Company Business

Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabia
and today is a leading international manufacturer of air conditioning systems and is Number One in the Middle East.

Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55
countries in the Middle East, Europe, Africa and Asia.

The companys operations are structured into four Strategic Business Units (SBUs) supporting five in-house product and
service brands as well as a number of international brands under the OEM sales.

The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.

The four SBUs are:


1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.
2. Unitary & Applied Business Unit supporting Zamil, Cooline, GE and OEM brands for commercial and industrial customers.
3. Zamil CoolCare Business Unit providing industrial, electro mechanical contracting services, HVAC maintenance, retrofit
& operation services and parts.
4. Geoclima srl is an independent business supporting other SBUs for their requirements of chillers & double skin AHUs.

The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare direct their business operations
from the corporate headquarters in Dammam, Saudi Arabia.

Geoclima has its engineering & production operations located at Monfalcone, Italy and has a design center in Austria.

All the four SBUs, while operating independently, supplement each others activities in a way that makes synergy work at
its best and achieve the corporate goals of maximizing customer satisfaction.

Factories and Productions


Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one specialty production facility
in Italy operated by Geoclima.

The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air
Conditioning systems per year.

Quality & Product Certificates


The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.

Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabias Standard Organization)
Certificate for Room Air Conditioners. ZACs products are also certified with:
1. CE (Council of European Community)
2. UL (Underwriters Laboratory)
3. Eurovent (Certified Performance)
4. ETL (Test Facilities)
5. SASO (Saudi Arabian Standards Organization)
6. ISO 9001:2008 (International Organization for Standardization)
7. ASME (American Quality of Mechanical Engineers)

Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed
bin Fahd Al Saud Award for Factory Safety.

Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners
manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the Concealed
Units up to 5 TR, the Ducted Splits up to 30 TR, the Packaged Units up to 95 TR, the Single and Double Skin Air Handling Units
up to 138,316 CFM and the Water Chillers up to 600 TR cooling capacity. In addition, centrifugal chillers - powered by MHI
compressors - are available up to 5,000 TR.
INDEX

Contents Page

Model decoding ........................................................................................................................................ 2

Unit features, standard specifications & options .................................................................................... 3-6

Microprocessor controller .......................................................................................................................... 7

Physical data ....................................................................................................................................... 8-11

Selection procedure ............................................................................................................................ 12-13

Performance data ................................................................................................................................ 14-19

Electrical data ..................................................................................................................................... 20-22

Water side pressure drop ........................................................................................................................ 23

Recommended installation for sensor & water flow switch ...................................................................... 24

Unit dimensions ................................................................................................................................. 25-31

Typical schematic wiring diagram ....................................................................................................... 32-33

Typical sequence of operation ................................................................................................................. 34

Application guidelines ......................................................................................................................... 35-43

Rigging instructions ................................................................................................................................. 44

Installation clearance .............................................................................................................................. 45

Mounting location .................................................................................................................................... 46

Load distribution .................................................................................................................................. 47-48

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1
MODEL DECODING
1, 2 & 3 4, 5 & 6 7 8 9 10 11 12 13 14 & 15 16 & 17
BASIC UNIT SIZE REFRIGER- ELECTRICAL CONDENSER COIL CIRCUIT BREAKER COOLER COMPRESSOR HGBP OPTIONS UL
(SERIES) ANT SUPPLY OPTIONS OPTIONS OPTIONS OPTIONS & OPTIONS
( V-Ph-Hz ) ACCESSORIES

ASY 050 B : R-134a H : 208/230-3-60 A : ALUMINUM FIN A : STANDARD A : STANDARD WITH A : STANDARD UNIT A : STANDARD UNIT SEE NOTE # 2 A : STANDARD
060 VICTAULIC CONN. WITHOUT SUCTION WITHOUT HGBP & BELOW UNIT
AIR COOLED
070 M: 380-3-60 B : PRE-COATED B : COMPRESSOR SERVICE VALVE WITHOUT SUCTION WITHOUT UL
SCREW WATER
080 (4 WIRE) ALUMINUM FIN CIRCUIT B : FLANGE CONN. SERVICE VALVE
CHILLERS
090 BREAKER (OPTIONAL) B : UNIT WITH B : STANDARD
100 C : COPPER FIN
F : 460-3-60 SUCTION SERVICE B : WITH HGBP & UNIT WITH UL
120 C : ASME STAMPED VALVE WITHOUT SUCTION LISTED
D : ALUMINUM FIN
130 WITH ResisTec WITH VICTAULIC (OPTIONAL) SERVICE VALVE
140 COATING CONN. (OPTIONAL)
150 (OPTIONAL)
160 E : COPPER FIN C : WITHOUT HGBP &
170 WITH ResisTec WITH SUCTION
180 COATING D : ASME STAMPED SERVICE VALVE
190 WITH FLANGE (OPTIONAL)
(SEE NOTE # 1 CONN.
200
BELOW)
215 (OPTIONAL) D : WITH HGBP &
230 WITH SUCTION
240 SERVICE VALVE
250 (OPTIONAL)
270
295
310

2
330
350
375
400
420
450
475
500
540
560
590

NOTES:
1. FOR OTHER COATING, SPECIFY YOUR REQUIREMENTS IN WRITING.
2. COMPUTER SELECTED DIGITS (FROM 'AA' TO 'ZZ') DESCRIBING OTHER OPTIONS & ACCESSORIES OR COMBINATIONS THEREOF, SUCH AS: - CONDENSER COIL GUARD
- COMPRESSOR & COOLER GUARD
- UNIT MAIN NON-FUSED DISCONNECT SWITCH
- COMPRESSOR ENCLOSURE
- WATER FLOW SWITCH
- SPRING ISOLATOR
- MULTI-ResisTec PIPING
- MULTI-ResisTec SHEET METAL etc...
FEATURES
These ASY air cooled screw water chillers offer the ultimate combination of energy saving design, superior engineering
features and flexibility of application as required by todays market.

* These chillers incorporate the newest advanced microprocessor controller. This controller monitors analog and digital
inputs to achieve precise control & protective functions of the air cooled water chiller units. This microprocessor
controller is complete with all the hardware and software necessary to control the chiller unit and ensures its efficiency
and reliability.

Designed to conform to ARI standard 550/590 water chilling packages using the vapor compression cycle.
*
Designed to conform to ANSI/ASHRAE 15-1994 Safety code for Mechanical Refrigeration.
*
Compact unit design and excellent serviceability.
*
All packaged chillers incorporate compact water coolers with enhanced inner grooved copper tubes bundled into a "U"
*
shape and expanded into a steel tubular sheets which offer efficient water flow as well as heat transfer design resulting
in optimal unit performance.

High Energy Efficiency Ratio (EER) semi-hermetic compact twin screw compressors are provided in these units.
*
Single point power connection (for models ASY050B - ASY500B) to minimize job site installation cost and time. Dual
*
point power connection for models ASY540B - ASY590B.

Completely wired control panel with the advanced microprocessor controller provides all the necessary operat-
*
ing and safety controls.

* Compressors are with part winding start.

Low noise condenser fans, direct drive at 1000 RPM with rolled form venturi design to eliminate short circuiting of
*
airflow.

* All fans are die cast aluminum propeller type with aerodynamic design, top discharge, provided with protective
grille mounted on top panel within the unit casing.

* All condenser fan motors are totally enclosed air over type (TEAO) with class ''F'' winding insulation and ball
bearings. Inherent thermal protection of the automatic reset type and specially designed for outdoor applica-
tion is included.

STANDARD SPECIFICATIONS
CAPACITY CONTROL
These chillers are equipped with stepless capacity control system as standard for very accurate response to load require-
ments and best part load efficiency. Each compressor is equipped with a slider controller that enables to modulate capac-
ity between 25% to 100%, thus giving a broad range to control total chiller capacity between 10% to 100% on an average.
This system has the following advantages:

1. Infinite capacity modulation that allows the compressor capacity to exactly match the cooling load.

2. Reduce compressor cycling which leads to better operational reliability.

3. Reduce operating cost.

4. For units with Hot gas bypass (optional): The unit modulates to approximately 50% of its compressor lowest unloaded
capacity.

3
SEMI-HERMETIC COMPACT TWIN SCREW COMPRESSORS
All compressors are compact semi-hermetic twin screw of the high capacity and efficiency due to their perfect profile
form ratio 5:6. They are simple and of robust construction with slider control valve for capacity unloading, discharge shut-
off valves with optional suction service valves, built-in check valve in discharge gas outlet, oil sight glass, oil fill/drain
service valve, directly flanged-on three stage oil separator with long-life fine filter 10 microns mesh size, robust axial
bearings in tandem configuration, suction gas filter, internal pressure relief valve and manual lock-out electronic protection
system for thermal motor winding temperature, phase reversal, discharge gas temperature protection controls.

CONDENSER COILS
W-configuration condenser coils are corrugated fin and tube type, constructed of seamless 3/8" dia. & 0.011" (0.27 mm)
thick copper tubes, mechanically bonded to aluminum fins for maximum heat transfer efficiency.

As a standard on aluminum fins, ZAC provides Coil Coating, which is a single component of aluminum
impregnated coating applied on the fins of heat exchanging coils. The product has been designed for Middle East
climate conditions. A high chemical, abrasion and UV resistance has been proven in both laboratories and on field
environment. The coating can be applied at the Zamil Air Conditioners factory as well as in the field for maintenance
or rejuvenation purposes.

The fins have full self spacing collars which completely cover each tube. The staggered tube design improves the
thermal efficiency. End plates support sheets are 14 gauge galvanized steel, formed to provide structural strength.
Each coil is pressure tested in the factory at not less than 450 psi air pressure.

COMPACT DESIGN SHELL AND TUBE WATER COOLERS


The DX shell & tube cooler with removable U shaped bundled tubes are made of internally grooved copper tubes
expanded into a heavy steel tubular sheets.

The chiller cooler & baffles are constructed of steel and brass respectively. The coolers are insulated with heavy closed
cellular foam insulation (3/4" thick). All chiller barrels are fitted with vent, drain connection and victaulic water pipe
connection as standard.
SHELL & TUBE WATER SIDE REFRIGERANT SIDE
HEAT
EXCHANGER DESIGN PRESSURE, TEST PRESSURE, DESIGN PRESSURE, TEST PRESSURE,
(COOLER) (BAR/PSIG) (BAR/PSIG) (BAR/PSIG) (BAR/PSIG)
CE (STD) 16/235 22.8/335 29/426 41.5/610

ASME (option) 10/147 11.3/165 15.5/228 23.3/342

CABINET
All units are of heavy gauge (G-90) galvanized steel. Steel sheet panels are zinc coated and galvanized by hot dip
process of lock-forming quality conforming to ASTM A 653 commercial weight G-90 followed by air dry paint or backed on
electrostatic polyester dry powder coat.

CONTROL PANEL
The control panel design is equivalent to NEMA 4 (IP55) with hinged door for easy access ensuring dust and weather-
proof construction. Internal power and control wiring is neatly routed, adequately anchored and all wires are identified
with cable markers as per NEC standards applicable to HVAC industry.

The electrical controls used in the control panel are UL approved which are reliable in operation at high ambient condi-
tions for a long period.

CONDENSER FANS
Condenser fans, the impeller and motors are so constructed to form an integral unit. All fan motors shall be three phase
with class ''F'' winding insulation and ball bearings for high ambient application. These fan motors are of totally enclosed
air over type (TEAO) with inherent thermal protection of automatic reset type.

4
STANDARD CONTROL & SAFETY DEVICES
MICROPROCESSOR CONTROLLER: This controller monitors analog and digital inputs to achieve precise control & safety
functions of the unit.
COMPRESSOR IN-BUILT PROTECTION DEVICE: Protects the compressor by monitoring:
A) Motor winding temperature in case of overload.
B) Discharge gas temperature in case of overheating.
C) Phase reversal for direction of rotation.
STARTERS: The starter is operated by the control circuit and provides power to the compressor motors. These devices are
rated to handle safely both RLA and LRA of motors.
CRANKCASE HEATERS: Each compressor has immersion type crankcase heater. The compressor crankcase heater is
always on when the compressors are de-energized. This protects the system against refrigerant migration, oil dilution and
potential compressor failure.
HIGH PRESSURE SWITCH: This switch provides an additional safety protection in the case of excessive discharge
pressure.
UNDER & OVER VOLTAGE AND PHASE PROTECTION: Protects against low & high incoming voltage as well as single
phasing, phase reversal and phase imbalance by de-energizing the control circuit. It is an automatic reset device, but it can
be set up for manual reset.
COMPRESSOR CIRCUIT BREAKERS: Protects against compressor branch circuit fault. When tripped (manually or
automatically), the breaker opens the power supply to the compressor and control circuit through auxiliary contacts.
HARD WIRE TO BMS: Communicate the controller to site BMS thru hard wire:
1. Remote Unit Enable/Disable (Start/Stop) a digital input to the controller that allows the user to Start and normally
shutdown the chiller unit from remote or control room.
2. Unit General Alarm a digital output signal from the controller to indicate that alarm is existing in the chiller.
3. Compressor Circuit Enable/Disable a digital input to the controller that allows the user to Start and normally shutdown
the compressor from remote or control room.
4. Second Temperature Control Set point a digital input to the controller that allows the user to enable the second set
point. Value for the second temperature control set point can be modified at the controller parameter.
5. Set point correction an analog input to the controller that allows the user adjust the temperature control set point via
external analog signal (4-20mA).

STANDARD ACCESSORIES
UNIT ON-OFF SWITCH: ON-OFF switch is provided for manually switching the unit control circuit.
INDICATOR LIGHTS: LED lights indicates power ON to the units, MENU adjustment and FAULT indications due to trip on
safety devices.
ELECTRONIC EXPANSION VALVE: Electronic expansion valve is used to regulate the refrigerant flow to the water cooler
and maintain a constant superheat and load optimization.
FILTER DRIER (REPLACEABLE CORE TYPE): Refrigerant circuits are kept free of harmful moisture, sludge, acids and oil
contaminating particles by the filter drier.
SIGHT GLASS: A moisture indicating sight glass is installed in the liquid line. An easy-to-read color indicator shows
moisture contents and provides a mean for checking the system refrigerant charge.
LIQUID LINE SOLENOID VALVE: Closes when the compressor is off to prevent any liquid refrigerant from accumulating in
the water cooler during the off cycle.
CONTROL CIRCUIT TRANSFORMER: On 460V-3Ph-60Hz power supply factory mounted and wired control circuit trans-
former is furnished eliminating the need for running a separate 220 volt control circuit power supply.

5
OPTIONS
(All options are at extra cost. Please check with your nearest dealer/sales office)
HOT GAS BYPASS SYSTEM: Hot gas bypass is provided on the lead circuit to permit operation of the system down to 50% of
its unloaded capacity. Under low ambient condition, it controls temperature by eliminating the need to cycle the compressor on
and off, ensuring narrow temperature swing and lengthen the life span of the compressor.
WATER FLOW SWITCH: Paddle type field adjustable flow switch for water cooler circuits. Interlock into unit safety circuits
so that the unit will remain off until water flow is determined.
UNIT MOUNT SPRING ISOLATORS: This housed spring assemblies have a neoprene friction pad on the bottom to
prevent vibration transmission.
LIQUID COOLERS: ASME code stamped liquid cooler.
PRESSURE GAUGES: Suction & discharge pressures gauges.
SUCTION SERVICE VALVE: Compressor suction port service valves.
NON-FUSED MAIN DISCONNECT SWITCHES: De-energize power supply during servicing/repair works as well as with
door interlock.
CONDENSER COIL GUARD: Protects the condenser coils from physical damage.
COMPRESSOR/COOLER GUARD: Protects the compressor from vandalism.
COMPRESSOR OIL LEVEL SWITCH: This monitors the oil level inside the compressor.
COMPRESSOR ENCLOSURE BOX: Reduces compressor operating noise and keeps the compressor clean.
FLANGED COOLER CONNECTION: Easy on-site piping connections.
COOLER HEATER WRAPPED: Prevents freezing up of water on low ambient temperature.
COPPER FINS/TUBES CONDENSER COILS: For seashore salty corrosive environments. Provided with 12 FPI as standard.
COATED COPPER FINS/TUBES CONDENSER COILS: For seashore or acid corrosive environments.
BMS: BACNET-IP, MODBUS-RS485, GSM and stand alone remote display panel.
POWER LINE ANALYZER: Performs motor current limitation. Protects against high motor current & over/under voltage.
: A two component coating system that withstands the extreme climate conditions. The coating can be
applied to all metal parts of HVAC equipment; the piping, the compressors and grids might require a different pre- treatment
and layer build up. Please check ResisTec product information sheets, the heat exchangers can not be coated using this
type. The coating can be applied at the Zamil Air Conditioners factory as well as in the field for maintenance or rejuvenation
purposes.
UL LISTED CHILLERS: ASY chillers in the range of ASY050B thru ASY500B can be optionally offered as UL listed. These
chillers are UL listed under UL file number SA13167.
HAND HELD CONTROLLER: Enables the chiller technician to monitor and serve the chiller by plugging this portable wired
controller into the chiller controller. With built-in magnets, it provides convenient access for chiller status diagnoses and
trouble shooting.
EXTERNAL COMPRESSOR MOTOR OVERLOAD RELAY: Added protection for compressor motor thermal overloading
and prolonged stalling of the motor.
DUAL MAIN POWER ENTRY: Provide flexibility of connecting the chiller to the field power supply. Applicable for chiller
models ASY090B - ASY500B.
EXTENDED MAIN BUSBAR: Provide extended termination for multi cable that may require for chiller with Single power
Entry point. This is applicable only for ASY180B - ASY590B.
MAIN POWER TERMINAL LUGS: A ready to install power main terminal lugs for easy connection of main cable in the
field. The lug has wide range to accept cable sizes and designed to fix a maximum of 4 cables per lug.

6
MICROPROCESSOR CONTROLLER
The microprocessor controller works on the state of art microprocessor technology. This standalone controller monitors
analog and digital inputs to achieve precise control and safety functions of the unit.
The Software works on the Proportional Integral Derivative (PID) algorithm for precise control logic. Also it has with built-in
Adaptive control logic that prevents unnecessary service call, while the controller manage to operate the chiller at safe and
designed operating limits.
The simple to use push button keyboard allows accessing to the operating conditions, control set points and alarm history
that are clearly displayed on a multi-line back illuminated LCD panel.
An easy to install serial port/modem option allows remote monitoring of the operating parameters. With corresponding
windows software, the system allows data to be viewed in tabular or graphic format as well as interact with system set up.
This chiller controller is compatible with the Building Management System (BMS) BACNET/MODBUS protocols through
corresponding optional gateway interfaces.
It is also compatible with GSM protocol through GSM optional gateway that sends up to 3 mobile phone SMS messages
whenever alarm take place, indicating the type of alarm, the corresponding compressor, the related chiller and which location.
The microprocessor consists of the following hardware:
1. User Interface Board: Provided with simple to use push button keyboard and menu driven software to access operating
conditions, control set points & alarm history that are clearly displayed on the LCD panel.
2. Main Board: This controls up to two (2) compressor system.
3. Auxiliary Boards: Required for controlling an additional two (2) or more compressors.
4. Remote Monitoring System [Optional]: The micro controller is complete with all hardware and software necessary to
remotely monitor and control the chiller unit.
DISPLAY INFORMATION:
In the normal operating mode the 20 x 4 characters LCD panel display the system status, the temperature of the water inlet
& outlet, the set point, run time of the compressor & the alarm history.
Easily accessible measurements for each circuit include the following:
Suction and discharge temperatures
Suction and discharge pressures
Water inlet/outlet temperatures
Compressor status
Fan status
Liquid line solenoid status
Unit/Compressor run time
Compressor amps (optional)
Unit amps (optional)
Unit 3 phase voltage (optional)
The control temperature is continuously displayed on the 3 Digit 7 segments LED Display. The 3 LED lights indicate the
Power ON, Menu adjustment and Fault.
SYSTEM PROTECTION:
The following system protection is provided to ensure system reliability:
Compressor winding overheating
Low suction pressure
High discharge pressure
Freeze protection
Low oil level (optional)
Sensor error/Thermistor malfunction
Time delay Anti recycle time for compressor
Serial communication error
Compressor/fan motor overload
Compressor/fan motor circuit breaker
Compressor reverse rotation
Under/over voltage
Low/high superheat

7
PHYSICAL DATA
UNIT SIZE ASY050B ASY060B ASY070B ASY080B ASY090B ASY100B ASY120B ASY130B ASY140B ASY150B

COMPRESSOR
PART NUMBER 208/230V-3Ph-60Hz 800-683-13 800-683-16 800-683-19 800-683-22 800-683-13 (2) 800-683-13 (2) 800-683-16 (2) 800-683-19 (2) 800-683-19 (2) 800-683-19 (2)

380V-3Ph-60Hz 800-683-14 800-683-17 800-683-20 800-683-23 800-683-14 (2) 800-683-14 (2) 800-683-17 (2) 800-683-20 (2) 800-683-20 (2) 800-683-20 (2)

460V-3Ph-60Hz 800-683-15 800-683-18 800-683-21 800-683-24 800-683-15 (2) 800-683-15 (2) 800-683-18 (2) 800-683-21 (2) 800-683-21 (2) 800-683-21 (2)

NUMBER OF COMPRESSORS 1 1 1 1 2 2 2 2 2 2

OIL CHARGE PER COMPRESSOR, Liters 15 22 22 22 15 15 22 22 22 22

CAPACITY CONTROL (STEPLESS) % 100 - 50 100 - 25

MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC

OIL LUBRICATION INJECTION

TOTAL CRANKCASE HEATER WATTS 200 300 300 300 400 400 600 600 600 600

REFRIGERANT R-134a

EXPANSION DEVICE ELECTRONIC EXPANSION VALVE

CONTROL VOLTAGE 220V-1Ph-60Hz

AIRCOOLED CONDENSER
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8214 3/8314 3/8414 3/8414 3/8414 3/8414 3/8314 3/8414 3/8414 3/8314
COIL
Total face area, Sq. ft. 87.5 87.5 87.5 87.5 100.1 100.1 140 140 140 175

AIRFLOW, CFM 45264 43920 47644 47644 63798 63798 93256 87032 87032 116570

NUMBER OF FAN/FAN DIA.,mm 4/762 4/762 4/800 4/800 6/800 6/800 8/800 8/800 8/800 10/800

FAN MOTOR RPM @ 230/380/460-3-60 1100/1100/1100 1100/1100/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/11001080/1080/1100

COOLER
COOLER PART NUMBER 800-893-00 800-893-01 800-893-01 800-893-01 800-893-02 800-893-02 800-893-03 800-893-04 800-893-04 800-893-05

SHELL DIAMETER, mm 219 273 273 273 324 324 324 324 324 406

TOTAL LENGTH, mm 2314 2152 2152 2152 2496 2496 2696 2677 2677 2739

WATER HOLDING VOLUME, Liters 49 76.5 76.5 76.5 120 120 128 117 117 206

WATER IN/OUT PIPE DIA.mm 75 100 100 100 125 125 125 125 125 150

ECONOMIZER
PART NUMBER N.A. N.A. N.A. N.A. N.A. 800-516-68(2) N.A. N.A. 800-516-69(2) 800-516-69(2)

EXPANSION DEVICE N.A. N.A. N.A. N.A. N.A. T.E.V. N.A. N.A. T.E.V. T.E.V.

GENERAL
NUMBER OF REFRIGERANT CIRCUITS 1 1 1 1 2 2 2 2 2 2

REFRIGERANT CHARGE PER COMP., kg 33 39 45 50 33 33 39 45 47 48

SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 72.2/68.7/63.4 72.6/69.1/63.8 75.4/71.9/66.6 75.6/72.1/66.8 74.4/71/65.7 74.5/71/65.7 75.3/71.8/66.5 78.4/74.9/69.6 78.4/74.9/69.6 78.7/75.2/69.9

SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 1865/1914 2336/2412 2455/2531 2472/2548 3220/3340 3233/3353 4319/4447 4468/4585 4494/4611 4998/5204

SHIPPING /OPERATING WEIGHTS (Copper coils), kg 1990/2039 2529/2605 2735/2811 2751/2827 3540/3660 3553/3673 4627/4755 4914/5031 4941/5058 5383/5589
NOTES: 1. All compressors with slider control valve unloading.
2. All compressors operate at 3500 RPM @ 60Hz.
3. Cooler vent and drain size are 1/2" MPT.
4. All coolers are single face refrigerant connection.
5. Sound pressure level : 2dBA.
* CU/CU option has 12FPI.
8
PHYSICAL DATA
UNIT SIZE ASY160B ASY170B ASY180B ASY190B ASY200B ASY215B ASY230B ASY240B ASY250B ASY270B

COMPRESSOR
800-683-22 (2)
PART NUMBER 208/230V-3Ph-60Hz 800-683-22 (2) 800-683-22 (2) 800-683-16 (3) 800-683-16 (3) 800-683-16 (3) 800-683-19 (1) 800-683-22 (3) 800-683-22 (3) 800-683-16 (4) 800-683-19 (4)

800-683-23 (2)
380V-3Ph-60Hz 800-683-23 (2) 800-683-23 (2) 800-683-17 (3) 800-683-17 (3) 800-683-17 (3) 800-683-20 (1) 800-683-23 (3) 800-683-23 (3) 800-683-17 (4) 800-683-20 (4)

800-683-24 (2)
460V-3Ph-60Hz 800-683-24 (2) 800-683-24 (2) 800-683-18 (3) 800-683-18 (3) 800-683-18 (3) 800-683-21 (1) 800-683-24 (3) 800-683-24 (3) 800-683-18 (4) 800-683-21 (4)

NUMBER OF COMPRESSORS 2 2 3 3 3 3 3 3 4 4

OIL CHARGE PER COMPRESSOR, Liters 22 22 22 22 22 22 22 22 22 22

CAPACITY CONTROL (STEPLESS) % 100 - 25 100 - 16 100 - 12

MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC

OIL LUBRICATION INJECTION

TOTAL CRANKCASE HEATER WATTS 600 600 900 900 900 900 900 900 1200 1200

REFRIGERANT R-134a

EXPANSION DEVICE ELECTRONIC EXPANSION VALVE

CONTROL VOLTAGE 220V-1Ph-60Hz

AIRCOOLED CONDENSER
3/8414 3/8414
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8314 3/8414 3/8314 3/8314 3/8414 3/8314 3/8414 3/8414 3/8314 3/8314
COIL
Total face area, Sq. ft. 175 175 210 210 210 240 240 240 304 304

AIRFLOW, CFM 116570 108790 139884 133524 130548 140892 138276 138276 192048 192048

NUMBER OF FAN/FAN DIA.,mm 10/800 10/800 12/800 12/800 12/800 12/800 12/800 12/800 16/800 16/800

FAN MOTOR RPM @ 230/380/460-3-60 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/11001080/1080/1100

COOLER
COOLER PART NUMBER 800-893-05 800-893-05 800-893-06 800-893-06 800-893-06 800-893-07 800-893-08 800-893-08 800-893-04(2) 800-893-05(2)

SHELL DIAMETER, mm 406 406 406 406 406 406 406 406 324 406

TOTAL LENGTH, mm 2739 2739 2749 2749 2749 3241 3741 3741 2677 2739

WATER HOLDING VOLUME, Liters 206 206 190 190 190 225 260 260 234 412

WATER IN/OUT PIPE DIA.mm 150 150 150 150 150 150 150 150 125 150

ECONOMIZER
PART NUMBER N.A. 800-516-69(2) N.A. 800-516-69(2) 800-516-69(3) N.A. 800-516-69 800-516-69(3) N.A. N.A.

