
Circuit breaker
NS1600b / 2500A
OFF
OFF
OFF
OFF
Voltage
release
Communication
module
E59271A
OFF
OFF
Fixed Compact NS
Mounting on rails
Connection
E59281A
Front connection
NS1600 to 2500 NS3200
E59726A
E59272A
OFF OFF
OFF OFF
Bars
Bars may be directly connected to the terminals of Compact NS1600b to 3200
E59275A
circuit breakers.
NS1600b to 2500
E59273
OFF
OFF
E59728A
OFF OFF
OFF OFF
Indication contacts
044314
E59433A
E46554A
E46553A
opening opening delayed
order order opening
order 10 12
delay
unit
3 6
C2 D2 instantaneous
opening D2
order
MX MN MN
C1 D1 D1
MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply non-adjustable 100/130 - 200/250
V AC 50/60 Hz /DC adjustable 48/60 - 100/130 - 200/250 - 380/480
Operating threshold opening 0.35 to 0.7 Un
closing 0.85 Un
Consumption (VA or W) pick-up: 200 - hold: 4.5
Circuit-breaker response adjustable 0.5s - 0.9s - 1.5s - 3s
time at Un non-adjustable 0.25s
Device locking
Locking in the OFF position guarantees isolation as per IEC 60947-2.
Padlocking systems can receive up to three padlocks with shackle diameters
ranging from 5 to 8 mm (padlocks not supplied).
Control device Function Means Required
accessories
Toggle lock in OFF position padlock removable device
lock in OFF or ON padlock fixed device
position
The mini test kit is a portable unit requiring no external power supply, used to check
operation of the electronic trip unit and circuit-breaker tripping.
It connects to the test connector on the front of the circuit breaker.
Required power source: five 9 V alkaline batteries (not supplied).
Perfectly integrated in the Compact DMB300 and DMC300 display modules use the power and communications
and Masterpact ranges, Display modules capabilities of the Micrologic control units to centralise the display of electrical
values, status conditions and alarms of one or more Compact
are designed for use with Micrologic control or Compact circuit breakers.
units to provide instant and highly intuitive The mounting and cabling system for the display modules ensures fast,
access to all the information provided by easy and reliable installation.
the circuit breakers, including device status, Start-up is immediate with no configuration or programming required.
current, voltage and power values, etc. Display modules are high-performance devices combining:
c simple and easy-to-read dials
c powerful and accurate digital processing.
057454
Their small size and extensive communications capabilities make for easy and
flexible installation and operation.
E59178
Wiring system
The wiring system is designed for low-voltage
24 V DC 1
power
power switchboards. Installation requires no tools
or special skills.
The prefabricated wiring ensures both data 2
transmission (ModBus protocol) and 24V DC power ON ON
E59081A
ON
n 4n 4 4 ON ON
n 3n 3 n n 4
n 2n 2 n 3 n 3
n 1n 1 n 2 n 2
1 n
units.
3
CDM 303:
Reset
Micrologic
Ir Ii
Ig
70
Isd I n
Ap
reset
push
OFF
push
discharge
ON
d
NX 32
Ue (V)
220/440
525
690
cat.B
Ics =
100%
H2
Icu (kA)
100
100
85
Icw 85kA/1s
Icu
Connection cable between
display module and junction
50/60Hz
O OFF IEC
947-2
UNE
AS NEMA
EN 60947-2
BS CEI
VDE
UTE
53
012
Digipact
DMB300
com
Test
volets
shutters
block
1
2 ?
P
U
3 I
select
4
E59180A
2
H1
1251
NW Uimp
12kV
Ui 1000V
8kV
Uimp Icu
Ue (kA)
(V) 100
220/240 85
70 480/690
Micrologic
reset
Ap
Ig
Isd I n
Ir Ii
I ON
push
OOFF
push
discharged
O OFF ON
Icu
100%
Ics =
947-2 NEMA
IEC UNE
BS CEI
UTE VDE
ON
012
53
n 4
n 3
n 2
n 1
OUT
IN
H1
1251
NW Uimp
12kV
Ui 1000V
8kV
Uimp Icu
Ue (kA)
(V) 100
220/240 85
70 480/690
Micrologic
reset
Ap
Ig
Isd I n
Ir Ii
I ON
push
OOFF
push
discharged
O OFF
Icu
947-2 NEMA
IEC UNE
BS CEI
UTE VDE
53
012
E59179
3
4
E59082A
2 2 2
H1 H1
1251 1251
NW Uimp
12kV NW Uimp
12kV
Ui 1000V Ui 1000V
8kV 8kV
Uimp Icu Uimp Icu
Ue (kA) Ue (kA)
(V) 100 (V) 100
220/240 85 220/240 85
70 480/690 70 480/690
Micrologic Micrologic
reset reset
Ap Ap
Ig Ig
Isd I n Isd I n
Ir Ii Ir Ii
I ON I ON
push push
OOFF OOFF
push push
discharged discharged
O OFF O OFF
Icu Icu
100% 100%
Ics = Ics =
Reset push
ON NX 32
H2
Icu (kA)
012
53
012
53
CCR 301:
3 3
Ue (V) 100
OFF 100
push 220/440
70 25
525 85
Micrologic
690
reset Icw 85kA/1s
Ap
Ig
Isd I n d cat.B
Icu
Ir Ii discharge 100%
Ics =
3
(2 RS485 wires + 2 power
NW
Ui 1000V
Uimp
1251
8kV
Uimp
H1
Icu
12kV NW
Ui 1000V
Uimp
1251
8kV
H1
Uimp
Icu
12kV
supply wires)
Ue (kA) Ue (kA)
(V) 100 (V) 100
220/240 85 220/240 85
70 480/690 70 480/690
Micrologic Micrologic
reset reset
Ap Ap
Ig Ig
Isd I n Isd I n
Ir Ii Ir Ii
I ON I ON
push push
OOFF OOFF
push push
E59177A
discharged discharged
O OFF O OFF
Icu Icu
100% 100%
5
Ics = Ics =
53 53
012 012
H2
ON NX 32
Reset push
Icu (kA)
Ue (V) 100
OFF 100
push 220/440
525 85
70 690
Micrologic Icw 85kA/1s
d cat.B
Icu
reset
Ap discharge 100%
Ig
Isd I n Ics = H1 H1
Ir Ii 1251 1251
NW Uimp
12kV NW Uimp
12kV
50/60Hz
O OFF 947-2 AS NEMA
Ui 1000V
8kV
Ui 1000V
8kV
IEC UNE Uimp Icu Uimp Icu
EN 60947-2
BS CEI (kA) (kA)
UTE
VDE Ue Ue
(V) 100 (V) 100
220/240 85 220/240 85
70 480/690 70 480/690
Micrologic Micrologic
reset reset
Ap Ap
Ig Ig
Isd I n Isd I n
Ir Ii Ir Ii
I ON I ON
push push
OOFF OOFF
push push
discharged discharged
O OFF O OFF
Icu Icu
100% 100%
Ics = Ics =
53 53
012 012
CSD 309:
SubD 9-pin connector for
colour-coded connection of
wires to screw terminals
Compact circuit breakers equipped with Micrologic control units and the ModBus eco COM option
Presentation 1
Functions and characteristics 11
Altitude derating
Altitude does not significantly affect circuit-breaker characteristics up to 2000 m.
Above this altitude, it is necessary to take into account the decrease in the dielectric
strength and cooling capacity of air.
The following table gives the corrections to be applied for altitudes above 2000
metres. The breaking capacities remain unchanged.
2000 m
Vibrations
E59571A
Electromagnetic disturbances
Compact NS devices are protected against:
E59572A
Power supply
E23947
Compact NS circuit breakers can be supplied from either the top or the bottom
without any reduction in performance. This capability facilitates connection when
installed in a switchboard.
push
to
trip
Weights
A1
A2
E23942
E50701
front F
panel if F < 8 mm : an
insulating screen
E50700
is mandatory
D1
D2 C1
C2
E50782
E50781
insulation
side panel
F
40 30
insulating kit
40 bare or painted
sheetmetal; 30
F insulation or
insulated bars
B=0
Insulating kit is standard. Connection using cables with lugs or busbars, F = 100.
Connection using bare cables, F = 150.
E59718A
E59720A
40
180
F
painted sheetmetal
E50704
A A A A
E59429A
this locking device prevents opening of the door if the Y
circuit breaker is in the connected or test positions. If
the circuit breaker was connected with the door open,
the door may be closed without having to disconnect
the circuit breaker.
4
61
2 (1) (2)
11
Dimensions (mm)
Type (1) (2)
NS630b to 1600 (3P) 135 168
NS630b to 1600 (4P) 205 168
door
F
5
23
Release wiring
During pick-up, the power drawn is approximately 150 to 200 VA. For low supply
voltages (12, 24, 48 V), the maximum cable length therefore depends on the
supply voltage and the size of the cables.
Indicative values for maximum wire lengths (in metres)
12 V 24 V 48 V
2.5 mm2 1.5 mm2 2.5 mm2 1.5 mm2 2.5 mm2 1.5 mm2
MN 100 % U source 58 35 280 165
85 % U source 16 10 75 45
MX 100 % U source 21 12 115 70 550 330
85 % U source 10 6 75 44 350 210
Note. The lengths mentioned are for each of the two supply wires.
E54545
L S (mm2) Cu / Al 1.5 to 70 rigid 1.5 to 16 rigid
E59291A
E39432
Distribution connector
E50702
I (mm) d + 10 d + 10 d + 15
d (mm) i 10 i 10 i 15
E59292A
e (mm) i6 i6 3 i e i 10
400
(mm) 6.5 8.5 10.5
d
l
L L
e
push
Lugs L (mm) i 25 i 25 i 32
to
trip
NS100 NS160/250
E18599
Bars L (mm) i 25 i 25
E50702
l (mm) 20 i I i 25 20 i I i 25
Where U > 600 V, the mandatory insulation kit means d (mm) i 10 i 10
400 e (mm) i6 i6
separate spreaders cannot be used. The one-piece
d (mm) 6.5 8.5
spreader must be used. l Lugs L (mm) i 25 i 25
Straight terminal Right-angle terminal L L (mm) 6.5 8.5
extensions extensions e Tighten. (Nm) 10 (1), 5 (2) 15 (1), 5 (2)
Tinned copper. Tinned copper. torque
Upstream side. (1) Tightening torque for spreaders or terminal extensions on the circuit breaker
(2) Tightening torque for spreaders or terminal extensions on plug-in base
E18601
Spreaders, straight and right-angle terminal extensions are supplied with flexible
E18600
interphase barriers.
Bars L (mm) i 40 i 32
spreaders requires a
E18599
l (mm) d + 15 30 i I i 34
specific insulation kit.
d (mm) i 20 i 15
The 70 mm spreaders
400 e (mm) 3 i e i 10 3 i e i 10
may not be used.
(mm) 12,5 10,5
Edgewise terminal Right-angle terminal d
l Lugs L (mm) i 40 i 32
extension extensions (mm) 12,5 10,5
L L
Tinned copper Tinned copper Tighten. (Nm) 50 (1), 20 (2) 50 (1), 20 (2)
Upstream side e torque
(1) Tightening torque for spreaders or terminal extensions on the circuit breaker
(2) Tightening torque for spreaders or terminal extensions on plug-in base
E18600
E21276
Spreaders, straight and right-angle terminal extensions are supplied with flexible
interphase barriers.
E25961
NS100 to 250
E54471
E59293A
E54472
E58540
E54468
1-cable connector Distribution connector Polybloc distribution block
aa
E59568A
aa
B
E59566A
E59569A
155
Power connections for
Compact NS630b to 3200
Type of
tie
Maximum distance
between ties (mm)
Short-circuit
current (kA rms)
"Panduit" ties
Width: 4.5 mm
Maximum load: 22 kg
Colour: white
200
10
100
15
50
20
Connection of bars
B
E
E59567A
Compact
B
30
350
A
C
50
300
65
250
80
150
E59570A
"Sarel" ties
Width: 9 mm
Maximum load: 90 kg
Colour: black
350
20
100
150
200
27
100
35
150
150
70
45
Bars must be adjusted to ensure correct positioning on the terminals before bolting (B)
Bars must rest on a support firmly attached to the switchboard frame, such that the
circuit-breaker terminals do not bear any weight (C).
