Documente Academic
Documente Profesional
Documente Cultură
Faculty of Engineering
Electrical Power and Machine Department
Electrical Substation
Protection and Sizing
Under Supervision of
Prof.Ass.Saady Abd-El Hameed
Electrical Substation
Protection and Sizing
Under Supervision of
Prof.Ass.Saady abd-el Hameed
Group2014 | Confidential
Chapter 1 Introduction to Substation
Substation definition
An electrical sub-stations an assemblage of electrical
components including bus-bars, switchgear, power
transformers, auxiliaries etc. substation is a part of an
electrical generation, transmission, and distribution system.
Substations transform voltage from high to low, or the
reverse, or perform any of several other important
functions. Electric power may flow through several
substations between generating plant and consumer, and
its voltage may change in several steps.
Briefly, Sub-stations are integral parts of a power system
and form important links between the generating station,
transmission systems, distribution systems and the load
points.
Functions of Substations
Substations serve the following functions;
Substations serve as sources of energy supply for
the local areas of distribution in which these are
located
Power Transfer
in power
Connected CT Line
to control Operated by
CB Line
and protection control and
system. protection
Local and system
remote
VT
SA
Transformers
with tap changers
Shunt Shunt
reactor capacitor
Types of substation
One of the substations of the new 1,500 kilometer HVDC transmission line in
China
2-1-transformer substations
They are known as transformer substations as because
transformer is the main component employed to change the
voltage level, depending upon the purposed served
.transformer substations may be classified into:
2-1-1STEP UP SUBSTATION
Associated with generating station as the generating
voltage is low, the generation voltage is steeped up to high
voltage to affect economy in transmission of electric
power. These are generally located in the power houses
and are of outdoor type.
2-1-2 Step Down Substation
Uses a transformer to convert high voltage to lower levels,
although the voltages in step down substations are lower
than at a power plant, the levels at this stage are still much
too high to be used directly by consumers, Some industrial
factory installations are able to use these high voltages,
and can tap directly into power from a step down
substation without needing additional substations.
Air
AIS
1. Bus bar
2. Disconnector
3. Maintenance Earthing Switch
4. Current Transformer
5. Circuit Breaker
6. Current Transformer
7. Maintenance Earthing Switch
8. Disconnector
9. Earthing Switch
10. Voltage Transformer
11. Bushing
Switchyard
Control & Protection House
Includes:
1. AC/DC room
2. Battery room
3. Telecom room
4. Control & protection room
Main Office Building:
Administrative Building.
Conference Room - etc.
Switch Yard
It is the field where components used in controlling
supply and measuring supply (incoming and outgoing)
are placed.
Switchyards generally have Breakers, Isolators , CTs
,PTs , Bus bars, protection and control equipment,
transformers ,grounding wires and switches, disconnects
and metering devices, etc.
Ac/Dc Board
It provides ac supply for station (for lighting & heater
&sockets) and provides DC supply which is the more
important than A.C. supply as it feed the relays.
NOTE
That the digital relays become blind (useless) if D.C
drops so D.C supervision relay is used to check D.C
continuity.
Battery Room
In normal operation:
The battery supply intermittent medium-rate and momentary
high-rate loads, such as trip coils and dc motors of C.B. &
Disconnectors.
When we lost D.C. supply or failure of charger , the battery
Supply D.C. for all loads for hours i.e. 8 hours then it needs
re-charging
Aux transformer
Protection panels
Contain protective relays that are very essential part of the
substation, that is capable of detecting faults and isolating
them selectively and quickly from the network as a whole,
so that the consequences of the fault are limited as much
as possible.
Remote control
Alarm system:
Substation operator must be informed by:
1. Switchgear status.
2. Switchgear settings.
3. Faults.
Alarm Annunciate Panels are widely used as a central
indicator of status of equipment or systems in an aircraft,
industrial process, building and installation. These Alarm
Annunciate devices provide a visual indication of a
number of electric circuits
Telecom room
Like SCADA system in the station which take signal from
protection panel.
Supervisory control refers to equipment that allows for
remote control of a substation's functions from a system
control center or other point of control. Supervisory
control can be used to:
substation equipment.