EXPANSION DEVICE N.A. T.E.V. N.A. T.E.V. T.E.V. N.A. T.E.V. T.E.V. N.A. N.A.

GENERAL
NUMBER OF REFRIGERANT CIRCUITS 2 2 3 3 3 3 3 3 4 4

REFRIGERANT CHARGE PER COMP., kg 50 54 39 42/39 42 50/45 54/50 54 39 45

SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 78.9/75.4/70.1 78.9/75.4/70.1 77.1/73.6/68.3 77.1/73.6/68.3 77.1/73.6/68.3 80.3/76.8/71.5 80.4/76.9/71.6 80.4/76.9/71.6 81.4/77.9/72.6 81.4/77.9/72.6

SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 5003/5209 5149/5355 6542/6732 6663/6853 6724/6914 6885/7110 7040/7300 7070/7330 8745/8979 9208/9620

SHIPPING /OPERATING WEIGHTS (Copper coils), kg 5388/5594 5708/5914 7004/7194 7264/7454 7393/7583 7572/7797 7805/8065 7836/8096 9414/9648 9876/10288
NOTES: 1. All compressors with slider control valve unloading.
2. All compressors operate at 3500 RPM @ 60Hz.
3. Cooler vent and drain size are 1/2" MPT.
4. All coolers are single face refrigerant connection.
5. Sound pressure level : 2dBA.
* CU/CU option has 12FPI.
9
PHYSICAL DATA
UNIT SIZE ASY295B ASY310B ASY330B ASY350B ASY375B ASY400B ASY420B ASY450B ASY475B ASY500B

COMPRESSOR
800-683-22 (2) 800-683-16 (4) 800-683-22 (3) 800-683-22 (4)
PART NUMBER 208/230V-3Ph-60Hz 800-683-19 (2) 800-683-22 (4) 800-683-13 (2) 800-683-16 (6) 800-683-19 (6) 800-683-19 (6) 800-683-19 (3) 800-683-19 (2) 800-683-22 (6) 800-683-22 (6)
800-683-23 (2) 800-683-17 (4) 800-683-23 (3) 800-683-23 (4)
380V-3Ph-60Hz 800-683-20 (2) 800-683-23 (4) 800-683-14 (2) 800-683-17 (6) 800-683-20 (6) 800-683-20 (6) 800-683-20 (3) 800-683-20 (2) 800-683-23 (6) 800-683-23 (6)
800-683-24 (2) 800-683-18 (4) 800-683-24 (3) 800-683-24 (4)
460V-3Ph-60Hz 800-683-21 (2) 800-683-24 (4) 800-683-15 (2) 800-683-18 (6) 800-683-21 (6) 800-683-21 (6) 800-683-21 (3) 800-683-21 (2) 800-683-24 (6) 800-683-24 (6)

NUMBER OF COMPRESSORS 4 4 6 6 6 6 6 6 6 6

OIL CHARGE PER COMPRESSOR, Liters 22 22 22/15 22 22 22 22 22 22 22

CAPACITY CONTROL (STEPLESS) % 100 - 12 100 - 8

MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC

OIL LUBRICATION INJECTION

TOTAL CRANKCASE HEATER WATTS 1200 1200 1600 1800 1800 1800 1800 1800 1800 1800

REFRIGERANT R-134a

EXPANSION DEVICE ELECTRONIC EXPANSION VALVE

CONTROL VOLTAGE 220V-1Ph-60Hz

AIRCOOLED CONDENSER
3/8414 3/8414
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8414 3/8414 3/8314 3/8414 3/8414 3/8314 3/8314 3/8414 3/8414 3/8414
COIL
Total face area, Sq. ft. 304 304 430.7 430.7 430.7 521.3 521.3 521.3 521.3 521.3

AIRFLOW, CFM 180560 180560 224046 220770 220770 281490 275110 269038 269038 269038

NUMBER OF FAN/FAN DIA.,mm 16/800 16/800 18/800 18/800 18/800 22/800 22/800 22/800 22/800 22/800

FAN MOTOR RPM @ 230/380/460-3-60 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100

COOLER
COOLER PART NUMBER 800-893-05(2) 800-893-05(2) 800-893-09(2) 800-893-09(2) 800-893-06(2) 800-893-06(2) 800-893-06(2) 800-893-10(2) 800-893-10(2) 800-893-10(2)

SHELL DIAMETER, mm 406 406 406 406 406 406 406 457 457 457

TOTAL LENGTH, mm 2739 2739 2741 2741 2749 2749 2749 2754 2754 2754

WATER HOLDING VOLUME, Liters 412 412 412 412 380 380 380 488 488 488

WATER IN/OUT PIPE DIA.mm 150 150 150 150 150 150 150 200 200 200

ECONOMIZER
PART NUMBER N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. 800-516-69(3) 800-516-69(6)

EXPANSION DEVICE N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. T.E.V. T.E.V.

GENERAL
NUMBER OF REFRIGERANT CIRCUITS 4 4 6 6 6 6 6 6 6 6

REFRIGERANT CHARGE PER COMP., kg 50/45 50 39/33 39 45 47 50/45 50/45 54/50 54

SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 81.5/78/72.7 81.6/78.1/72.8 79.4/75.8/70.6 79.4/75.9/70.6 82.9/79.3/74.1 83.1/79.5/74.3 83.2/79.7/74.4 83.2/79.7/74.4 83.3/79.8/74.5 83.3/79.8/74.5

SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 9441/9853 9474/9886 11809/12221 12668/13080 12808/13188 13039/13419 13248/13628 13777/14265 13856/14344 13902/14390

SHIPPING /OPERATING WEIGHTS (Copper coils), kg 10441/10823 10444/10856 13021/13433 14042/14454 14182/14562 14186/14566 14654/15034 15439/15927 15518/16006 15564/16052

NOTES: 1. All compressors with slider control valve unloading.


2. All compressors operate at 3500 RPM @ 60Hz.
3. Cooler vent and drain size are 1/2" MPT.
4. All coolers are single face refrigerant connection.
5. Sound pressure level : 2dBA.
* CU/CU option has 12FPI.
10
PHYSICAL DATA
UNIT SIZE ASY540B ASY560B ASY590B

COMPRESSOR
800-683-19 (4) 800-683-22 (4)
PART NUMBER 208/230V-3Ph-60Hz 800-683-19 (8) 800-683-19 (4)
800-683-16 (4)
800-683-20 (4) 800-683-23 (4)
380V-3Ph-60Hz 800-683-20 (8)
800-683-17 (4) 800-683-20 (4)
800-683-21 (4) 800-683-24 (4)
460V-3Ph-60Hz 800-683-21 (8)
800-683-18 (4) 800-683-21 (4)
NUMBER OF COMPRESSORS 8 8 8

OIL CHARGE PER COMPRESSOR, Liters 22 22 22

CAPACITY CONTROL (STEPLESS) % 100 - 6

MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC

OIL LUBRICATION INJECTION

TOTAL CRANKCASE HEATER WATTS 1800 1800 1800

REFRIGERANT R-134a

EXPANSION DEVICE ELECTRONIC EXPANSION VALVE

CONTROL VOLTAGE 220V-1Ph-60Hz

AIRCOOLED CONDENSER
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8414 3/8414 3/8414
COIL
Total face area, Sq. ft. 608 608 608

AIRFLOW, CFM 361120 361120 361120

NUMBER OF FAN/FAN DIA.,mm 32/800 32/800 32/800

FAN MOTOR RPM @ 230/380/460-3-60 1080/1080/1100 1080/1080/1100 1080/1080/1100

COOLER
COOLER PART NUMBER 800-893-41(2) 800-893-41(2) 800-893-41(2)

SHELL DIAMETER, mm 508 508 508

TOTAL LENGTH, mm 3326 3326 3326

WATER HOLDING VOLUME, Liters 802 802 802

WATER IN/OUT PIPE DIA.mm 200 200 200

ECONOMIZER
PART NUMBER N.A. N.A. N.A.

EXPANSION DEVICE N.A. N.A. N.A.

GENERAL
NUMBER OF REFRIGERANT CIRCUITS 8 8 8

REFRIGERANT CHARGE PER COMP., kg 45/39 45 50/45

SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 83.6/80.1/74.8 84.4/80.9/75.6 84.6/81/75.8

SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 2 x 9355/2 x 9756 2 x 9390/2 x 9791 2 x 9423/2 x 9824

SHIPPING /OPERATING WEIGHTS (Copper coils), kg 2 x 10325/2 x 10726 2 x 10360/2 x 10761 2 x 10393/2 x 10794
NOTES: 1. All compressors with slider control valve unloading.
2. All compressors operate at 3500 RPM @ 60Hz.
3. Cooler vent and drain size are 1/2" MPT.
4. All coolers are single face refrigerant connection.
5. Sound pressure level : 2dBA.
* CU/CU option has 12FPI.
11
SELECTION PROCEDURE (English units)
DESIGN REQUIREMENTS
The following design requirements must be known to select a package chiller. ELEVATION ABOVE CAPACITY
CORRECTION
1. Required cooling capacity in tons SEA LEVEL (FT.) FACTOR
2. Leaving chilled water temperature in 0F (LCWT) 0 1.00
2000 0.99
3. Chilled water flow rate in GPM 4000 0.98
4. Chilled water cooling range in 0F (water in temp. _ water out temp.) 6000 0.97
5. Design ambient temperature 8000 0.96
10000 0.95
6. Minimum ambient temperature
TABLE - 1
7. Altitude
8. Electrical power supply EVAPORATOR FOULING CAPACITY POWER ARI
20
CORRECTION INPUT STANDARDS
FACTOR (HR-FT - F/BTU) FACTOR FACTOR
SAMPLE SELECTION 0.00010 1.000 1.000
Select an Air Cooled Packaged chiller for the following conditions: 0.00025 0.992 0.997
0.00050 0.978 0.990 ARI-550/590
Required system capacity is 115 tons at 540F entering chilled water 0.965
0.00075 0.984
and 44 F leaving water. Design ambient temperature is 95 F.
0 0
0.00100 0.951 0.978
Altitude is 2000 feet above sea level. TABLE - 2
Water cooler fouling factor is 0.00010. Power supply: 380V-3Ph-60Hz.
STEP-1: UNIT SELECTION
Entering the capacity performance data at given LCWT and ambient temperature.
ASY120B chiller unit at sea level will produce 116.5 tons and 129.3 kW compressor +0.6

CORRECTION FACTOR (0F)


power input at 440F leaving chilled water temperature with 100F water temperature +0.4
difference and 950F ambient temperature.
+0.2

For the conditions required, the unit actual cooling capacity when corrected for
0
altitude (0.99) and fouling factor (1.0).
Capacity = 116.5x0.99x1.0 = 115.3 Tons, which then exceeds the requirements. -0.2

So the selection is correct.


-0.4
5 10 15 20
STEP-2: CHILLED WATER FLOW (GPM): CHILLED WATER TEMPERATURE RISE (0F)

Required capacity (Tons) x 24 115 x 24 TABLE - 3


Water GPM = = = 276 GPM
Cooling Range, T 100F

Referring to pressure drop chart (page # 23), pressure drop at 276 GPM = 13.5 ft. of water for selected model.
NOTE: The total flow rate should be divided by 2 for models ASY250B - ASY590B to find out the total pressure drop.
STEP-3: ELECTRICAL
Refer to electrical data at 380V-3Ph-60Hz, the main power wire size for ASY120B is to be sized for a minimum circuit
ampacity (MCA) of 311 Amps and maximum over current protection (MOCP) of 437 Amps.

STEP-4: CHILLED WATER PUMP SELECTION


For chilled water pump selection, add all pressure drop in the closed chilled water loop piping to the pressure drop calcu-
lated in step 2.

STEP-5: LCWT CORRECTION


Refer to table-3: Add correction factor to design leaving chilled water temperature (LCWT) when chilled water temperature
range is above 100F and subtract correction from design leaving chilled water temperature (LCWT) when water temperature
range is below 100F.
EXAMPLE:
If LCWT rise is 12.50F, enter correction curve at 12.50F and read the correction factor of 0.2. The corrected LCWT is 44+0.2 = 44.20F.
NOTE: 1. When the chilled water temperature rise is less than 50F, the high water flow rate will result to excessive pressure
drop. In such cases, contact factory for special selection of a cooler with wider baffle spacing.
2. Please refer to water pressure drop curves.

12
SELECTION PROCEDURE (Metric units)
DESIGN REQUIREMENTS
The following design requirements must be known to select a proper package chiller. ELEVATION ABOVE CAPACITY
CORRECTION
1. Required cooling capacity in kilowatt (kW) SEA LEVEL (Meter) FACTOR
2. Leaving chilled water temperature in 0C (LCWT) 0 1.00
600 0.99
3. Chilled water flow rate in LPS
1200 0.98
0 _
4. Chilled water cooling range in C (water in temp. water out temp.) 1800 0.97
5. Design ambient temperature 2400 0.96
3000 0.95
6. Minimum ambient temperature
7. Altitude TABLE - 1
8. Electrical power supply EVAPORATOR FOULING CAPACITY POWER ARI
CORRECTION INPUT STANDARDS
FACTOR (M2-0C/W) FACTOR FACTOR
SAMPLE SELECTION 0.000018 1.000 1.000
Select an Air Cooled Packaged chiller for the following conditions: 0.000044 0.992 0.997
0.000088 0.978 0.990 ARI-550/590
Required system capacity is 390 kW at 120C entering chilled water 0.000132 0.965 0.984
and 60C leaving water. Design ambient temperature is 350C. 0.000176 0.951 0.978
Altitude is 600 meter above sea level. TABLE - 2
Water cooler fouling factor is 0.000018. Power supply: 380V-3Ph-60Hz.
STEP-1: UNIT SELECTION
Entering the capacity performance data at given LCWT and ambient temperature. +0.33
ASY120B chiller unit at sea level will produce 408.1 kW and 129.1 kW compressor

CORRECTION FACTOR (0C)


power input at 60C leaving chilled water temperature with 60C water temperature +0.22

difference and 350C ambient temperature.


+0.11

For the conditions required, the unit actual cooling capacity when corrected for 0
altitude (0.99) and fouling factor (1.0).
Capacity = 408.1x0.99X1.0 = 404 kW, which then exceeds the requirements. -0.11

So the selection is correct.


-0.22
4 5 6 7 8 9 10
STEP-2: CHILLED WATER FLOW (LPS): CHILLED WATER TEMPERATURE RISE (0C)

Required capacity (kW) x 0.239 390 x 0.239 TABLE - 3


Water LPS = = = 15.5 LPS
Cooling Range, T 60C
Referring to pressure drop chart (page # 23), pressure drop at 15.5 LPS = 34.4 kPa for selected model.
NOTE: The total flow rate should be divided by 2 for models ASY250B - ASY590B to find out the total pressure drop.

STEP-3: ELECTRICAL
Refer to electrical data at 380V-3Ph-60Hz, the main power wire size for ASY120B is to be sized for a minimum circuit
ampacity (MCA) of 311 Amps and maximum over current protection (MOCP) of 437 Amps.

STEP-4: CHILLED WATER PUMP SELECTION


For chilled water pump selection, add all pressure drop in the closed chilled water loop piping to the pressure drop
calculated in step 2.
STEP-5: LCWT CORRECTION
Refer to table-3: Add correction factor to design leaving chilled water temperature (LCWT) when chilled water tempera-
ture range is above 60C and subtract correction from design leaving chilled water temperature (LCWT) when water
temperature range is below 60C.
EXAMPLE:
If LCWT rise is 7.40C, enter correction curve at 7.40C and read the correction factor of 0.11. The corrected LCWT is 60C+0.11 = 6.110C.

NOTE: 1. When the chilled water temperature rise is less than 30C, the high water flow rate will result to excessive pressure
drop. In such cases, contact factory for special selection of a cooler with wider baffle spacing.
2. Please refer to water pressure drop curves.

13
PERFORMANCE DATA (English units)
LEAVING 950F AMBIENT TEMPERATURE 1050F AMBIENT TEMPERATURE 1150F AMBIENT TEMPERATURE 1250F AMBIENT TEMPERATURE 1300F AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP.
WATER CAP.
COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
EER EER FLOW EER EER EER
(LCWT) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM)
ASY 050B 44.4 50.7 9.7 106.6 41.6 56.5 8.2 100.0 38.7 63.3 6.9 92.9 35.6 71.1 5.7 85.5 34.0 75.3 5.1 81.6
ASY 060B 53.1 61.3 9.7 127.5 49.8 69.0 8.2 119.5 46.3 77.9 6.8 111.1 42.6 88.1 5.5 102.2 40.7 93.7 5.0 97.6
ASY 070B 59.4 67.9 9.6 142.5 55.6 75.4 8.2 133.5 51.7 84.0 6.9 124.0 47.4 93.6 5.7 113.7 45.1 98.8 5.2 108.3
ASY 080B 65.8 83.3 8.8 157.9 62.0 93.2 7.5 148.8 58.1 104.0 6.3 139.3 53.9 115.9 5.3 129.2 51.7 122.3 4.8 124.0
ASY 090B 90.1 102.0 9.7 216.2 84.3 113.6 8.3 202.2 78.1 127.1 6.9 187.5 71.6 142.5 5.7 172.0 68.3 150.9 5.1 163.9
ASY 100B 94.8 112.5 9.4 227.5 90.2 128.3 7.9 216.4 85.1 146.8 6.6 204.2 79.5 168.1 5.4 190.8 76.5 179.8 4.9 183.6
ASY 120B 111.9 127.3 9.7 268.7 104.6 142.8 8.1 250.9 96.8 160.7 6.7 232.3 88.7 181.1 5.5 212.8 84.5 192.2 5.0 202.8
ASY 130B 124.5 144.0 9.6 298.8 116.0 159.5 8.1 278.5 107.0 177.0 6.8 256.8 97.4 196.4 5.6 233.8 92.4 206.7 5.1 221.8
ASY 140B 133.9 170.0 8.8 321.3 126.8 195.5 7.3 304.3 118.8 224.9 6.0 285.0 109.6 258.3 4.9 263.1 104.6 276.3 4.4 251.1
ASY 150B 142.3 166.6 9.4 341.4 134.8 191.2 7.8 323.5 126.2 219.6 6.5 303.0 116.6 251.8 5.2 279.8 111.3 269.2 4.7 267.2
ASY 160B 148.7 176.1 9.3 356.8 139.2 196.3 7.9 334.1 129.3 218.3 6.7 310.3 118.8 242.4 5.5 285.2 113.4 255.3 5.0 272.2
ASY 170B 159.9 186.3 9.5 383.7 152.7 212.6 8.1 366.5 144.8 242.0 6.8 347.5 136.1 274.6 5.6 326.7 131.5 292.1 5.1 315.5
ASY 180B 165.1 189.6 9.5 396.2 154.4 213.0 8.0 370.7 143.2 240.1 6.7 343.7 131.4 270.8 5.5 315.5 125.3 287.5 4.9 300.8
ASY 190B 176.8 205.8 9.5 424.4 167.9 235.9 7.9 403.1 158.4 271.4 6.6 380.3 148.4 312.3 5.4 356.1 143.1 334.9 4.9 343.4
ASY 200B 182.6 214.2 9.4 438.2 174.6 247.9 7.9 419.1 166.0 287.9 6.5 398.5 156.8 334.3 5.3 376.4 152.0 360.0 4.8 364.8
ASY 215B 205.4 247.5 9.3 492.9 192.3 275.5 7.9 461.5 178.5 306.5 6.6 428.3 163.8 340.5 5.5 393.2 156.2 358.6 5.0 374.9
40 0F ASY 230B 217.9 271.1 9.1 523.0 205.7 304.7 7.7 493.7 192.7 341.8 6.4 462.5 178.8 382.6 5.4 429.2 171.5 404.4 4.9 411.6
ASY 240B 226.6 291.5 8.8 543.7 216.3 332.6 7.4 519.1 205.0 378.4 6.2 491.9 192.5 429.1 5.2 462.0 185.8 456.4 4.7 445.9
ASY 250B 235.8 254.7 10.2 565.8 219.9 285.0 8.5 527.7 203.3 320.0 7.1 488.0 186.1 359.8 5.8 446.6 177.2 381.4 5.3 425.4
ASY 270B 257.2 299.7 9.5 617.4 238.7 331.3 8.1 573.0 219.2 366.4 6.7 526.0 198.4 405.0 5.6 476.3 187.6 425.6 5.0 450.3
ASY 295B 279.4 322.5 9.7 670.5 260.7 358.1 8.2 625.6 241.0 397.6 6.9 578.3 220.2 440.8 5.7 528.4 209.3 463.9 5.2 502.4
ASY 310B 294.8 357.5 9.3 707.6 275.8 398.2 7.8 662.0 255.9 442.8 6.6 614.1 234.9 491.4 5.5 563.8 224.0 517.2 5.0 537.7
ASY 330B 314.6 351.7 10.0 755.1 294.2 393.6 8.4 706.0 272.6 442.4 7.0 654.3 250.0 498.0 5.7 600.0 238.3 528.3 5.2 571.9
ASY 350B 331.4 377.3 9.8 795.4 309.7 423.4 8.3 743.2 286.8 477.0 6.8 688.3 262.8 538.0 5.6 630.7 250.4 571.2 5.0 600.9
ASY 375B 360.1 442.3 9.2 864.2 334.8 490.1 7.8 803.6 308.0 543.7 6.5 739.1 279.4 602.9 5.3 670.6 264.5 634.4 4.8 634.7
ASY 400B 364.0 432.7 9.4 873.5 339.5 479.9 7.9 814.9 313.5 533.0 6.7 752.3 285.7 591.8 5.5 685.6 271.1 623.3 5.0 650.7
ASY 420B 388.7 473.6 9.2 932.8 364.1 527.4 7.8 873.9 338.1 587.2 6.5 811.4 310.4 652.9 5.4 745.0 295.9 688.1 4.9 710.3
ASY 450B 430.3 495.5 9.8 1032.6 402.0 551.0 8.3 964.9 372.3 612.3 6.9 893.6 341.0 679.4 5.8 818.5 324.8 715.1 5.2 779.5
ASY 475B 458.4 558.5 9.3 1100.3 432.9 629.4 7.8 1039.0 405.6 707.9 6.6 973.5 376.3 794.1 5.5 903.2 360.9 840.1 5.0 866.2
ASY 500B 471.9 589.3 9.1 1132.6 449.5 671.8 7.7 1078.8 424.8 763.8 6.4 1019.6 397.7 865.4 5.3 954.5 383.1 919.8 4.8 919.5
ASY 540B 504.6 535.6 10.4 1211.1 470.5 595.5 8.8 1129.2 434.6 663.8 7.3 1043.0 396.8 740.5 6.0 952.4 377.3 781.9 5.5 905.4

