Sunteți pe pagina 1din 2

Air System Sizing Summary for Air Cooled Chiller

Project Name: Gazibu Bandung 04/25/2017


Prepared by: PT. METAKOM C PRANATA 04:33PM

Air System Information


Air System Name ............................ Air Cooled Chiller Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 183.0 ft
Air System Type ................................................ SZCAV Location ............................................. Jakarta, Indonesia

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1.0 Tons Load occurs at ................................................... Feb 1600
Total coil load .......................................................... 12.0 MBH OA DB / WB ...................................................... 87.4 / 79.4 F
Sensible coil load ..................................................... 8.6 MBH Entering DB / WB ............................................. 75.7 / 64.6 F
Coil CFM at Feb 1600 ............................................. 456 CFM Leaving DB / WB .............................................. 56.4 / 55.4 F
Max block CFM ....................................................... 456 CFM Coil ADP ..................................................................... 54.2 F
Sum of peak zone CFM .......................................... 456 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio ............................................... 0.717 Resulting RH ................................................................. 54 %
ft/Ton ................................................................... 182.7 Design supply temp. ................................................... 53.6 F
BTU/(hr-ft) ............................................................. 65.7 Zone T-stat Check .................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... 2.40 gpm Max zone temperature deviation .................................. 0.0 F

Humidifier Sizing Data

Max steam flow at Feb 1600 .................................. 1.42 lb/hr Air mass flow ........................................................ 1858.33 lb/hr
Airflow Rate ............................................................. 456 CFM Moisture gain .......................................................... .00076 lb/lb

Supply Fan Sizing Data

Actual max CFM ...................................................... 456 CFM Fan motor BHP ........................................................... 0.06 BHP
Standard CFM ......................................................... 413 CFM Fan motor kW ............................................................. 0.05 kW
Actual max CFM/ft ................................................. 2.49 CFM/ft Fan static .................................................................... 0.60 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 34 CFM CFM/person .............................................................. 17.10 CFM/person
CFM/ft ................................................................... 0.19 CFM/ft

Hourly Analysis Program v4.90 Page 1 of 2


Air System Design Load Summary for Air Cooled Chiller
Project Name: Gazibu Bandung 04/25/2017
Prepared by: PT. METAKOM C PRANATA 04:33PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 79.4 F HEATING OA DB / WB 73.4 F / 70.0 F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 102 ft 5875 - 102 ft - -
Wall Transmission 64 ft 244 - 64 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 102 ft 854 - 102 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 183 ft 211 - 183 ft 0 -
Overhead Lighting 170 W 482 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 255 W 803 - 0 0 -
People 2 361 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8831 240 - 0 0
Zone Conditioning - 8042 240 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 456 CFM 0 - 456 CFM 0 -
Ventilation Load 34 CFM 422 1663 34 CFM -114 0
Supply Fan Load 456 CFM 156 - 456 CFM -156 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8621 1903 - -270 0
Central Cooling Coil - 8621 3396 - -270 0
Humidification Load - - -1493 - - 0
>> Total Conditioning - 8621 1903 - -270 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 2 of 2