Supervisory control room
Contents
1- Overview
2- Instrument Transformers
3- Disconnecting Switches
4- Circuit Breaker
IP = n IS
2.2.1.1 Operation
Like any other transformer, a current transformer has a
primary winding, a magnetic core and a secondary winding.
The alternating current in the primary produces an alternating
magnetic field in the core, which then induces an alternating
current in the secondary winding circuit.
2.2.1.2 Construction
Reference values for rated output are 2.5, 5, 7.5, 10, 15, 30
and up to 200 VA.
Main Differences
1 - Accuracy Class:
Metering CTs require high accuracy at rated full load current.
Protection CTs don't have to be with high accuracy.
2 - Difference in Operating Conditions:
Protection CTs will have to carry the fault currents which may
reach to 10 and 20 times the normal full load current. So it is
designed at much bellow the saturation point (knee) in order to
avoid saturation.
Metering CTs used for metering will have to carry only full load
current. So it is designed near to knee point
General Features:
Dry Type Insulation Maintenance Free
Metering accuracy class: 0.2, 0.2S, 0.5, 0.5S
Protection accuracy class: 5P, 10P, TPY
Easy Operation and Maintenance
No risk of explosion - protect your people and equipment
Excellent Seismic Performance
Lighter than conventional technologies
No risk of toxic leakage - environmentally friendly
No Oil Filling, No Gas Filling and No ceramic
Silicone Rubber Outer Insulation
Dramatic Weight Reduction Compared to Porcelain or Glass
Insulators
Can be used at Temperatures Ranging From -40C to Over
+100C
Application
Outdoor bushing current transformers are used for relaying
on existing Power Transformers, Bulk Oil Circuit Breakers and
other Dead Tank Circuit Breakers.
General Features:
Weather proof outdoor terminal box
Stainless steel or aluminum, nameplate
Weather resistant Easy installed
High mechanical impact and dielectric strength
Clearly identified secondary terminals
Ratios may be single-ratios, dual-ratio, or multi-ratios
This design can be manufactured to customer specified size
and electrical rating
The core and coils are all completely encapsulated in
polyurethane which Provide excellent electrical, physical
and chemical protection for Outdoor Installation
Corrosion resistant outdoor termination box
2.3.1.2 Construction
Secondary low voltage winding has few turns wound over the
magnetic core and the primary high voltage winding is
comprised of several turns wound over the secondary
winding.
Tank made from galvanized steel filled with oil contains the
magnetic core wound with primary and secondary windings of
VT.
In a voltage transformer the core size is comparatively large so
that a low flux is maintained at operating point.
Where
Kn is the rated transformation ratio;
Vp is the actual primary voltage;
Vs is the actual secondary voltage.
2.3.1.2.4 Construction
Due to their rotating blade design which pivots about its long
axis, vertical break switches are excellent for application in
environments which experience formation large amount of ice.
Southern States - Whip Type Arcing Horns Increase the Speed of Contact
Separation during the Opening of Switch
Coelme Egic - Vertical Break Disconnector - Model SLOB - Rating 72.5 - 550kV -
Open Position
| Electric Substation Protection and Sizing 70
Chapter 2 Elements of High Voltage Substation
Operating Technique
There are 2 Models available for double end break switch:
Central Arm moves only perpendicularly to the plane of the
insulators up to direct engagement of the moving contacts
into the fixed ones happened.
Central Arm upon completing its movement perpendicularly
to the plane of the insulators, it rotates around its own
longitudinal axis leading to complete engagement and
locking of the moving contacts into the fixed ones.
ITG LLC - Reliable Energy Solutions - 72.5-300kV Disconnecting Switch - Close Position
Sieyuan - Rated Voltage 72.5 - 550kV - High Short Circuit Carrying Capacity Up to 63kA -
Close Position
Liaoning Mec - Model GW4 - Ratings 40.5 - 252 kV / Current 630 - 3150 A - Open Position
A Pair of Double End Break Vee Switches in Closed Position Feeding a Circuit Breaker
Southern States - Center Rotate Switch - Ratings 121 - 362 kV / 1200 - 4000 Amps
Center break Vee switches have all the same features and
characteristics that center break switches have but with one
additional feature which is space saving advantage, producing
one of the most compact disconnect switch installation
possible.