14
ASY 560B 526.9 579.1 10.1 1264.6 490.3 640.3 8.6 1176.7 451.5 708.9 7.2 1083.5 410.3 784.8 5.9 984.8 388.8 825.3 5.3 933.2
ASY 590B 558.8 645.0 9.7 1341.0 521.4 716.3 8.2 1251.3 481.9 795.2 6.9 1156.6 440.3 881.6 5.7 1056.8 418.7 927.7 5.2 1004.9
ASY 050B 47.4 52.1 10.1 113.7 44.4 58.0 8.5 106.5 41.2 64.7 7.2 98.9 37.9 72.4 5.9 90.9 36.1 76.5 5.4 86.7
ASY 060B 57.0 62.9 10.2 136.9 53.4 70.6 8.6 128.3 49.7 79.5 7.1 119.2 45.7 89.6 5.8 109.7 43.7 95.1 5.3 104.8
ASY 070B 64.0 69.8 10.1 153.6 59.9 77.4 8.6 143.8 55.6 86.0 7.3 133.4 51.0 95.5 6.0 122.3 48.5 100.7 5.5 116.5
ASY 080B 71.0 85.5 9.3 170.5 66.9 95.5 7.9 160.5 62.5 106.6 6.7 150.1 57.9 118.7 5.6 139.0 55.5 125.1 5.1 133.1
ASY 090B 92.5 103.2 9.9 222.0 86.6 114.8 8.4 207.8 80.3 128.3 7.0 192.8 73.7 143.7 5.8 176.9 70.3 152.0 5.2 168.7
ASY 100B 97.1 113.6 9.5 233.0 92.4 129.4 8.0 221.7 87.2 147.9 6.7 209.3 81.5 169.2 5.5 195.5 78.4 180.8 5.0 188.2
ASY 120B 114.5 128.4 9.8 274.8 107.0 144.0 8.2 256.9 99.2 161.9 6.9 238.1 91.1 182.3 5.6 218.5 86.8 193.4 5.1 208.4
ASY 130B 127.2 145.3 9.7 305.4 118.7 160.9 8.2 284.8 109.6 178.5 6.9 263.0 99.9 197.9 5.7 239.8 94.8 208.2 5.2 227.6
ASY 140B 136.5 171.3 8.9 327.5 129.3 197.0 7.4 310.4 121.2 226.5 6.1 290.8 111.9 260.0 4.9 268.5 106.8 278.1 4.4 256.3
ASY 150B 145.8 168.1 9.6 349.9 138.2 192.9 8.0 331.6 129.4 221.4 6.6 310.6 119.5 253.7 5.3 286.9 114.1 271.1 4.8 273.9
ASY 160B 152.6 177.8 9.5 366.2 142.9 198.1 8.1 343.1 132.8 220.4 6.8 318.8 122.2 244.8 5.6 293.2 116.6 257.7 5.1 279.9
ASY 170B 163.7 187.6 9.7 392.9 156.4 214.1 8.2 375.4 148.3 243.8 6.9 356.0 139.4 276.6 5.7 334.6 134.6 294.3 5.2 323.1
ASY 180B 171.5 192.5 9.8 411.7 160.5 215.9 8.2 385.3 149.0 243.0 6.9 357.5 136.9 273.6 5.6 328.5 130.6 290.3 5.1 313.5
ASY 190B 183.5 208.5 9.7 440.4 174.3 238.8 8.2 418.4 164.6 274.4 6.8 395.1 154.3 315.5 5.6 370.3 148.9 338.1 5.0 357.4
ASY 200B 189.3 216.9 9.7 454.4 181.2 250.8 8.1 434.8 172.4 291.1 6.7 413.7 163.0 337.7 5.5 391.2 158.1 363.5 5.0 379.4
ASY 215B 210.4 249.8 9.4 505.0 197.1 278.1 8.0 473.1 183.1 309.3 6.7 439.5 168.3 343.6 5.6 403.8 160.5 361.8 5.1 385.2
42 0F ASY 230B 223.0 273.3 9.2 535.2 210.6 307.2 7.8 505.5 197.4 344.7 6.5 473.8 183.3 385.9 5.5 439.8 175.8 407.9 5.0 422.0
ASY 240B 231.5 293.6 8.9 555.6 221.0 335.0 7.5 530.5 209.5 381.3 6.3 502.8 196.8 432.4 5.2 472.2 189.9 459.9 4.8 455.7
ASY 250B 242.4 257.5 10.3 581.7 226.2 287.9 8.7 542.9 209.4 323.0 7.2 502.6 192.0 362.7 6.0 460.8 183.0 384.3 5.4 439.3
ASY 270B 264.2 303.2 9.7 634.1 245.4 335.0 8.2 589.0 225.5 370.3 6.9 541.2 204.4 409.0 5.7 490.7 193.5 429.7 5.1 464.3
ASY 295B 286.8 325.9 9.8 688.4 267.8 361.8 8.3 642.8 247.8 401.5 7.0 594.6 226.6 445.0 5.8 543.8 215.6 468.2 5.3 517.4
ASY 310B 302.5 361.1 9.4 726.0 283.2 402.2 8.0 679.6 262.8 447.2 6.7 630.8 241.5 496.2 5.6 579.5 230.4 522.3 5.1 552.9
ASY 330B 323.0 355.4 10.1 775.3 302.3 397.5 8.6 725.4 280.4 446.3 7.1 673.1 257.5 501.8 5.8 618.1 245.7 532.0 5.3 589.7
ASY 350B 340.2 381.1 10.0 816.5 318.2 427.5 8.4 763.6 295.0 481.1 7.0 708.1 270.8 542.0 5.7 649.9 258.3 575.1 5.2 619.9
ASY 375B 369.3 447.0 9.4 886.2 343.7 495.3 7.9 824.9 316.5 549.1 6.6 759.5 287.5 608.4 5.4 690.0 272.3 640.0 4.9 653.6
ASY 400B 378.3 439.5 9.6 907.9 353.0 487.1 8.1 847.2 326.1 540.4 6.8 782.5 297.3 599.2 5.6 713.6 282.3 630.6 5.1 677.5
ASY 420B 404.1 480.7 9.4 969.8 378.6 535.0 8.0 908.7 351.6 595.2 6.7 843.8 322.9 661.3 5.6 774.9 307.9 696.6 5.1 738.9
ASY 450B 439.3 499.5 9.9 1054.4 410.8 555.4 8.4 985.9 380.7 617.0 7.0 913.7 349.0 684.6 5.8 837.7 332.5 720.5 5.3 798.1
ASY 475B 467.5 562.4 9.4 1121.9 441.6 633.8 8.0 1059.9 413.9 712.9 6.7 993.3 384.1 799.7 5.5 921.9 368.4 846.1 5.0 884.2
ASY 500B 480.7 593.1 9.2 1153.7 458.0 676.2 7.8 1099.2 432.9 768.8 6.5 1038.9 405.2 871.1 5.4 972.5 390.3 925.9 4.9 936.8
ASY 540B 518.6 541.4 10.6 1244.7 484.0 601.6 8.9 1161.6 447.5 670.1 7.5 1074.1 409.2 746.8 6.2 982.1 389.4 788.3 5.6 934.4
ASY 560B 541.3 585.4 10.3 1299.2 504.1 647.1 8.7 1209.9 464.7 716.1 7.3 1115.3 422.9 792.1 6.0 1014.9 401.0 832.7 5.5 962.5
ASY 590B 573.7 651.8 9.8 1376.8 535.7 723.6 8.3 1285.6 495.5 803.0 7.0 1189.3 453.2 890.0 5.8 1087.7 431.1 936.4 5.3 1034.7
LEGEND: NOTES: 4. Direct interpolation is permissible. Do not extrapolate.
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590. 5. kW power input is for compressor only.
GPM - Gallons Per Minute 2. Performance data are based on 100F water range in evaporator. 6. EER for entire unit. Refer to electrical data for fan kW.
EER - Energy Efficiency Ratio 3. Ratings are based on 0.00010 (hr-ft2-0F/Btu) fouling factor for evaporator.
PERFORMANCE DATA (English units)
LEAVING 950F AMBIENT TEMPERATURE 1050F AMBIENT TEMPERATURE 1150F AMBIENT TEMPERATURE 1250F AMBIENT TEMPERATURE 1300F AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP.
WATER CAP.
COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
EER EER FLOW EER EER EER
(LCWT) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM)
ASY 050B 49.7 53.3 10.3 119.3 46.5 59.1 8.8 111.6 43.1 65.8 7.4 103.4 39.5 73.3 6.1 94.8 37.6 77.3 5.5 90.3
ASY 060B 60.4 64.4 10.6 145.0 56.5 72.0 8.9 135.7 52.4 80.9 7.4 125.9 48.2 90.9 6.1 115.7 46.0 96.3 5.5 110.4
ASY 070B 68.2 71.5 10.6 163.7 63.7 79.1 9.0 153.0 59.0 87.7 7.6 141.6 54.0 97.1 6.3 129.5 51.3 102.2 5.7 123.2
ASY 080B 76.0 87.6 9.7 182.4 71.4 97.7 8.3 171.4 66.6 108.9 7.0 159.7 61.4 121.1 5.8 147.4 58.8 127.6 5.3 141.0
ASY 090B 94.7 104.3 10.0 227.4 88.8 116.0 8.5 213.1 82.5 129.6 7.2 198.1 75.9 144.9 5.9 182.1 72.4 153.2 5.4 173.8
ASY 100B 99.2 114.5 9.6 238.0 94.4 130.4 8.1 226.7 89.2 149.0 6.8 214.1 83.4 170.3 5.6 200.2 80.3 181.9 5.1 192.8
ASY 120B 116.5 129.3 9.9 279.6 109.2 145.0 8.4 262.1 101.5 163.1 7.0 243.7 93.5 183.6 5.7 224.4 89.4 194.7 5.2 214.5
ASY 130B 129.0 146.1 9.8 309.6 120.7 161.9 8.3 289.6 111.8 179.7 7.0 268.2 102.2 199.3 5.8 245.4 97.3 209.8 5.3 233.4
ASY 140B 137.9 172.0 9.0 331.0 130.9 197.9 7.5 314.2 122.9 227.7 6.2 295.0 113.7 261.3 5.0 272.9 108.7 279.6 4.5 260.8
ASY 150B 149.2 169.6 9.7 358.1 141.5 194.6 8.1 339.6 132.7 223.3 6.7 318.5 122.7 255.7 5.4 294.4 117.2 273.2 4.9 281.2
ASY 160B 156.2 179.4 9.6 374.9 146.6 200.0 8.2 351.7 136.4 222.6 6.9 327.4 125.7 247.2 5.8 301.7 120.1 260.4 5.2 288.3
ASY 170B 167.1 188.8 9.8 401.1 159.8 215.5 8.3 383.5 151.7 245.4 7.0 364.1 142.7 278.6 5.8 342.4 137.8 296.4 5.3 330.8
ASY 180B 177.8 195.3 10.0 426.8 166.5 218.9 8.4 399.7 154.7 245.9 7.0 371.3 142.4 276.5 5.8 341.7 136.0 293.1 5.3 326.4
ASY 190B 189.9 211.1 10.0 455.8 180.6 241.7 8.3 433.4 170.6 277.5 6.9 409.5 160.1 318.7 5.7 384.3 154.7 341.3 5.2 371.2
ASY 200B 195.8 219.4 9.9 470.0 187.5 253.7 8.3 450.0 178.6 294.2 6.9 428.6 169.1 341.1 5.7 405.7 164.1 367.0 5.1 393.8
ASY 215B 214.3 251.5 9.5 514.3 201.2 280.2 8.1 482.9 187.3 311.8 6.8 449.5 172.6 346.5 5.7 414.1 164.8 365.0 5.2 395.6
ASY 230B 226.6 274.9 9.3 543.9 214.4 309.2 7.9 514.6 201.3 347.1 6.6 483.2 187.3 388.8 5.5 449.4 179.8 411.1 5.0 431.6
44 0F ASY 240B 234.8 295.1 9.0 563.5 224.5 336.8 7.6 538.8 213.0 383.5 6.4 511.3 200.3 435.2 5.3 480.8 193.4 463.0 4.8 464.2
ASY 250B 249.4 260.6 10.5 598.5 233.2 291.2 8.9 559.6 216.3 326.5 7.4 519.2 198.8 366.3 6.1 477.2 189.8 387.9 5.5 455.6
ASY 270B 271.3 306.8 9.8 651.1 252.5 339.0 8.4 605.9 232.5 374.6 7.0 558.0 211.3 413.6 5.8 507.1 200.2 434.3 5.2 480.5
ASY 295B 294.1 329.2 10.0 705.7 275.0 365.5 8.5 660.1 254.9 405.6 7.1 611.8 233.6 449.6 5.9 560.7 222.5 473.0 5.4 534.0
ASY 310B 309.7 364.5 9.6 743.3 290.3 406.0 8.1 696.8 269.9 451.6 6.8 647.9 248.4 501.4 5.7 596.2 237.2 527.8 5.2 569.3
ASY 330B 330.6 358.7 10.3 793.3 309.9 401.1 8.7 743.7 288.1 450.2 7.2 691.4 265.3 505.8 6.0 636.7 253.5 536.0 5.4 608.3
ASY 350B 347.8 384.4 10.1 834.6 325.9 431.1 8.5 782.1 302.8 485.0 7.1 726.8 278.8 546.1 5.8 669.1 266.4 579.3 5.3 639.3
ASY 375B 376.6 450.8 9.5 903.8 351.2 499.6 8.0 843.0 324.2 554.0 6.7 778.0 295.3 613.8 5.5 708.8 280.2 645.6 5.0 672.5
ASY 400B 392.0 446.2 9.8 940.8 366.1 494.2 8.3 878.6 338.4 547.7 7.0 812.2 308.9 606.6 5.8 741.5 293.5 638.0 5.3 704.4
ASY 420B 418.6 487.4 9.7 1004.8 392.5 542.2 8.2 941.9 364.7 602.9 6.9 875.3 335.1 669.5 5.7 804.4 319.7 705.0 5.2 767.2
ASY 450B 446.6 502.7 10.0 1071.8 418.5 559.2 8.5 1004.4 388.9 621.6 7.1 933.2 357.5 690.0 5.9 857.9 341.1 726.5 5.4 818.6
ASY 475B 473.9 565.3 9.5 1137.4 448.5 637.4 8.0 1076.4 421.1 717.3 6.7 1010.7 391.6 805.2 5.6 939.9 376.0 852.1 5.1 902.4
ASY 500B 486.7 595.7 9.3 1168.1 464.3 679.5 7.8 1114.4 439.5 772.9 6.5 1054.8 412.0 876.2 5.4 988.8 397.1 931.6 4.9 953.1
ASY 540B 533.1 547.3 10.8 1279.4 498.3 608.1 9.1 1196.0 461.8 677.1 7.6 1108.3 423.3 754.2 6.3 1016.0 403.3 795.7 5.7 968.0

15
ASY 560B 555.8 591.8 10.4 1333.9 518.6 654.2 8.9 1244.6 479.0 723.8 7.5 1149.7 437.0 800.4 6.2 1048.8 415.0 841.3 5.6 996.1
ASY 590B 588.1 658.3 10.0 1411.5 550.1 731.0 8.5 1320.2 509.8 811.3 7.1 1223.6 467.3 899.2 5.9 1121.4 445.0 946.0 5.4 1068.1
ASY 050B 51.3 54.1 10.5 123.1 47.9 59.8 8.9 114.9 44.3 66.4 7.5 106.4 40.6 73.9 6.2 97.4 38.6 77.9 5.6 92.7
ASY 060B 62.7 65.4 10.8 150.5 58.6 73.0 9.1 140.6 54.3 81.8 7.6 130.3 49.8 91.7 6.2 119.6 47.6 97.1 5.6 114.1
ASY 070B 71.1 72.7 10.8 170.5 66.3 80.3 9.2 159.2 61.3 88.8 7.8 147.1 56.0 98.2 6.4 134.3 53.2 103.3 5.8 127.6
ASY 080B 79.4 89.1 10.0 190.6 74.5 99.2 8.5 178.7 69.3 110.4 7.1 166.3 63.8 122.6 6.0 153.2 61.0 129.1 5.4 146.3
ASY 090B 97.5 105.7 10.2 234.1 91.6 117.5 8.7 219.9 85.3 131.1 7.3 204.8 78.7 146.4 6.1 188.8 75.2 154.7 5.5 180.4
ASY 100B 101.3 115.6 9.8 243.2 97.0 131.7 8.3 232.8 91.7 150.4 6.9 220.2 85.9 171.6 5.7 206.2 82.8 183.2 5.2 198.7
ASY 120B 119.3 130.5 10.0 286.2 112.2 146.5 8.5 269.4 104.8 164.9 7.1 251.6 97.1 185.6 5.9 233.0 93.1 196.8 5.4 223.4
ASY 130B 131.3 147.1 9.9 315.0 123.3 163.3 8.4 295.9 114.8 181.4 7.1 275.4 105.6 201.4 5.9 253.4 100.8 212.0 5.4 241.8
ASY 140B 139.6 172.8 9.1 335.1 132.9 199.0 7.6 319.0 125.2 229.2 6.2 300.5 116.3 263.2 5.1 279.0 111.3 281.7 4.6 267.2
ASY 150B 153.5 171.5 9.88 368.5 145.8 196.7 8.26 349.9 136.9 225.7 6.83 328.6 126.8 258.3 5.57 304.3 121.2 275.9 5 291
ASY 160B 160.8 181.5 9.82 385.8 151.2 202.3 8.35 362.8 141 225.3 7.04 338.5 130.3 250.4 5.89 312.7 124.7 263.8 5.37 299.2
ASY 170B 171.4 190.3 10.02 411.3 164.1 217.3 8.48 393.8 155.9 247.5 7.13 374.2 146.9 281 5.95 352.5 141.9 299.1 5.42 340.7
ASY 180B 184.1 198.2 10.22 441.9 172.6 221.9 8.63 414.2 160.5 249 7.21 385.2 148 279.6 5.97 355.1 141.5 296.2 5.4 339.6
ASY 190B 196.3 213.8 10.16 471.1 186.8 244.6 8.53 448.2 176.7 280.6 7.1 424 166 321.9 5.86 398.4 160.4 344.6 5.31 385
ASY 200B 202.2 222 10.11 485.3 193.8 256.6 8.47 465 184.7 297.4 7.03 443.3 175.1 344.5 5.79 420.2 170 370.5 5.25 408
ASY 215B 219.1 253.8 9.67 525.8 206.3 282.9 8.23 495.2 192.7 315.1 6.94 462.6 178.2 350.4 5.81 427.8 170.6 369.3 5.29 409.4
ASY 230B 231 276.9 9.4 554.4 219.1 311.6 7.98 525.8 206.3 350.1 6.72 495.1 192.4 392.5 5.62 461.7 185.1 415.3 5.13 444.3
46 0F ASY 240B 238.7 296.8 9.1 573 228.7 339 7.69 548.9 217.5 386.3 6.45 521.9 204.9 438.7 5.38 491.7 198 466.8 4.9 475.2
ASY 250B 258.6 264.6 10.75 620.5 242.3 295.6 9.1 581.6 225.4 331.1 7.62 541.1 207.9 371.1 6.31 499 198.9 392.8 5.73 477.3
ASY 270B 280.4 311.5 10.03 673 261.6 344.1 8.53 627.9 241.6 380.2 7.17 579.9 220.3 419.7 5.96 528.8 209.2 440.6 5.4 502
ASY 295B 303.3 333.4 10.18 727.9 284.3 370.3 8.65 682.4 264.2 411 7.29 634.1 242.8 455.6 6.08 582.8 231.6 479.3 5.52 556
ASY 310B 318.8 368.8 9.74 765.1 299.5 411 8.26 718.8 279.1 457.4 6.96 669.8 257.5 508.1 5.81 618 246.2 535 5.28 590.9
ASY 330B 339.9 362.9 10.46 815.8 319.4 405.8 8.86 766.6 297.9 455.2 7.41 714.9 275.2 511 6.14 660.6 263.5 541.3 5.56 632.4
ASY 350B 357 388.5 10.31 856.9 335.4 435.7 8.7 805 312.7 490.1 7.26 750.5 289 551.5 5.99 693.5 276.7 584.8 5.43 664.1
ASY 375B 385.4 455.5 9.59 925 360.5 505 8.13 865.1 333.8 560.1 6.82 801 305.2 620.6 5.66 732.5 290.2 652.7 5.12 696.5
ASY 400B 405.5 452.7 10.02 973.2 379.1 501.2 8.52 909.7 350.8 555 7.16 842 320.7 614.1 5.95 769.7 304.9 645.6 5.39 731.7
ASY 420B 432.8 494 9.86 1038.7 406.1 549.3 8.37 974.6 377.7 610.6 7.04 906.4 347.4 677.7 5.87 833.8 331.4 713.4 5.33 795.4
ASY 450B 456.8 507.2 10.15 1096.4 429.8 564.8 8.63 1031.5 401 628.5 7.27 962.5 370.4 698.4 6.08 889 354.3 735.7 5.53 850.4
ASY 475B 482.8 569.2 9.62 1158.7 458.3 642.4 8.14 1099.9 431.7 723.7 6.85 1036.1 402.8 813.3 5.71 966.8 387.5 861.2 5.2 929.9
ASY 500B 494.7 599.2 9.39 1187.4 473.1 684 7.92 1135.5 449 778.7 6.64 1077.6 422 883.6 5.52 1012.8 407.3 939.9 5.02 977.6
ASY 540B 551.7 555 10.98 1324.1 517.1 616.6 9.34 1240.9 480.5 686.4 7.85 1153.2 442 764 6.53 1060.7 421.9 805.8 5.93 1012.6
ASY 560B 574.4 600.1 10.63 1378.6 537.3 663.5 9.06 1289.6 497.8 734 7.64 1194.7 455.7 811.4 6.36 1093.6 433.6 852.6 5.78 1040.5
ASY 590B 606.5 666.7 10.18 1455.7 568.6 740.5 8.65 1364.8 528.4 822 7.29 1268.2 485.7 911.2 6.08 1165.6 463.3 958.7 5.52 1111.9
LEGEND: NOTES: 4. Direct interpolation is permissible. Do not extrapolate.
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590. 5. kW power input is for compressor only.
GPM - Gallons Per Minute 2. Performance data are based on 100F water range in evaporator. 6. EER for entire unit. Refer to electrical data for fan kW.
EER - Energy Efficiency Ratio 3. Ratings are based on 0.00010 (hr-ft2-0F/Btu) fouling factor for evaporator.
PERFORMANCE DATA (English units)
LEAVING 950F AMBIENT TEMPERATURE 1050F AMBIENT TEMPERATURE 1150F AMBIENT TEMPERATURE 1250F AMBIENT TEMPERATURE 1300F AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP.
WATER CAP.
COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
EER EER FLOW EER EER EER
(LCWT) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM)
ASY 050B 52.6 54.8 10.67 126.2 49.1 60.5 9.08 117.8 45.4 67 7.63 109 41.6 74.4 6.33 99.7 39.6 78.4 5.74 95
ASY 060B 64.5 66.1 10.97 154.8 60.2 73.8 9.24 144.6 55.8 82.6 7.7 134 51.2 92.5 6.35 123 48.9 97.8 5.74 117.3
ASY 070B 73.2 73.5 11.04 175.7 68.3 81.2 9.4 163.9 63.1 89.7 7.91 151.5 57.6 99.1 6.58 138.3 54.7 104.1 5.96 131.4
ASY 080B 81.8 90.1 10.22 196.4 76.7 100.3 8.66 184.1 71.3 111.6 7.28 171.2 65.6 123.9 6.07 157.6 62.7 130.4 5.52 150.5
ASY 090B 101.2 107.5 10.42 242.8 95.2 119.4 8.89 228.4 88.8 133.1 7.5 213.2 82.1 148.3 6.26 197 78.5 156.5 5.69 188.5
ASY 100B 105.1 117.3 9.99 252.3 100.3 133.4 8.45 240.8 95 152.1 7.08 228 89 173.3 5.86 213.7 85.8 184.9 5.31 206
ASY 120B 123.7 132.6 10.27 296.8 116.8 148.8 8.72 280.4 109.6 167.4 7.33 263.1 102.1 188.3 6.11 244.9 98.1 199.6 5.56 235.5
ASY 130B 135.4 149 10.09 324.9 127.7 165.6 8.63 306.4 119.4 184 7.31 286.5 110.4 204.4 6.13 265.1 105.7 215.2 5.58 253.7
ASY 140B 143.2 174.6 9.21 343.7 136.7 201.2 7.69 328.1 129.1 231.8 6.35 309.8 120.3 266.2 5.19 288.7 115.4 284.8 4.67 276.9
ASY 150B 159.1 173.8 10.11 381.7 151.2 199.4 8.46 362.9 142.2 228.6 7 341.2 131.8 261.4 5.72 316.4 126.2 279.1 5.15 302.9
ASY 160B 166.7 184.2 10.05 400.1 157 205.4 8.55 376.9 146.8 228.7 7.23 352.3 135.9 254.3 6.05 326.1 130.1 267.9 5.52 312.3
ASY 170B 177.1 192.3 10.25 424.9 169.7 219.6 8.68 407.3 161.4 250.2 7.3 387.4 152.2 284.1 6.1 365.2 147.1 302.4 5.56 353.1
ASY 180B 190.3 201.1 10.43 456.7 178.6 224.9 8.82 428.6 166.3 252.2 7.39 399.2 153.6 282.8 6.13 368.6 147 299.4 5.56 352.8
ASY 190B 202.5 216.5 10.37 486.1 192.9 247.5 8.72 462.9 182.6 283.7 7.26 438.3 171.8 325.2 6.01 412.3 166.1 347.9 5.45 398.7
ASY 200B 208.4 224.5 10.31 500.3 199.9 259.4 8.65 479.8 190.8 300.5 7.19 457.8 181 347.9 5.94 434.3 175.8 374 5.38 421.9
ASY 215B 226.3 257.1 9.87 543.1 213.7 286.7 8.41 512.8 200.2 319.5 7.12 480.4 185.7 355.5 5.97 445.6 178 374.7 5.44 427.3
ASY 230B 237.9 280 9.58 571 226.2 315.3 8.14 542.8 213.4 354.5 6.88 512.2 199.6 397.7 5.76 478.9 192.2 420.8 5.26 461.2
48 0F ASY 240B 245.3 299.7 9.27 588.7 235.3 342.5 7.83 564.7 224.1 390.4 6.58 537.7 211.4 443.5 5.5 507.3 204.4 472.1 5.01 490.7
ASY 250B 269.8 269.6 11.03 647.4 253.3 301 9.35 608 236.3 336.8 7.86 567.1 218.5 377 6.54 524.3 209.3 398.7 5.94 502.3
ASY 270B 291.8 317.3 10.26 700.4 272.9 350.5 8.74 654.9 252.6 387.1 7.37 606.3 231 426.9 6.15 554.4 219.6 448 5.58 527.1
ASY 295B 315 338.8 10.42 756.1 295.9 376.2 8.87 710.2 275.6 417.6 7.49 661.4 253.9 462.8 6.26 609.4 242.5 486.9 5.7 582.1
ASY 310B 330.6 374.4 9.96 793.4 311.1 417.4 8.46 746.7 290.5 464.6 7.13 697.1 268.5 516.2 5.97 644.4 257 543.6 5.43 616.8
ASY 330B 352.4 368.5 10.69 845.7 331.8 411.9 9.07 796.4 310.2 461.6 7.62 744.5 287.5 517.6 6.34 690 275.7 547.8 5.76 661.7
ASY 350B 369.7 394.1 10.53 887.2 348.1 441.9 8.91 835.3 325.4 496.7 7.46 780.9 301.7 558.4 6.18 724 289.4 591.8 5.61 694.6
ASY 375B 397.9 462.1 9.76 955.1 373.1 512.4 8.3 895.4 346.4 568.2 6.98 831.4 317.8 629.3 5.81 762.7 302.7 661.8 5.27 726.5
ASY 400B 418.7 459.2 10.21 1004.9 391.8 508.1 8.69 940.4 363.1 562.3 7.32 871.5 332.4 621.7 6.09 797.9 316.3 653.3 5.53 759.2
ASY 420B 446.6 500.4 10.05 1071.8 419.4 556.3 8.54 1006.6 390.5 618.2 7.2 937.1 359.6 685.9 6 863.1 343.4 721.9 5.46 824.2
ASY 450B 474 514.7 10.38 1137.6 447.7 573.8 8.85 1074.4 419.5 639 7.49 1006.8 389.3 710.6 6.28 934.3 373.3 748.8 5.73 896
ASY 475B 498.6 576.2 9.82 1196.6 474.7 650.9 8.33 1139.2 448.6 733.9 7.02 1076.6 420 825.5 5.87 1008 404.7 874.6 5.35 971.3
ASY 500B 509.7 605.7 9.58 1223.3 488.5 691.9 8.09 1172.5 464.7 788.3 6.79 1115.3 437.9 895.2 5.66 1050.8 423.2 952.6 5.15 1015.6
ASY 540B 574.9 564.7 11.26 1379.8 540 627.2 9.6 1295.9 503 697.6 8.1 1207.3 464 775.9 6.76 1113.5 443.6 817.8 6.15 1064.6