Electrodynamic forces
The first spacer between bars must be positioned within a maximum distance (see
table below) of the connection point to the circuit breaker. This distance is
calculated to resist the electrodynamic stresses exerted between the bars of each
phase during a short-circuit.
Maximum distance A between the circuit-breaker connection and the first spacer
50 (double
ties)
100
Schneider Electric
Installation Power connections for
recommendations Compact NS630b to 3200
1 2 3 4 5 Connections
E47678A
The quality of bar connections depends, among other things, on the tightening
torques used for the nuts and bolts. Over-tightening may have the same
consequences as under-tightening.
The correct tightening torques for the connection of bars to the circuit-breaker
terminals are indicated in the table below.
The values below are for copper bars (Cu ETP-NFA51-100) and steel nuts and
bolts (class 8.8).
The same values apply to AGS-T52 quality aluminium bars
(French standard NFA 02-104 and American National Standard H-35-1).
Examples of bar connections
E47668
E47667B
E47665
6
1 terminal screws, factory tightened to 13 Nm
2 circuit-breaker terminal
3 bars Tightening torque for bars
4 bolt Rated diameter (mm) Drilling (mm) Tightening torque (Nm) Tightening torque (Nm)
5 washer diameter with flat or grower with contact or split
6 nut washers washers
10 11 37.5 50
Bar drilling
Examples
E47329A
E47330A
E47331A
Insulation distance
E47680A
X
Dimensions (mm)
Utilisation voltage X minimum
Ui i 600 V 8 mm
Ui i 1000 V 14 mm
Bar bending
Bars must be bent according to the table below. A tighter bend may cause cracks.
E47679A
r
e
Dimensions (mm)
e radius r
Minimum Recommended
5 5 7.5
10 15 18 to 20
E59294A
Compact Maximum Ti : 40 C Ti : 50 C Ti : 60 C
service Number of bars Number of bars Number of bars
current 5 mm thick 10 mm thick 5 mm thick 10 mm thick 5 mm thick 10 mm thick
NS630b 400 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10
NS630b 630 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10
NS800 800 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.63 x 10
NS1000 1000 3b.50 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10
NS1250 1250 3b.50 x 5 2b.40 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10
2b.80 x 5 2b.40 x 10 2b.80 x 5
NS1600 / 1600b 1400 3b.50 x 5 2b.40 x 10 2b.80 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10
NS1600 / 1600b 1600 3b.63 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10 3b.80 x 5 3b.50 x 10
NS2000 1800 3b.80 x 5 2b.63 x 10 3b.80 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10
NS2000 2000 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 3b.100 x 5 3b.63 x 10
NS2500 2200 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 4b.80 x 5 2b.100 x 10
NS2500 2500 4b.100 x 5 2b.100 x 10 4b.100 x 5 2b.100 x 10 4b.100 x 5 3b.80 x 10
NS3200 2800 4b.100 x 5 3b.80 x 10 4b.100 x 5 3b.80 x 10 5b.100 x 5 3b.100 x 10
NS3200 3000 5b.100 x 5 3b.80 x 10 6b.100 x 5 3b.100 x 10 8b.100 x 5 4b.80 x 10
NS3200 3200 6b.100 x 5 3b.100 x 10 8b.100 x 5 3b.100 x 10 4b.100 x 10
Note
With Compact NS630b to NS1600, it is recommended to use 50 mm wideness bars (see "Recommanded busbars drilling")
E59422A
Compact Maximum Ti : 40 C Ti : 50 C Ti : 60 C
service Number of bars Number of bars Number of bars
current 5 mm thick 10 mm thick 5 mm thick 10 mm thick 5 mm thick 10 mm thick
NS630b 400 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10
NS630b 630 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10
NS800 800 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10
NS1000 1000 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10
NS1250 1250 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10
NS1600 1400 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10
NS1600 1600 2b.80 x 5 1b.80 x 10 2b.80 x 5 1b.80 x 10 3b.63 x 5 2b.50 x 10
E59308A
E59309A
E59310A
50 50 63 80
15 15
12,5 12,5 12,5 12,5 25,5 12,5
12 maxi 12 maxi 12 maxi 12 maxi
Middle left or middle Middle spreader for 3P Left or right spreader Left or right spreader
right spreader for 4P for 4P for 3P
E59325A
E59326A
E59327A
E59328A
77 77 77 77
38,5 38,5 38,5
E59324B
44 38,5
13,5 13,5 13,5 13,5
25 9,5 12,5 25 = = 25 = = 25 = = 25 = =
30 30 30 30
60
82 52 15 82 52 15 82 52 82 52 15
12,5 15
5 11 5 11 5 11 5 11
2 11
25 25 25 25
52 52 52 52
E59315 A
E59311A
E59312A
E59313A
E59314A
32 40 50 63 80
12,5 12,5 12,5 12,5 12,5 12,5 12,5 12,5 12,5 12,5
60
E59329B
12,5
12,5 9,5
25 44
2 11
E59308A
E59309A
E59310A
50 50 63 80
15 15
12,5 12,5 12,5 12,5 25,5 12,5
12 maxi 12 maxi 12 maxi 12 maxi
9,5
25 2 vis M10 15
15 21
101 21
3 11
25 15
2 vis M10 15 9,5 15 20
44
E59309A
80
E59310A
50 63
15 15
12,5 12,5 25,5 12,5
12 maxi 12 maxi 12 maxi
76 25
13 = =
=
=
3 11
15
E59732A
E59733A
63 80 100
25 25 25 25
25 25 25 100 25
25 25 25 25
4 11
E59735A
25
25 60 100
25
20
20 12,5 20
45 15 25 25
60 80
100 12 maxi
E59734A
12 maxi
25
25 100 25
25 25
25
12,5 12,5
12,5 12,5
4 11
E59735A
25
25 60 100
25
20
20 12,5 20
45 15 25 25
60 80
The values opposite are valid for fixed circuit When the ambient temperature is greater than 40 C, overload-protection
breakers equipped with one of the following modules: characteristics are slightly modified.
c Vigi module To determine tripping times using time/current curves, use Ir values corresponding
c ammeter module to the thermal setting on the device, corrected as indicated in the tables below.
c insulation-monitoring module
c current-transformer module. Single-pole and two-pole Compact NS
They also apply to plug-in / withdrawable circuit Rating (A) 40 C 45 C 50 C 55 C 60 C 65 C 70 C
breakers equipped with one of the following modules: 16 16 15.6 15.2 14.8 14.5 14 13.8
c ammeter module 25 25 24.5 24 23.5 23 22 21
c current-transformer module. 40 40 39 38 37 36 35 34
However, for plug-in / withdrawable circuit breakers 63 63 61.5 60 58 57 55 54
equipped with a Vigi module or an insulation- 80 80 78 76 74 72 70 68
monitoring module, the coefficients in the table below 100 100 97.5 95 92.5 90 87.5 85
must be applied. 125 125 122 119 116 113 109 106
Trip unit Coefficient 160 160 156 152 147.2 144 140 136
TM16 to TM125 1 200 200 195 190 185 180 175 170
TM160 to TM250 0.9 250 250 244 238 231 225 219 213
Compact NS100 to 250 equipped with TM-D and TM-G trip units
Rating (A) 40 C 45 C 50 C 55 C 60 C 65 C 70 C
16 16 15.6 15.2 14.8 14.5 14 13.8
25 25 24.5 24 23.5 23 22 21
32 32 31.3 30.5 30 29.5 29 28.5
40 40 39 38 37 36 35 34
50 50 49 48 47 46 45 44
63 63 61.5 60 58 57 55 54
80 80 78 76 74 72 70 68
100 100 97.5 95 92.5 90 87.5 85
125 125 122 119 116 113 109 106
160 160 156 152 147.2 144 140 136
200 200 195 190 185 180 175 170
250 250 244 238 231 225 219 213
Compact NSA160
Rating (A) 40 C 45 C 50 C 55 C 60 C 65 C 70 C
16 16 15.6 15.2 14.8 14.5 14 13.8
25 25 24.5 24 23.5 23 22 21
32 32 31.3 30.5 30 29.5 29 28.5
40 40 39 38 37 36 35 34
50 50 49 48 47 46 45 44
63 63 61.5 60 58 57 55 54
80 80 78 76 74 72 70 68
100 100 97.5 95 92.5 90 87.5 85
125 125 122 119 116 113 109 106
160 160 156 152 147.2 144 140 136
Compact NB50NB600
NB50 / NB100 40 C 45 C 50 C 55 C 60 C
NB50N 1 1 1 1 1
NB100F/N 1 1 1 1 1
NB250N
Rating (A) 50 C 55 C 60 C 65 C 70 C
125 125 122 119 116 113
150 150 146 143 139 135
175 175 171 166 162 158
200 200 195 190 185 180
225 225 220 214 208 203
NB400N
Rating (A) 50 C 55 C 60 C 65 C 70 C
400 400 390 380 370 360
NB600N
Rating (A) 50 C 55 C 60 C 65 C 70 C
600 600 585 570 550 535
The values opposite are valid for fixed circuit Electronic trip units are not affected by variations in temperature. However, the
breakers equipped with one of the following modules: maximum permissible current in the circuit breaker still depends on the ambient
c Vigi module temperature.
c ammeter module
c insulation-monitoring module
c current-transformer module. Compact NS100...NS250
They also apply to plug-in / withdrawable circuit The table below indicates the maximum long-time (LT) protection setting depending
breakers equipped with one of the following modules: on the ambient temperature.
c ammeter module NS100N/H/L 40 C 45 C 50 C 55 C 60 C 65 C 70 C
c current-transformer module. In: 40 to 160 A no derating
However, for plug-in / withdrawable circuit breakers Ir max 1 1 1 1 1 1 1
equipped with a Vigi module or an insulation- NS250N/H/L 40 C 45 C 50 C 55 C 60 C 65 C 70 C
monitoring module, the coefficients in the table below In: 100 to 160A no derating
must be applied. Ir max 1 1 1 1 1 1 1
Circuit breaker Trip unit Coeff. In: 250A 250 250 250 237.5 237.5 225 225
NS100N/H/L STR22SE/GE 40 to 100 1 Ir max 1 1 1 0.95 0.95 0.90 0.90
NS160N/H/L STR22SE/GE 40 to 160 1
NS250N/H/L STR22SE/GE 100 and 160 1 Compact NS400 and NS630
NS250N/H/L STR22SE/GE 250 0.86 The table below indicates the maximum long-time (LT) protection setting depending
on the ambient temperature.
The values opposite are valid for fixed or plug-in / NS400N/H/L 40 C 45 C 50 C 55 C 60 C 65 C 70 C
withdrawable circuit breakers equipped with one of Fixed In: 400A 400 400 400 390 380 370 360
the following modules: Io/Ir max 1/1 1/1 1/1 1/0.98 1/0.95 1/0.93 1/0.9
c ammeter module Plug-in / In: 400 400 390 380 370 360 350 340
c current-transformer module. withdrawable Io/Ir max 1/1 1/0.98 1/0.95 1/0.93 1/0.9 1/0.88 1/0.85
However, for fixed or plug-in / withdrawable circuit
NS630N/H/L 40 C 45 C 50 C 55 C 60 C 65 C 70 C
breakers equipped with a Vigi module or an insulation-
Fixed In: 630A 630 615 600 585 570 550 535
monitoring module, the coefficients in the table below
Io/Ir max 1/1 1/0.8 1/0.95 1/0.93 1/0.9 1/0.88 1/0.85
must be applied.
Plug-in / In: 570A 570 550 535 520 505 490 475
Circuit breaker Trip unit Coeff. withdrawable Io/Ir max 1/0.9 1/0.88 1/0.85 1/0.83 1/0.8 0.8/0.98 0.8/0.95
NS400N/H/L STR23SE and 53UE 0.97
STR23SV and 53SV
NS630N/H/L STR23SE and 53UE 0.9
STR23SV and 53SV
Note. To provide the Visu function, Compact NS circuit
breakers, with or without a Vigi module, are combined with
INV switch-disconnectors. Tripping values for the selected
combination are indicated in the Interpact catalogue.