Sieyuan - Rating 40.5 - 126kV / Short Circuit Carrying Capacity 40kA - Close Position
Southern States - Ratings 15.5 - 242 kV / 1200 - 3000 Amps - Close Position
Coelme Egic - Model CBVD - Rating 72.5-170 kV - Earthing Switch Shown - Open Position
Single side break switch enjoys the same economic advantage that
center break and center break Vee switches do. Moreover it just
require only six insulators versus nine insulators required for vertical
`
Cleaveland Price - Model RL-C - Ratings 7.2-69kV / 600-2000A - Close Position - Horizontal Mounted
Southern States - Model ES-1 - Ratings 115kV / 1200A - Close Position - Horizontal Mounted
7- Pantograph Type
Pantograph disconnector consists of two half-arms which
move in a coordinated way vertically on the plane of the
insulators to close the circuit on a fixed contact connected the
upper Busbar.
Pantograph disconnectors are an ideal solution for
connection to Busbar systems, since they allow minimizing
the substation area and ensure free maintenance.
1 -Scissors Arms
2 -Bearing Frame
3 -Support Insulator
4 -Rotating Insulator
5 -Motor Operating Mechanism
Since the movement of the arm takes place on the same plane
as that of the insulators, the phase-to-phase spacing is
minimized.
Siemens - SF6 Insulated - Rating 400kV Outdoor High Voltage Circuit Breaker
Western Electrical Services - High Voltage Circuit Breaker Contacts and Cluster
Zensol - Make Break Contacts in Power Circuit Breakers in Close and Open Positions
2.4.1 Construction
High Voltage Circuit Breakers are mounted on support
structures made of Aluminum.
The part of circuit breaker connected in one phase is called
pole while the circuit breaker that suitable for three phase
system is called triple-pole circuit breaker.
This design is simple and robust (), with few moving parts
and a vibration-isolated latch system of the highest reliability.
All components of the operating mechanism, the control and
monitoring equipment and all terminal blocks are arranged in a
compact and convenient way in one cabinet.
2.4.4.1 Precaution
A tripped circuit-breaker often indicates that fault has
occurred somewhere down the line from the panel. The fault
must usually be isolated before switching the power on, or an
arc flash can easily be generated.
If the voltage is high enough, and the wires leading to the fault
are large enough to allow a substantial amount of current, an
arc flash can form within the panel when the switch is turned
on
Operation Mechanism
Siemens - Model 3AP1FG - Rating 145KV SF6 Live Tank Circuit Breaker
2.5 Transformer
2.5.1. Introduction
Fig(2.5.1)
The more current that flows, the stronger is the magnetic field.
stronger magnetic field can be produced by winding the wire
into a coil.
Fig (2.5.2)
Fig (2.5.3)
The electrical current flowing in a transformer is alternating
current. The current flows first in one direction, stops, then
reverses and flows in the other direction, as shown in
fig(2.5.4). The magnetic field around the winding is constantly
in motion.
Fig(2.5.4)
Fig (2.5.5)
Fig (2.5.6)
= (. . )
= (. . )
= (. . )
= (. . )
2.5.4.3. Polarity:
A dot convention is often used in transformer circuit
diagrams, nameplates or terminal markings to define the
relative polarity of transformer windings. Positively-increasing
instantaneous current entering the primary winding's dot end
induces positive polarity voltage at the secondary winding's
dot end.
b.Leakage flux:
The ideal transformer model assumes that all flux generated
by the primary winding links all the turns of every winding,
including itself.
Fig (2.5.9)
c. Equivalent circuit:
Fig (2.5.10)
Fig (2.5.11)
2.5.6. Construction:
2.5.6.1. Cores :
a. Laminated steel cores:
The effect of laminations is to confine eddy currents to
highly elliptical paths that enclose little flux, and so
reduce their magnitude. Thinner laminations reduce
losses, but are more laborious and expensive to
construct.
Thin laminations are generally used on high-frequency
transformers, with some of very thin steel laminations
able to operate up to 10 kHz.
Laminated steel cores are shown in figures (2.5.12) &
(2.5.13).
b. Solid cores:
Powdered iron cores are used in circuits such as
switch-mode power supplies that operate above mains
frequencies and up to a few tens of kilohertz.