16
ASY 560B 597.8 610.6 10.89 1434.7 560.4 674.9 9.3 1345.1 520.5 746.3 7.86 1249.2 477.8 824.5 6.57 1146.8 455.4 866 5.98 1092.9
ASY 590B 630.1 677.5 10.42 1512.2 591.9 752.5 8.87 1420.5 551.2 835.2 7.49 1322.9 507.8 925.7 6.26 1218.8 485 973.8 5.7 1164.1
ASY 050B 54.4 55.6 10.87 130.5 50.8 61.4 9.26 121.9 47 67.9 7.8 112.9 43.1 75.2 6.49 103.4 41 79.2 5.89 98.5
ASY 060B 66.6 67.1 11.18 159.8 62.3 74.8 9.44 149.4 57.8 83.6 7.88 138.7 53.1 93.5 6.51 127.5 50.8 98.9 5.9 121.8
ASY 070B 75.5 74.5 11.25 181.1 70.5 82.2 9.6 169.2 65.3 90.8 8.09 156.6 59.7 100.2 6.74 143.2 56.8 105.3 6.12 136.2
ASY 080B 84.2 91.1 10.41 202.1 79 101.5 8.82 189.6 73.5 112.8 7.43 176.5 67.8 125.2 6.2 162.6 64.8 131.9 5.64 155.4
ASY 090B 104.8 109.4 10.62 251.5 98.6 121.3 9.08 236.5 91.9 134.8 7.67 220.7 84.9 149.9 6.42 203.8 81.2 158 5.84 195
ASY 100B 108.6 119 10.19 260.7 103.6 135.1 8.63 248.7 98 153.7 7.23 235.3 91.8 174.8 5.99 220.4 88.5 186.3 5.44 212.4
ASY 120B 128.4 134.8 10.5 308.2 121.2 151.1 8.92 290.9 113.6 169.6 7.51 272.7 105.7 190.5 6.26 253.7 101.6 201.7 5.7 243.8
ASY 130B 140.9 151.6 10.33 338 132.7 168.2 8.84 318.6 124 186.7 7.49 297.6 114.6 206.9 6.28 275 109.6 217.7 5.72 263
ASY 140B 148.8 177.4 9.43 357.2 141.8 204.2 7.87 340.4 133.7 234.8 6.5 320.9 124.4 269.2 5.31 298.5 119.2 287.7 4.77 286.1
ASY 150B 164.2 176 10.31 394.1 156 201.7 8.64 374.4 146.6 231 7.15 351.8 135.9 263.9 5.85 326.1 130.1 281.6 5.26 312.1
ASY 160B 172.5 186.8 10.26 414 162.4 208.2 8.74 389.9 151.8 231.7 7.38 364.2 140.4 257.4 6.18 336.9 134.4 271.1 5.64 322.6
ASY 170B 182.9 194.4 10.48 439 175.2 221.9 8.88 420.5 166.6 252.7 7.47 399.8 156.9 286.8 6.24 376.5 151.6 305.2 5.68 363.9
ASY 180B 196.2 203.8 10.61 470.9 184.3 227.9 9 442.3 171.9 255.2 7.55 412.6 159 285.9 6.28 381.5 152.3 302.5 5.7 365.4
ASY 190B 208.5 219 10.55 500.3 198.7 250.3 8.89 476.8 188.3 286.7 7.42 451.9 177.3 328.3 6.14 425.5 171.5 351.1 5.58 411.7
ASY 200B 214.4 226.9 10.5 514.4 205.7 262.1 8.81 493.7 196.5 303.5 7.33 471.5 186.5 351 6.07 447.7 181.3 377.2 5.5 435.1
ASY 215B 234.8 261.1 10.1 563.6 221.6 290.9 8.61 531.8 207.4 323.9 7.28 497.8 192.3 360 6.1 461.4 184.2 379.2 5.57 442.2
ASY 230B 246.9 284 9.81 592.5 234.5 319.6 8.33 562.7 221 359.1 7.03 530.5 206.5 402.6 5.89 495.5 198.7 425.9 5.37 476.9
50 0F ASY 240B 254.2 303.6 9.49 610.1 243.6 346.8 8.01 584.7 231.7 395.1 6.73 556.1 218.3 448.6 5.61 523.8 210.9 477.4 5.11 506.2
ASY 250B 278.8 273.7 11.24 669.1 261.8 305.2 9.54 628.4 244.2 341.1 8.03 586.1 225.8 381.1 6.69 541.8 216.2 402.7 6.08 518.9
ASY 270B 301.6 322.4 10.45 724 282 355.7 8.91 676.8 261 392.3 7.52 626.5 238.6 432.1 6.28 572.8 226.9 453.1 5.71 544.6
ASY 295B 325.9 343.8 10.63 782.1 306.1 381.5 9.06 734.5 284.9 423 7.65 683.8 262.4 468.4 6.4 629.8 250.6 492.5 5.82 601.4
ASY 310B 342 379.9 10.16 820.7 321.7 423.2 8.63 772.1 300.2 470.8 7.28 720.5 277.3 522.7 6.09 665.6 265.3 550.3 5.54 636.8
ASY 330B 365.2 374.3 10.92 876.4 343.8 417.8 9.28 825.2 321.4 467.5 7.8 771.3 297.8 523.2 6.5 714.8 285.6 553.3 5.91 685.5
ASY 350B 383.4 400.3 10.77 920 360.9 448.3 9.11 866.1 337.4 503.1 7.64 809.8 312.8 564.7 6.34 750.8 300.1 598 5.76 720.3
ASY 375B 412.8 469.9 9.97 990.6 386.9 520.5 8.48 928.6 359.2 576.4 7.14 862 329.4 637.4 5.95 790.6 313.7 669.8 5.4 753
ASY 400B 431.2 465.3 10.38 1034.8 404 514.6 8.85 969.6 374.9 569.3 7.47 899.7 343.7 629 6.23 824.9 327.3 660.7 5.66 785.6
ASY 420B 459.5 506.4 10.22 1102.7 431.9 563 8.7 1036.6 402.6 625.4 7.34 966.2 371.2 693.6 6.13 891 354.7 730 5.58 851.4
ASY 450B 491.8 522.7 10.62 1180.4 464.1 582 9.05 1113.8 434.4 647.5 7.66 1042.6 402.6 719.3 6.42 966.3 385.8 757.5 5.86 926
ASY 475B 517.1 584.5 10.05 1241 491.8 659.7 8.52 1180.2 464.1 743.3 7.17 1113.9 433.9 835.3 6 1041.3 417.7 884.6 5.46 1002.6
ASY 500B 528.2 613.8 9.8 1267.6 505.7 700.7 8.27 1213.6 480.3 797.8 6.94 1152.7 451.8 905.3 5.78 1084.3 436.3 962.9 5.26 1047.1
ASY 540B 594.7 573.1 11.49 1427.2 558.5 635.8 9.8 1340.4 520.3 706.3 8.28 1248.6 479.8 784.5 6.92 1151.5 458.7 826.3 6.3 1100.8
ASY 560B 618.4 619.8 11.11 1484.2 579.7 684.5 9.5 1391.3 538.3 756 8.03 1292 494.1 834.1 6.72 1185.9 470.9 875.6 6.12 1130.1
ASY 590B 651.8 687.5 10.63 1564.2 612.1 763 9.06 1469.1 569.9 846.1 7.65 1367.7 524.8 936.8 6.4 1259.6 501.2 985 5.82 1202.8
LEGEND: NOTES: 4. Direct interpolation is permissible. Do not extrapolate.
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590. 5. kW power input is for compressor only.
GPM - Gallons Per Minute 2. Performance data are based on 100F water range in evaporator. 6. EER for entire unit. Refer to electrical data for fan kW.
EER - Energy Efficiency Ratio 3. Ratings are based on 0.00010 (hr-ft2-0F/Btu) fouling factor for evaporator.
PERFORMANCE DATA (Metric units)
LEAVING 350C AMBIENT TEMPERATURE 400C AMBIENT TEMPERATURE 460C AMBIENT TEMPERATURE 520C AMBIENT TEMPERATURE 550C AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP. CAP. COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
COP COP FLOW COP COP COP
(LCWT) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS)
ASY 050B 154.3 50.4 2.8 6.2 145.5 55.6 2.4 5.8 134.4 62.9 2.0 5.4 122.6 71.3 1.6 4.9 116.4 75.9 1.5 4.6
ASY 060B 184.9 61.1 2.8 7.4 174.4 67.9 2.4 7.0 161.1 77.4 2.0 6.4 146.9 88.5 1.6 5.9 139.5 94.5 1.4 5.6
ASY 070B 207.0 67.7 2.8 8.3 195.2 74.4 2.4 7.8 180.0 83.6 2.0 7.2 163.6 93.9 1.6 6.5 155.0 99.5 1.5 6.2
ASY 080B 229.7 83.1 2.6 9.2 217.8 91.9 2.2 8.7 202.6 103.5 1.9 8.1 185.7 116.1 1.5 7.4 178.1 123.1 1.4 7.1
ASY 090B 314.1 101.7 2.8 12.5 295.9 112.0 2.5 11.8 272.8 126.4 2.0 10.9 248.3 143.1 1.6 9.9 235.5 152.3 1.5 9.4
ASY 100B 330.8 112.2 2.7 13.2 316.3 126.2 2.3 12.6 297.3 146.0 1.9 11.9 276.1 169.1 1.5 11.0 264.7 181.9 1.4 10.6
ASY 120B 390.6 126.9 2.8 15.6 367.5 140.7 2.4 14.7 338.2 159.9 2.0 13.5 307.5 182.0 1.6 12.3 291.6 194.1 1.4 11.6
ASY 130B 434.5 143.6 2.8 17.3 407.9 157.4 2.4 16.3 374.0 176.2 2.0 14.9 337.7 197.1 1.6 13.5 318.7 208.4 1.5 12.7
ASY 140B 467.3 169.5 2.6 18.6 445.3 192.2 2.2 17.8 415.3 223.7 1.8 16.6 380.9 259.8 1.4 15.2 361.8 279.5 1.2 14.4
ASY 150B 496.4 166.1 2.7 19.8 473.0 188.0 2.3 18.9 441.1 218.4 1.9 17.6 404.7 253.2 1.5 16.1 384.6 272.2 1.3 15.3
ASY 160B 518.6 175.6 2.7 20.7 488.9 193.6 2.3 19.5 451.5 217.2 1.9 18.0 412.0 243.2 1.6 16.4 391.5 257.1 1.4 15.6
ASY 170B 558.0 185.9 2.8 22.2 535.6 209.4 2.4 21.4 506.0 240.9 2.0 20.2 473.2 276.0 1.6 18.9 455.5 295.0 1.5 18.2
ASY 180B 575.1 189.0 2.8 22.9 541.7 209.8 2.4 21.6 499.5 238.8 2.0 19.9 454.8 272.1 1.6 18.1 431.7 290.3 1.4 17.2
ASY 190B 616.4 205.2 2.8 24.6 588.5 232.0 2.3 23.5 552.7 269.9 1.9 22.0 514.4 314.2 1.5 20.5 494.3 338.8 1.4 19.7
ASY 200B 636.6 213.6 2.8 25.4 611.6 243.6 2.3 24.4 579.2 286.3 1.9 23.1 544.2 336.5 1.5 21.7 525.8 364.5 1.4 21.0
ASY 215B 716.7 246.8 2.7 28.6 675.6 271.8 2.3 26.9 623.6 305.1 1.9 24.9 568.3 341.8 1.6 22.7 539.3 361.4 1.4 21.5
ASY 230B 760.6 270.4 2.6 30.3 722.4 300.4 2.3 28.8 673.5 340.2 1.9 26.9 621.1 384.2 1.5 24.8 593.4 407.8 1.4 23.7
4 0C ASY 240B 791.1 290.8 2.6 31.5 759.0 327.5 2.2 30.3 716.5 376.5 1.8 28.6 669.5 431.3 1.5 26.7 644.0 460.9 1.3 25.7
ASY 250B 821.9 253.9 3.0 32.8 772.1 280.9 2.5 30.8 709.6 318.4 2.1 28.3 644.4 361.4 1.7 25.7 610.8 385.0 1.5 24.4
ASY 270B 897.1 298.7 2.8 35.8 839.0 326.8 2.4 33.5 765.3 364.5 2.0 30.5 686.9 406.3 1.6 27.4 645.9 428.7 1.4 25.8
ASY 295B 974.3 321.5 2.8 38.9 915.6 353.3 2.4 36.5 841.4 395.6 2.0 33.6 762.8 442.3 1.6 30.4 721.8 467.3 1.5 28.8
ASY 310B 1028.4 356.4 2.7 41.0 968.7 392.8 2.3 38.6 893.6 440.5 1.9 35.6 814.5 492.9 1.6 32.5 773.3 520.9 1.4 30.8
ASY 330B 1097.1 350.6 2.9 43.7 1032.9 387.9 2.5 41.2 951.8 440.2 2.0 38.0 866.2 500.4 1.6 34.5 821.7 533.5 1.5 32.8
ASY 350B 1155.8 376.1 2.9 46.1 1087.5 417.3 2.5 43.4 1001.3 474.7 2.0 39.9 910.3 540.7 1.6 36.3 863.2 576.9 1.4 34.4
ASY 375B 1256.1 440.8 2.7 50.1 1176.8 483.5 2.3 46.9 1075.7 541.0 1.9 42.9 967.6 604.9 1.5 38.6 910.8 639.2 1.4 36.3
ASY 400B 1268.3 431.1 2.7 50.6 1191.7 473.3 2.3 47.5 1093.6 530.2 1.9 43.6 988.5 593.7 1.6 39.4 933.1 627.9 1.4 37.2
ASY 420B 1354.6 472.1 2.7 54.0 1277.6 520.1 2.3 50.9 1179.7 584.1 1.9 47.0 1075.1 655.1 1.6 42.9 1020.1 693.2 1.4 40.7
ASY 450B 1501.4 494.1 2.8 59.9 1413.0 543.7 2.5 56.3 1301.3 609.4 2.0 51.9 1183.3 681.9 1.7 47.2 1121.7 720.7 1.5 44.7
ASY 475B 1600.2 557.0 2.7 63.8 1520.4 620.4 2.3 60.6 1417.9 704.5 1.9 56.5 1307.6 797.5 1.6 52.1 1249.2 847.5 1.4 49.8
ASY 500B 1647.7 587.9 2.7 65.7 1577.7 661.6 2.3 62.9 1485.4 760.1 1.9 59.2 1383.2 869.8 1.5 55.2 1328.0 928.9 1.4 53.0
ASY 540B 1759.3 533.9 3.0 70.2 1652.2 587.3 2.6 65.9 1516.9 660.5 2.1 60.5 1374.1 743.4 1.7 54.8 1299.8 788.6 1.5 51.8

17
ASY 560B 1837.4 577.1 2.9 73.3 1722.3 631.8 2.5 68.7 1576.1 705.3 2.1 62.8 1420.5 787.3 1.7 56.6 1339.1 831.5 1.5 53.4
ASY 590B 1948.7 643.0 2.8 77.7 1831.3 706.6 2.4 73.0 1682.8 791.1 2.0 67.1 1525.6 884.5 1.6 60.8 1443.6 934.5 1.5 57.6
ASY 050B 162.3 51.5 2.9 6.5 153.2 56.7 2.5 6.1 141.6 64.0 2.1 5.6 129.3 72.4 1.7 5.2 122.8 76.9 1.5 4.9
ASY 060B 194.9 62.2 2.9 7.8 183.9 69.1 2.5 7.3 170.0 78.6 2.0 6.8 155.5 89.6 1.6 6.2 147.9 95.7 1.5 5.9
ASY 070B 218.2 69.0 2.9 8.7 205.9 75.8 2.5 8.2 190.1 85.0 2.1 7.6 173.1 95.3 1.7 6.9 164.1 101.0 1.5 6.5
ASY 080B 242.0 84.6 2.7 9.7 229.5 93.5 2.3 9.2 213.7 105.3 1.9 8.5 196.8 118.3 1.6 7.8 187.9 125.3 1.4 7.5
ASY 090B 323.1 102.9 2.9 12.9 304.4 113.3 2.5 12.1 280.7 127.7 2.0 11.2 255.5 144.3 1.7 10.2 242.4 153.4 1.5 9.7
ASY 100B 339.5 113.4 2.8 13.5 324.7 127.4 2.4 12.9 305.0 147.2 2.0 12.2 283.2 170.2 1.6 11.3 271.5 182.9 1.4 10.8
ASY 120B 401.1 128.2 2.9 16.0 377.4 142.1 2.5 15.0 347.5 161.3 2.0 13.9 316.2 183.3 1.6 12.6 300.0 195.3 1.5 12.0
ASY 130B 446.4 145.1 2.8 17.8 419.1 159.1 2.5 16.7 384.3 177.8 2.0 15.3 347.2 198.7 1.6 13.8 327.6 210.0 1.5 13.1
ASY 140B 479.3 171.2 2.6 19.1 456.6 194.1 2.2 18.2 425.6 225.7 1.8 17.0 389.9 261.8 1.4 15.5 370.2 281.5 1.3 14.8
ASY 150B 509.4 167.7 2.8 20.3 485.4 189.8 2.4 19.4 452.4 220.3 1.9 18.0 414.8 255.1 1.5 16.5 394.1 274.1 1.4 15.7
ASY 160B 533.1 177.4 2.8 21.3 502.6 195.5 2.4 20.0 464.1 219.4 2.0 18.5 423.6 245.6 1.6 16.9 402.5 259.6 1.5 16.0
ASY 170B 572.6 187.3 2.8 22.8 549.5 211.0 2.4 21.9 519.0 242.7 2.0 20.7 485.1 278.1 1.6 19.3 466.8 297.3 1.5 18.6
ASY 180B 596.1 191.6 2.8 23.8 561.5 212.5 2.4 22.4 517.9 241.4 2.0 20.7 472.1 274.6 1.6 18.8 448.4 292.7 1.4 17.9
ASY 190B 638.2 207.7 2.8 25.4 609.4 234.6 2.4 24.3 572.6 272.7 2.0 22.8 533.5 317.1 1.6 21.3 513.0 341.7 1.4 20.5
ASY 200B 658.7 216.1 2.8 26.3 633.0 246.3 2.4 25.2 599.9 289.2 2.0 23.9 564.2 339.6 1.6 22.5 545.4 367.7 1.4 21.7
ASY 215B 737.2 249.4 2.8 29.4 695.0 274.7 2.4 27.7 641.4 308.1 2.0 25.6 584.6 345.0 1.6 23.3 554.8 364.7 1.5 22.1
ASY 230B 782.0 273.1 2.7 31.2 742.5 303.3 2.3 29.6 692.1 343.4 1.9 27.6 638.0 387.8 1.6 25.4 609.4 411.6 1.4 24.3
5 0C ASY 240B 812.2 293.4 2.6 32.4 779.0 330.4 2.2 31.1 735.1 379.9 1.9 29.3 686.3 435.1 1.5 27.4 659.8 464.9 1.4 26.3
ASY 250B 844.9 256.6 3.0 33.7 793.8 283.7 2.6 31.7 730.1 321.2 2.1 29.1 663.7 364.2 1.7 26.5 629.5 387.7 1.5 25.1
ASY 270B 921.8 302.2 2.8 36.8 862.4 330.5 2.4 34.4 787.0 368.3 2.0 31.4 706.8 410.1 1.6 28.2 664.9 432.4 1.5 26.5
ASY 295B 1001.5 325.0 2.9 39.9 941.4 357.0 2.5 37.5 865.2 399.5 2.0 34.5 784.7 446.3 1.7 31.3 742.6 471.4 1.5 29.6
ASY 310B 1056.9 360.2 2.8 42.1 995.6 396.8 2.4 39.7 918.5 444.9 2.0 36.6 837.2 497.8 1.6 33.4 794.8 526.0 1.5 31.7
ASY 330B 1129.1 354.5 3.0 45.0 1063.2 392.0 2.5 42.4 980.1 444.2 2.1 39.1 892.7 504.2 1.7 35.6 847.4 537.1 1.5 33.8
ASY 350B 1189.8 380.3 2.9 47.4 1119.8 421.6 2.5 44.7 1031.6 478.9 2.0 41.1 938.9 544.7 1.6 37.4 890.9 580.8 1.5 35.5
ASY 375B 1292.7 446.2 2.7 51.5 1211.4 489.2 2.3 48.3 1107.8 546.7 1.9 44.2 997.0 610.6 1.6 39.8 938.9 644.9 1.4 37.4
ASY 400B 1315.2 437.5 2.8 52.4 1235.8 479.9 2.4 49.3 1134.3 537.0 2.0 45.2 1025.7 600.5 1.6 40.9 968.5 634.6 1.5 38.6
ASY 420B 1405.4 478.7 2.8 56.0 1325.4 527.1 2.4 52.9 1223.7 591.5 2.0 48.8 1115.1 662.8 1.6 44.5 1058.1 701.0 1.4 42.2
ASY 450B 1539.1 498.8 2.9 61.4 1448.3 548.6 2.5 57.8 1333.8 614.6 2.1 53.2 1212.6 687.4 1.7 48.4 1149.5 726.3 1.5 45.8
ASY 475B 1639.1 561.9 2.8 65.4 1556.9 625.6 2.4 62.1 1451.4 710.2 2.0 57.9 1337.6 803.9 1.6 53.3 1277.5 854.1 1.4 50.9
ASY 500B 1685.7 592.6 2.7 67.2 1614.2 666.8 2.3 64.4 1518.8 766.0 1.9 60.6 1413.0 876.3 1.5 56.3 1355.9 935.8 1.4 54.1
ASY 540B 1809.0 539.7 3.1 72.1 1699.3 593.3 2.7 67.8 1561.0 666.6 2.2 62.2 1415.1 749.4 1.8 56.4 1339.3 794.5 1.6 53.4
ASY 560B 1889.0 583.6 3.0 75.3 1771.3 638.6 2.6 70.6 1621.6 712.3 2.1 64.7 1462.5 794.4 1.7 58.3 1379.1 838.4 1.6 55.0
ASY 590B 2003.1 650.0 2.9 79.9 1882.7 714.0 2.5 75.1 1730.4 798.9 2.0 69.0 1569.3 892.7 1.7 62.6 1485.2 942.9 1.5 59.2
LEGEND: NOTES:
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590. 4. Direct interpolation is permissible. Do not extrapolate.
LPS - Liters Per Second 2. Performance data are based on 60C water range in evaporator. 5. kW power input is for compressor only.
COP - Coefficient of Performance 3. Ratings are based on 0.000018 (m2 -0C/W) fouling factor for evaporator. 6. COP for entire unit. Refer to electrical data for fan kW.
PERFORMANCE DATA (Metric units)
LEAVING 350C AMBIENT TEMPERATURE 400C AMBIENT TEMPERATURE 460C AMBIENT TEMPERATURE 520C AMBIENT TEMPERATURE 550C AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP. CAP. COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
COP COP FLOW COP COP COP
(LCWT) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS)
ASY 050B 171.2 52.8 3.0 6.8 161.4 58.0 2.6 6.4 148.9 65.2 2.1 5.9 135.7 73.4 1.7 5.4 128.8 77.8 1.6 5.1
ASY 060B 207.2 63.7 3.0 8.3 195.3 70.6 2.6 7.8 180.4 80.1 2.1 7.2 164.8 90.9 1.7 6.6 156.7 96.9 1.5 6.2
ASY 070B 233.2 70.7 3.0 9.3 219.8 77.5 2.6 8.8 202.5 86.7 2.2 8.1 184.1 97.0 1.8 7.3 174.4 102.6 1.6 7.0
ASY 080B 259.5 86.7 2.8 10.3 245.6 95.7 2.4 9.8 228.1 107.6 2.0 9.1 209.5 120.8 1.6 8.4 199.7 127.8 1.5 8.0
ASY 090B 330.3 103.9 2.9 13.2 311.4 114.3 2.5 12.4 287.4 128.8 2.1 11.5 262.0 145.3 1.7 10.4 248.7 154.4 1.5 9.9
ASY 100B 346.2 114.2 2.8 13.8 331.2 128.4 2.4 13.2 311.3 148.2 2.0 12.4 289.2 171.2 1.6 11.5 277.3 183.8 1.4 11.1
ASY 120B 408.1 129.1 2.9 16.3 384.5 143.0 2.5 15.3 354.7 162.3 2.0 14.1 323.5 184.4 1.6 12.9 307.4 196.4 1.5 12.3
ASY 130B 453.3 146.0 2.9 18.1 426.2 160.1 2.5 17.0 391.6 179.0 2.0 15.6 354.5 200.0 1.7 14.1 335.0 211.3 1.5 13.4
ASY 140B 485.6 172.1 2.6 19.4 463.0 195.1 2.2 18.5 431.9 226.9 1.8 17.2 396.1 263.1 1.4 15.8 376.4 282.9 1.3 15.0
ASY 150B 520.1 169.0 2.8 20.7 495.7 191.2 2.4 19.8 462.3 221.9 2.0 18.4 424.1 256.8 1.6 16.9 403.0 275.8 1.4 16.1
ASY 160B 544.7 178.9 2.8 21.7 513.9 197.2 2.4 20.5 475.1 221.2 2.0 18.9 434.1 247.7 1.6 17.3 412.7 261.8 1.5 16.5
ASY 170B 583.8 188.5 2.9 23.3 560.5 212.2 2.5 22.4 529.6 244.2 2.0 21.1 495.1 279.9 1.7 19.7 476.5 299.1 1.5 19.0
ASY 180B 616.3 194.2 2.9 24.6 580.8 215.1 2.5 23.2 536.1 244.1 2.0 21.4 489.3 277.2 1.7 19.5 465.2 295.3 1.5 18.5
ASY 190B 658.9 210.1 2.9 26.3 629.4 237.2 2.5 25.1 591.9 275.5 2.0 23.6 552.0 319.9 1.6 22.0 531.2 344.6 1.5 21.2
ASY 200B 679.6 218.4 2.9 27.1 653.4 248.9 2.5 26.1 619.7 292.1 2.0 24.7 583.5 342.7 1.6 23.3 564.4 370.9 1.5 22.5
ASY 215B 750.9 251.2 2.8 29.9 708.7 276.7 2.4 28.3 655.1 310.4 2.0 26.1 598.0 347.6 1.6 23.8 568.0 367.6 1.5 22.7
ASY 230B 795.4 274.8 2.7 31.7 755.9 305.3 2.3 30.1 705.4 345.7 1.9 28.1 651.0 390.5 1.6 26.0 622.1 414.6 1.4 24.8
6 0C ASY 240B 825.0 295.0 2.6 32.9 791.7 332.2 2.3 31.6 747.6 382.1 1.9 29.8 698.3 437.7 1.5 27.8 671.5 467.8 1.4 26.8
ASY 250B 865.8 259.2 3.1 34.5 814.3 286.4 2.6 32.5 750.0 324.0 2.2 29.9 683.2 367.0 1.8 27.2 648.8 390.5 1.6 25.9
ASY 270B 943.4 305.3 2.9 37.6 883.5 333.9 2.5 35.2 807.4 371.9 2.0 32.2 726.5 413.8 1.7 29.0 684.1 436.2 1.5 27.3
ASY 295B 1024.1 327.9 2.9 40.8 963.5 360.2 2.5 38.4 886.7 403.0 2.1 35.4 805.3 450.2 1.7 32.1 762.7 475.5 1.5 30.4
ASY 310B 1079.9 363.3 2.8 43.1 1018.1 400.2 2.4 40.6 940.2 448.8 2.0 37.5 857.9 502.2 1.6 34.2 814.9 530.7 1.5 32.5
ASY 330B 1153.7 357.6 3.0 46.0 1087.4 395.3 2.6 43.4 1004.0 447.6 2.1 40.0 916.2 507.6 1.7 36.5 870.7 540.5 1.5 34.7
ASY 350B 1215.0 383.4 3.0 48.4 1144.7 424.9 2.5 45.6 1056.3 482.4 2.1 42.1 963.5 548.3 1.7 38.4 915.5 584.4 1.5 36.5
ASY 375B 1318.2 450.0 2.8 52.6 1236.7 493.3 2.4 49.3 1132.7 551.2 2.0 45.2 1021.5 615.4 1.6 40.7 963.0 649.8 1.4 38.4
ASY 400B 1359.6 443.6 2.8 54.2 1278.1 486.3 2.5 51.0 1173.8 543.6 2.0 46.8 1062.3 607.1 1.7 42.4 1003.5 641.2 1.5 40.0
ASY 420B 1452.8 484.9 2.8 57.9 1370.5 533.7 2.4 54.6 1265.8 598.5 2.0 50.5 1154.0 670.2 1.6 46.0 1095.3 708.7 1.5 43.7
ASY 450B 1563.9 501.9 2.9 62.4 1473.3 552.1 2.5 58.7 1358.8 618.6 2.1 54.2 1237.4 692.0 1.7 49.3 1174.0 731.2 1.5 46.8
ASY 475B 1662.7 564.8 2.8 66.3 1580.6 629.0 2.4 63.0 1474.9 714.3 2.0 58.8 1360.7 808.7 1.6 54.3 1300.2 859.4 1.5 51.8
ASY 500B 1708.9 595.4 2.7 68.1 1636.7 670.1 2.3 65.3 1541.1 769.9 1.9 61.5 1434.6 881.0 1.6 57.2 1377.0 940.9 1.4 54.9
ASY 540B 1852.7 544.8 3.1 73.9 1742.2 598.8 2.7 69.5 1602.8 672.4 2.2 63.9 1455.7 755.4 1.8 58.0 1379.2 800.5 1.6 55.0