Compact NS100 to 250 equipped with TM-D and TM-G trip units
Fixed device Additional modules
3/4 poles Rat. (A) R/pole P/pole Vigi Vigi With- Ammeter Transfo.
(N, L3) (L1, L2) drawable module module
NS100N/H/L 16 11.42 2.92 0 0 0 0 0
25 6.42 4.01 0 0 0.1 0 0
32 3.94 4.03 0.06 0.03 0.15 0.1 0.1
40 3.42 5.47 0.10 0.05 0.2 0.1 0.1
50 1.64 4.11 0.15 0.08 0.3 0.1 0.1
63 2.17 8.61 0.3 0.15 0.4 0.1 0.1
80 1.37 8.77 0.4 0.2 0.6 0.1 0.1
100 0.88 8.8 0.7 0.35 1 0.2 0.2
NS160N/H/L 80 1.26 8.06 0.4 0.2 0.6 0.1 0.1
100 0.77 7.7 0.7 0.35 1 0.2 0.2
125 0.69 10.78 1.1 0.55 1.6 0.3 0.3
160 0.55 13.95 1.8 0.9 2.6 0.5 0.5
NS250N/H/L 125 0.61 9.45 1.1 0.55 1.6 0.3 0.3
160 0.46 11.78 1.8 0.9 2.6 0.5 0.5
200 0.39 15.4 2.8 1.4 4 0.8 0.8
250 0.3 18.75 4.4 2.2 6.3 1.3 1.3
Power dissipated per pole (P/pole) in Watts (W). Compact NS100 to NS630
Resistance per pole (R/pole) in milliohms (m) Fixed device Additional modules
(measured cold). Total power dissipation is the value 3/4 poles Rat. (A) R/pole P/pole Vigi Vigi With- Ammeter Transfo.
measured at In, 50/60 Hz, for a three-pole or four- (N, L3) (L1, L2) drawable module module
pole circuit breaker (values above power P = 3RI2). NS100N/H/L 40 0.84 1.34 0.1 0.05 0.2 0.1 0.1
100 0.468 4.68 0.7 0.35 1 0.2 0.2
NS160N/H/L 40 0.73 1.17 0.4 0.2 0.6 0.1 0.1
100 0.36 3.58 0.7 0.35 1 0.2 0.2
160 0.36 9.16 1.8 0.9 2.6 0.5 0.5
NS250N/H/L 100 0.27 2.73 1.1 0.55 1.6 0.2 0.2
250 0.28 17.56 4.4 2.2 6.3 1.3 1.3
NS400N/H/L 400 0.12 19.2 3.2 1.6 9.6 2.4 2.4
NS630N/H/L 630 (1) 0.1 39.69 6.5 3.25 19.49 5.95 5.95
(1) The dissipation values for the Vigi modules and withdrawable circuit breakers are given
for 570 A
Compact NSA160
Fixed device Additional modules
3/4 poles Rat. (A) R/pole P/pole Vigi Vigi
(N, L3) (L1, L2)
NSA160 16 15 4 0.06 0.06
25 8 5 0.16 0.16
32 5.4 5.5 0.26 0.26
40 3.7 6 0.4 0.4
50 2.8 7 0.63 0.63
63 2 8 1 1
80 1.4 9 1.6 1.6
100 1 10 2.5 2.5
125 0.8 12.5 3.9 3.9
160 0.6 15.4 6.4 6.4
NSA125NA 125 0.7 11
NSA160NA 160 0.6 15.4
Presentation 1
Functions and characteristics 11
Installation recommendations 143
Compact NB 166
Compact NS80H-MA 168
Compact NSC100 170
Compact NSA160 171
Compact NS100 to 630 (fixed version) 172
Vigicompact NS100 to 630 (fixed version) 174
Compact NS100 to 630 176
(plug-in and withdrawable versions)
Vigicompact NS100 to 630 178
(plug-in and withdrawable versions)
Compact NS100 to 250 180
(single-pole and two-pole versions)
Visu function for Compact NS100 to 630 182
(combination with Interpact INV)
Motor-mechanism module for Compact NS100 to 630 184
Rotary handle for Compact NS100 to 630 186
Indication and measurement modules 188
for Compact NS100 to 630
Front accessories for Compact NS100 to 630 190
Compact NS630b to 1600 (fixed version) 192
Dimensions 192
Mountings 193
Front-panel cutouts 194
Rotary handle 195
Compact NS630b to 1600 (withdrawable version) 196
Dimensions, mounting and cutouts 196
Rotary handle 197
Compact NS1600b to 3200 (fixed version) 198
Dimensions 198
Compact NS630b to 3200 200
External modules 200
Accessories 204
Connection 205
Electrical diagrams 221
Additional characteristics 251
Catalogue numbers 267
E58736A
X H1 H3 H5 X
H
H2 H4
(d)
(c)
Y
P1 L
P2 L1
P3
(c) interphase barriers
Z
(d) terminal shields.
K1
K1
E58739A
K U (e)
K
T G1
X X
G1
G T G
Y
Y
Door cutout
Cutout (A) (B, C)
E62276A
E62278A
E62279A
E62277A
X X X X
C1 C1 C1
C C C
B/C Y Y Y
R R2
R1 R3
P4
P5
Z
Dimensions (mm)
Type C C1 G G1 H H1 H2 H3 H4 H5 K K1 L L1 P1 P2 P3 P4 P5 R R1 R2 R3 T U (e)
NB50N 27 54 55.5 111 65 130 ?? ?? ?? ?? 12.5 25 37.5 75 68 72 90 70 74 12.5 25 30.5 61 6 i32
NB100F/N 27 54 66 132 77.5 155 ?? ?? ?? ?? 15 30 45 90 68 72 90 70 74 12.5 25 43.5 87 6 i32
K1
K
E58738A
K1
E43683A
K
E58740A
H1 H3 H5 H7 G1
X X X G1 X
T T
G G
H H2 H4 H6
(a) Y
(b)
(c) Y
Y
P1 L
P2 L1
P3
Z
(a) short terminal shields.
(b) long terminal shields (available for spreaders on NB400
to 600, pitch 52.5 : L1 = 157.5 mm).
(c) interphase barriers.
Door cutout
Cutout (A) (B, C)
E62280A
E62283A
E62281A
E62282A
X X C1 X X
C3 C3
C
C2 C2
Y Y Y
B/C R R2
R1 R3
P4
P5
Z
E62307A
E62308A
X X X C7
C5
C6
C4
Y Y
R4 R6
R5 R7
P5
Z
Dimensions (mm)
Type C C1 C2 C3 C4 C5 C6 C7 G G1 H H1 H2 H3 H4 H5 H6 H7 K K1 L L1
NB250N 29 76 54 108 43 104 34 86 62.5 125 80.5 161 94 188 160.5 321 178.5 357 17.5 35 52.5 105
NB400/600N 41.5 116 92.5 184 56.5 146 46.5 126 100 200 127.5 255 142.5 285 240 480 237 474 22.5 45 70 140
Type P1 P2 P3 P4 P5 R R1 R2 R3 R4 R5 R6 R7 T U (e)
NB250N 81 86 111 83 88 14.5 29 54 108 29 58 43 86 6 i32
NB400/600N 95.5 110 168 117 112 31.5 63 71.5 143 46.5 93 63 126 6 i32
Dimensions Mounting
On backplate On rails
E21875
E21874
30 30
E21876
E21873 15 15
32
103
120
100 100
X X X X
(a) 4
Y Y
4
Y
64,5 45
70 90
80
84
100
Z
(a) long terminal shields
Front-panel cutouts
Cutout A Cutout B Cutout C
E21881
E21884
E21882
E21883
B/C
Y Y Y
71 14,5 46
81 29 92
Z
E21885
E21888
E21886
7,5
E21887
ON
I
65,5 60 4,2
X 68,5
tripped X X
28,5 60 X 30
O
OFF
Y
47,5 Y
82,5 45 85 43
112 80 Z 86
Z 90
75
E21889
37,5
E21890
45
7,5
7,5
E21891
60 50
4,2 75 4,2
X
X 37,5 X
60 4,2
Y 72 36 Y
mini 175
L ( maxi 590 )
Z
shaft length = L _ 109
120
69,2
7,5
E21893
E21892
E21894
1 to 3 maxi Y
Y 51,7
116 2
100
E22046
Note. h
Door cutout dimensions are given for a device position in the
enclosure where u 100 + (h x 5) with respect to the door
hinge.
Dimensions
Compact NSC100
3 poles 4 poles
E43398
E43400
E43399
103
120
X X X
60 206
90
(a) (a)
Y Y
15 70
80 45 45
84 90 120
100
Z (a) long terminal shields
Vigicompact NSC
3 poles 4 poles
101,2
E43401
E43403
E43402
103
120
X X
X
60 206
90
(a) (a)
Y Y
15 70
80 45 75
84 210 240
100
Z (a) long terminal shields.
83
E31296
E43404
E31295
50
60
3 3
X 75
X 37,5 X
60 4,2
Y 72 36 Y
mini 122
Z
maxi 147
Note.
Centre line X indicates the centre of the mounting r ail.
Dimensions
Compact NSA160
3 poles 4 poles
E21897
E21895
E21896
98,5
120
X X X
45
64,5 206
90
(a) (a)
Y Y
15 72,5
82,5 45 45
89,5 90 120
102,5
Z
Vigicompact NSA160
3 poles 4 poles
101,2
E21903
E21902
E21901
98,5
120
X X
45
X
64,5 206
90
(a) (a)
Y Y
15 72,5
82,5 45 75
89,5 210 240
102,5
Z
75
37,5
E31296
5 45 5
E31294
83
50
60
3 3
X 75
X 37,5 X
60 4,2
Y 72 36 Y
mini 122
Z
maxi 147
Note.
Centre line X indicates the centre of the mounting r ail.
Dimensions
2 poles or 3 poles 4 poles
E21503
E21504
E21502
H1 H3 H5 H7
X X
X
H H2 H4 H6
(a)
Y (b)
(c) (a) short terminal shields.
(b) long terminal shields Y
L (available for spreaders on
L
P1 L1 NS400 to 630, pitch 52.5 :
L2
P2 L1 = 157.5 mm,
P4 L2 = 210 mm).
Z (c) interphase barriers.
Mounting
On backplate
2 poles or 3 poles 4 poles
E21507
K1 K1 K1 K1 K1
E21508
K1 K2
K K
G1 G5
X X
G G4
T
T4 (d)
Y Y
(d) for rear connection only. For two-pole circuit breakers,
the centre hole is not necessary.
On rails
2 poles or 3 poles 4 poles
K1 K2
E21511
E21512
U (e) K K
G1
X X
G T
Y Y
G50
G51
G49
G48
G47
E21601
E21603
E21604
A
C1 C3 C3
X X X X
C
C2 C2
B/C Y Y Y
R R2
R4(3P)
P5 R1 R5(4P)
P6
Z
E21602
E21608
C7
X X X C21
C6 C20
Y Y
R6 R12
P6 R7 R13
Z
Dimensions (mm)
Type C C1 C2 C3 C6 C7 C20 C21 G G1 G4
NS100/160/250N/H/L 29 76 54 108 43 104 34 86 62.5 125 70
NS400/630N/H/L 41.5 116 92.5 184 56.5 146 46.5 126 100 200 113.5
Type H5 H6 H7 K K1 K2 L L1 L2 P1 P2
NS100/160/250N/H/L 321 178.5 357 17.5 35 70 52.5 105 140 81 86
NS400/630N/H/L 480 237 474 22.5 45 90 70 140 185 95.5 110
Type P4 P5 P6 R R1 R2 R4 R5 R6 R7 R12
NS100/160/250N/H/L 111(1) 83 88 14.5 29 54 108 143 29 58 43
NS400/630N/H/L 168 107 112 31.5 63 71.5 143 188 46.5 93 63
(1) : P4 = 126 mm for Compact NS250N/H/L.