These materials combine high magnetic permeability
with high bulk electrical resistivity.
c. Toroidal cores:
Toroidal transformers are built around a ring-shaped
core, which, depending on operating frequency, is
made from a long strip of silicon
steel or permalloy wound into a coil, powdered iron,
or ferrite.
A strip construction ensures that the grain
boundaries are optimally aligned, improving the
transformer's efficiency by reducing the
core's reluctance.
The cross-section of the ring is usually square or
rectangular, but more expensive cores with circular
cross-sections are also available.
The primary and secondary coils are often wound
concentrically to cover the entire surface of the core.
Toroidal core is shown in figure (2.5.14).
Fig (2.5.14)
d. Air cores :
A physical core is not an absolute requisite and a
functioning transformer can be produced simply by
placing the windings near each other, an arrangement
termed an 'air-core' transformer.
The air which comprises the magnetic circuit is
essentially lossless, and so an air-core transformer
eliminates loss due to hysteresis in the core material.
The leakage inductance is inevitably high, resulting in
very poor regulation, and so such designs are
unsuitable for use in power distribution.
2.5.6.2. Windings :
The conducting material used for the windings
depends upon the application, but in all cases the
individual turns must be electrically insulated from
each other to ensure that the current travels
throughout every turn.
For small power and signal transformers, in which
currents are low and the potential difference between
adjacent turns is small, the coils are often wound
from enamelled magnet wire.
Larger power transformers operating at high voltages
may be wound with copper rectangular strip
conductors insulated by oil-impregnated paper and
blocks of pressboard.
High-frequency transformers operating in the tens to
hundreds of kilohertz often have windings made of
braided Litz wire to minimize the skin-effect and
proximity effect losses.
Large power transformers use multiple-stranded
conductors as well, since even at low power
frequencies non-uniform distribution of current would
otherwise exist in high-current windings. Each strand
is individually insulated, and the strands are arranged
so that at certain points in the winding, or throughout
the whole winding, each portion occupies different
relative positions in the complete conductor.
Fig(2.5.15)
2.5.7. Cooling:
To place the cooling problem in perspective, the
accepted rule of thumb is that the life expectancy of
insulation in all electric machines including all
transformers is halved for about every 7 C to 10 C
increase in operating temperature, this life expectancy
halving rule holding more narrowly when the increase
is between about 7 C to 8 C in the case of transformer
winding cellulose insulation.
b.ONAF cooling:
Heat dissipation can obviously be increased, if
dissipating surface is increased but it can be make
further faster by applying forced air flow on that
dissipating surface. Fans blowing air on cooling
surface is employed. Forced air takes away the heat
from the surface of radiator and provides better
cooling than natural air. The full form of ONAF is
"Oil Natural Air Forced". As the heat dissipation rate
is faster and more in ONAF transformer cooling
method than ONAN cooling system, electrical power
transformer an be put into more load without
crossing the permissible temperature limits.
c. OFAF cooling:
In oil forced air natural cooling system of
transformer, the heat dissipation is accelerated by
using forced air on the dissipating surface but
circulation of the hot oil in transformer tank is
natural convectional flow. The heat dissipation rate
can be still increased further if this oil circulation is
accelerated by applying some force. In OFAF
cooling system the oil is forced to circulate within
the closed loop of transformer tank by means of oil
pumps. OFAF means "Oil Forced Air Forced"
cooling methods of transformer. The main
advantage of this system is that it is compact
system and for same cooling capacity OFAF
occupies much less space than farmer two systems
of transformer cooling. Actually in oil natural
cooling system, the heat comes out from
conducting part of the transformer is displaced from
its position, in slower rate due to convectional flow
of oil but in forced oil cooling system the heat is
displaced from its origin as soon as it comes out in
the oil, hence rate of cooling becomes faster.
d.OFWF cooling:
We know that ambient temperature of water is much
less than the atmospheric air in same weather
condition. So water may be used as better heat
exchanger media than air. In OFWF cooling system
of transformer, the hot oil is sent to a oil to water
heat exchanger by means of oil pump and there the
oil is cooled by applying sewers of cold water on
the heat exchanger's oil pipes. OFWF means "Oil
Forced Water Forced" cooling in transformer.