18
ASY 560B 1933.4 589.2 3.0 77.1 1814.9 644.6 2.6 72.4 1664.0 718.8 2.2 66.4 1503.4 801.2 1.8 59.9 1419.2 845.4 1.6 56.6
ASY 590B 2048.3 655.8 2.9 81.7 1927.0 720.4 2.5 76.8 1773.5 806.0 2.1 70.7 1610.6 900.4 1.7 64.2 1525.4 950.9 1.5 60.8
ASY 050B 177.5 53.7 3.1 7.1 167.0 58.8 2.6 6.7 153.8 65.9 2.2 6.1 139.9 74.0 1.8 5.6 132.6 78.4 1.6 5.3
ASY 060B 216.4 64.9 3.1 8.6 203.7 71.7 2.7 8.1 187.9 81.1 2.2 7.5 171.3 91.9 1.8 6.8 162.8 97.8 1.6 6.5
ASY 070B 244.7 72.1 3.1 9.8 230.2 78.9 2.7 9.2 211.8 88.0 2.3 8.4 192.0 98.3 1.8 7.7 181.7 103.8 1.7 7.2
ASY 080B 273.2 88.3 2.9 10.9 258.1 97.4 2.5 10.3 239.1 109.4 2.1 9.5 219.0 122.6 1.7 8.7 208.5 129.7 1.5 8.3
ASY 090B 338.0 105.0 3.0 13.5 319.1 115.5 2.6 12.7 295.1 130.0 2.1 11.8 269.6 146.5 1.7 10.7 256.2 155.5 1.6 10.2
ASY 100B 353.3 115.2 2.8 14.1 338.3 129.4 2.4 13.5 318.3 149.3 2.0 12.7 296.0 172.2 1.6 11.8 284.0 184.9 1.5 11.3
ASY 120B 415.4 130.0 2.9 16.6 392.3 144.1 2.5 15.6 363.2 163.6 2.1 14.5 332.7 185.8 1.7 13.3 316.9 197.9 1.5 12.6
ASY 130B 459.5 146.9 2.9 18.3 433.2 161.1 2.5 17.3 399.5 180.3 2.1 15.9 363.2 201.6 1.7 14.5 344.1 213.0 1.5 13.7
ASY 140B 490.5 172.8 2.7 19.6 468.5 196.0 2.3 18.7 438.0 228.1 1.8 17.5 402.8 264.6 1.5 16.1 383.2 284.4 1.3 15.3
ASY 150B 531.9 170.5 2.9 21.2 507.5 192.9 2.4 20.2 473.8 223.7 2.0 18.9 435.1 258.8 1.6 17.4 413.8 277.9 1.4 16.5
ASY 160B 557.3 180.5 2.8 22.2 526.5 199.0 2.5 21.0 487.7 223.3 2.0 19.4 446.5 250.1 1.7 17.8 425.0 264.5 1.5 16.9
ASY 170B 595.6 189.6 2.9 23.7 572.3 213.6 2.5 22.8 541.3 245.8 2.1 21.6 506.5 281.8 1.7 20.2 487.6 301.3 1.5 19.4
ASY 180B 636.3 196.7 3.0 25.4 600.0 217.8 2.5 23.9 554.5 246.8 2.1 22.1 506.9 279.9 1.7 20.2 482.3 297.9 1.5 19.2
ASY 190B 679.3 212.5 3.0 27.1 649.3 239.9 2.5 25.9 611.1 278.2 2.1 24.4 570.6 322.9 1.7 22.8 549.5 347.6 1.5 21.9
ASY 200B 700.2 220.7 2.9 27.9 673.5 251.4 2.5 26.9 639.4 294.9 2.0 25.5 602.7 345.8 1.7 24.0 583.3 374.1 1.5 23.3
ASY 215B 764.3 253.0 2.8 30.5 722.8 278.7 2.4 28.8 669.9 312.9 2.0 26.7 613.3 350.6 1.7 24.5 583.5 370.8 1.5 23.3
ASY 230B 807.8 276.3 2.7 32.2 769.0 307.2 2.4 30.7 719.1 348.1 2.0 28.7 665.1 393.5 1.6 26.5 636.4 417.9 1.5 25.4
7 0C ASY 240B 836.2 296.4 2.7 33.3 803.5 334.0 2.3 32.0 759.8 384.3 1.9 30.3 710.8 440.5 1.5 28.3 684.0 470.9 1.4 27.3
ASY 250B 890.6 262.3 3.1 35.5 838.9 289.7 2.7 33.5 774.5 327.5 2.2 30.9 707.5 370.7 1.8 28.2 673.0 394.2 1.6 26.8
ASY 270B 968.3 308.9 2.9 38.6 908.3 337.8 2.5 36.2 832.1 376.2 2.1 33.2 750.7 418.4 1.7 29.9 708.0 441.0 1.5 28.2
ASY 295B 1049.4 331.2 3.0 41.8 988.8 363.8 2.5 39.4 911.9 407.1 2.1 36.4 830.1 454.8 1.7 33.1 787.2 480.4 1.6 31.4
ASY 310B 1104.9 366.6 2.8 44.1 1043.1 404.0 2.4 41.6 965.1 453.3 2.0 38.5 882.3 507.4 1.7 35.2 839.1 536.3 1.5 33.5
ASY 330B 1179.7 360.9 3.0 47.0 1113.7 398.9 2.6 44.4 1030.7 451.5 2.2 41.1 943.4 511.7 1.8 37.6 898.0 544.5 1.6 35.8
ASY 350B 1241.0 386.7 3.0 49.5 1171.2 428.5 2.6 46.7 1083.5 486.4 2.1 43.2 991.5 552.5 1.7 39.5 943.9 588.6 1.5 37.6
ASY 375B 1343.1 453.7 2.8 53.6 1262.5 497.5 2.4 50.3 1159.4 556.0 2.0 46.2 1048.8 620.8 1.6 41.8 990.5 655.4 1.5 39.5
ASY 400B 1403.1 449.6 2.9 55.9 1319.8 492.6 2.5 52.6 1213.3 550.2 2.1 48.4 1099.2 613.9 1.7 43.8 1039.2 648.0 1.5 41.4
ASY 420B 1498.8 491.0 2.9 59.8 1414.6 540.2 2.5 56.4 1307.4 605.5 2.0 52.1 1192.9 677.7 1.7 47.6 1132.7 716.4 1.5 45.2
ASY 450B 1590.4 505.2 3.0 63.4 1501.6 556.1 2.5 59.9 1388.9 623.5 2.1 55.4 1269.1 697.9 1.7 50.6 1206.3 737.7 1.6 48.1
ASY 475B 1686.0 567.7 2.8 67.2 1605.6 632.6 2.4 64.0 1501.6 718.9 2.0 59.9 1388.6 814.5 1.6 55.4 1328.5 865.8 1.5 53.0
ASY 500B 1730.3 598.1 2.7 69.0 1659.5 673.3 2.3 66.2 1565.2 774.1 1.9 62.4 1459.7 886.4 1.6 58.2 1402.3 946.9 1.4 55.9
ASY 540B 1903.5 550.7 3.2 75.9 1792.9 605.3 2.7 71.5 1653.2 679.4 2.3 65.9 1505.7 762.9 1.9 60.0 1428.9 808.1 1.7 57.0
ASY 560B 1984.1 595.6 3.1 79.1 1865.7 651.7 2.7 74.4 1714.7 726.6 2.2 68.4 1553.4 809.6 1.8 61.9 1468.7 854.0 1.6 58.6
ASY 590B 2098.8 662.3 3.0 83.7 1977.6 727.7 2.5 78.9 1823.8 814.2 2.1 72.7 1660.2 909.7 1.7 66.2 1574.4 960.7 1.6 62.8
LEGEND: NOTES:
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590. 4. Direct interpolation is permissible. Do not extrapolate.
LPS - Liters Per Second 2. Performance data are based on 60C water range in evaporator. 5. kW power input is for compressor only.
COP - Coefficient of Performance 3. Ratings are based on 0.000018 (m2 -0C/W) fouling factor for evaporator. 6. COP for entire unit. Refer to electrical data for fan kW.
PERFORMANCE DATA (Metric units)
LEAVING 350C AMBIENT TEMPERATURE 400C AMBIENT TEMPERATURE 460C AMBIENT TEMPERATURE 520C AMBIENT TEMPERATURE 550C AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP. CAP. COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
COP COP FLOW COP COP COP
(LCWT) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS)
ASY 050B 181.9 54.3 3.1 7.3 171.1 59.5 2.7 6.8 157.4 66.5 2.2 6.3 143.0 74.5 1.8 5.7 135.5 78.8 1.6 5.4
ASY 060B 222.9 65.7 3.2 8.9 209.6 72.5 2.7 8.4 193.1 81.9 2.2 7.7 176.0 92.6 1.8 7.0 167.2 98.5 1.6 6.7
ASY 070B 252.8 73.0 3.2 10.1 237.6 79.8 2.8 9.5 218.3 89.0 2.3 8.7 197.7 99.1 1.9 7.9 186.9 104.6 1.7 7.5
ASY 080B 282.7 89.5 3.0 11.3 266.8 98.6 2.5 10.6 246.8 110.6 2.1 9.8 225.6 123.9 1.7 9.0 214.6 130.9 1.6 8.6
ASY 090B 347.8 106.4 3.0 13.9 328.9 117.0 2.6 13.1 304.9 131.5 2.2 12.2 279.2 148.0 1.8 11.1 265.8 157.0 1.6 10.6
ASY 100B 362.4 116.4 2.9 14.5 347.3 130.7 2.5 13.8 327.2 150.6 2.0 13.0 304.7 173.6 1.7 12.2 292.5 186.2 1.5 11.7
ASY 120B 426.1 131.4 3.0 17.0 403.7 145.7 2.6 16.1 375.5 165.4 2.1 15.0 345.9 187.9 1.7 13.8 330.6 200.1 1.6 13.2
ASY 130B 468.6 148.1 2.9 18.7 443.4 162.6 2.5 17.7 410.9 182.1 2.1 16.4 375.8 203.8 1.7 15.0 357.2 215.4 1.6 14.2
ASY 140B 497.8 173.8 2.7 19.8 476.5 197.3 2.3 19.0 447.0 229.8 1.9 17.8 412.7 266.7 1.5 16.5 393.4 286.7 1.3 15.7
ASY 150B 547.2 172.4 2.9 21.8 522.6 195.0 2.5 20.8 488.6 226.1 2.0 19.5 449.5 261.4 1.6 17.9 427.9 280.6 1.5 17.1
ASY 160B 573.5 182.5 2.9 22.9 542.8 201.3 2.5 21.6 503.9 226.1 2.1 20.1 462.4 253.3 1.7 18.4 440.7 267.9 1.6 17.6
ASY 170B 610.7 191.1 3.0 24.4 587.5 215.3 2.5 23.4 556.2 247.9 2.1 22.2 521.2 284.3 1.7 20.8 502.0 304.0 1.6 20.0
ASY 180B 656.4 199.4 3.0 26.2 619.3 220.6 2.6 24.7 573.1 249.6 2.1 22.9 524.8 282.7 1.8 20.9 499.8 300.7 1.6 19.9
ASY 190B 699.6 214.9 3.0 27.9 669.1 242.5 2.6 26.7 630.4 281.1 2.1 25.1 589.3 325.8 1.7 23.5 567.8 350.6 1.5 22.6
ASY 200B 720.6 223.1 3.0 28.7 693.6 254.0 2.5 27.7 659.0 297.8 2.1 26.3 621.7 348.9 1.7 24.8 602.2 377.3 1.5 24.0
ASY 215B 782.2 255.3 2.9 31.2 741.6 281.5 2.5 29.6 689.6 316.2 2.1 27.5 633.7 354.6 1.7 25.3 604.2 375.2 1.5 24.1
ASY 230B 824.3 278.4 2.8 32.9 786.4 309.7 2.4 31.4 737.3 351.3 2.0 29.4 683.9 397.4 1.6 27.3 655.4 422.2 1.5 26.1
8 0C ASY 240B 851.4 298.3 2.7 33.9 819.3 336.3 2.3 32.7 776.2 387.2 1.9 31.0 727.5 444.1 1.6 29.0 700.7 474.9 1.4 27.9
ASY 250B 922.6 266.3 3.2 36.8 870.7 294.1 2.7 34.7 806.1 332.2 2.3 32.1 738.7 375.5 1.9 29.5 703.9 399.0 1.7 28.1
ASY 270B 1000.3 313.6 3.0 39.9 940.4 342.9 2.6 37.5 863.8 381.7 2.1 34.4 781.9 424.4 1.7 31.2 738.8 447.1 1.6 29.5
ASY 295B 1081.9 335.4 3.0 43.1 1021.4 368.5 2.6 40.7 944.3 412.4 2.2 37.7 862.0 460.8 1.8 34.4 818.8 486.7 1.6 32.6
ASY 310B 1137.0 371.0 2.9 45.3 1075.4 409.0 2.5 42.9 997.1 459.0 2.1 39.8 913.8 514.0 1.7 36.4 870.1 543.4 1.5 34.7
ASY 330B 1213.0 365.2 3.1 48.4 1147.5 403.6 2.7 45.8 1065.0 456.5 2.2 42.5 978.1 516.9 1.8 39.0 933.0 549.8 1.6 37.2
ASY 350B 1274.2 390.8 3.0 50.8 1205.1 433.2 2.6 48.1 1118.3 491.5 2.2 44.6 1027.2 557.9 1.8 41.0 980.0 594.2 1.6 39.1
ASY 375B 1375.0 458.4 2.8 54.8 1295.5 502.9 2.4 51.7 1193.4 562.2 2.0 47.6 1083.6 627.7 1.7 43.2 1025.5 662.6 1.5 40.9
ASY 400B 1446.1 455.5 3.0 57.7 1361.4 499.0 2.6 54.3 1253.0 556.8 2.1 50.0 1136.8 620.7 1.7 45.3 1075.5 654.9 1.6 42.9
ASY 420B 1544.0 496.9 2.9 61.6 1458.2 546.6 2.5 58.1 1348.9 612.5 2.1 53.8 1232.0 685.2 1.7 49.1 1170.5 724.1 1.5 46.7
ASY 450B 1630.6 510.2 3.0 65.0 1544.7 562.1 2.6 61.6 1435.1 630.9 2.2 57.2 1317.7 706.9 1.8 52.5 1255.8 747.6 1.6 50.1
ASY 475B 1721.4 572.2 2.8 68.6 1643.6 638.1 2.5 65.5 1542.3 725.9 2.0 61.5 1431.3 823.3 1.7 57.1 1371.9 875.7 1.5 54.7
ASY 500B 1763.0 602.1 2.8 70.3 1694.4 678.3 2.4 67.6 1602.2 780.5 2.0 63.9 1498.2 894.6 1.6 59.7 1441.3 956.1 1.5 57.5
ASY 540B 1968.8 558.5 3.3 78.5 1858.2 613.7 2.8 74.1 1718.3 688.6 2.3 68.5 1570.1 772.7 1.9 62.6 1492.7 818.1 1.7 59.5

19
ASY 560B 2049.5 603.9 3.1 81.7 1931.2 660.8 2.7 77.0 1780.0 736.6 2.3 71.0 1617.9 820.5 1.9 64.5 1532.6 865.3 1.7 61.1
ASY 590B 2163.7 670.8 3.0 86.3 2042.7 737.1 2.6 81.5 1888.6 824.9 2.2 75.3 1724.1 921.6 1.8 68.7 1637.6 973.3 1.6 65.3
ASY 050B 191.9 55.7 3.2 7.7 180.5 60.9 2.8 7.2 166.2 67.9 2.3 6.6 151.1 75.8 1.9 6.0 143.3 80.0 1.7 5.7
ASY 060B 235.3 67.2 3.3 9.4 221.5 74.1 2.8 8.8 204.4 83.5 2.3 8.1 186.6 94.2 1.9 7.4 177.5 100.1 1.7 7.1
ASY 070B 266.8 74.6 3.3 10.6 251.0 81.5 2.9 10.0 231.0 90.8 2.4 9.2 209.6 101.0 2.0 8.4 198.3 106.5 1.8 7.9
ASY 080B 297.8 91.3 3.1 11.9 281.2 100.6 2.6 11.2 260.3 112.8 2.2 10.4 238.1 126.2 1.8 9.5 226.6 133.4 1.6 9.0
ASY 090B 371.2 109.8 3.1 14.8 351.4 120.4 2.7 14.0 326.0 134.8 2.3 13.0 299.0 151.1 1.9 11.9 284.8 159.9 1.7 11.4
ASY 100B 384.7 119.3 3.0 15.3 368.8 133.7 2.6 14.7 347.4 153.7 2.1 13.9 323.5 176.5 1.7 12.9 310.5 188.9 1.6 12.4
ASY 120B 456.1 135.4 3.1 18.2 433.0 149.9 2.7 17.3 403.9 169.8 2.2 16.1 373.1 192.3 1.8 14.9 357.2 204.5 1.6 14.2
ASY 130B 500.7 152.3 3.0 20.0 474.6 167.2 2.7 18.9 441.1 187.0 2.2 17.6 404.6 208.9 1.8 16.1 385.3 220.6 1.7 15.4
ASY 140B 528.8 178.2 2.8 21.1 506.5 202.2 2.4 20.2 475.3 235.0 1.9 19.0 439.1 272.1 1.5 17.5 418.8 292.2 1.4 16.7
ASY 150B 581.4 176.5 3.0 23.2 555.3 199.5 2.6 22.1 519.3 230.9 2.1 20.7 478.2 266.4 1.7 19.1 455.7 285.7 1.5 18.2
ASY 160B 611.3 187.4 3.0 24.4 579.1 206.6 2.6 23.1 538.2 231.8 2.2 21.5 494.4 259.7 1.8 19.7 471.3 274.5 1.6 18.8
ASY 170B 648.2 194.9 3.1 25.8 623.6 219.5 2.7 24.9 590.4 252.6 2.2 23.5 553.1 289.6 1.8 22.1 532.7 309.6 1.6 21.2
ASY 180B 695.1 204.5 3.1 27.7 657.1 226.0 2.7 26.2 609.6 255.3 2.2 24.3 559.8 288.5 1.8 22.3 534.0 306.5 1.6 21.3
ASY 190B 738.3 219.7 3.1 29.4 707.3 247.7 2.7 28.2 667.6 286.7 2.2 26.6 625.3 331.7 1.8 24.9 603.0 356.4 1.6 24.0
ASY 200B 759.5 227.6 3.1 30.3 732.0 259.1 2.6 29.2 696.5 303.3 2.2 27.8 658.2 354.9 1.8 26.2 637.9 383.4 1.6 25.4
ASY 215B 834.0 262.2 3.0 33.3 791.6 288.9 2.6 31.6 737.2 324.3 2.2 29.4 678.5 363.4 1.8 27.1 647.4 384.3 1.6 25.8
ASY 230B 876.9 285.2 2.9 35.0 837.1 317.1 2.5 33.4 785.4 359.6 2.1 31.3 729.0 406.7 1.7 29.1 698.9 432.0 1.5 27.9
10 0C ASY 240B 902.7 304.7 2.8 36.0 868.8 343.4 2.4 34.6 823.0 395.4 2.0 32.8 770.9 453.4 1.6 30.7 742.3 484.7 1.5 29.6
ASY 250B 986.8 274.5 3.3 39.3 932.7 302.7 2.8 37.2 865.2 341.1 2.4 34.5 794.3 384.4 1.9 31.7 757.4 407.9 1.8 30.2
ASY 270B 1068.1 323.5 3.1 42.6 1005.4 353.3 2.7 40.1 925.2 392.6 2.2 36.9 839.2 435.5 1.8 33.5 793.9 458.3 1.6 31.7
ASY 295B 1154.4 344.9 3.1 46.0 1091.1 378.7 2.7 43.5 1010.2 423.3 2.3 40.3 923.6 472.4 1.9 36.8 877.9 498.5 1.7 35.0
ASY 310B 1211.6 381.2 3.0 48.3 1146.9 420.0 2.6 45.7 1064.5 471.1 2.2 42.4 976.4 527.3 1.8 38.9 930.0 557.3 1.6 37.1
ASY 330B 1294.8 375.8 3.2 51.6 1226.5 414.6 2.8 48.9 1140.5 467.8 2.3 45.5 1049.9 528.0 1.9 41.9 1002.6 560.6 1.7 40.0
ASY 350B 1359.8 401.9 3.2 54.2 1287.9 444.8 2.7 51.4 1197.8 503.5 2.3 47.8 1103.2 570.0 1.9 44.0 1054.1 606.2 1.7 42.0
ASY 375B 1464.6 471.9 2.9 58.4 1381.9 517.2 2.5 55.1 1275.6 577.1 2.1 50.9 1160.9 643.1 1.7 46.3 1100.3 678.2 1.6 43.9
ASY 400B 1528.4 467.0 3.1 60.9 1441.5 511.2 2.7 57.5 1330.1 569.8 2.2 53.0 1210.2 634.3 1.8 48.3 1146.9 668.7 1.6 45.7
ASY 420B 1629.3 508.3 3.0 65.0 1541.3 558.9 2.6 61.5 1428.7 625.9 2.2 57.0 1308.0 699.8 1.8 52.2 1244.2 739.2 1.6 49.6
ASY 450B 1745.8 524.8 3.1 69.6 1656.9 577.9 2.7 66.1 1542.9 648.3 2.3 61.5 1420.2 726.0 1.9 56.6 1355.2 767.5 1.7 54.0
ASY 475B 1835.4 586.7 3.0 73.2 1754.2 654.2 2.5 69.9 1648.0 744.0 2.1 65.7 1531.2 843.6 1.8 61.1 1468.4 897.2 1.6 58.6
ASY 500B 1874.3 616.0 2.9 74.7 1802.3 693.9 2.5 71.9 1704.9 798.2 2.0 68.0 1594.6 914.6 1.7 63.6 1534.3 977.3 1.5 61.2
ASY 540B 2105.8 574.9 3.4 84.0 1990.3 631.0 2.9 79.4 1844.0 706.6 2.4 73.5 1688.5 791.0 2.0 67.3 1607.0 836.5 1.8 64.1
ASY 560B 2190.2 621.9 3.3 87.3 2066.7 679.7 2.8 82.4 1908.5 756.5 2.4 76.1 1738.5 840.9 2.0 69.3 1648.8 885.9 1.8 65.7
ASY 590B 2308.9 689.8 3.1 92.1 2182.2 757.4 2.7 87.0 2020.5 846.6 2.3 80.6 1847.2 944.7 1.9 73.7 1755.9 997.0 1.7 70.0
LEGEND: NOTES:
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590. 4. Direct interpolation is permissible. Do not extrapolate.
LPS - Liters Per Second 2. Performance data are based on 60C water range in evaporator. 5. kW power input is for compressor only.
COP - Coefficient of Performance 3. Ratings are based on 0.000018 (m2 -0C/W) fouling factor for evaporator. 6. COP for entire unit. Refer to electrical data for fan kW.
ELECTRICAL DATA
SUPPLY VOLTAGE COMPRESSOR TYPE-1 COMPRESSOR TYPE-2 CONDENSER FAN MOTORS CRANKCASE HEATER COMP.
UNIT WIND-
SIZE Nominal RLA LRA CB CB RLA LRA CB CB FLA Total CB Total Total ING
Min. Max. MCA MOCP Qty. Qty. Qty. FCA Volts
(V-Ph-Hz) (each) (each) Poles MTA Qty. (each) (each) Poles MTA Qty. (each) kW (Qty.) Watts Amps
220-3-60 198 242 227 393 1 165.6 885 3 265 1 - - - - - - 4 5.05 4.40 20.2 2 230 200 0.87 PW
ASY 050B 380-3-60 342 418 137 237 1 100.2 534 3 160 1 - - - - - - 4 2.93 4.40 11.7 2 230 200 0.87 PW
460-3-60 414 506 115 197 1 82.8 423 3 132 1 - - - - - - 4 2.78 4.40 11.1 2 230 200 0.87 PW
220-3-60 198 242 280 488 1 208.0 1040 3 333 1 - - - - - - 4 5.05 4.40 20.2 2 230 300 1.30 PW
ASY 060B 380-3-60 342 418 169 295 1 125.9 631 3 201 1 - - - - - - 4 2.93 4.40 11.7 2 230 300 1.30 PW
460-3-60 414 506 141 245 1 104.0 520 3 166 1 - - - - - - 4 2.78 4.40 11.1 2 230 300 1.30 PW
220-3-60 198 242 323 562 1 239.0 1224 3 382 1 - - - - - - 4 6.10 6.00 24.4 2 230 300 1.30 PW
ASY 070B 380-3-60 342 418 195 340 1 144.9 742 3 232 1 - - - - - - 4 3.52 6.00 14.1 2 230 300 1.30 PW
460-3-60 414 506 164 283 1 119.7 612 3 192 1 - - - - - - 4 3.50 7.60 14.0 2 230 300 1.30 PW
220-3-60 198 242 371 648 1 277.0 1330 3 443 1 - - - - - - 4 6.10 6.00 24.4 2 230 300 1.30 PW
ASY 080B 380-3-60 342 418 224 391 1 167.6 807 3 268 1 - - - - - - 4 3.52 6.00 14.1 2 230 300 1.30 PW
460-3-60 414 506 187 326 1 138.5 665 3 222 1 - - - - - - 4 3.50 7.60 14.0 2 230 300 1.30 PW
220-3-60 198 242 409 575 2 165.6 885 3 265 2 - - - - - - 6 6.10 9.00 36.6 3 230 400 1.74 PW
ASY 090B 380-3-60 342 418 247 347 2 100.2 534 3 160 2 - - - - - - 6 3.52 9.00 21.1 3 230 400 1.74 PW
460-3-60 414 506 207 290 2 82.8 423 3 132 2 - - - - - - 6 3.50 11.40 21.0 3 230 400 1.74 PW
220-3-60 198 242 434 611 2 176.7 885 3 283 2 - - - - - - 6 6.10 9.00 36.6 3 230 400 1.74 PW
ASY 100B 380-3-60 342 418 262 369 2 107.0 534 3 171 2 - - - - - - 6 3.52 9.00 21.1 3 230 400 1.74 PW
460-3-60 414 506 220 308 2 88.4 423 3 141 2 - - - - - - 6 3.50 11.40 21.0 3 230 400 1.74 PW
220-3-60 198 242 517 725 2 208.0 1040 3 333 2 - - - - - - 8 6.10 12.00 48.8 4 230 600 2.61 PW