Nota : h
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
Dimensions
2 poles or 3 poles 4 poles
E21515
E21514
E21513
X X X
(a)
(b)
(c)
Y Y
P1 L L
P2 L1
(a) short terminal shields L2
P4 (b) long terminal shields
Z (c) interphase barriers
Mounting
On backplate
2 poles or 3 poles 4 poles
K1 K1 K1 K1 K1
E21518
E21519
K1 K2
K K
G7 G1 G9
X X
G6 G8
T4 (d)
Y Y
(d) for rear connection only. For two-pole circuit breakers,
the centre hole is not necessary.
On rails
2 poles or 3 poles 4 poles
K1 K2
E21520
E21521
U (e) K K
G7 G1
X X
G6
Y Y
E21796
E21795
E21605
R1
A R
C1
X X X
C
C3
C4
C2
C5
R28
B
Y Y
P5 R28 R26
P6 R26 R2
Z R4 (3P)
R5 (4P)
With escutcheons
R7
E21800
R6
E21610
C7
X X
C6
C18
C19
Y
P6 R27
Z R11
Dimensions (mm)
Type C C1 C2 C3 C4 C5 C6 C7 C18 C19 C20 C21 G G1 G6 G7 G8 G9
NS100/160/250N/H/L 29 76 130 184 86 37 43 104 71 68 34 86 62.5 125 137.5 200 145 215
NS400/630N/H/L 41.5 116 192 276 147.5 37 56.5 146 132 68 46.5 126 100 200 200 300 213.5 327
Note.
h
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
Dimensions
Plug-in base 2 poles or 3 poles 4 poles
N M
Z
(*)
K1 K1 K1
E21524
E21522
E21523
H17 G11
X X X
H16 G10
(*)
Y Y
L L
P7 L1 L2
P8
P9 P4
N M
E21586
E21584
E21585
H19
X X X
H18
(*) (*)
Z Y Y
P7 L6 L6
P8 L7 L9
P9 P2 P12 L8 L10
P4
Mounting
Through panel M (plug-in base) Through panel M (chassis)
2P, 3P K1 4P K2 2P, 3P K1 4P K2
K K K K
E21588
E21587
E21526
E21525
Y Y Y Y
T K5 K5 T K11 K11
K6 K7 K12 K13
E21534
X X
G21
(*) short terminal shields are mandatory.
Nota :
G20 Door cutout dimensions are given for a device position in the
Y Y enclosure where u100 + (h x 5) with respect to the door
T hinge.
E21590
K1 K2
K K
G15
X X
G14
Y Y
T
E21592
E21593
E21594
T6
Y Y Y Y
T K1 K1 K1 K1 K1 T5 K1 K1 K1 K1 K1
Front-panel cutouts
Plug-in base Chassis with protection collar and escutcheons
E21619
E21620
C11
X X
C17
P44
Z
Y
R8
R9
Dimensions (mm)
Type C11 C17 G10 G11 G12 G13 G14 G15 G16 G17 G18 G19 G20 G21 G22 G23 G24
NS100/160/250N/H/L 103 42.5 95 190 87 174 77.5 155 66 132 82 164 37.5 75 111 222 190
NS400/630N/H/L 155 56 150 300 137 274 125 250 101 202 126 252 75 150 170.5 341 283.5
Type G25 G26 G27 H16 H17 H18 H19 K K1 K2 K5 K6 K7 K11 K12 K13 K20
NS100/160/250N/H/L 380 208 416 102.5 205 103.5 210 17.5 35 70 54.5 109 144 74 148 183 35
NS400/630N/H/L 567 318.5 637 157.5 315 140 280 22.5 45 90 71.5 143 188 91.5 183 228 50
Type K21 K22 L L1 L2 L6 L7 L8 L9 L10 P2 P4 P7 P8 P9 P10 P12
NS100/160/250N/H/L 70 105 52.5 105 140 92.5 185 216 220 251 86 111(1) 27 45 75 64 32
NS400/630N/H/L 100 145 70 140 185 110 220 250 265 295 110 168 27 45 100 86 32
Type P44 R8 R9 U(2) T T5 T6
NS100/160/250N/H/L 123 74 148 32 6 24 30
NS400/630N/H/L 147 90 180 32 6 33 33
(1) P4 = 126 mm for Compact NS250N/H/L
(2) U 20 mm if automatic auxiliary connectors are used (NS100 to 250).
Dimensions
Plug-in base
2 poles or 3 poles 4 poles
E21537
N M K1 K1 K1
(*)
E21536
E21535
H17 G11
X X X
H16 G10
(*)
Y Y
P7 L L
P8 L1 L2
P9 P4
Z
Chassis
See withdrawable Compact, page XXX.
Mounting
Through panel M (plug-in base) Through panel M (chassis)
2P, 3P 4P 2P, 3P 4P
E21587
K1
E21526
E21588
K2 K1 K2
E21525
K K K K
Y Y Y Y
T K5 K5 T K11 K11
K6 K7 K12 K13
E21534
U K20 K20
X X
G21
G20
Y Y
T
E21813
R8
E21623
C11
X X
C16
C17
C13
Y
P44 R33
Z R34
Dimensions (mm)
Type C11 C13 C16 C17 G10 G11 G12 G13 G20 G21 H16
NS100/160/250N/H/L 103 84 55 42.5 95 190 87 174 37.5 75 102.5
NS400/630N/H/L 155 84 116.5 56 150 300 137 274 75 150 157.5
Note.
h
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
Dimensions
1 pole 2 poles
E29213
E29214
E29215
H1 H3 H7
X X X
H H2 H6
(a)
(b)
Y
L3 Y
L3
P1 L5
L4
P2
P4 (a) short terminal shields
Z (b) interphase barriers
Mounting
On backplate
1 pole 2 poles
E29216
E21506
K1 K1
K K
G1 G5
X X
G G4
T
T4 (c)
Y Y
(c) for rear connection only
On rails
1 pole 2 poles
E29217
K1
U (d)
E21510
K K
G1
X X
G T
Y Y
(d) U 20 mm if automatic auxiliary connectors are used
E21601
E29218
E21604
A
C1 C3 C3
X X X X
C
C2 C2
B/C Y Y Y
R R2
R1 R4(1P)
P5 R5(2P)
P6
Z
With escutcheon
E21609
E21608
C7
X X
C6
Y
R6
P6 R7
Dimensions (mm)
Type C C1 C2 C3 C6 C7 G G1 G4 G5 H
NS100/160/250 29 76 54 108 43 104 62.5 125 70 140 80.5
Type H1 H2 H3 H4 H6 H7 K K1 L3 L4 L5
NS100/160/250 161 94 188 160.5 178.5 357 17.5 35 17.5 70 35
Type P1 P2 P4 P5 P6 R R1 R2 R4 R5 R6
NS100/160/250 81 86 111 83 88 14.5 29 19 38 73 29
Type R7 T T4 U(d)
NS100/160/250 58 6 22 32
(d) U 20 mm if automatic auxiliary connectors are used
E22046
Note. h
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
Fixed Compact NS100 to 250 with Visu function Interpact INV100 to 250
3 poles 4 poles
138 (a)
131 314 for front
96 connection. 140
E62428
E62429
140
86 316.5 for rear 52,5 52,5
connection. 35 35 35 35 35 35
322.5 with
E62427
connectors.
(b)
80.5 for front
connection.
83 for rear
510 connection.
474 89 with connectors.
215 215
(a)
277,5 277,5
X X X
93,7 (b)
178,5 160,5
Y Y
52,5 52,5
105 140
Z
Mounting on rails
3 poles 4 poles
E62431
70 70
E62430
35 35
7 6 17,5 9 6 17,5
X X
100 100
50 50
22,3 22,3
157,5 157,5
125 X 125 X
62,5 62,5
Y Y
Front-panel cutout
E62432A
E62433A
86 132
65,5
84
17,5
115,5
X X 76
29
Y 14,5
29
z
E62435
160,4 185
E62436
185
120 connection 70 70
110 493.5 for rear 45 45 45 45 45 45
connection
E62434
Y Y
70 70
Z
140 185
Mounting on rails
3 poles 4 poles
90 E62438
E62437
90
45 45
7 6 22,5 7 6 22,5
75 75
X X
150 150
241 241
33 33
200 X X
200
100 100
Y
Y
Front-panel cutout
E62440
E62439
172
110 86
127
22,5
177,5
X X 116
41,5
Y
31,5
Z
63
Dimensions
3 poles 4 poles
E21599
E21598
E21597
H20
H22
H21 X
X X
H23
Y Y
L L
L12 L2
L11
P33 L1
P32
Z
Front-panel cutouts
With IP 40, IK 07 escutcheons and protection collar
for Vigi module
R9
E21813
R8
E21614
E21621
E21612
C11
X X C23 X X
C16
C22 C17
Y C13
R14
R15
Y
P45 P45 R33
Z Z R34
E22046
Note. h
Door cutout dimensions are given for a device position in the
enclosure where u100 + (h x 5) with respect to the door
hinge.
Type L2 L11 L12 P32 P33 P45 R8 R9 R14 R15 R33 R34
NS100/160/250N/H/L 140 91 45.5 178 143 145 74 148 48.5 97 74 148
NS400/630N/H/L 185 123 61.5 250 215 217 90 180 64.5 129 91.5 148
E21625
L12
E21626
I
H23 60 I
H24 60
X DD DD
X
H20 60 O
X 60 O
(a) sans se
(b) avec se
Y Y
(c) avec se
L15 L
P34 L L2
P35 (a) L11
P36 (b) L1
Z P37 (c)
Front-panel cutouts
Fixed or plug-in circuit breaker
Compact Vigicompact
E21614
E21805
E21613
E21615
X X C23 X X C23
C22
C4
C22
Y C5
R14
P43
Z R15
Y
Z P43 R28
R26
R14
R15
R8
E21618
E21622
E21620
C11 C11
X X X X
C16
C17 C17
C13
P44
Z
Y Y
R8 P44 R33
R9 Z R34
E21632
L7
L12
E21633
E21634
H24 H10 G39
X
X X H9 G38
1 to 3 maxi Y
K14
P422 Y
K15
Z
Extended rotary handle
Fixed or plug-in circuit breaker Withdrawable circuit breaker
Cut shaft at length: Cut shaft at length:
P38-126 mm (NS100 to 250) P40-122 mm (NS100 to 250)
P38-150 mm (NS400 to 630) P40-150 mm (NS400 to 630)
L14
E21628
L13
E21629
L12
E21630
10 60
I
H24 H26
X X
O
X H25
60
Y
P38
Z
Front-panel cutout
E21631
45
L12
T7
H24
T6
G36
G37 Y
Dimensions (mm)
Type C4 C5 C11 C13 C16 C17 C22 C23 G36 G37 G38 G39 H9 H10 H20 H23 H24
NS100/160/250N/H/L 86 37 103 84 55 42,5 29 76 36 72 41 100 60 120 28 73 9
NS400/630N/H/L 147,5 37 155 84 116,5 56 41,5 126 36 72 51 145 83 160 40 123 24,5
Type H25 H26 K14 K15 L L1 L2 L7 L8 L11 L12 L13 L14 L15 P34 P35 P36
NS100/160/250N/H/L 37,5 75 50 100 52,5 105 140 69 120 91 9,25 37,5 75 55 121 155 156
NS400/630N/H/L 37,5 75 72,5 145 70 140 185 85 160 123 5 37,5 75 66,5 145 179 180
Type P37 P38(1) P40(1) P42 P43 P44 R1 R8 R9 R14 R15 R26 R33 R34 T6 T7
NS100/160/250N/H/L 164 185 248 125 89 123 29 74 148 48,5 97 14,5 74 148 4,2 50
NS400/630N/H/L 188 209 272 149 112 147 29 90 180 64,5 129 32 91,5 148 4,2 50
(1) 600 mm.
Nota :
Door cutout dimensions are given for a device position in the enclosure where 100 + (h x 5)
with respect to the door hinge.