e. ODAF cooling:
ODAF or oil directed air forced cooling of
transformer can be considered as the improved
version of OFAF. Here forced circulation of oil
directed to flow through predetermined paths in
transformer winding. The cool oil entering the
transformer tank from cooler or radiator is passed
through the winding where gaps for oil flow or pre-
decided oil flowing paths between insulated
conductor are provided for ensuring faster rate of
heat transfer. ODAF or oil directed air forced
cooling of transformer is generally used in very high
rating transformer.
f. ODWF cooling:
ODAF or oil directed water forced cooling of
transformer is just like ODAF only difference is that
here the hot oil is cooled in cooler by means of
forced water instead of air. Both of these
transformer cooling methods are called forced
directed oil cooling of transformer.
Fig (2.5.16)
Fig (2.5.17)
Fig (2.5.18)
Fig (2.5.19)
. With two buses and a bus tie available, there is some ease in
doing maintenance, but maintenance on line breakers and
switches would still require outside the substation switching
to avoid outages
2.6.5-Ring Bus
2.6.6- Breaker-and-a-Half:
the capacitor is
A device for storing electric charge. It comprises of two electrodes
separated by an
insulation medium called the dielectric.
Capacitor Application
Capacitors provide tremendous benefits to distribution system
performance.
Most noticeably, capacitors reduce losses, free up capacity,
and reduce voltage drop:
Losses; Capacity
By canceling the reactive power to motors and other loads with low
power factor, capacitors decrease the line current.
Reduced current frees up capacity; the same circuit can serve more
load. Reduced current also significantly lowers the I2R Line losses.
Voltage drop
Capacitors provide a voltage boost, which cancels
part of the drop caused by system loads. Switched capacitors can
regulate voltage on a circuit.
2) Location Considerations
A lightning
arrester is a
device used on
electrical power
systems and
telecommunicati
ons systems to
protect the
insulation and
conductors of
the system from
the damaging
effects of
lightning
The typical
lightning arrester
has a High-voltage
terminal and a
ground terminal.
When a lightning
surge travels along
the power line to
the arrester, the
current from the
surge is diverted
through the
arrestor, in most
cases to earth.
1- Rod arrester.
2- Horn gap arrester.
3- Multi gap arrester.
4- Expulsion type lightning arrester.
5- Valve type lightning arrester.
Configuring MO Arresters
In order to configure an MO arrester, it is first of all necessary
to understand how the different requirements and parameters
affect the operational performance of the arrester.
With knowledge of the basic principles and interdependencies
- MO diameter: 40* mm
- 10 kA/Ur = 2.65* (This factor is characteristic for the MO
resistor used when
configuring it for the line discharge class 1.)
The resulting protective characteristics*:
- lightning impulse protective level (10 kA, 8/20 ms): 159 kV
- switching impulse protective level (0,5 kA, 30/60 ms): 122
kV
- steep current impulse protective level (10 kA, 1/<20 ms):
169 kV
62 CONFIGURING MO ARRESTERS
Checking the protective values:
- LIWV/10 kA, 8/20 s = 325 kV/159 kV = 2.04 definitely
sufficient
Height of the MO resistor column:
- hMO = 400* mm
Selecting a Housing
Minimal requirements:
- lightning impulse withstand voltage =
1.3 . lightning impulse protective level = 1.3 . 159 kV = 207 kV
- power-frequency withstand voltage 1 min, wet =
1.06/ 2 . switching impulse protective level = 1.06/ 2 . 122 kV =
92 kV
- creepage distance: 16 mm/kV . 72.5 kV (27.7 mm/kV 41.9 kV)
= 1160 mm
- permissible head load static (SLL): 350 N
- permissible head load dynamic (SSL): 500 N
- rated short-circuit current (rated short-circuit (withstand)
current Is): 20 kA
- possible length of the active part: 400 mm
- number of units: 1
- grading ring: no
IEC arrester standards:
| Electric Substation Protection and Sizing 194
Chapter 2 Elements of High Voltage Substation
2.9.1 Definition
GIS is a substation that uses a superior dielectric gas,
sulfur hexafluoride (SF6) for insulation high-voltage
gas-insulated substations have been in service since
the early 1960s. Operation of 800 kV equipment have
proved successful
EXAMPLE:
A typical space (420/525) kV SF6 GIS requires only
920m2 site area against 30000 m2 for a conventional air
insulated substation
2. Reliable:
The complete enclosure of all live parts guards against any
impairment of the insulation system.