20
ASY 120B 380-3-60 342 418 311 437 2 125.9 631 3 201 2 - - - - - - 8 3.52 12.00 28.2 4 230 600 2.61 PW
460-3-60 414 506 262 366 2 104.0 520 3 166 2 - - - - - - 8 3.50 15.20 28.0 4 230 600 2.61 PW
220-3-60 198 242 587 826 2 239.0 1224 3 382 2 - - - - - - 8 6.10 12.00 48.8 4 230 600 2.61 PW
ASY 130B 380-3-60 342 418 354 499 2 144.9 742 3 232 2 - - - - - - 8 3.52 12.00 28.2 4 230 600 2.61 PW
460-3-60 414 506 297 417 2 119.7 612 3 192 2 - - - - - - 8 3.50 15.20 28.0 4 230 600 2.61 PW
220-3-60 198 242 643 907 2 264.0 1224 3 422 2 - - - - - - 8 6.10 12.00 48.8 4 230 600 2.61 PW
ASY 140B 380-3-60 342 418 387 547 2 159.5 742 3 255 2 - - - - - - 8 3.52 12.00 28.2 4 230 600 2.61 PW
460-3-60 414 506 325 456 2 131.8 612 3 211 2 - - - - - - 8 3.50 15.20 28.0 4 230 600 2.61 PW
220-3-60 198 242 655 919 2 264.0 1224 3 422 2 - - - - - - 10 6.10 15.00 61.0 5 230 600 2.61 PW
ASY 150B 380-3-60 342 418 394 554 2 159.5 742 3 255 2 - - - - - - 10 3.52 15.00 35.2 5 230 600 2.61 PW
460-3-60 414 506 332 463 2 131.8 612 3 211 2 - - - - - - 10 3.50 19.00 35.0 5 230 600 2.61 PW
220-3-60 198 242 684 961 2 277.0 1330 3 443 2 - - - - - - 10 6.10 15.00 61.0 5 230 600 2.61 PW
ASY 160B 380-3-60 342 418 412 580 2 167.6 807 3 268 2 - - - - - - 10 3.52 15.00 35.2 5 230 600 2.61 PW
460-3-60 414 506 347 485 2 138.5 665 3 222 2 - - - - - - 10 3.50 19.00 35.0 5 230 600 2.61 PW
LEGEND: NOTES:
MCA - Minimum Circuit Ampacity per NEC 430-24 1. Customer to specify the exact nominal power supply available at site so that electrical components are selected accurately, failing to do so will affect unit
MOCP - Maximum Over Current Protection performance & terms of warranty.
RLA - Rated Load Amps 2. Main power must be supplied from a single field supplied and mounted fused disconnects, using dual element time delay fuse or circuit breaker.
LRA - Locked Rotor Amps 3. The maximum incoming wire size is 500 MCM. On units having MCA greater than 500 MCM wire, the factory supplied power terminal block will accept
CB - Circuit Breaker two or more parallel field wires per pole phase.
MTA - Must Trip Amps 4. The compressor crankcase heaters must be energized for 12 hours before the unit is initially started or after a prolonged power disconnection.
FLA - Full Load Amps 5. Under compressor type 1 are the big compressors or compressor with economizer, and type 2 are the small compressors or compressor without Economizer.
FCA - Fan Circuit Amps 6. All field wiring must be in accordance with NEC and local standards.
PW - Part Winding Start Compressor 7. Minimum and maximum unit supply voltages are shown in the tabulated data above.
kW - Kilo Watt 8. Neutral line required on 380V-3Ph-60Hz power supply only.
9. The 10% voltage variation from the nominal is allowed for a short time only, not permanent.
10. RLA & MCA values are based on nominal conditions.
ELECTRICAL DATA
SUPPLY VOLTAGE COMPRESSOR TYPE-1 COMPRESSOR TYPE-2 CONDENSER FAN MOTORS CRANKCASE HEATER COMP.
UNIT WIND-
SIZE Nominal RLA LRA CB CB RLA LRA CB CB FLA Total CB Total Total ING
Min. Max. MCA MOCP Qty. Qty. Qty. FCA Volts
(V-Ph-Hz) (each) (each) Poles MTA Qty. (each) (each) Poles MTA Qty. (each) kW (Qty.) Watts Amps
220-3-60 198 242 725 1020 2 295.0 1330 3 472 2 - - - - - - 10 6.10 15.00 61.0 5 230 600 2.61 PW
ASY 170B 380-3-60 342 418 438 616 2 178.8 807 3 286 2 - - - - - - 10 3.52 15.00 35.2 5 230 600 2.61 PW
460-3-60 414 506 367 515 2 147.7 665 3 236 2 - - - - - - 10 3.50 19.00 35.0 5 230 600 2.61 PW
220-3-60 198 242 749 957 3 208.0 1040 3 333 3 - - - - - - 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 180B 380-3-60 342 418 451 577 3 125.9 631 3 201 3 - - - - - - 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 380 484 3 104.0 520 3 166 3 - - - - - - 12 3.50 22.80 42.0 6 230 900 3.91 PW
220-3-60 198 242 810 1045 2 235.0 1040 3 376 2 1 208 1040 3 333 1 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 190B 380-3-60 342 418 488 630 2 142.1 631 3 227 2 1 125.9 631 3 201 1 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 410 528 2 117.4 520 3 188 2 1 104 520 3 166 1 12 3.50 22.80 42.0 6 230 900 3.91 PW
220-3-60 198 242 837 1072 3 235.0 1040 3 376 3 - - - - - - 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 200B 380-3-60 342 418 504 646 3 142.1 631 3 227 3 - - - - - - 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 424 541 3 117.4 520 3 188 3 - - - - - - 12 3.50 22.80 42.0 6 230 900 3.91 PW
220-3-60 198 242 935 1212 2 277.0 1330 3 443 2 1 239.0 1224 3 382 1 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 215B 380-3-60 342 418 564 732 2 167.6 807 3 268 2 1 144.9 742 3 232 1 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 473 612 2 138.5 665 3 222 2 1 119.7 612 3 192 1 12 3.50 22.80 42.0 6 230 900 3.91 PW
220-3-60 198 242 996 1291 1 295.0 1330 3 472 1 2 277.0 1330 3 443 2 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 230B 380-3-60 342 418 601 780 1 178.8 807 3 286 1 2 167.6 807 3 268 2 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 504 651 1 147.7 665 3 236 1 2 138.5 665 3 222 2 12 3.50 22.80 42.0 6 230 900 3.91 PW
220-3-60 198 242 1032 1327 3 295.0 1330 3 472 3 - - - - - - 12 6.10 18.00 73.2 6 230 900 3.91 PW

21
ASY 240B 380-3-60 342 418 623 802 3 178.8 807 3 286 3 - - - - - - 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 522 670 3 147.7 665 3 236 3 - - - - - - 12 3.50 22.80 42.0 6 230 900 3.91 PW
220-3-60 198 242 982 1190 4 208.0 1040 3 333 4 - - - - - - 16 6.10 24.00 97.6 8 230 1200 5.22 PW
ASY 250B 380-3-60 342 418 591 717 4 125.9 631 3 201 4 - - - - - - 16 3.52 24.00 56.3 8 230 1200 5.22 PW
460-3-60 414 506 498 602 4 104.0 520 3 166 4 - - - - - - 16 3.50 30.40 56.0 8 230 1200 5.22 PW
220-3-60 198 242 1113 1352 4 239.0 1224 3 382 4 - - - - - - 16 6.10 24.00 97.6 8 230 1200 5.22 PW
ASY 270B 380-3-60 342 418 672 817 4 144.9 742 3 232 4 - - - - - - 16 3.52 24.00 56.3 8 230 1200 5.22 PW
460-3-60 414 506 565 684 4 119.7 612 3 192 4 - - - - - - 16 3.50 30.40 56.0 8 230 1200 5.22 PW
220-3-60 198 242 1199 1476 2 277.0 1330 3 443 2 2 239 1224 3 382 2 16 6.10 24.00 97.6 8 230 1200 5.22 PW
ASY 295B 380-3-60 342 418 723 891 2 167.6 807 3 268 2 2 144.9 742 3 232 2 16 3.52 24.00 56.3 8 230 1200 5.22 PW
460-3-60 414 506 607 746 2 138.5 665 3 222 2 2 119.7 612 3 192 2 16 3.50 30.40 56.0 8 230 1200 5.22 PW
220-3-60 198 242 1275 1552 4 277.0 1330 3 443 4 - - - - - - 16 6.10 24.00 97.6 8 230 1200 5.22 PW
ASY 310B 380-3-60 342 418 769 936 4 167.6 807 3 268 4 - - - - - - 16 3.52 24.00 56.3 8 230 1200 5.22 PW
460-3-60 414 506 645 783 4 138.5 665 3 222 4 - - - - - - 16 3.50 30.40 56.0 8 230 1200 5.22 PW
LEGEND: NOTES:
MCA - Minimum Circuit Ampacity per NEC 430-24 1. Customer to specify the exact nominal power supply available at site so that electrical components are selected accurately, failing to do so will affect unit
MOCP - Maximum Over Current Protection performance & terms of warranty.
RLA - Rated Load Amps 2. Main power must be supplied from a single field supplied and mounted fused disconnects, using dual element time delay fuse or circuit breaker.
LRA - Locked Rotor Amps 3. The maximum incoming wire size is 500 MCM. On units having MCA greater than 500 MCM wire, the factory supplied power terminal block will accept
CB - Circuit Breaker two or more parallel field wires per pole phase.
MTA - Must Trip Amps 4. The compressor crankcase heaters must be energized for 12 hours before the unit is initially started or after a prolonged power disconnection.
FLA - Full Load Amps 5. Under compressor type 1 are the big compressors or compressor with economizer, and type 2 are the small compressors or compressor without Economizer.
FCA - Fan Circuit Amps 6. All field wiring must be in accordance with NEC and local standards.
PW - Part Winding Start Compressor 7. Minimum and maximum unit supply voltages are shown in the tabulated data above.
kW - Kilo Watt 8. Neutral line required on 380V-3Ph-60Hz power supply only.
9. The 10% voltage variation from the nominal is allowed for a short time only, not permanent.
10. RLA & MCA values are based on nominal conditions.
ELECTRICAL DATA
SUPPLY VOLTAGE COMPRESSOR TYPE-1 COMPRESSOR TYPE-2 CONDENSER FAN MOTORS CRANKCASEHEATER COMP.
UNIT WIND-
SIZE Nominal RLA LRA CB CB RLA LRA CB CB FLA Total CB Total Total ING
Min. Max. MCA MOCP Qty. Qty. Qty. FCA Volts
(V-Ph-Hz) (each) (each) Poles MTA Qty. (each) (each) Poles MTA Qty. (each) kW (Qty.) Watts Amps
220-3-60 198 242 1325 1533 4 208.0 1040 3 333 4 2 165.6 885 3 265 2 18 6.10 27.00 109.8 9 230 1600 6.96 PW
ASY 330B 380-3-60 342 418 799 925 4 125.9 631 3 201 4 2 100.2 534 3 160 2 18 3.52 27.00 63.4 9 230 1600 6.96 PW
460-3-60 414 506 671 775 4 104.0 520 3 166 4 2 82.8 423 3 132 2 18 3.50 34.20 63.0 9 230 1600 6.96 PW
220-3-60 198 242 1410 1618 6 208.0 1040 3 333 6 - - - - - - 18 6.10 27.00 109.8 9 230 1800 7.83 PW
ASY 350B 380-3-60 342 418 850 976 6 125.9 631 3 201 6 - - - - - - 18 3.52 27.00 63.4 9 230 1800 7.83 PW
460-3-60 414 506 713 817 6 104.0 520 3 166 6 - - - - - - 18 3.50 34.20 63.0 9 230 1800 7.83 PW
220-3-60 198 242 1604 1843 6 239.0 1224 3 382 6 - - - - - - 18 6.10 27.00 109.8 9 230 1800 7.83 PW
ASY375B 380-3-60 342 418 969 1114 6 144.9 742 3 232 6 - - - - - - 18 3.52 27.00 63.4 9 230 1800 7.83 PW
460-3-60 414 506 811 931 6 119.7 612 3 192 6 - - - - - - 18 3.50 34.20 63.0 9 230 1800 7.83 PW
220-3-60 198 242 1628 1867 6 239.0 1224 3 382 6 - - - - - - 22 6.10 33.00 134.2 11 230 1800 7.83 PW
ASY 400B 380-3-60 342 418 983 1128 6 144.9 742 3 232 6 - - - - - - 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 825 945 6 119.7 612 3 192 6 - - - - - - 22 3.50 41.80 77.0 11 230 1800 7.83 PW
220-3-60 198 242 1751 2028 3 277.0 1330 3 443 3 3 239 1224 3 382 3 22 6.10 33.00 134.2 11 230 1800 7.83 PW
ASY 420B 380-3-60 342 418 1057 1224 3 167.6 807 3 268 3 3 144.9 742 3 232 3 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 886 1025 3 138.5 665 3 222 3 3 119.7 612 3 192 3 22 3.50 41.80 77.0 11 230 1800 7.83 PW
220-3-60 198 242 1789 2066 4 277.0 1330 3 443 4 2 239.0 1,224 3 382 2 22 6.10 33.00 134.2 11 230 1800 7.83 PW
ASY 450B 380-3-60 342 418 1080 1247 4 167.6 807 3 268 4 2 144.9 742 3 232 2 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 905 1044 4 138.5 665 3 222 4 2 119.7 612 3 192 2 22 3.50 41.80 77.0 11 230 1800 7.83 PW
220-3-60 198 242 1924 2219 3 295.0 1330 3 472 3 3 277 1330 3 443 3 22 6.10 33.00 134.2 11 230 1800 7.83 PW

22
ASY 475B 380-3-60 342 418 1161 1340 3 178.8 807 3 286 3 3 167.6 807 3 268 3 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 973 1120 3 147.7 665 3 236 3 3 138.5 665 3 222 3 22 3.50 41.80 77.0 11 230 1800 7.83 PW
220-3-60 198 242 1978 2273 6 295.0 1330 3 472 6 - - - - - - 22 6.10 33.00 134.2 11 230 1800 7.83 PW
ASY 500B 380-3-60 342 418 1195 1374 6 178.8 807 3 286 6 - - - - - - 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 1000 1148 6 147.7 665 3 236 6 - - - - - - 22 3.50 41.80 77.0 11 230 1800 7.83 PW
220-3-60 198 242 1051/1051 1290/1290 4 239.0 1224 3 382 4 4 208 1040 3 333 4 32 6.10 48.00 195.2 16 230 2400 10.43 PW
ASY5 40B 380-3-60 342 418 634/634 779/779 4 144.9 742 3 232 4 4 125.9 631 3 201 4 32 3.52 48.00 112.6 16 230 2400 10.43 PW
460-3-60 414 506 533/533 653/653 4 119.7 612 3 192 4 4 104 520 3 166 4 32 3.50 60.80 112.0 16 230 2400 10.43 PW
220-3-60 198 242 1113/1113 1352/1352 8 239.0 1224 3 382 8 - - - - - - 32 6.10 48.00 195.2 16 230 2400 10.43 PW
ASY560B 380-3-60 342 418 672/672 817/817 8 144.9 742 3 232 8 - - - - - - 32 3.52 48.00 112.6 16 230 2400 10.43 PW
460-3-60 414 506 565/565 684/684 8 119.7 612 3 192 8 - - - - - - 32 3.50 60.80 112.0 16 230 2400 10.43 PW
220-3-60 198 242 1199/1199 1476/1476 4 277.0 1330 3 443 4 4 239 1224 3 382 4 32 6.10 48.00 195.2 16 230 2400 10.43 PW
ASY 590B 380-3-60 342 418 723/723 891/891 4 167.6 807 3 268 4 4 144.9 742 3 232 4 32 3.52 48.00 112.6 16 230 2400 10.43 PW
460-3-60 414 506 607/607 746/746 4 138.5 665 3 222 4 4 119.7 612 3 192 4 32 3.50 60.80 112.0 16 230 2400 10.43 PW
LEGEND: NOTES:
MCA - Minimum Circuit Ampacity per NEC 430-24 1. Customer to specify the exact nominal power supply available at site so that electrical components are selected accurately, failing to do so will affect
MOCP - Maximum Over Current Protection unit performance & terms of warranty.
RLA - Rated Load Amps 2. Main power must be supplied from a single field supplied and mounted fused disconnects, using dual element time delay fuse or circuit breaker.
LRA - Locked Rotor Amps 3. The maximum incoming wire size is 500 MCM. On units having MCA greater than 500 MCM wire, the factory supplied power terminal block will accept two
CB - Circuit Breaker or more parallel field wires per pole phase.
MTA - Must Trip Amps 4. The compressor crankcase heaters must be energized for 12 hours before the unit is initially started or after a prolonged power disconnection.
FLA - Full Load Amps 5 . Under compressor type 1 are the big compressors or compressor with economizer, and type 2 are the small compressors or compressor without Economizer.
FCA - Fan Circuit Amps 6. All field wiring must be in accordance with NEC and local standards.
PW - Part Winding Start Compressor 7. Minimum and maximum unit supply voltages are shown in the tabulated data above.
8. Neutral line required on 380V-3Ph-60Hz power supply only.
kW - Kilo Watt
9. The 10% voltage variation from the nominal is allowed for a short time only, not permanent.
10. RLA & MCA values are based on nominal conditions.
11. Models ASY540B - ASY590B are with dual main power supply. So, MCA & MOCP have two values.
WATER SIDE PRESSURE DROP
200

1 2 34 5 86
7
60 70 80 90 100

9
10
50
40
30
PRESSURE DROP (FT. OF WATER)
20
8 9 10
7
6
5
4
3
2
1

10 20 30 40 50 60 70 80 90 100 200 300 400 500 600 700 800 900 1000 1200 1500
FLOW RATE - GPM
MODEL No. CURVE No. Minimum GPM Maximum GPM MODEL No. CURVE No. Minimum GPM Maximum GPM
ASY050B 1 82 138 ASY230B 8 412 620
ASY060B 2 98 170 ASY240B 8 447 633
ASY070B 2 108 192 ASY250B 5 425 708
ASY080B 2 124 214 ASY270B 6 450 768
ASY090B 3 164 265 ASY295B 6 502 826
ASY100B 3 184 271 ASY310B 6 537 866
ASY120B 4 203 325 ASY330B 6 572 925
ASY130B 5 222 356 ASY350B 6 601 971
ASY140B 5 251 372 ASY375B 7 634 1048
ASY150B 6 267 411 ASY400B 7 650 1095
ASY160B 6 272 437 ASY420B 7 710 1164
ASY170B 6 315 455 ASY450B 9 779 1242
ASY180B 7 301 498 ASY475B 9 866 1297
ASY190B 7 343 522 ASY500B 9 886 1332
ASY200B 7 365 534 ASY540B 10 896 1514
ASY215B 8 375 593 ASY560B 10 924 1577
CONVERSION FACTOR: GPM = 0.063 Liters per second. ASY590B 10 995 1662
Feet of water = 2.989 Kilo Pascal (kpa).
NOTE: 1. If an application requires certain water flow rate outside these limits, please check with your nearest dealer/sales office.
2. If the chiller has 2 evaporators, then the total water flow must be divided by 2 while applying the above curves (applicable for models
ASY250B - ASY590B.

23
RECOMMENDED INSTALLATION
LEAVING/RETURN WATER TEMPERATURE SENSOR & WATER FLOW SWITCH
NOTE: 1. For chiller with 2 coolers, leaving water temperature sensor and return water temperature sensor should be installed in the water piping
main header of every chiller.
2. Water flow switch should be installed vertically on the horizontal pipe line closed to the leaving water port of every cooler.

LEAVING RETURN
WATER WATER

CHILLER # 1

CONTROL PANEL

IN COOLER 1 OUT IN COOLER 2 OUT

FLS1 FLS2
FS

(FIELD INSTALLATION] (FIELD INSTALLATION]

FS
RWT
RETURN WATER SENSOR
(FIELD INSTALLATION]

LWT
LEAVING WATER SENSOR
(FIELD INSTALLATION]

CHILLER # 2

CONTROL PANEL

IN COOLER 1 OUT IN COOLER 2 OUT

FLS1 FLS2
FS

(FIELD INSTALLATION] (FIELD INSTALLATION]


FS

RWT
RETURN WATER SENSOR
(FIELD INSTALLATION]

LWT
LEAVING WATER SENSOR
(FIELD INSTALLATION]

CHILLER # n

CONTROL PANEL

IN COOLER 1 OUT IN COOLER 2 OUT

FLS1 FLS2
FS

(FIELD INSTALLATION] (FIELD INSTALLATION]


FS

RWT
RETURN WATER SENSOR
(FIELD INSTALLATION]

LEGEND : LWT
BULB WELL FOR THE LWT/RWT (ZAC NOT SUPPLIED) LEAVING WATER SENSOR
(FIELD INSTALLATION]
LWT LEAVING WATER SENSOR (ZAC SUPPLIED - LOOSE PART)
NOTE :
RWT RETURN WATER SENSOR (ZAC SUPPLIED - LOOSE PART)
1. CHECK WITH THE ENGINEERING DEPARTMENT FOR THE FULL DETAILS
> or < WATER DIRECTION AND ACCURATE DRAWING.
FS WATER FLOW SWITCH / FLS# (ZAC SUPPLIED AS OPTIONAL)
2.HARDWIRE FROM FLOW SWITCH AND LWT/RWT SHOULD BE ROUTED
HARD WIRE TO THE UNIT CONTROLLER (ZAC NOT SUPPLIED)
INDIVIDUALLY AND DIRECT TO THE UNIT CONTROLLER.REFER TO THE
WATER PIPE LINE (CONTRACTOR SCOPE) ACTUAL UNIT WIRING DIAGRAM FOR DETAILS.