Dimensions
Circuit breaker with ammeter module Circuit breaker with current-transformer module
E21517
E21516
X X
P1 P1
P2 P2
P47 P4
Z Z
Mounting
On backplate
2 poles or 3 poles 4 poles
E21518
E21519
K1 K1 K1 K1 K1
K1 K2
K K
G7 G1 G9
X X
G6 G8
T4 (d)
Y Y
On rails
2 poles or 3 poles 4 poles
K1 K2
E21521
E21520
U (e) K K
G7 G1
X X
G6
Y Y
E21674
E21673
C30
C1
X X
C
C28
C27
Y
P6 R
Z R1
R16
R17
T8
E21678
E21677
C30
C23
X X
C22
C28
C27
Y
R16
P43
Z R17
R14
R15
Dimensions (mm)
Type C C1 C22 C23 C27 C28 C29 C30 G G1 G6 G7 G8 G9 H8 H9 H10
NS100/160/250N/H/L 28 76 28 76 56.5 124 30 78.5 62.5 125 137.5 200 145 215 155.5 236 169
NS400/630N/H/L 41.5 116 41.5 126 56.5 185.5 30 122 100 200 200 300 213.5 327 227.5 355 242.5
Protection collar
Toggle protection collar
E21636
E21637
E21635
.
.
M
A D
E21464
E21640
E21638
52,4
91 35 53
M8
A3 D3
Front-panel escutcheons
For toggle
E21642
E21643
E21641
M2 M3
A1 D1 D2
79 64
69 3,5 6,5
E21648
E21649
E21647
M6 M7
A2 D1 D2
E21652
E21650
93,5 80,5
Dimensions (mm)
Type A A1 A2 A3 D D1 D2 D3 M M2 M3 M6 M7 M8
NS100/160/250N/H/L 91 69 157 94 35 3.5 6.5 40 73 115 102 114 101 94
NS400/630N/H/L 123 102 189 35 134 3.5 6.5 60 123 155 142 164 151 134
Manual control
Front connection
E47973A
E47972B
(1)
254
163,5
327
508 200
X X
100
Z Y
107,5 99,5 (3P) 99,5
169,5 (4P)
205
(1) terminal shields are
F optional
Rear connection
105 (3P)
E47914A
123
105
234 210
113 X X
92,5
117 123
Z F
107,5 35
140,5 70
146,5
205 14
Electrical control
Front and rear connection
105 (3P)
E47897A
123
105
Front connection
On rails On backplate
Y
Y
E47898A
4 6,5
4 6,5
E47899A
200 200
X X
100 100
99,5 (3P)
169,5 (4P) 99,5
99,5 (3P)
169,5 (4P) 99,5
Rear connection
On backplate or rails
3P 4P
4 6,5 6 6,5
Y Y
E47969A
E47970A
106 106
44 44
234 234
X 44
X 44
106 106 117
117
35 35
70 70 70
100 100
200 270
Note.
Mounting parameters for electrically operated devices are identical to those for manually
operated devices.
X and Y are the symmetry planes for a 3-pole device
Z is the back plane of the device.
Toggle control
124 mini
E59368
(A)
(1) (2)
Door cutout
(B) A B
(C) 150
194 mini (3P) 194 mini (3P)
E47901A
E59201B
(2) 194 mini 194 mini
264 mini (4P) 264 mini (4P)
Y Y 201 (1)
X 216 (1) X
266 (2)
X
194 mini
264 mini (4P)
Y
119 (1)
144 (2)
95,5 (1)
108 (2)
35,5 (1)
60,5 (2)
(1) Without escutcheon 71 (1)
(2) With escutcheon 121 (2)
Electrical control
Door cutout
A
E59369
194 mini
264 mini (4P)
Y
X 216 (1)
266 (2)
X
108 (1)
133 (2)
107,5
194 (1) 97 (1)
169,5 244 (2) 122 (2)
175,5
F
Z
60
E47955A
R80
195
X X
24
60
107,5 25
154,5
160,5
189,5
229,5
F
Z
Door cutout
A B D
108 (1)
133 (2)
90,5 (1) 90,5 (1)
194 (1) 97 (1) 130 (1)
244 (2) 122 (2) 181 (1)
Y Y 51
E47960A
60
E47958A
E47959A
R100
51
25,5
X X X
24 24
60 5
Z 25
212,5 25
25,5
605,5 maxi
F Note. 51
X and Y are the symmetry planes for a 3-pole device
F : Datum Z is the back plane of the device.
Dimensions
Manual control Electrical control
E47944A
210 210 197,5 (4P)
E47943B
E59370B
mini mini 188
94
Y
70 (*) 46 (*)
199
X X X
45,5 123
69
5 5
90 (3P)
60 mini 60 mini 160 (4P) 90
F F
Mounting
Bottom mounting on base plate or rails Vertical on uprights or backplate
Y
E47175B
Y
E47945
E47937A
X
4 6,5
6 6,5
150
X
24 25 50
25 100
100
216
231
F 90 (3P) F
90 109 (3P)
160 (4P) 109
179 (4P)
Cutouts
Door cutout Rear panel cutout
170 mini (3P)
E47177B
E47178A
230 mini
240 mini (4P)
Y Y
X 259 (1) X
303 (2) 234
117
109 (1)
130,8 (2) 102,5 (3P)
161 (1) 102,5
183 (2) 172,5 (4P)
259 (1)
307 (2)
Y
E47962A
E47963A
136 (*)
60
R80
X X
93 24
60
5
60 mini 25
F
(*) Widrawable position
Door cutout
E47964B
259 (1)
303 (2)
X
109 (1)
130,8 (2)
161 (1)
183 (2) (1) Without escutcheon
259 (1)
307 (2) (2) With escutcheon
Y 51
E47967A
60
E47965A
E47966A
R200
51
25,5
X X X
24 24
60 5
25
509 maxi 25 25
25,5
F
51
Note.
X and Y are the symmetry planes for a 3-pole device
Dimensions
E59440A
E59439
(C)
165
105
20 162
40 169
131 338
160,5 180 (3P)
180
166,5 195 (3P) 295 (4P)
310 (4P) 195
242 210 (3P)
F 325 (4P) 210
390
Z
Mounting on rails
E59456A
Y
4 12
X
150
75
195 (3P)
310 (4P) 195
Note.
F : Datum X and Y are the symmetry planes for a 3-pole device
E59729A
X X 201
216
108 100,5
173 166
346 332
Y
E59458A
X 119
95,9
73
146
Note.
X and Y are the symmetry planes for a 3-pole device
E47683A
E47684A
S : 0,6 mm2
S : 2,5 mm2 2
8
3,5
60 2 6
E47690A
L4
73 60
L3 t
Inpu C
24VD
0A
ut
Outp C +
AD 22 24VD G2
G1
112
E47691A
75
L4
L3 t
Inpu C
24VD
0A
ut
Outp C +
AD 22 24VD G2
G1
60 2 6
E47692A
60
H3 t
H4
+
73
Inpu C
24VD
ut
24V Outp C
BAT + 24VD H1
H2
E47693A
112
75
H4
H3 t
Inpu C +
24VD
ut
24V Outp C
BAT + 24VD H1
H2
2 4,2
57
E47694A
6
3 4 5
1 2
66
81 3 6
S
1
42
0.5
MN 1.5
3 MN
UVR r de R
dateu UV
Retardelay for
30 V Time
100/1C
AC/D
10 12 73
E47695A
2 3
1
6
3 4 5
2
73,5 1
72
S
3 6
1
0.5
MN 1.5
3 MN
UVR r de R
dateu UV
Retardelay for
30 V Time
100/1C
AC/D
10 12
2 3
1
46
E47686A
++ 90
Network
Rseau
CCM
modb
us
45
shield
A A
Fault
B B
A A
B B
Com.
Breaker
Disjoncteur
ss
Addre
.
sync
+
CE
CD
CT
58
54
E47687A
200
130 90
45
F
MDG
45 76
150
58
106
4 14
E47699
GND VN VC
H1 H2
35 76
X2 X1 SG2 SG1
177
208
8 14
H1 H2
E47701
SG1
SG2
X1
X2 44 127
GND
VN
VC
44 174 44
295
Installation
400/1600 (NS630b to NS1600) 1000/4000 A (NS1600b to NS3200)
E47697A
E47696
E47704B
E47703A
197
115 215
2 M3
M1 M
M1 M2 M3
280 70
362
380
146 242
160 260
2 M3
M1 M
M1 M2 M3
456 70
470
552
570
Busbars path
E47708
M1 M2 M3
M1 M2 M3
2 bars 50 x 10
4 bars 100 x 5
E67970
E67971
M1 M2 M3
M1 M2 M3
2 bars 100 x 5
4 bars 125 x 5
Escutcheon
NS630b to 1600 (fixed control)
A C
(A)
E59891A
(C) Y
E59885A
Y
E59886A
X X
275 154
X
27
27 27
131
27
253
Y
E59887A
X 313
X
27
27 13 27
317
Presentation 1
Functions and characteristics 11
Installation recommendations 143
Dimensions, volumes 165
Compact NS80H-MA
E21878
E21877
97
X X
48,5
Y
32 29,2 29,2
Compact NSC100N
30 30 34,5
E43405
E43406
48,5
X X
48,5
Y
45 34,5
90 83
Z
Compact NSA160
30 30 30 30 30 34,5
E21900
E62454
E21898
44 44
X X X
53 53
Y Y
45 45 34,5
90 120 83
Z
E43407
60,8 30 30 30 60,8 30 30 30
30 30 30 30 30
incoming incoming
X X
Y Y
outgoing outgoing
Top connection
3 poles 4 poles
60,8 30 30 30 60,8 30 30 30
E62456
E43408
30 30 30 30 30
X X
Y Y
Connection dimensions
P21
E21748
P13
E21747
G4
X X
G5
G19
Y
Z K1 K1 K1
Front connection
Terminals
NS100/160/250 NS400/630
Z
E21554
E21750
Z
10,5
14
E35578
70 113,5
X
X
Connectors
NS100/160/250 NS400/630
E21752
Z
E21751
E21553
Z Z
46,5
19
14
70 113,5
113,5
X
X X
Rear connection
NS100/160/250 NS400/630
10
E21561
E21756
15 13 23,2
E21755
8,6 20
13 14
18 30
70
43 short RC 50 short RC 113,5
88 long RC X 115 long RC X
Z Z
6 8
E21563
4
E21556
39,5 (b)
41 Z
20,5 30
E35577
70 70
Z
E35580
X X
(b) Vigi module or NS250.
NS400/630
View F
E21754
NS400/630 F
8 Z
61
E21758
58
Z 42
34 8
113,5
113,5
X
X
E21558
K10 K9
E21557
K8 K8 K8 K8 K8
G27
X
G26
70
E21566
X X
41
64,5 Y Y
66,5 (b)
Z
(b) Vigi module or NS250.
Dimensions (mm)
Type G4 G5 G19 G26 G27 K1 K8 K9 K10 P13 P21
NS100/160/250N/H/L 70 140 215 30 41 35 45 159 114 19.5(1)
NS400/630N/H/L 113.5 227 327 39 54 45 52.5 187.5 135 26 44
52,5 67,5 70 240 170
(1) P13 = 21.5 mm for NS250N/H/L and Vigi MH module
Note.
For dimensions of conductors, see pages 00 to 00
E21569
X
X
Z
Y
Front connection
Terminals
NS100/160/250 NS400/630
E21571
42 8
E21939
(*) P21
P21 E
Z
E21572
G32
G32 G31
G31 195,5
210,5
X X
(1) For backplate mounting, the insulating screen, supplied
with the plug-in base, must be installed.
Connectors
NS100/160/250 NS400/630
Mounting on backplate or on rails (1) With spreaders
94
E21941
(*)
68
Z
P28
E21581
E21580
G31
G32
G34 202
X X
E21942
83
P29
P30
Z
E21582
Z
G32
G34
X 66 X
94
Rear connection
Mounting through backplate or on rails
E21573
E21574
(*) P22 Z
P23
G35 P24
G33 P25
Mounting on backplate
Right-angle extensions (mounted down and out)
Long, insulated right-angle
E21577
(*)
P26 Z terminal extensions are
P27 mandatory.