2.9.7.1Switchgear Definition
A sitchgear is a general term that covering switching devices
and their combination with associated control, measuring,
protective and regulating equipment, also assemblies of such
devices and equipment with associated inter
connections,accessories, enclosures and supporting
structures, intended in principle for use in connection with
generation, transmission, distribution and conversion of
electric energy,
A switchgear installation contains all the apparatus and
auxiliary equipment necessary to ensure reliable operation of
the installation and a secure supply of electricity.
Three phase AC High-voltage switchgear installations with
operating voltages of up to 800 kV are used for distributing
electricity in towns and cities , regions ,industrial centers, and
also for power transmission.
1- Circuit Breaker
2-Disconnector switch
3- Earthing switch
4-Instruement transformer
a- current transformer
b- voltage transformer
5- cable connection
6- Transformer connection
1- Circuit Breaker:
are mechanical switching devices able to make, carry and
interrupt currents occurring in the circuit under normal
conditions, and can make, carry for a specified time and break
currents occurring in the circuit (e.g. short circuit) under
specified abnormal conditions.
A circuit breaker is an automatically-operated electrical switch
designed to protect an electrical from damage caused by
overload or short circuit.
Its basic function is to detect a fault condition and, by
interrupting continuity, to immediately discontinue electrical
flow.\
Unlike a fuse, which operates once and then has to be
replaced, a circuit breaker can be reset (either manually or
automatically) to resume normal operation
2- Disconnector Switch:
are used for galvanic isolation of networks or sections of
switchgear installations.
As an independent air-insulated device, they form a visible
isolating distance in their open position.
They are suitable for switching small currents ( 0.5A) or also
larger currents if the voltage does not change significantly
between the contacts of a disconnector pole during switching
(commutation currents).
Disconnectors have a moving contact that opens or closes a
gap between stationary contacts when activated by an
insulating operating rod that is itself moved by a sealed shaft
coming through the enclosure wall, the Figure 3.2 shows a
disconnector with its main parts.
The stationary contacts have shields that provide the
appropriate electric field distribution to avoid too high a
surface stress.
The moving contact velocity is relatively low compared to a
circuit breaker moving contact,
And the disconnector can interrupt only low levels of
capacitive current (e.g. disconnecting a section of GIS bus) or
small inductive currents (e.g. transformer magnetizing
current).
3-Earthing switches:
are used for earthing and short-circuiting de-energized station
components
Earthing switches can withstand currents during a specified
time (1s, 3s) under abnormal conditions, such as a short
circuit,
But they are not required to carry continuous operating
currents.
In general, earthing switches are combined with the adjacent
disconnectors to form one unit.
However, earthing switches can also be installed separately.
The earthing switches can be adapted to diverse components,
and according to the layout and the buyer specifications, can
be mounted in any point of the installation, as maintenance
earthing switches or as fast-closing earthing switches.
Locking bolts provided with padlocks or similar devices
ensure the locking in the desired position.
4-Instrument transformers
Their function is to transform high voltages and currents to
values that can be unified or measured safely with low internal
losses.
With current transformers, the primary winding carries the
load current, while with voltage transformers, the primary
winding is connected to the service voltage
The voltage or the current of the secondary winding is
identical to the value on the primary side in phase and ratio
except for the transformer error.
Current transformers operate almost under short circuit
conditions while voltage transformers operate at no-load
Primary and secondary sides are nearly always electrically
independent and insulated from one another as required by
the service voltage. Above a service voltage of 110 kV,
Instrument transformers are frequently manufactured as
combined current and voltage transformers.
A- Current transformers:
B-Voltage Transformer :
VTs are one-phase (phase-to-ground connection) and can be
inductive or capacitive
5- CABLE TERMINATION:
High-Voltage cables of various types are connected to SF6
switchgear via cable connection assembly & also it enables
the GIS & Cables to be tested separated
6- Transformer connection:
consists of Oil/SF6 bushing, the enclosure, the main circuit
end terminal & removable connection.