24
DIMENSIONS
ASY050B

ASY060B, ASY070B & ASY080B


DIMENSIONS
MODEL A

ASY060B 100

ASY070B - ASY080B 275

NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.

25
DIMENSIONS
ASY090B & ASY100B

ASY120B, ASY130B & ASY140B

NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.

26
DIMENSIONS
ASY150B, ASY160B & ASY170B

ASY180B, ASY190B, ASY200B, ASY215B, ASY230B & ASY240B


DIMENSIONS
MODEL A B C

ASY180B 2075 2200 500

ASY190B - ASY200B 2075 2200 1650

ASY215B 2185 2700 1115

ASY230B - ASY240B 2185 3200 800

NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.

27
DIMENSIONS
ASY250B, ASY270B, ASY295B & ASY310B

DIMENSIONS
MODEL A B C D

ASY250B 417 1890 2250 375

ASY270B - ASY310B 457 1940 2200 445

28
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
DIMENSIONS
ASY330B, ASY350B & ASY375B

29
* EXTRA HEIGHT FOR 230V CONTROL BOX.

NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
DIMENSIONS
ASY400B, ASY420B, ASY450B, ASY475B & ASY500B

DIMENSIONS
MODEL A B C D

ASY400B - ASY420B 2200 3420 457 500

ASY450B - ASY500B 2130 3474 487 700

30
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
DIMENSIONS
ASY540B, ASY560B & ASY590B

31
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
TYPICAL SCHEMATIC WIRING DIAGRAM
(PART WINDING START)
HVTB / NF DISCONNECT SWITCH
L1
REFER TO UNIT L2
NAMEPLATE FOR
L3
POWER SUPPLY

NTB CB17 CB18 CB19 CB20


CB1 CB2
SEE NOTE # 7

ETB/LUG L1I L1J L1K L1L


L2I L2J L2K L2L
L1A

L1B
L2C
L3C

L2D
L3D
L2A
L3A

L2B
L3B
L1C

L1D
L3I L3J L3K L3L
CC1 CC3 CC2 CC4
FMC1 FMC2 FMC3 FMC4 FMC5 FMC6 FMC7 FMC8
T2C
T3C

T2D
T3D
T1A
T2A
T3A

T1B
T2B
T3B
T1C

T1D

35G
36G
37G

35F
36F
37F
35C
36C
37C

35D
36D
37D

35H
36H
37H
35A
36A
37A

35E
36E
37E

35B
36B
37B
COMP COMP FM FM FM FM FM FM FM FM
1 2 3 7 1 5 4 8 2 6

L1 NTB

CONTROL VOLTAGE
1B F1 5A 230V-1PH 2
ATB ATB
CCA1-1 3A
1HTR COMP1 OILHTR
SEE ALSO UNLOADER
CCA2-1 TIMER DETAILS
3B
2HTR COMP2 OILHTR

T1 T2
SSPS1 COMP1 SSPS
T1 T2
SSPS2 COMP2 SSPS
S1( CONTROL POWER)
SERIAL CABLE
UVR
1A 1 230VAC
(SEE UVM CONNECTION) TO ATB
TRANS
230VAC
4 24VAC 5 MB 1 2
SSPS1
8A
A1/D1(SSPS-1)
CBA1-1 TRANS2
23A
A2/D2(CB-1) EEVB
JP2A 6 7
A3/D3(OL-1)
HPS1 12/24VAC OB1 EEVB JUMPER & DIP SWITCH
10A 9A +
X1 RED
A4/D4(HPS-1)
EEV X9 A1 X1 GRN TD1 CLOSED
A5/D5(FCB-1) - 2A - - EEV
SSPS2 AO1 V1 + X1 WHT 1 TU1 CLOSED
8B 5A
A6/D6(SSPS-2) + + B1 X1 BLK
CBA2-1 DIP S1 -
TL1 OPEN
23B
A7/D7(CB-2)
JP3A
4 JU1 OPEN
A8/D8(OL-2) 3 EEV CARD
2 1 2 3 4
HPS2 10B 9B 1 S1
A9/D9(HPS-2) X2 RED
+ 24V ON OFF ON OFF
- 2B - A2 X2 GRN
(DIP)
A10/D10(FCB-2)
FLS 10 CWP* 11 A02 5B V2 - 12V OFF ON OFF OFF
EEV
+ + X2 WHT 2
A11/D11(FLW) +
B2 X2 BLK
1 2G PE - **SEE ALSO DISCHARGE TEMPERATURE
A12/D12 (EXT. ENABLE)
CONNECTION
1 2H PE
A13/D13 (EMERGENCY)

AC/DC(DIGITAL COM)
1C R1(DIG OUT) 1O 12A CC1
COMP1 CONTACTOR
LLS1
R2(DIG OUT) LIQUID LINE SOLENOID1
2C 2O

R3(DIG OUT) UL2-1


3C 3O 14A POWER DECREASE CP1
4C
R4(DIG OUT)
4O 12B CC2 COMP2 CONTACTOR
R5(DIG OUT)
LLS2
5C 5O LIQUID LINE SOLENOID2
R6(DIG OUT) UL2-2
6C 6O 14B POWER DECREASE CP2
R7(DIG OUT)
7C 7O HOT GAS BYPASS SOLENOID
7A 8C R8(DIG OUT) 8NO
6A ALARM - NO CONTACT
8NC
16 ALARM - NC CONTACT
R9(DIG OUT) TK3
C 9O 18A 112 FMC1
TK7 CTR-FAN 3
116 FMC2
R10(DIG OUT) TK1 CTR-FAN 7
10O 19A 110 FMC3
TK5 CTR-FAN 1
114 FMC4
R11(DIG OUT) CTR-FAN 5
11O
R12(DIG OUT) SL.I1
12O 20A
LIQUID INJECTION 1
R13(DIG OUT) TK4
C 13O 18B 113 FMC5 CTR-FAN 4
TK8
117 FMC6 CTR-FAN 8
R14(DIG OUT) 14O TK2
19B 111 FMC7 CTR-FAN 2
REMOTE MONITORING TK6
115 FMC8
R15(DIG OUT)
CTR-FAN 6
INTERFACE 15O
(SEE OPTION BOX) R16(DIG OUT) SL.I2
16O 20B
COM2 LIQUID INJECTION 2
R17(DIG OUT) UL4-1
17C 17O 15A
POWER INCREASE CP1
18C
R18(DIG OUT)
18O 15B UL4-2
POWER INCREASE CP2

22A 28A
- - SPT1 - COMP1
T1S ST1 O1 SUCTION PRESSURE
23A 29A
SUCTION TEMP SENSOR COMP1 (A1-ST1) (A5-SP1) + + TRANSDUCER

SH SH

24A (A2-TOUT) 30A


- - DPT1 - COMP1
T2S TOUT D1 DISCHARGE PRESSURE
25A 31A
TOUT/LWT TEMP. SENSOR (A6-DP1) + + TRANSDUCER

22B -
O1
T3S 23B
ST2
(A7-OP1) +
(A3-ST2)
SUCTION TEMP SENSOR COMP2
SH
SH
28B
26A - - SPT2 - COMP2
S2 SUCTION PRESSURE
T4S TIN (A8-SP2) +
29B + TRANSDUCER
27A (A4-TIN)
TIN/RWT TEMP. SENSOR JU1 JU2
TU1
TD1
30B
JUMPER & DIP SWITCH TL1 D2 - - DPT2 - COMP2
SELECTION ON MAIN BOARD
DISCHARGE PRESSURE
S1 (A9-DP2)+ 31B + TRANSDUCER
JU1 CLOSED USER INTERFACE BOARD
ON DIP
JU2 CLOSED On/Off * SH
TU1 CLOSED
TD1 CLOSED 1 2 3 4
TOUT=10C TIN=15C
SET MENU * O2 -
TL1 OPEN COOLING 75% X53
S1 1 2 3 4 ESC
SERIAL CABLE (A10-OP2) +
* X52
(DIP) GND
ON OFF OFF OFF

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

32
TYPICAL SCHEMATIC WIRING DIAGRAM
(PART WINDING START)
FIELD INTERFACE
LEGEND
UNIT EXTERNAL ENABLE/DISABLE
ATB
VFC
CBA THERMAL MAGNETIC CIRCUIT BREAKER AUXILIARY
1
COMP COMPRESSOR
ATB
2G
VFC FROM CLIENT CC COMPRESSOR CONTACTOR
CCA COMPRESSOR CONTACTOR AUXILIARY
COMPRESSOR EXTERNAL ENABLE/DISABLE CWP CHILLED WATER PUMP
ATB
1 VFC1
ATB
1 VFC2 ETB EARTH TERMINAL BLOCK
FLS FLOW SWITCH
ATB
ATB
A17 A18 FM FAN MOTOR
FMC FAN MOTOR CONTACTOR
VFC1 FOR COMPRESSOR 1 VFC2 FOR COMPRESSOR 2
VFC1 AND VFC2 FROM CLIENT
F FUSE
UNIT GENERAL ALARM HPS HIGH PRESSURE SWITCH
VFC
ATB
7A FACTORY WIRED
HGBS HOT GAS BYPASS SOLENOID
VFC UNLOADER TIMER DETAILS HVTB HIGH VOLTAGE TERMINAL BLOCK
FROM
MAIN
ATB
6A
TO CLIENT TIMER 11 JP JUMPER
BOARD CCAT11-1 AR11
3A
4AA 2 LPS LOW PRESSURE SWITCH
AR11-1 UL3-1
SECOND TEMPERATURE CONTROL SET POINT 3AA
UL3-1
MB MASTER BOARD
ATB
1 VFC
TIMER 21 NTB NEUTRAL TERMINAL BLOCK
CCAT21-1 AR21
3B
4BB OLR OVER LOAD RELAY
ATB VFC FROM CLIENT UL3-2
A16 AR21-1
3BB PT PRESSURE TRANSDUCER
UL3-2
P POTENTIAL BAND
SET POINT CORRECTION
ABOVE CONNECTION IS APPLICABLE ONLY FOR ZAC P/N 80062300.
SLE ECONOMIZER SOLENOID
ATB
RH1 4-20mA SET POINT = 180 SEC SB SLAVE BOARD
256
ANALOG SIGNAL
1 2 4 8 16 32 64 128 512 S1 CONTROL SWITCH
ATB ON
SSPS SOLID STATE PROTECTION SYSTEM
RH2 FROM CLIENT

TK FAN THERMAL CONTACT


MODBUS CONNECTION FOR 1 CHILLER (OPTIONAL) COMPRESSOR CONTACTOR CONNECTION FOR PART WIND START TMCB THERMAL MAGNETIC CIRCUIT BREAKER
CC1 CC2
12A 2 12B 2 TRANS TRANSFORMER
GND
- RS485 TO CLIENT CC1A-2 CC3 CC2A-2 CC4 TDS TIME DELAY SWITCH
TO MAIN + CONNECT GND 61A 61B
TS TEMPERATURE SENSOR
1 2 1 2
BOARD AT ONE END ONLY
RS485
(COM2)
FOR PART WIND START TIME DELAY SWITCH (TDS) (OPTIONAL) UL UNLOADER
CC1A-2 TDS1-1SEC CC3
1 61A 62A
2 UVM UNDER VOLTAGE MONITOR
CC2A-2
61B
TDS2-1SEC
62B
CC4 UVR UNDER VOLTAGE RELAY
BACNET CONNECTION FOR 1 CHILLER (OPTIONAL) 1 2
TERMINAL BLOCK
GND
** DISCHARGE TEMPERATURE SENSOR CONNECTION
- - - - - FIELD SUPPLY
TO MAIN
-
C1 D1 LEGEND ON MAIN BOARD
+ X7 DT1
BOARD
RS485
RS485 TO GATEWAY
T1 D1 DIGITAL INPUT 1
(COM2) CONNECT GND
AT ONE END ONLY
USE FOR OB1 EEVB ONLY
C/1C COMMON
C2 D2
X8 DT2 1O DIGITAL OUT 1
T2
DC DIGITAL COMMON
EEVB
T1 THERMISTOR 1
ECONOMIZER CONNECTION (WHEN AVAILABLE) SH SHIELD
IP TO 13A
ECO1 X52/X53 SERIAL COMMUNICATION PORT
CLIENT BMS TO MB (20) 2 ECONOMIZER 1
- GND PE POTENTIAL EARTH
+

13B ECO2
RS485
TO MB (50) 2 ECONOMIZER 2 JU/TU/TD/TL BOARD JUMPERS
BACNET GATEWAY 24VAC
HOT GAS BYPASS (OPTIONAL)
FROM CLIENT
MB

1 7C R7 HGBS 2
NOTES
SINGLE MAIN POWER ENTRY 7O 15
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
L1
ALL FIELD WIRING TO COMPLY WITH LOCAL CODES.
L2 MAIN POWER IF THE HGBS IS ENABLE COOLER HEATER TAPE WHEN REQUIRED MUST USE EXTERNAL DEVICE
TERMINAL # 1
2. FUSES TO DUAL ELEMENT TYPE.
L3 COOLER HEATER TAPE (OPTIONAL)
MB 3. USE COPPER CONDUCTORS ONLY.
HEATER
FIELD POWER
SUPPLY
1 7C R7 7O 15
2
4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
SEE NOTE #4 NTB TO BE PROVIDED BY END USER WITH RATING AS
SEE NOTE #7.
2 RECOMMENDED BY MANUFACTURER.
IF THE HGBS IS ENABLE COOLER HEATER TAPE WHEN REQUIRED MUST USE EXTERNAL DEVICE
5. POWER MUST BE SUPPLIED TO CRANKCASE
ETB/LUG
UVM CONNECTION JUMPER SETUP ON
MAIN BOARD
HEATER FOR MINIMUM OF 12 HOURS PRIOR TO
L1
TL2 OPEN
SYSTEM START UP.
L2
L3
TD2 CLOSED IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
DUAL MAIN POWER ENTRY NOTE:
TERMINAL A,B,& C TU2 CLOSED HEATER MUST BE ON FOR 12 HOURS BEFORE
UVR
1L1 ON UVM TO BE UVM
JU11 1-2 CLOSED
OPERATING THE SYSTEM.
PHASE MATCHED WITH
UNIT CONTROLS.
1L2 MAIN POWER 1A 1
JU13 1-2 CLOSED FAILURE TO FOLLOW THESE INSTRUCTIONS MAY
1L3
TERMINAL # 1 GROUND FAULT PROTECTION (OPTIONAL) RESULT IN COMPRESSOR DAMAGE.
JU15 1-2 CLOSED

COMP JU5 1-2 CLOSED


6. MARK IN THE BOX FOUND AT THE UPPER RIGHT OF
2 1
THE RESPECTIVE OPTIONAL ITEM, IF THE OPTIONAL
2L1 JU6 1-2 CLOSED
70A/B ITEM IS INCLUDED IN THE UNIT.
2L2 MAIN POWER 71A/B JU7 1-2 CLOSED
FIELD POWER
TERMINAL # 2 7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz
SUPPLY TI T2 A1 A2
SEE NOTE #4 2L3
Current Transformer EARTH FAULT RELAY
JU8 1-2 CLOSED POWER SUPPLY ONLY.
wire number, 70A/71A for 32 31 34
Comp 1 and 70B/71B for
JU9 1-2 CLOSED
Comp 2.
L JU4 1-2 CLOSED
CONTROL 32 31 A3/D3 (MB)
POWER 1 65A JU3 1-2 CLOSED
N Comp 1 REMOVE JP2A
TERMINAL # 3 EFR1 JU19 1-2 CLOSED
32 31
ETB/LUG A8/D8 (MB)
JU12 1-2 CLOSED
1 65A
Comp 2 REMOVE JP3A
EFR2 JU10 1-2 CLOSED

33
TYPICAL SEQUENCE OF OPERATION
Sequence of operation
The following describes the sequence of operation for a two screw compressor chiller unit.
Operation is similar for a one or four compressor unit.
For initial start-up, the following conditions must be met:
All power supplied to the unit shall be energized for 12 hours.
Control power switch on for at least 5 minutes.
All safety conditions satisfied.
Press ESC on the microcomputer keypad.
Chilled water pump running and chilled water flow switch contact closed.
Customer interlock contact closed, if any.

STAGE - ON SEQUENCE
Staging ON & OFF sequence, shall be accomplished by the Leaving water temperature control selection.

Stage #1:
If the Leaving Water Temperature is greater than the Stage 1- ON water temperature set point value, the Compressor #1
liquid line solenoid & slider control valves shall be switched ON. Now the compressor is in the minimum or unloaded
capacity. The compressor capacity is varied to achieve the full/part load capacity as per the load demand.

As discharge pressure of Compressor #1 rises, the corresponding fans are energize accordingly to the fan stage-ON set
point. If the discharge pressure falls below the fan stage-OFF set point value, the corresponding fans will turn off.

Stage #2:
If the Leaving Water Temperature is greater than the Stage 2- ON water temperature set point value, the Compressor #2
liquid line solenoid & slider control valves shall be switched ON. Now the compressor is in the minimum or unloaded
capacity. The compressor capacity is varied to achieve the full/part load capacity as per the load demand.

As discharge pressure of Compressor #2 rises, the corresponding fans are energize accordingly to the fan stage-ON set
point. If the discharge pressure falls below the fan stage-OFF set point value, the corresponding fans will turn off.

STAGE - OFF SEQUENCE


During the staging OFF, the first-in last-out sequence is adopted, if equalization of compressor timing is not selected.
Else the more used is switched off.

As the applied load decreases and when the leaving water temperature falls below the stage 2 -OFF water temperature
set point value, stage 2 is turned off.

If the leaving water temperature falls below the stage 1-OFF water temperature set point value, the stage 1 is turned off.

34
APPLICATION GUIDELINES
INTRODUCTION
These guidelines should be considered when designing systems and their installation utilizing Zamil ASY series liquid
chillers. Stable operation, performance and reliability of units is often dependent upon proper compliance with these
recommendations. When any application varies from these guidelines, it should be referred with Zamil Air Conditioners
for specific recommendations.

UNIT SELECTION/SIZING
Unit selection procedure and capacities are provided in this catalog for proper selection. The Zamil electronic selection
program may also be utilized for this purpose.
Over sizing chillers beyond a maximum limit of 5 10 % in order to assure adequate capacity or considering future
expansions is not recommended. Over sizing adversely affects the operating efficiency due to erratic system operation
and excessive compressor cycling which also results in reduced compressor life. It should be noted that, units operate
more efficiently when fully loaded rather than larger equipment operating at partial capacities. In addition, an oversized
unit is usually more costly to purchase, install and operate.
When over sizing is desired due to anticipation of future plant expansion, consider using multiple units. For example,
install a single chiller for the present load requirement and install a second chiller for the foreseen additional load demand
due to expansion. Further, it is also recommended that installing two chillers instead of a single chiller be considered in
applications where partial load operation at low capacities is necessary.
Operation of two chillers at higher loading is preferred to operating a single chiller at or near its minimum possible capacity.

FOULING FACTOR AND WATER REQUIREMENT


The tabulated performance data provided in this catalog are based on a fouling factor of 0.00010 hr-ft2-0F/Btu (0.000018 m2-0C/W).
As fouling factor is increased, unit capacity decreases and power input increases. For unit selection at other fouling factors, apply
appropriate correction factor from the table provided in this catalog.
These chillers are suitable for operation with well maintained water systems. Using unclean and untreated water may
result in scale and deposit formation causing reduced cooler efficiency or heat transfer and corrosion or pitting leading to
possible equipment damage. The more scale forming material and suspended solids in the system water, the greater the
chances of scale and deposit formation and fouling. These include calcium, magnesium, biological growth (algae, fungi
and bacteria), dirt, silt, clays, organic contaminants (oils), silica, etc. which should be kept to the minimum to retard scale
and deposit formation. In order to prevent corrosion and pitting, the pH value of the water flowing through the cooler must
be kept between 7 and 8.5. Zamil recommends that a water treatment specialist is consulted to provide and maintain
water treatment, this is particularly critical with glycol systems.

EFFECT OF ALTITUDE ON UNIT CAPACITY


The tabulated performance data provided in this catalog are for use at or near sea level altitude application. At altitudes
substantially above sea level, the decreased air density will reduce condenser capacity and therefore unit capacity. For unit
selection at these higher altitudes, apply appropriate correction factor from the table provided in this catalog.

HIGH AMBIENT CONSIDERATION


These chillers are designed for year round operation over a range of ambient temperatures. As a standard, these chillers
can start and operate satisfactorily up to 1300F (550C) ambient temperature at rated nominal voltage.

WATER FLOW RATES AND COOLER PRESSURE DROP


The maximum and minimum water flow rates for all unit models and the pressure drop chart are provided in this catalog.
The design water flow rate must be within this range. Design flow rates below the minimum limits will result in laminar
flow causing freeze-up problems, stratification and poor control and flow rates beyond the maximum limits cause exces-
sive pressure drop and severe tube erosion.
During unit operation, water flow rate must not vary more than 5% from the design flow rate. The water flow switch should be
calibrated accordingly. The piping and pumping layout should be right for the application and must assure proper water return
and circulation. When using glycol solution, flow rate and pressure drop are higher than with water, therefore care must be
taken not to exceed the limits. In such applications, consult Zamil Air Conditioners for specific recommendations.

35
COOLER FLUID (WATER OR GLYCOL) TEMPERATURES RANGE
Unit can start and pull down from 950F (350C) entering fluid temperature. The design leaving chilled fluid temperature
(LCWT) range as mentioned earlier in the tabulated performance data is 40 to 500F. The design entering chilled fluid
temperature range is 50 to 600F. The design cooler temperature drop (T) range is 5 to 150F.
The tabulated performance data provided in this catalog is based on a chilled water temperature drop of 100F. Units may
be operated at any desired temperature drop within the range of 5 to 150F as long as the temperature and flow limits are
not violated and appropriate correction factors are applied on the capacity and power input. The Zamil electronic selec-
tion program can be very handy in selecting equipment at different temperature drops.
It should be noted that temperature drop outside the aforesaid range is not permitted as it is beyond the optimum range of
control and could adversely affect the functioning of microprocessor controller and may also prove to be detrimental for the
equipment.

FLOW RATES AND/OR WATER TEMPERATURES OUT OF RANGE


Certain applications (particularly process cooling jobs) call for flow rates and/or water temperatures that are outside the
above mentioned limits/range. Our chillers can be utilized for these applications by selecting the chiller based on the
specific process load and making a suitable piping and mixing arrangement in order to bring the flow rates and/or water
temperatures relevant to the chiller within acceptable limits.
Example 1:
An application requires 240 GPM of water at 450F and the return water temperature is 650F.
A standard chiller can be used for this application as shown in the following basic schematic layout (single mixing arrange-
ment).
45F 45F
500 GPM 240 GPM

200 TR
Chiller 45F Load
260 GPM 200 TR

54.6F
500 GPM

65F
240 GPM
Example 2:
An application requires 192 GPM of water at 650F and the return water temperature is 800F.
A standard chiller can be used for this application as shown in the following basic schematic layout (dual mixing arrangement).

45F 45F 65F


340 GPM 82.2 GPM 192 GPM

120 TR
Chiller 80F Load
45F
257.8 GPM 109.8 GPM 120 TR
53.4F
340 GPM

53.4F 80F 80F


340 GPM 82.2 GPM 192 GPM

36
COOLER FREEZE PROTECTION
If the unit is located in an area where ambient temperatures fall below 320F (00C), cooler protection in the form of Ethylene
Glycol Solution is required to protect the cooler and fluid piping from low ambient freeze-up. This glycol solution must be
added to the water system loop to bring down the freezing point of water to a difference of 150F (8.30C) below minimum
operating ambient temperature.

Using this glycol solution causes a variation in unit performance, flow rate and pressure drop, therefore appropriate
correction factors from the aforementioned table in this catalog should be applied.

MULTIPLE CHILLER ARRANGEMENT OR PLANT CONFIGURATION


A multiple chiller system has two or more chillers connected by parallel or series piping to a common distribution system.
Multiple chiller arrangements offer the advantage of operational flexibility, standby capacity and less disruptive mainte-
nance. Also, they offer some standby capacity if repair work must be done on a chiller from a set of duty chillers. Starting
in-rush current is reduced, as well as power costs at partial-load conditions.

A multiple chiller arrangement should be provided if the system load is greater than a single chiller capacity, standby
capability is desired, large temperature drop (greater than 150F) is desired or application calls for splitting the total
capacity for better part load operation.

In designing a multiple chiller plant, units of same size should be preferred over different sizes to facilitate balanced water
flow. It is mandatory that cooler flow rates must be balanced to ensure proper flow to each chiller based on its respective
capacity. As mentioned above, two basic multiple chiller systems are used: parallel and series chilled water flow.

In the parallel arrangement, liquid to be chilled is divided among the liquid chillers; the multiple chilled streams are
combined again in a common line after chilling. Water temperatures (EWT or LWT) can be used to cycle units On and Off
based on the cooling demand. Parallel arrangements permit adding chillers in the future for plant expansion with the
appropriate considerations beforehand.

In the series arrangement, the chilled liquid pressure drop may be higher unless coolers with fewer liquid-side passes or
baffles are used. No over chilling by either unit is required, and compressor power consumption is lower than it is for the
parallel arrangement at partial loads. It is also possible to achieve higher overall entering to leaving temperature drops,
which may in turn provide the opportunity for lower chilled water design temperature, lower design flow and resulting
installation and operational cost savings. Series chiller arrangements can be controlled in several ways based on the
water temperatures depending on cooling demand.