E21576
G33
X
Right-angle extensions (mounted up and out)
(*)
E21579
P26 Z
P27
E21578
G35
Dimensions (mm)
Type E G31 G32 G33 G34 G35 K1 P21 P22 P23 P24 P25 P26 P27 P28 P29 P30
NS100/160/250N/H/L 4 108.5 100 63.5 110 80.5 35 19 75.5 67 49 57.5 75.5 67 26.5 54.5 36.5
NS400N/H/L 6 171 156.5 104 129 45 26 114.5 100 82 96.5 108.5 94
NS630N/H/L 6 181 166.5 104 129 45 26 124.5 110 92 104.5 108.5 94
E47904A
43,5
E47905A
70 70 70
15
E47918A
123
67,5
N Y
X 44
E47201B
67,5
25 9,5 12,5
123
15 60
12,5
31
2 11
F
Z
E47908A
15
E47919A
View A
97
X N Y
97
60
E47205B
12,5
12,5 9,5
31
F 44
Z
25
2 11
View A detail
Front connection
E47910A
70 70 70
30
E47916A
E47911B
163,5
129
N Y
View A
X
Top terminal Bottom terminal
129
E47971A
44
9,5
163,5 25 2 vis M10 15
15
16,5 25 15
2 vis M10 15 9,5
F 44
Z View A detail
Note.
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer
E47921A
E47922A
70 70
25 25
E47920A
196
181
Y 15
View A
E47923A
95 95 95
181 70 70 70
196
12,5 12,5
N Y 15
31,5
View A
F
Z
98 95 95
E47926A
70 70
123
15
82,5
X 52,5
15
Y
123
E47927A
95 95 95
83
70 70 70
F
Z 12,5 12,5
N Y
Spreader detail
Middle left or middle right Middle spreader for 3P Left or right spreader for 4P Left or right spreader for 3P
spreader for 4P
E47234A
E47292A
E47293A
E47294A
77 77 77 77
38,5 38,5 38,5 38,5
13,5 13,5 13,5 13,5
25 = = 25 = = 25 = = 25 = =
30 30 30 30
82 52 82 52 15 82 52 15 82 52 15
15
5 11 5 11 5 11 5 11
25 25 25 25
52 52 52 52
View A detail
Note.
F : Datum X and Y are the symmetry planes for a 3-pole device.
E47929A
E47930A
E47928A
70 70 70
15
View A
200
N Y
430
X
E47218A
200 89 12,5
25 = = 15
21 (1)
101 21
3 11
10
62,5 15 20
F
Z View A detail
Note.
(1) two mounting possibilities for vertical-connection adapters
(pitch 21 mm).
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer
E47933A
E47931A
70 70 70
E47932A
View A
250
N Y
200
15
530
X 184
E47230A
17 50 50 50
200
250 80 50
5 13 5 11
View A detail
15
10
150
F
Z
70 70 70
E59203A
E59204A
E59202A
199 206,5
N Y
398 413
X 4 21,5
E59205A
199 206,5
26 63
26
16,5 54
35
61
F
Z
E47181A
E47179A
E47948A
70 70 70
49
15
67,5
228
X N Y
67,5
114
E47201B
44
25 9,5 12,5
267,5 15
F 60
12,5
2 11
70 70 70
E47182A
E47940A
49 15
View A
E47184A
97
X
97 N Y
E47205B
60
12,5
267,5 12,5 9,5
F
44
25
2 11
View A detail
Front connection
E47941A
View A
E47185A
15 12,5 70 70 70
E47187A
171
N Y
336
X Top terminal Bottom terminal
140 44
9,5 25 37,9 9,5
2 11
E47188B
26
235 12,5 83 100
131 52
F
26
2 11
25
9,5
37,9 9,5 44
View A detail
Note.
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer
E47952A
E47225A
95 95
View A
70 70
238
223
Y
X
E47226A
95 95 95
207
70 70 70
192
View A
12,5 12,5
250
F
N Y
Spreader detail
Middle left or middle right Middle spreader for 3P Left or right spreader for 4P Left or right spreader for 3P
spreader for 4P
E47234A
E47292A
E47293A
E47294A
77 77 77 77
38,5 38,5 38,5 38,5
13,5 13,5 13,5 13,5
25 = = 25 = = 25 = = 25 = =
30 30 30 30
82 52 82 52 15 82 52 15 82 52 15
15
5 11 5 11 5 11 5 11
25 25 25 25
52 52 52 52
View A detail
E47953A
15
E47227A
50
E47229A
71
292
21
171
N Y 15
583 184
X 17 50 50 50
E47230A
140
21 80 50
261
71 5 13 5 11
View A detail
50
193,5 15
F
F : Datum
Note.
X and Y are the symmetry planes for a 3-pole device.
Tightening torque: 50 Nm with contact washer
X and Y are the symmetry planes for a 3-pole device
E59460
E59461A
165
150
E59459A
N Y
View A
OFF
OFF
X
E59462B
76 25
150 13 = =
165 =
=
3 11
15
View A detail
20
F
Z
E59737
230
142,5
N Y Vue A
X
Z
OFF
OFF
142,5 4 11
E59735
230
25
25 60 100
25
20
25
F 20 12,5 20
40
45 15 25 25
60 80
View A detail
E59741A
230
142,5
N Y View A
X
OFF
Z 4 11
OFF
142,5
E59735
230 25
25 60 100
25
20
20 12,5 20
25
F 45 15 25 25
40
60 80
Note.
Recommended connection screws: M10 class 8.8 View A detail
Tightening torque: 50 Nm with contact washer
Presentation 1
Functions and characteristics 11
Installation recommendations 143
Dimensions, volumes 165
Connection 205
VT
WH
RD
D1 C1 92 94 12 14 12 14
E43821
E43822
Q OF1 CAO1 OF1 CAF1 CAF2
trip unit
MN (1)
MX SD
D4 C2 91 11 11
WH
GY
RD
(1) MN or MX (MN: D1, D4; MX: C1, C2)
With MN With MX
E43823
- CN 1 + - CN 1 +
E43824
CN1 CN1
CN2 - CN 2 CN2 - CN 2
F1 F1
D1 92 94 C1 92 94
Q Q
MN MX
SD SD
D4 91 C2 91
X1
1 2 3 4 5 6
WH
WH
WH
RD
RD
BL
D1
E43831
WH
D1 C1
Q CAF1 CAF2
trip unit
MN
D4
BL
D4
With MN + SD
CN1 - CN1 +
(1) trippinng
order
CN2 - CN2
X1
1 2 3 4 5 6
WH
GN
WH
WH
RD
RD
BK
BL
D1 92 94
E43830
WH
GN
RD
D1 C1 92 94
Q CAF1 CAF2
trip unit
MN
SD
D4 91
BL
BL
D4 91
E62467
Q OF1 CAO1
trip unit
MN (1)
MX SD
D4 C2 91 11
(1) MN or MX (MN: D1, D4; MX: C1, C2)
Symbols
Q Compact NS
SD trip indication contact
OF ON / OFF indication contact
MN undervoltage release
MX shunt release
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
XI terminal block for CAF wiring (must be ordered)
F1 breaker for the protection of MN/MX
H1 lamp signalling tripped position
E43823
CN1 - CN 1 +
CN2 - CN 2
F1
tripping order
H1
D1 92 94
trip unit
MN
SD
D4 91
With MX
E43824
CN1 - CN 1 +
CN2 - CN 2
F1
tripping order
H1
C1 92 94
trip unit
MX
SD
C2 91
WH
GY
GY
E18916
VT
VT
RD
YE
VT
314 312 352 354 D1 C1 92 94 12 14 22 24 82 84
WH
GN
GN
RD
RD
YE
YE
VT
VT
CE
D1 C1 92 94 12 14 22 24 72 74 82 84
trip unit
SDE
MN (1) (2)
MX SD
Id
SDV
D4 C2 91 11 21 71 81
OR
GY
GY
BK
BK
BL
CD
311 351 D4 C2 91 11 21 81
WH
RD
GY
YE
YE
VT
E18917
GN (3)
WH
WH
GN
OR
RD
YE
YE
VT
VT
BL
CE
D1 C1 92 94 12 14 22 24 72 74 82 RD 84 B2 A2 A4 B4
Q OF OF2
MT
trip unit
SDE
MN (1) (2)
MX SD
BK (3)
Id
SDV
D4 C2 91 11 21 71 81 A1 L1
GN
OR
GY
GY
BK
BK
BL
CD
311 351 D4 C2 91 11 21 A1 L1
YE
YE
GY
GY
E22042
VT
VT
WH
RD
YE
VT
314 312 352 354 Z11 e+ T1 D1 C1 92 94 12 14 22 24 32 34 82 84
WH
GN
OR
GN
GN
RD
RD
BK
YE
YE
YE
VT
VT
VT
CE
D1 C1 92 94 12 14 22 24 32 34 72 74 82 84
MX SD
Id SDV
D4 C2 91 11 21 31 71 81
WH
OR
RD
GY
GY
GY
BK
BL
BL
CD
311 351 Z12 e- T2 D4 C2 91 11 21 31 81
WH
RD
GY
YE
YE
VT
VT
GN (4)
WH
WH
GN
OR
GN
OR
RD
BK
YE
YE
YE
VT
VT
VT
BL
CE
RD
D1 C1 92 94 12 14 22 24 32 34 72 74 82 84 B2 A2 A4 B4
MX SD
BK (4)
Id SDV
D4 C2 91 11 21 31 71 81 A1 L1
WH
GN
OR
GY
GY
GY
RD
BK
BK
BL
BL
CD
311 351 Z12 e- T2 D4 C2 91 11 21 31 A1 L1
YE
YE
31 32 34 _
SDV earth-fault indication contact 11 12 14 21 22 24 71 72 74 T2 24 e
OF ON / OFF indication contact _
MN undervoltage release 91 92 94 81
A1
82
L1 84 Z11 e+ e T1 22 e+
MX shunt release
MT motor-mechanism module Z12 21 Z11
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
B4 34 84 D4 14 94
CE connected-position carriage switch 74
CD disconnected-position carriage switch D1
C1 C2 D4 A2 A4 B4 Z12 T1 R1 T2 R2 32 82
A4 72 L1 C2 12 92
Colour code for auxiliary wiring
RD red Fixed part 31 81 D1
A2 71 A1 C1 11 91
GN green (front view looking into base)
BK black
Fixed part (rear view).
VT violet
YE yellow
GY grey
BL blue
OR orange
WH white
E43825
- CN1 +
charged and relays in the normal position. CN1
CN2 - CN2
F O
tripping H1 H2
order
(2)
D1 A2 A4 B4
RD
WH
GN (1)
WH
OR
BL
D1 82 84 B2 A2 A4 B4
MT
trip unit
SDE
MN
BK (1)
D4 81 A1 L1
GN
BK
BL
D4 A1 L1
CN1 - CN1 +
CN2 - CN2
F1
F O
H1 H2
A2 A4 B4
RD
WH
GN (1)
OR
BL
82 84 B2 A2 A4 B4
Q
Symbols
Q Compact NS100 to 630 trip unit MT
SDE fault indication contact SDE
MT motor-mechanism module
F1 breaker for protection of motor-mechanism module circuits
H1 lamp signalling an electrical fault BK (1)
H2 lamp signalling motor mechanism in manual position
F closing order
O opening order orders must not be simultaneous 81 A1 L1
GN
BK
CN1 - CN1 +
CN2 - CN2
F1
F O
H1 H2
A2 A4 B4
RD
WH
GN (1)
OR
BL
82 84 B2 A2 A4 B4
trip unit MT
SDE
BK (1)
81 A1 L1
GN
BK
A1 L1
1 2 F O F O
locked by locked by
tripping tripping
order order
B2 A2 A4 B4 B2 A2 A4 B4
MT MT
82 81 82 81
Without auxiliary
Controlled by switch Controlled by relay
E43841
E43840
1 2 F O F O
B2 A2 A4 B4 B2 A2 A4 B4
MT MT
82 81 82 81
E43834
charged and relays in the normal position. CN1 - CN1 +
CN2 - CN2
R F O
tripping H2
order
(3)
D1 84 A2 A4 B4
RD
WH
WH
OR
(1)
BL
D1 82 84 B2 A2 A4 B4
MT
trip unit
(2) SDE
MN
D4 81 A1 L1
BL
GN
BK
D4 A1 L1
CN1 - CN1 +
CN2 - CN2
F1
R F O
tripping H2
order
(3)
C1 84 A2 A4 B4
WH
(1)
OR
BL
operation.