Relays
Relay is a device when detects the fault supplies information to the
breaker for circuit interruption
Group 2014 | Electrical Substation Protection and Sizing 218
Chapter 3 Transformer Protective Relays
CTs CB
Protected
Control Equipment
Relay
VTs
Stability:
The term stability is usually associated with unit protection
schemes and refers to the ability of the protection system to remain
unaffected by conditions external to the protected zone, for
example through load current and external fault conditions.
advantages
Electromagnetic Relays Solid-state Relays
Digital relays
Operation
Earth-Fault Protection
When the fault current flows through earth return path, the fault is
called Earth Fault. Other faults which do not involve earth are called
phase faults. Since earth faults are relatively frequent, earth fault
protection is necessary in most cases. When separate earth fault
protection is not economical, the phase relays sense the earth fault
currents. However such protection lacks sensitivity.
Hence separate earth fault protection is generally provided. Earth
fault protection senses earth fault current. Following are the
method of earth fault protection.
Trans.-REFR
Figure show how lock out relay can be used in tripping & in
initiating breaker failure (The Sequence for initiate breaker failure
signal)
PROTECTIVE
4
If fault is not cleared, the over current relay(50) will detect
current which will be higher than its setting as fault current is
very high, so the (OC) relay will operate and its normally open
contacts will be closed.
One of its contacts will send another trip signal to the (TC) of
the circuit breaker and at the same time and another contact
will energize a timer (62).
Group 2014 | Electrical Substation Protection and Sizing 246
Chapter 3 Transformer Protective Relays
PROTECTIVE
Block close
2- Mechanical protection
1- Buchhloz relay.
5- Oil level.
Test Socket
Features
3.
Exi
sti
ng
au
xili
ary
su
ppl
y
to
th
e
eq
uip
me
nt
un
de
r
tes
t
ma
y
be
Iso
lat
ed.
Schemes Arrange:
AC Supply Scheme
DC Supply Scheme
ANNUNCIATION CARD
SCADA System
Z-sheet
Ac and Dc Supply:
The AC supply in this scheme is provided by one winding
Transformer with rating 33kv/220v
2- The DC supply
2-Metering:
- It is required to measure Power Quantities like (voltage
Ampere-Power)
-We achieve that by using Instrument transformers
connecting to measuring devices
For Current :
For Voltage :
3-Incoming cell
Incoming cell consists of :
1- 3-ph transimission line
5- Zero sequence CT: used for ground fault sensing and can be
used to detect a ground fault on a circuit by summing the
current on the three phase legs.
4-Trip Circuit
5-Alarm
6- Outgoing Cell
Define the short circuit current that the load will present.
Many loads, such as motors, require a large burst of current
(referred to as inrush current) to break the load free of a
standing start and transition the load to normal operating
conditions.
Calculate the transformer size needed for a 3 phase
transformer. The 3 phase power requirements are determined
as
1-Introduction:
Cable (or conductor) sizing is the process of selecting
appropriate sizes for electrical power cable conductors. Cable
sizes are typically described in terms of cross-sectional area,
American Wire Gauge (AWG) or kcmil, depending on
geographic region.
4-General Methods:
When sizing a cable, the following general process is typically
followed:
Data Gathering
you will need to obtain the following data:
2- Load data
The characteristics of the load that the cable will supply, which
includes:
Cable installation
Where
V is the three phase or single phase voltage drop (V)
I is the nominal full load or starting current as applicable (A)
Rc is the ac resistance of the cable (Ohms/km or Ohms/ft)
Xc is the ac reactance of the cable (Ohms/km or Ohms/ft)
Cos(phi) is the load power factor (pu)
L is the length of the cable (m or ft)
Where
A is the minimum cross-sectional area of the cable (mm2)
i is the prospective short circuit current (A)
t is the duration of the short circuit (s)
k is a short circuit temperature rise constant
Where
theta-i and theta-f are the initial and final conductor
temperatures respectively.
ETAP CALCULATIONS
Single line diagram
ETAP Example
Power Grid
Lumped Load
Cable Sizing
1- Length
3 - Loading
4 - Ampacity
5 - Sizing