A valved piping bypass is suggested around each chiller to facilitate future servicing as it gives the personnel an option
for service without a complete shutdown.

Zamil recommends the parallel arrangement for design temperature drops (T) up to 150F and the series arrangement
beyond that i.e., 16 to 200F. Complete design details on these parallel and series chilled water flow arrangements can be
found in the ASHRAE handbooks and other design literature which should be referred by the designer in preparing his
detailed designs.

PIPING ARRANGEMENTS AND PLANT LAYOUT


Our chillers are suitable for incorporating in Two Pipe single temperature systems or Four Pipe independent load
systems. The system piping circuit (load distribution circuit) should be basically parallel piping either Direct Return or
Reverse Return system with a good pumping arrangement.

The method of circuiting and pumping is a judgment decision by the designer. The designer must weigh the pros and
cons of cost, nature of load and configuration of building, energy economics, flexibility, installation requirements and
others to determine the best arrangement for his project. In all cases, it must be ensured that the design water flow is
constantly maintained through the chillers at all stages of operation. Some suggested arrangements with basic sche-
matic layouts are as follows:

37
A. Single or multiple chillers with constant water flow through chillers and load system:

CHWS

Chiller Load Load

3-Way 3-Way
Valve Valve

CHWR

Constant Speed Pump

In this type of arrangement, constant water flow through the chillers and load distribution piping circuit is maintained.
Before proceeding further, a brief explanation on the operation of a typical chilled water system / valves which is funda-
mental to the design or analysis of a system.

Where multiple zones of control are required, the various load devices are controlled first; then the source (chillers)
system capacity is controlled to follow the capacity requirement of the loads. Control valves are commonly used to control
loads. These valves control the capacity of each load by varying the amount of water flow through the load device.
Control valves for these applications are two-way (straight-through) and three-way valves. The effect of either valve is to
vary the amount of water flowing through the load device. With a two-way valve, as the valve strokes from full-open to full-
closed, the quantity of water flowing through the load gradually decreases from design flow to no flow. The three-way
mixing valve has the same effect on the load as the two way valve - as the load reduces, the quantity of water flowing
through the load decreases in proportion to the load and the difference amount is directed through a bypass.

In terms of load control, a two-way valve and a three-way valve perform identical functionsthey both vary the flow
through the load as the load changes. The fundamental difference between the two-way valve and the three-way valve is
that as the source or distribution system sees the load, the two-way valve provides a variable flow load response and the
three-way valve provides a constant flow load response.

Referring to the foregoing schematic layout, this is a conventional system and is not as energy efficient as the two-way
valve systems especially on the pumping side due to constant water circulation in the system. On multiple chiller instal-
lations, pumps are required to operate continuously and the sequencing of chillers is dependent on water temperatures.

38
B. Single or multiple chillers with constant water flow through chillers and variable water flow through load
system (primary/secondary pumping arrangement):
A CHWS

Variable
Speed Secondary Pump

Chiller Load Load

Flow Sensor
P

2-Way 2-Way
Valve Valve

Constant Speed
Primary Pump

B CHWR

System
Controller

This system is called a Primary Secondary System and in this arrangement, the generation zone is separated from the
transportation or distribution zone. In this type of arrangement also, constant water flow through the chillers is main-
tained, however the quantity of water flowing through the load distribution pump/piping system decreases in proportion to
the load and the difference amount is directed through a bypass pipe that connects the supply and return headers. This
bypass pipe forms a Hydraulic Coupling between the points A B and is also called as Common Bridge or Decoupling
Line. The sequence of operation is similar as the foregoing system with the following explanation:

The speed of the secondary chiller pump is controlled by the differential pressure sensor/transmitter, maintaining the
desired differential pressure (P) across the cooling coils, their control valves and the branch piping. This pump speed is
modulated within a broad range in order to reduce the pumping head and alter the water flow rate based on the changing
load conditions.

The primary pumps are constant speed pumps and the design flow rate through the chillers remains constant. Each
chiller-pump combination operates independently from the remaining chillers and each pump is shutdown when the
respective chiller is stopped. The sequencing of chillers is dependent on water flow. If greater flow is demanded than that
supplied by the chiller-pumps, return water is forced through the bypass into the supply header. This flow indicates a
need for additional chiller capacity and another chiller-pump starts. Excess bypass flow with reference to the set points in
the system controller in the opposite direction i.e., into the return header indicates overcapacity and the chiller-pumps are
turned off.

Energy is saved because the system head and water flow rate are reduced on the Secondary Pump when there are
partial cooling loads on the system and due to cycling of Primary Pumps.

Note: Some designers may consider installing constant speed pumps and utilize pressure relief bypass control valves
controlled by a differential pressure sensor/controller to maintain a fixed differential pressure between the supply and return
mains of the chilled water system in order to accommodate for the required chiller flow and to achieve some form of variable
volume system. This method is not recommended as its a wasteful practice because a considerable amount of energy is
lost, an almost constant volume system results and the pumping energy remains substantially that required at full system
flow and head.

Also, the problem with this system is improper control of the bypass valve which does not guarantee proper flow through the
chillers and high differential pressures in the control valves on the cooling coils when the system friction subsides at low
loads which can cause lifting of the valve stems or wire cutting of the valve seats. Further, as all the water must be pumped
at a head equal to or greater than the design head, the pump or pumps are forced to run up the pump head capacity curve,
which increases the overpressure on the system and also increases the wear on the pumps, since they are forced to
operate with high radial thrusts.

39
UNIT LOCATION AND INSTALLATION
These chillers are designed for outdoor installation and can be installed at ground level or on a suitable rooftop location.
In order to achieve good operation, performance and trouble-free service, it is essential that the proposed installation
location and subsequent installing procedures meet the following requirements:

The most important consideration while deciding upon the location of air cooled chillers is the provision for supply of
adequate ambient air to the condenser and removal of heated discharge air from the condenser. This is accomplished
by maintaining sufficient clearances which have been specified in this Catalog around the units and avoiding obstruc-
tions in the condenser air discharge area to prevent the possibility of warm air circulation. Further, the condenser fans are
propeller type and are not recommended for use with ductwork or other hindrances in the condenser air stream. Where
these requirements are not complied, the supply or discharge airflow restrictions or warm air recirculation will cause
higher condensing temperatures resulting in poor unit operation, higher power consumption and possible eventual failure
of equipment.

The units longitudinal axis should be parallel to the prevailing wind direction in order to ensure a balanced air flow through
the condenser coils. Consideration should also be given to the possibility of down-drafts caused by adjacent buildings,
which may cause recirculation or uneven unit airflow. For locations where significant cross winds are expected, an
enclosure of solid or louver type is recommended to prevent wind turbulence interfering with the unit airflow. When units
are installed in an enclosure, the enclosure height should not exceed the height of the unit.
The location should be selected for minimum sun exposure and away from hot air sources, steam, exhaust vents and
sources of airborne chemicals that could attack the condenser coils and steel parts of the unit. Avoid locations where the
sound output and air discharge from the units may be objectionable.
If the location is an area which is accessible to unauthorized persons, steps must be taken to prevent access to the unit
by means of a protective fence. This will help to prevent the possibility of vandalism, accidental damage or possible
harm caused by unauthorized removal of panels or protective guards exposing rotating or high voltage components.
The clearance requirements prescribed above are necessary to maintain good airflow and provide access for unit opera-
tion and maintenance. However, it is also necessary to consider access requirements based on practical considerations
for servicing, cleaning and replacing large components.
The unit must be installed on a ONE-PIECE, FLAT and LEVELLED {within 1/2'' (13 mm) over its length and width} /
CONCRETE BASE that extends fully to support the unit. The carrying or supporting structure should be capable of
handling complete operating weight of the unit as given in the Physical Data tables in this Catalog.
For ground level installations, it must be ensured that the concrete base is stable and does not settle or dislocate upon
installation of the unit which can strain the refrigerant lines resulting in leaks and may also cause compressor oil return
problems. It is recommended that the concrete slab is provided with appropriate footings. The slab should not be
connected to the main building foundation to avoid noise and vibration transmission.
For rooftop installations, choose a place with adequate structural strength to safely support the entire operating weight of
the unit. The unit shall be mounted on a concrete slab similar to ground installations. The roof must be reinforced for
supporting the individual point loads at the mounting isolator locations. It must be checked and ensured that the concrete
base is perfectly horizontal and levelled, especially if the roof has been pitched to aid in water removal. It should be
determined prior to installation if any special treatment is required to assure a levelled installation else it could lead to the
above mentioned problems.
Vibration isolators are necessary for installing these chillers in order to minimize the transmission of vibrations. The two
types of vibration isolators generally utilized for mounting these units are Neoprene Pads and Spring Isolators. Neoprene
Pads are recommended for ground level normal installations jobs where vibration isolation is not critical and job costs
must be kept to a minimum. Spring Isolators are recommended for ground level installations which are noise-sensitive
areas or exposed to wind loads and all roof top installations. For critical installations (extremely noise and vibration
sensitive areas), follow the recommendations of structural and acoustical consultants.
Based on the specific project requirements, choose the type of vibration isolators best suited for the application. Care-
fully select the vibration isolators models / configuration based on the respective point loads and place each mount in its
correct position following the Load Distribution Data and Mounting Drawings provided in this Catalog. Refer to the
Schematic Mounting Layout drawings provided in the IOM manual of these chillers for further details in this regard.

40
COOLER PIPING CONNECTIONS
The following pertinent guidelines are served to ensure satisfactory operation of the units. Failure to follow these recommenda-
tions may cause improper operation and loss of performance, damage to the unit and difficulty in servicing and maintenance:
Water piping must be connected correctly to the unit i.e., water must enter from the inlet connection on the cooler and
leave from the outlet connection.
A flow switch must be installed in the field piping at the outlet of the cooler (in horizontal piping) and wired back to the unit
control panel using shielded cable. There should be a straight run of piping of at least five pipe diameters on either side
of the flow switch. Paddle type flow switches can be obtained from Zamil which are supplied as optional items.
The chilled water pump(s) installed in the piping system should discharge directly into the unit cooler. The pump(s) may
be controlled external to the unit - but an interlock must be wired to the unit control panel (as shown in the wiring diagram)
so that the unit can start only upon proof of pump operation.
Flexible connections suitably selected for the fluid and pressure involved should be provided as mandatory in order to
minimize transmission of vibrations to the piping / building as some movement of the unit can be expected during normal
operation. The piping and fittings must be separately supported to prevent any loading on the cooler.
The cooler must be protected by a strainer, preferably of 20 mesh, fitted as close as possible to the liquid inlet connec-
tion, and provided with a means of local isolation.
Thermometer and pressure gauge connections should be provided on the inlet and outlet connections of each cooler.
Pressure gauges are recommended to check the water pressure before and after the cooler and to determine if any
variations occur in the cooler and system. When installing pressure taps to measure the amount of pressure drop across
the water side of the cooler, the taps should be located in the water piping a minimum of 24 inches downstream from any
connection (flange etc.) but as near to the cooler as possible.
Drain and air vent connections should be provided at all low and high points in the piping system to permit complete
drainage of the cooler and piping as well as to vent any air in the pipes. Hand shut-off valves are recommended for use
in all lines to facilitate servicing.
The system water piping must be flushed thoroughly before connecting to the unit cooler. The cooler must not be
exposed to flushing velocities or debris released during flushing. It is recommended that a suitably sized bypass and
valve arrangement is installed to allow flushing of the piping system. The bypass can be used during maintenance to
isolate the cooler without disrupting flow to other units.
The following is a suggested piping arrangement at the chiller for single unit installations. For multiple chiller installa-
tions, each unit should be piped as shown:

OUT

IN

Isolating Valve - Normally Open Pressure tapping

Isolating Valve - Normally Closed Flow Switch

Balancing Valve Connection (flanged / Victaulic)

Flow meter Pipe work

Strainer Flexible connection

Note: For chillers with two coolers, the connecting pipes for entering and leaving water on one cooler must be joined to
the corresponding pipes on the other cooler before connecting to the main headers in the system piping.

41
CHILLED FLUID VOLUME REQUIREMENT
The volume of water in a piping system loop is critical to the smooth and proper operation of a chilled water system. If
sufficient volume of water is not there in the system, the temperature control can be lost resulting in erratic system
operation and excessive compressor cycling. Therefore, to prevent this effect of a Short Water Loop ensure that total
volume of water in the piping system loop equals or exceeds 3 Gallons per Nominal Ton of cooling capacity for standard
air conditioning applications and 6 Gallons per Nominal Ton of cooling capacity for process cooling jobs where accuracy
is vital and applications requiring operation at very low ambient temperatures and low loading conditions.

For example, chiller model ASY100 operating with a design water flow rate of 205 GPM for a standard air conditioning
application would require 100 (Nom. Cap.) x 3 = 300 Gallons of water in the piping system loop.

To achieve the aforementioned water volume requirements, it may be necessary to install a tank in the piping system
loop to increase the volume of water in the system and therefore, reduce the rate of change of return water temperature.
This tank should be provided on the return water side to the chiller and the tank should be baffled to ensure that there is
no stratification and the entering stream thoroughly mixes with the tank water. See recommended tank design schemat-
ics below:

TANK SCHEMATIC

SUGGESTIONS ON SYSTEM DESIGN AND PIPING PRACTICES


The prospective chilled water system should be designed to the specific requirements of the owner and to achieve the
most efficient system possible. Following are some recommendations:
The first decision a designer of a chilled water system must make is the selection of the temperature differential.
Temperature differential is the difference between the supply water and the return water temperatures. There is no one
temperature difference for all chilled water systems. The actual temperature difference that is selected for a specific
installation is determined by the cost of the cooling coils for various temperature differences and the effect that higher
differences may have on the operating cost of the chillers. A careful balance between energy savings and first cost
should be made by the designer. These are the decisions that must be made by the designer for each application and
only experienced designers should entertain water temperature differences in excess of 120F on chilled water sys-
tems. A number of conditions must be recognized before making the final selection of temperature differential:
a) An increase in temperature differential decreases water flow and therefore saves pumping energy.
b) An increase in temperature differential may increase the cost of cooling coils that must operate with a higher mean
temperature difference.
c) Higher temperature differentials increase the possibilities of loss of temperature difference in coils due to dirt on the
air side and chemical deposits on the water side of them.
d) Laminar flow on the water side due to lower velocities at low loads on a coil is always a concern of the water system
designer. The possibility of laminar flow is greater with higher temperature differences. Laminar flow reduces the
heat-transfer rate and should not occur in a coil at any point in its load range. Many systems operate inefficiently
because of coils that were selected at too low a friction loss through them at design load; therefore, at reduced
loads and flows, they operate with laminar flow.

42
Control of Return Water Temperature: Return water temperature is one of the most important operating values for a
chilled water system. It tells the operator just how good a job the control system and coils are doing in converting
energy from the chillers to the air or water systems that are cooling the building. This is such a basic criterion that it
should be addressed early in the design of a chilled water system. The proper method of controlling return temperature
is through the correct selection of control valves and cooling coils. In conclusion, one of the designers most important
tasks is the selection of a sound temperature differential that will provide maximum possible system efficiency. The
second step in this process is to ensure that the differential is maintained after the system is commissioned.
The water system should be configured to distribute the water efficiently with a minimum use of energy-wasting
devices. These devices are listed here:
a) Three-way temperature control valves
b) Balancing valves, manual or automatic
c) Pressure-reducing or pressure-regulating valves
The piping should be designed without
a) Reducing flanges or threaded reducing couplings
b) Bullhead connections (e.g., two streams connected to the run connections of a tee with the discharge on the branch
of the tee)
The friction for the piping should be calculated for all pipe runs, fittings and valves.
Cooling coils should be selected with a high enough water velocity in the tubes to avoid laminar flow throughout the
normal load range imposed on the coils.
Coil control valves and their actuators should be sized to ensure that they can operate at all loads on the system
without lifting the valve head off the valve seat.
Expansion tank should be provided to so that water volume changes can be accommodated. Expansion tanks are
generally connected to the suction side of the pump - lowest pressure point.
Pumps in parallel must always operate at the same speed. There may be some exceptional cases where parallel
pumps are operated at different speeds, but only experienced designers should make evaluations for such a proposed
operation. Also, it is better to use pumps of the same size when operating them in parallel. Variable speed pumps
should be controlled so that pumps operating in parallel never have more than one percent difference in actual oper-
ating speed. Mixing of constant and variable speed pumps in parallel operation is wrong and leads to disastrous
results.
Distribution pumps should be selected for maximum efficiency at the design condition and within the economic con-
straints of the project. Distribution pumps should be added and subtracted to avoid operation of pumps at points of
high thrust and poor efficiency. Pump sequencing should achieve maximum possible system efficiency.
Differential pressure control (bypass) valves should never be installed at the pump discharges.
Check valves should be provided in pump discharges when pumps are operating in parallel. Pump discharge check
valves should be center guided, spring loaded, disc type check valves and should be sized so that the check valve is
full open at design flow rate. Generally this will require the check valve to be one pipe size smaller than the connecting
piping.
Circuiting Chilled water to Multiple Chillers : There are fundamentals for the circuiting of chillers that should not be
violated in order to achieve maximum efficiency. Some of these are:
a) Design the piping arrangement so that energy consumption of chillers is not increased.
b) Arrange the piping so that all chillers receive the same return water temperature.
c) Ensure that the required design water flow through the coolers is always maintained.

43
RIGGING INSTRUCTIONS
ATTENTION TO RIGGERS
Hook rigging sling thru holes in base rail, as shown below.
Holes in base rail are centered around the unit center of gravity.
Center of gravity is not unit center line.
Ensure center of gravity aligns with the main lifting point before lifting.
Use spreader bar when rigging, to prevent the slings from damaging the unit.
CAUTION
All panels should be in place when rigging.
Care must be taken to avoid damage to the coils during handling.
Insert packing material between coils & slings as necessary.
MODELS: ASY050B - ASY240B

MODELS: ASY250B - ASY310B &


ASY540B, ASY560B & ASY590B (2 MODULES)*

* Please refer to page-31 for the total unit dimensions of ASY540B, ASY560B & ASY590B
MODELS: ASY330B - ASY500B

44
INSTALLATION CLEARANCE

WALL

MODEL NUMBER A B
ASY050B - ASY080B 2500 2000
ASY090B - ASY310B 3000 2000 FIGURE - 1
ASY330B - ASY500B 3500 2500 STRAIGHT WALL
ASY540B - ASY590B 4500 3500

FIGURE - 2
CORNER WALL
NOTE: 1. All dimensions are in mm.
2. Pit installations are not recommended. Re-circulation of hot condenser air in combination with surface air
turbulence can not be predicted, hot air re-circulation will severely affect unit efficiency (EER) and can
cause high pressure or fan motor temperature trips.

45
MOUNTING LOCATION
MODELS: ASY050B - ASY080B

MODELS: ASY090B - ASY140B MODEL A


ASY090B 1249
ASY100B 1249
ASY120B 1858
ASY130B 1858
ASY140B 1858

MODELS: ASY150B - ASY240B MODEL A


ASY150B 1586
ASY160B 1586
ASY170B 1586
ASY180B 2094
ASY190B 2094
ASY200B 2094
ASY215B 2094
ASY230B 2094
ASY240B 2094

MODELS: ASY250B - ASY310B

MODELS: ASY330B - ASY500B

MODELS: ASY540B - ASY590B

MODULE - A MODULE - B

NOTE: All dimensions are in mm. Tolerance: 2mm.

46
LOAD DISTRIBUTION, kg. (ALUMINUM CONDENSER COIL)
MODEL No. R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14 R15 R16 R17 R18 R19 R20
ASY050 518 491 462 444 - - - - - - - - - - - - - - - -
ASY060 671 632 571 541 - - - - - - - - - - - - - - - -
ASY070 702 663 600 569 - - - - - - - - - - - - - - - -
ASY080 705 669 604 573 - - - - - - - - - - - - - - - -
ASY090 625 594 578 540 509 493 - - - - - - - - - - - - - -
ASY100 628 597 581 542 510 495 - - - - - - - - - - - - - -
ASY120 848 817 801 687 655 640 - - - - - - - - - - - - - -
ASY130 872 841 825 708 677 661 - - - - - - - - - - - - - -
ASY140 878 847 831 711 680 664 - - - - - - - - - - - - - -
ASY150 729 701 692 683 627 600 590 581 - - - - - - - - - - - -
ASY160 730 702 693 684 628 600 591 582 - - - - - - - - - - - -
ASY170 749 722 713 703 645 617 608 599 - - - - - - - - - - - -
ASY180 964 930 918 907 788 753 742 730 - - - - - - - - - - - -
ASY190 981 946 935 923 801 767 756 744 - - - - - - - - - - - -
ASY200 989 954 943 931 808 774 763 751 - - - - - - - - - - - -
ASY215 1011 977 966 954 835 801 789 778 - - - - - - - - - - - -
ASY230 1032 998 986 975 862 827 816 804 - - - - - - - - - - - -
ASY240 1037 1003 991 980 864 830 818 807 - - - - - - - - - - - -
ASY250 1035 1001 984 978 972 843 809 791 786 780 - - - - - - - - - -
ASY270 1083 1048 1031 1025 1020 924 889 872 866 861 - - - - - - - - - -
ASY295 1107 1073 1056 1050 1044 946 912 894 889 883 - - - - - - - - - -
ASY310 1112 1077 1060 1054 1048 948 914 897 891 885 - - - - - - - - - -
ASY330 991 973 964 955 945 941 936 821 803 794 785 776 771 766 - - - - - -
ASY350 1070 1052 1043 1033 1024 1020 1015 865 847 838 829 820 815 810 - - - - - -
ASY375 1079 1061 1051 1042 1033 1028 1024 872 854 844 835 826 822 817 - - - - - -
ASY400 1099 1079 1069 1059 1049 1044 1039 891 871 861 851 841 836 831 - - - - - -
ASY420 1114 1094 1084 1074 1064 1059 1054 905 885 875 865 855 850 845 - - - - - -
ASY450 1150 1130 1120 1110 1100 1095 1090 961 941 931 921 911 906 901 - - - - - -
ASY475 1157 1137 1127 1117 1107 1102 1097 965 945 935 925 915 910 905 - - - - - -
ASY500 1162 1142 1132 1122 1112 1107 1102 967 947 937 927 917 912 907 - - - - - -
ASY540 1107 1066 1045 1038 1031 943 902 881 874 867 1031 1038 1045 1066 1107 867 874 881 902 943
ASY560 1112 1071 1050 1043 1036 945 904 884 877 870 1036 1043 1050 1071 1112 870 877 884 904 945
ASY590 1116 1075 1054 1047 1041 948 906 886 879 872 1041 1047 1054 1075 1116 872 879 886 906 948

R1 R2 R1

R3 R4 R6

47
LOAD DISTRIBUTION, kg. (COPPER CONDENSER COIL, 12FPI)
MODEL No. R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14 R15 R16 R17 R18 R19 R20
ASY050 549 523 492 475 - - - - - - - - - - - - - - - -
ASY060 719 680 619 587 - - - - - - - - - - - - - - - -
ASY070 772 733 669 637 - - - - - - - - - - - - - - - -
ASY080 775 738 672 641 - - - - - - - - - - - - - - - -
ASY090 679 647 632 594 562 546 - - - - - - - - - - - - - -
ASY100 682 650 634 595 564 548 - - - - - - - - - - - - - -
ASY120 899 868 852 738 707 691 - - - - - - - - - - - - - -
ASY130 947 915 900 783 751 736 - - - - - - - - - - - - - -
ASY140 953 921 906 786 754 738 - - - - - - - - - - - - - -
ASY150 777 750 740 731 675 648 639 629 - - - - - - - - - - - -
ASY160 778 750 741 732 676 648 639 630 - - - - - - - - - - - -
ASY170 819 792 782 773 714 687 678 669 - - - - - - - - - - - -
ASY180 1022 988 976 965 845 811 799 788 - - - - - - - - - - - -
ASY190 1056 1021 1010 998 877 842 831 819 - - - - - - - - - - - -
ASY200 1072 1038 1027 1015 892 858 846 835 - - - - - - - - - - - -
ASY215 1097 1063 1051 1040 921 886 875 863 - - - - - - - - - - - -
ASY230 1128 1093 1082 1070 957 923 911 900 - - - - - - - - - - - -
ASY240 1133 1098 1087 1076 960 926 914 903 - - - - - - - - - - - -
ASY250 1102 1068 1051 1045 1039 910 876 858 853 847 - - - - - - - - - -
ASY270 1150 1115 1098 1092 1087 991 956 939 933 928 - - - - - - - - - -
ASY295 1204 1170 1153 1147 1141 1043 1009 991 986 980 - - - - - - - - - -
ASY310 1209 1174 1157 1151 1146 1045 1011 994 988 982 - - - - - - - - - -
ASY330 1078 1059 1050 1041 1032 1027 1023 908 890 881 871 862 858 853 - - - - - -
ASY350 1168 1150 1141 1132 1122 1118 1113 963 945 936 927 918 913 908 - - - - - -
ASY375 1177 1159 1149 1140 1131 1127 1122 970 952 943 933 924 920 915 - - - - - -
ASY400 1181 1161 1151 1141 1131 1126 1121 973 953 943 933 923 918 913 - - - - - -
ASY420 1215 1195 1185 1175 1165 1160 1155 1006 986 976 966 956 951 946 - - - - - -
ASY450 1268 1248 1238 1228 1218 1213 1208 1080 1060 1050 1040 1030 1025 1020 - - - - - -
ASY475 1276 1256 1246 1236 1226 1221 1216 1083 1063 1053 1043 1033 1028 1023 - - - - - -
ASY500 1280 1260 1250 1240 1230 1225 1220 1086 1066 1056 1046 1036 1031 1026 - - - - - -
ASY540 1204 1163 1142 1135 1129 1040 999 978 971 964 1129 1135 1142 1163 1204 964 971 978 999 1040
ASY560 1209 1168 1147 1140 1133 1042 1001 981 974 967 1133 1140 1147 1168 1209 967 974 981 1001 1042
ASY590 1213 1172 1151 1144 1138 1045 1003 983 976 969 1138 1144 1151 1172 1213 969 976 983 1003 1045

R1 R2 R1

R3 R4 R6

48