(2) connect SDE terminal 81 to auxiliary-connector terminal 84. C1 82 84 B2 A2 A4 B4
(3) the tripping order must lock out the closing order.
Symbols
Q Compact NS100 to 630
Q
SDE fault indication contact
MN undervoltage release MT
trip unit
MX shunt release (2) SDE
MT motor-mechanism module
MX
F1 breaker for protection of motor-mechanism module
circuits and MN/MX
H2 lamp signalling motor mechanism in manual position
R reset order
C2 81 A1 L1
(must be > 150 ms) orders
OR
GN
BK
R F O
H2
84 A2 A4 B4
RD
WH
OR
(1) BL
82 84 B2 A2 A4 B4
MT
trip unit
(2) SDE
81 A1 L1
GN
BK
A1 L1
1 2 F O F O
R R
locked by locked by
tripping tripping
order order
B2 A2 A4 B4 B2 A2 A4 B4
MT MT
81 81
Without auxiliary
Controlled by switch Controlled by relay
E43917
E43916
1 2 F O F O
R R
B2 A2 A4 B4 B2 A2 A4 B4
MT MT
81 81
E43837
CN1 - CN1 +
charged and relays in the normal position. CN2 - CN2
D1 84 A2 A4 B4
WH
WH
OR
RD
BL
D1 82 84 B2 A2 A4 B4
MT
trip unit
SDE
(2)
MN
(1)
D4 81 A1 L1
GN
BK
BL
D4 A1 L1
CN1 - CN1 +
CN2 - CN2
F1
F O
H1 H2
tripping
order
D1 84 A2 A4 B4
WH
WH
OR
RD
BL
D1 82 84 B2 A2 A4 B4
MT
trip unit
SDE
(2)
(1) (2) required to ensure correct indication of an electrical MX
fault. (1)
Symbols
Q Compact NS100 to 630 D4 81 A1 L1
SDE fault indication contact
GN
BK
BL
MN undervoltage release
MX shunt release
D4 A1 L1
MT motor-mechanism module
F1 breaker for protection of motor-mechanism module
circuits and MN/MX
H1 lamp signalling an electrical fault
H2 lamp signalling motor mechanism in manual position
F closing order orders
O opening order must not
(must be > 150 ms, be simultaneous
has priority over F order)
Colour code for auxiliary wiring
RD red
GN green
BK black
BL blue
OR orange
WH white
F1
F O
H1 H2
84 A2 A4 B4
WH
OR
RD
BL
82 84 B2 A2 A4 B4
MT
trip unit
SDE
(2)
(1)
81 A1 L1
GN
BK
A1 L1
1 2 F O F O
locked by locked by
tripping tripping
order order
B2 A2 A4 B4 B2 A2 A4 B4
MT MT
81 81
Without auxiliary
Controlled by switch Controlled by relay
E43912
E43913
1 2 F O F O
B2 A2 A4 B4 B2 A2 A4 B4
MT MT
81 81
E43831
charged and relays in the normal position. CN1 - CN1 +
(1) tripping
CN2 - CN2 order
WH
WH
WH
RD
RD
BL
D1
WH
D1 C1
Q CAF1 CAF2
trip unit
MN
D4
BL
D4
Symbols
Q Compact NS
SD trip indication contact
MN undervoltage release
CAF early-make contact of rotary handle
XI terminal block for CAF wiring
(must be ordered)
Colour code for auxiliary wiring
RD red
GN green
BK black
BL blue
WH white
CN1 - CN1 +
(1) trippinng
order
CN2 - CN2
X1
1 2 3 4 5 6
WH
GN
WH
WH
RD
RD
BK
BL
D1 92 94
WH
GN
RD
D1 C1 92 94
Q CAF1 CAF2
trip unit
MN
SD
D4 91
BL
BL
D4 91
Thermal-fault indication
E28434
CN1 - CN1 +
CN2 - CN2
F1
D1
BP1
WH
97 13 43
KA1 KA1
14 44
trip unit
SDTAM
98
BL
D4
A1 X1
KAI H1
A2 X2
Symbols
Q Compact NS100 to 630
F1 breaker for protection of the auxiliary circuit
SDTAM thermal-fault early-break signal
BP1 SDTAM reset button
KA1 auxiliary relay - Telemecanique
CA...DN31 or CA...DN22
H1 lamp signalling SDTAM fault
Colour code for auxiliary wiring
BL blue
WH white
I
overload
O
I
SDTAM
O
tr
I
BP1
O
I
H1
O
I
Q
O
IQ
CN1 - CN1 +
CN2 - CN2
F1
D1
WH
97
21 42
Q
BP1 KA1 KA1
22 44
trip unit
SDTAM
(1)
98
BL
D4
E1
A1 A1 X1
KA1 KM1 H1
KM1
A2 KA2 A2 X2
E2
Symbols
Q Compact NS100 to 630
F1 breaker for protection of the auxiliary circuit
SDTAM thermal-fault early-break signal
BP1 SDTAM reset button
KA1 auxiliary relay - Telemecanique
CA...DN31 or CA...DN22
KA2 mechanical latching unit -
Telemecanique LA6 DK1
RHK bistable relay - Telemecanique
RHK-41
H1 lamp signalling SDTAM fault
KM1 power contactor
Colour code for auxiliary wiring
BL blue
WH white
I
overload
O
tr
I
SDTAM
O
I
BP1
O
I
H1
O
I
KM1
O
I
Q
O
CN1 - CN1 +
CN2 - CN2
F1
D1
BP1
D4
E4
C
RHK
12 11 14 22 21 24 X
(1)
A1 X1
KM1 H1
A2 X2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
AT BPO BPF
D2
C2
A4
A2
B4
Z1
Z2
Z3
Z4
Z5
Q motor-mechanism
MN MX module
I
Micrologic
or
E59041A
E59040B
D1
C1
A1
F2+
M1
M2
T2
T3
T1/M3
T4/F1
SG1
SG2
X1
X2
24 V DC
motor-mechanism
module
A1
CN2 - 440/480 V
E59043A
E6 E5 E4 E3 E2 E1
MN/MX
OF1
open closed fault fault closed open 11 12 14
M1M2 M3 F1 F2 D1/C1
Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4
D2/C2 OF2
21 22 24
522
512
524
514
542
532
544
534
32
22
12
82
84
92
94
34
24
14
OF3
31 32 34
SD
91 92 94
511
541
531
31
21
11
91
81
E6 E5 E4 E3 E2 E1
MN/MX
SDE : fault-trip indication contact
(short-circuit, overload, earth fault) M1M2 M3 F1 F2 D1/C1
Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4
D2/C2
SD : trip indication contact
(manual operation)
81 31 21 11
CAO2 / CAO1 : early-break contact
(rotary handle) 82 32 22 12
84 34 24 14
B4 A4 A2 A1
E59037B
power
E59730A
upstream cb downstream cb
N L1 L2 L3
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
AT BPO BPF
D2
C2
B4
A4
A2
Z1
Z2
Z3
Z4
Z5
Q motor-mechanism
MN MX module
I
Micrologic
or
F2+
M1
M2
T2
T3
T1/M3
D1
C1
A1
T4/F1
SG1
SG2
X1
X2
24 V DC
E5 E6 Z5 M1 M2 M3 F2+ D2 C2 A4 A2
E3 E4 Z3 Z4 T3 T4 B4
E1 E2 Z1 Z2 T1 T2 F1 D1 C1 A1
motor-mechanism
module
A1
CN2 - 440/480 V
E47075A
E46134A
E47074A
open closed fault fault closed open disconnected connected Test
332
334
322
324
312
314
822
824
812
814
522
512
524
514
542
532
914
544
534
912
32
22
12
82
84
92
94
34
24
14
321
331
311
821
811
911
521
511
541
531
31
21
11
91
81
544 534 84 94 524 514 34 24 14 824 814 334 324 314 914
542 532 82 92 522 512 32 22 12 822 812 332 322 312 912
Legend
Connected
(only one wire per connection point)
motor-mechanism
module
914 812 314 912 812 312
N L1 L2 L3 manual opening order
operation
OF closing order
SDE OF
Z1
Z2
Z3
Z4
Z5
CT CD CE CT CD CE
+ +
Q B'
A'
Modbus Digipact
I device B COM craddle COM craddle
Micrologic communication A BB
module BB
+
shield
BB
BB
B' A' B A +
CCP 303
(2)
F2+
E1
E2
E3
E4
E5
E6
M1
M2
T1/M3
T2
T3
T4/F1
CCP 303
5
4
H1 H2
BAT
3 Modbus Digipact
module junction junction
(1) 2
block block
1 CJB306
H3 H4 (2)
0
G1 G2
yellow
brown
24 V
black
white
AD
blue
0V
red
module
E1 E2 E3 E4 E5 E6 0V 24 V
L3 L4
+ A B A' B' Modbus 24 VDC 24 VDC
communication
+ / / BB BB + Digipact 1A
power supply
DC 150
None of the control-unit protection functions require an auxiliary source. However, the 24 V DC external power supply (AD module) is
required for certain operating configurations as indicated in the table below.
Circuit breaker Closed Open
Fonction protection no no
Display function no (3) yes
Circuit-breaker status indications and control no no
communications bus
The communications bus requires its own 24 V DC power source (E1, E2). This source is not
the same as the 24 V DC external power-supply module (F1-, F2+).
If the 24 V DC external power supply (AD module) is used, the maximum cable length between
(1) Drawout device equipped with Com chassis modbus the 24 V DC external power supply (G1, G2) and the Micrologic control unit (F1-, F2+) is ten
(2) Fixed device or draw-out device without Com chassis metres.
Digipact The BAT battery module, mounted in series upstream of the AD module, ensures an
(3) except if current < 20% In uninterrupted supply of power if the AD module power supply fails.
E47976
variables managed by Micrologic control units DMB300 5 CCP303
equipped with the eco COM Modbus module. 1
4
c I (Micrologic A) 2
No programming is required. 3
3
4 I U P ?
For Micrologic A control unit (if current < 20% In), it is
switchboard 2
recommended to use the 24 VDC external power display unit
supply (AD module). 1
24 V
0V
Modbus power circuit
junction 24 VDC breaker
block 1A
CJB 306
Communicating switchboard
This configuration provides remote display and control
of Masterpacts equipped with the Modbus or Digipact
COM module. The Digipact bus can be combined with
the Modbus bus.
E59304
TCP/IP
Communication
interface
RS 232C Ethernet
RS 485 RS 485
communication
Bus
Data
concentrator DC150
Device
E59305A
Connection of current-transformer secondary N L1 L2 L3
circuit for external neutral
Z1
Z2
Z3
Z4
Z5
Compact equipped with a Micrologic 6 A:
c shielded cable with 2 twisted pairs
c SG1 twisted with SG2
c X1 twisted with X2
c shielding connected to GND on one end only
c maximum length 5 metres
c cable cross-sectional area 0.4 to 1.5 mm2
c recommended cable: Belden 9552 or equivalent.
Q
If supply is via the top, follow the shematics.
If supply is via the bottom, control wiring is identical; I
for the power wiring, H1 is connected to the source Micrologic 6
side, H2 to the load side.
For four-pole versions, for residual earth-fault
protection, the current transformer for the external
neutral is not necessary.
F2+
M1
M2
M3/T1
T2
T3
F1 /T4
H2
SG1
SG2
X1
X2
H1
GND
I
Micrologic 6
F2+
M1
M2
M3/T1
T2
T3
F1 /T4
H1 X1 12 5 6 7 10 11
1 MDGF module 9
E59306
H2 X2 3 13 14 8
PE
E59307A
Connection of the rectangular-sensor secondary
circuit
Compact equipped with a Micrologic 7 A:
Z1
Z2
Z3
Z4
Z5
c unshielded cable with 3 twisted conductors:
v M1, M2, M3 twisted together
c maximum length 4 metres
c cable cross-sectional area 0.4 to 1.5 mm2
c recommended cable: Belden 9493 or equivalent.
I
Micrologic 7
U
F2+
M1
M2
M3/T1
T2
T3
F1 /T4
M1
M2
M3
Neutral protection
Z1 downstream Z1
Z2 circuit breaker Z2
Z3 Z3
Z4 Z4
Z5 Z5
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
AT
D2
C2
Z1
Z2
Z3
Z4
Z5
Q
MN MX
I
Micrologic
or
E59463A
E59040B
D1
C1
F2+
M1
M2
T2
T3
T1/M3
T4/F1
SG1
SG2
X1
X2
24 V DC
E59465A
E6 E5 E4 E3 E2 E1
MN/MX
OF1
open closed fault fault 11 12 14
M1M2 M3 F1 F2 D1/C1
Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4
D2/C2 OF2
21 22 24
32
22
12
82
84
92
94
34
24
14
OF3
31 32 34
SD
91 92 94
21
11
91
81
81
82
84
SDE
Indication contacts
Presentation 1
Functions and characteristics 11
Installation recommendations 143
Dimensions, volumes 165
Connection 205
Electrical diagrams 221
1640 A
E44454
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
1
16A : Im = 37,5 x In
.5
20A : Im = 30 x In
.2 25A : Im = 24 x In
.1 32A : Im = 19 x In
.05 40A : Im = 15 x In
.02
.01
.005
.002
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir
5080 A 100 A
E44455
10 000 10 000
E44456
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
1 1 100A : Im = 12,5 x In
.5 50A : Im = 20 x In .5
.2 63A : Im = 16 x In .2
70A : Im = 14,3 x In
.1 .1
80A : Im = 12,5 x In
.05 .05
.02 .02
.01 .01
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
MA1.5MA80
10 000
E28466
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
Im = 614 x In
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir
1640 A 5080 A
E30207
E30206
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
1 1
16A : Im = 37,5 x In
.5 .5
50A : Im = 20 x In
25A : Im = 24 x In
.2 .2 63A : Im = 16 x In
32A : Im = 19 x In
.1 .1 80A : Im = 12,5 x In
40A : Im = 15 x In
.05 .05
.02 .02
.01 .01
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
100 A 125160 A
E30209
E30208
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5 160A : Im = 7,8 x In
t(s) t(s)
2 2
1 100A : Im = 12,5 x In 1 125A : Im = 10 x In
.5 .5
.2 .2
.1 .1
.05 .05
.02 .02
.01 .01
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
E58555
10 000 ambient temperature compensatory 10 000 ambient temperature compensatory
5 000 coefficient for trip time ( % ) 5 000 coefficient for trip time ( % )
160
NB50 150
2 000 130
2 000
1 000 100 1 000 100
500 500
60 60
0 20 40 60 0 20 40 60
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
NB50 Inst.
1 1
.5 15 A 11 In .5
20 A 10 In
30 A 12 In
.2 .2
40 A 11 In 10 In 20%
.1 50 A 12 In .1
.05 .05
.02 .02
.01 .01
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / In I / In
10 000 10 000
E58712
2 000 120
2 000 120
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
1 1
.5 .5
.2 .2
.1 .1
.05 .05
.02 .02
reflex tripping : reflex tripping :
.01 .01 t < 10 ms
t < 10 ms
.005 .005
.002 .002 I = 11 x In
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / In I / In
E28453
E28452
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
TM16D : 12 x In TM25D : 12 x In
1 1
.5 .5
.2 .2
TM16G : 4 x In TM25G :
.1 .1 3.2 x In
.05 .05
.02 .02
.01 reflex tripping : .01 reflex tripping :
t < 10 ms t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
10 000 10 000
E28455
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
TM40D : 12 x In TM63D : 8 x In
1 1
.5 .5
TM50D : 10 x In
.2 TM32D : 12,5 x In .2
TM40G : TM63G :
.1 2 x In .1 2 x In
.05 .05
.02 .02
.01 reflex tripping : .01 reflex tripping :
t < 10 ms t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
E28457
10 000 10 000
E28456
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5 TM125D
t(s) t(s) 10 x In
2 2
NS160/250
1 Im = 12,5 x In 1
.5 .5 TM160D
NS100 8 x In
.2 Im = 8 x In
.2
.1 .1
.05 .05
.02 .02
.01 reflex tripping: .01 reflex tripping :
t < 10 ms t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
TM200D / TM250D
E28458
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
Im = 5 10 x In
1
.5
.2
.1
.05
.02
.01 reflex tripping :
t < 10 ms
.005
.002
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir
E28460
10 000 10 000
5 000 5 000
2 000 2 000
Ir = 0.41 x In Ir = 0.41 x In
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
Im = 210 x Ir Im = 210 x Ir
1 1
.5 .5
.2 .2
.1 .1
.05 .05
.02 .02
reflex tripping reflex tripping
.01 t < 10 ms .01 t < 10 ms
.005 .005
.002 I = 11 x In .002 I = 11 x In
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
10 000
E28409
10 000
5 000 5 000
2 000 2 000
Ir = 0.41 x In
1 000 1 000
500 500
Ir = 0.41 x In
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
1 1
.5 .5
Im = 210 x Ir
.2 .2
Im = 210 x Ir
.1 .1
.05 .05
.02 .02
reflex tripping : reflex tripping :
.01 t < 10 ms .01 t < 10 ms
.005 .005
.002 I = 11 x In .002 I = 11 x In
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
10 000 10 000
E28467
5 000 5 000
2 000 2 000
1 000 1 000
500 500 thermal withstand
MA220
200 200
MA150
100 thermal withstand 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
Im = 6 14 x In Im = 9 14 x In
1 1
.5 .5
.2 .2
.1 .1
.05 .05
.02 .02
.01 reflex tripping : .01 reflex tripping :
t < 10 ms t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / In
10 000
5 000
2 000 Ir
1 000
500
200
100
50
10
5
t(s)
2
1
.5
Im = 13 x Ir
.2
.1
.05
.02
reflex tripping :
.01 t < 10 ms
.005
.002 I = 15 x In
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir
10 000
E28462
5 000 5 000
2 000 2 000
Ir = 0.41 x In Ir = 0.41 x In
1 000 1 000
500 500
200 200
100 100
50 50 tr = 0.516 s
20 20
Ii = 1.511 x In
10 10
5 5
t(s) t(s) Isd = 1.510 x Ir
2 2
I2t ON
Isd = 210 x Ir
1 1
.5 .5
0.3
.2 .2
0.2
.1 .1 i 2 t OFF 0.1
.05 .05
0
.02 .02
reflex tripping
.01 t < 10 ms
.01
.005 .005 reflex tripping :
t < 10 ms
.002 I = 11 x In .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 5 7 10 20 30 50
I / Ir I / Ir I / In
10 000
5 000
2 000
Ig = 0.21 x In
1 000
500
200
100
50
20
10
I2t ON
5
t(s)
2
1
.5 0.4
0.3
.2 0.2
.05
.02
.01
.005
.002
.001
.05 .07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 20 30
I / In
E28369
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 thermal withstand 100
50 50
class 10 A
20 20
10 10
5 5
t(s) t(s)
2 2 hot tripping curve
1 1 cold tripping curve
.5 .5
Isd = 613 x Ir
.2 .2
Im = 9 ... 14 x In
.1 .1
.05 .05
.02 .02
reflex tripping
.01 reflex tripping : .01 t < 10 ms
t < 10 ms
.005 .005
10 000
E38946
10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
class 20
50 class 10 50
20 20
10 10
5 5
t(s) t(s)
2 hot tripping curve 2 hot tripping curve
1 cold tripping curve 1 cold tripping curve
.5 .5
Isd = 613 x Ir Isd = 613 x Ir
.2 .2
.1 .1
.05 .05
.02 .02
reflex tripping reflex tripping
.01 t < 10 ms .01 t < 10 ms
.005 .005
Ii = 10,4 x In Ii = 10,4 x In
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
Thermal-withstand capacities are given for circuit
breakers operating in an ambient temperature of 65 C.
E46276
E46350
10 000
5 000 Ir = 0,41 x In 5 000 Ir = 0,41 x In
2 000 2 000
1 000 1 000
500 500
200 200
100 tr = 0,5...24 s 100 tr = 0,524 s
50 50
20 20
10 10
5 5
t(s) t(s) Isd = 1,510 x Ir
2 2
Isd = 1,510 x Ir
1 1
I2t ON
.5 .5 0,4 0,4
0,3 0,3
.2 .2 0,2 0,2
0,1 2 0,1
.1 .1 I t OFF
0 0
.05 .05
Ii = 215 x In . OFF
.02 .02
.01 .01
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 3 5 7 10 20 30
I / Ir x Ir x In
10 000
5 000
2 000
Ig = AJ x In (1)
1 000 1200 A max.
500
200
100
50
20
10
5
t(s) I2t ON
2
1
.5 0.4 0.4
0.3 0.3
.2 0.2 0.2
0.1 0.1
.1 I2t OFF
0 0
.05
.02
.01
.005
(1)
.002 Ig = In x A B C D E F G H J
.001 Ig < 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
.05.07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 200 300 400 A i Ig i 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
I / In Ig > 1200 A 500 640 720 800 880 960 1040 1120 1200
E28463
Compact NS100 to 630 devices TM160D...TM250D
STR22SE250
incorporate the exclusive reflex-tripping
20
system.
This system breaks very high fault currents NS630
2 3 4 6 10 20 30 40 60 100 200
kA rms
Current-limiting curves
The current-limiting capacity of a circuit breaker is expressed by two curves which
are a function of the prospective short-circuit current (the current which would flow
if no protection devices were installed):
c the actual peak current (limited current),
c thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 .
Example
What is the real value of a 150 kA rms prospective short-circuit (i.e. 330 kA peak)
limited by an NS250L upstream ?
Answer: 30 kA peak (see next page).
300 300
E58559
E58557
NS630bH
NS800H
200 NS630bN NS1000H 200
NS800N NS1250H NS630bH
NS1000N NS1600H NS800H
NS1250N NS1000H
NS1600N NS630bN NS1250H
100 NS630bL 100 NS800N
NS800L NS1600H
80 NS1000L
80 NS1000N
70 70 NS1250N
60 60 NS1600N
50 NS630 50 NS630bL
H NS400 NS800L
L
kA peak40 N
L
kA peak 40 NS1000L NS630 NS400
TC150/250/400
NS250 H
30 H NS160
30
NS100
N NS100
20 TM32...250 20 N L
NS250 TM40100
TM25 TM 25
N NH NS160
TM16
E N TM 16
10 10
8 NSA160 8
7 7
6 6
5 5
4 4
2 3 4 6 10 20 30 40 60 100 200 300 2 3 4 6 10 20 30 40 60 100 200 300
kA rms kA rms
Thermal-stress curves
Voltage 380/415 V AC Voltage 660/690 V AC
9 9
10 10
E58558
E58556
5 5
3 NS630bH 3
NS800H
2 NS630bN NS1000H
2
NS800N NS1250H NS630bH
8 8 NS800H
10 NS1000N NS1600H 10
NS1250N NS1000H
NS1600N NS1250H
NS630bN
5 5 NS800N
NS1600H
NS1000N
3 3 NS1250N
2 2 NS1600N
7 7
10 NS1000L
10 NS630bL
NS800L
2 NS630bL 2 NS1000L
As 5 L NS800L As 5 H NS630
H L L NS400
N NS630
3 L 3 H
TC150/250/400
N
H NS400
2 N 2
N L
6 6
10 H L 10 H
NS250
NS100
NS250
NS160 N TM 40100
NS160
5 NS100 5
N TM32250
3 E N 3 TM 25
NSA160 TM25
2 2 TM 16
5 5
10 TM16 10
5 5
3 3
2 2
2 3 4 6 10 20 30 40 60 100 150 200 300 2 3 4 6 10 20 30 40 60 100 150 200 300
kA rms kA rms